2. Types of M.V cabinets
Standard cabinets up to 7.2KV
All in one cabinets up to 4.16KV/400Amp
Incoming cabinet up to 12KV/1000Amp
Standard cabinets up to 12KV/1000Amp
Cabinets for multi start applications
3. Standard cabinets up to 7.2KV with
line and bypass vacuum contactors
Vacuum contactors from
J.C
Line + Bypass
Line
Bypass
Only SST
6. All in one cabinets up to 4.16KV/400A
Disconnector
Fuses up to 500Amp
Line vacuum contactor
Bypass vacuum contactor
Soft starter
Bus bar system 2000Amp
12. Cabinets for multi start applications
Main line contactor
Line contactor for each
motor
Disconnector with earth
switch and electrical
interlock
Temperature control
16. Applicable Standards
IEC 62271-200 High Voltage switchgear and controlgear
IEC 60061-1 High Voltage test techniques, General
definitions and test requirements.
IEC 60694 Common specifications for high voltage
switchgear and controlgear standard.
IEC 71-1 Insulation co- ordination
IEC 71-2 Insulation co- ordination
EN 50178:1998 Electronic equipment for use in power installation
EN 60265-1 Load break switch
EN 60420 Load break switch
IEC 129 Double section rotary disconnectors
IEC 129 Earthing switch
17. Applicable Standards
IEC 60470 Vacuum contactors
IEC 282-1 Vacuum contactors + fuses
IEC 60282-1 Medium voltage fuse
IEC 420 Medium voltage fuse
DIN 43624 Fuse base for indoor mounting
DIN 46234 Cable legs
DIN 0472+IEC 754 Medium voltage cables
EN 61000-6-2 Electromagnetic compatibility(EMC)- Immunity
EN 61000-6-4 Electromagnetic compatibility(EMC)- Emission
EEC/72/23 Electrical safety-Council Directive
18. BIL – Basic insulation level
96 Pulses of 60KV
48 Pulses with negative
polarity
48 Pulses with positive
polarity
According to IEC
Phase to phase
Phase to earth
Complete functioning
after the test
19. Notes for cabinet design
Design always for possible low
voltage test
Vertical mount of the HRVS-
DN power section
Keep always the minimum
distance between phase to
phase and earth to phase
Disassemble and reassemble
of phases
Fiber optics
Control module grounded
Use as much as possible
standard Solcon wiring
diagram
IP Protection
31. Final test procedure
Hi Pot test
Up to 3.6KV 10KV for 1 min
Up to 7.2KV 20KV for 1 min
Up to 12KV 28KV for 1 min
Partial discharge test
Low voltage test
M.V test with resistive load