Low Carbon Data Centres
  without compromise
         Th d 16th S t b 2010
         Thursday  September

Pip Squire, Engineering & Project Director
  p q         g       g      j

                            delivered by:




Ark Continuity - Continuously Delivering high integrity data centres
Low Carbon Data Centres without compromise
                                   p

         Introduction
         Since this conference last year we:
         • have completed SQ17 Module 1
                                         1.4         testing
         • have demonstrated a PUE of 1 4 during IST testing*
         • are now operational with a capacity of:
              – 800 kW of IT Load
              – 600m2 of supported Data Suite space
              – Tier III
              – Security to IL4

         This presentation will look at:
         • Wh l Life C l D t C t C t
           Whole Lif Cycle Data Centre Costs
         • Our focus on reducing carbon through efficient
           operation by sustainable design
         • The benefits arising from this approach




© Ark Continuity 2010             Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Definitions
         Data Centre
         A Facility that is dedicated to Data Centre operations
         Whole Life
         26 years from start of design to decommissioning and disposal
         Whole Life Costing
         ‘... the systematic consideration of all relevant costs associated with the
         development and ownership of an asset’
         Whole Life Stages
         Design, Build, Operate, Refresh, Decommission.




© Ark Continuity 2010              Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Definitions
         Power Usage Effectiveness (PUE)
         This is a metric for characterising and reporting overall data centre infrastructure
         efficiency based on annual energy consumption data as follows:
                  y                        gy        p
                PUE = Total Data Centre energy consumption/IT energy consumption.
                Total Data Centre Energy Consumption is measured in kWh and is the
                sum of the kWh recorded on the utility company bills
                IT Energy Consumption is measured in kWh. It is the sum of the kWh
                recorded at the PDUs supplying the IT load.
                                       pp y g
         PDU
         Power Distribution Unit
         UPS
         Uninterruptible Power Supply
         Autonomy
         Time the UPS can supply the technical load without an incoming supply.



© Ark Continuity 2010              Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Whole Life Cycle Data Centre Costs
         Only 44% of IT Managers see their Data Centre Energy Bills
         (Institute of Engineering and Technology, November 2009)




© Ark Continuity 2010                   Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Whole Life Cycle Data Centre Costs




© Ark Continuity 2010      Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Implementation and Impact on
         Whole Lif C l D t C t C t
         Wh l Life Cycle Data Centre Costs




         Focus on continuous improvement in terms of:
          - Design with sustainability at its core
             - Operations
© Ark Continuity 2010           Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         The Cycle of Continuous Improvement – The Virtual Circle




  Driven by our systems that are accredited to:
      - BS 25999–2:2007, Business Continuity Management
      - ISO/IEC 27001:2005, Information Security Management
                                               y     g
      - ISO 14001:2004, Environmental Management
© Ark Continuity 2010              Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Linking Carbon Impacts with Whole Life Cycle Costs

         In our SQ17 Facility we have:
         1.
         1 Measured our Construction
            Carbon Footprint, where we can:
              • Our M&E Suppliers are still
                working on their embedded
                carbon calculations
              • Shell & Core has 1,111 tonnes
                of CO2 equivalent
              • Anticipate a total of 3,000 tonnes
                of CO2 equivalent including the
                                            g
                M&E data
              • Embedded CO2 is 3,000 t per
                MW of IT Load




© Ark Continuity 2010               Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Linking Carbon Impacts with Whole Life Cycle Costs

         In our SQ17 Facility we have:
         2.
         2 Calculated our Operating Carbon Footprint:
                • At full load
                • With an annual operating PUE of between 1.4 and 1.5
                                   p     g
                • Based on the total UK electricity mix of coal, nuclear, oil, gas and
                  renewable generation mix and the 5 year rolling grid average of 0.54 t CO2
                  equivalent p kWh.
                   q           per
             As 6,600 to 7,000 tonnes CO2 equivalent per year
         This provides:
         a) A saving of 3,500 to 4,000 t CO2 equivalent a year over a data centre with a
            PUE of 2.5
         b) The basis on which to build a carbon accounting tool for compliance with:
            - the CRC Energy Efficiency Scheme
            - the EU Code of Conduct on Data Centres


© Ark Continuity 2010               Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Sustainable Design - local renewable energy
         and water conservation
           d    t          ti




            Sustainable Design - local renewable energy and water conservation


© Ark Continuity 2010                 Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Sustainable Design -
         local renewable energy and water conservation
         l   l       bl           d   t           ti
         We anticipate that this will enable the site to achieve a PUE of around 1.2 and
         provide an annual saving of around 6 000 t of CO2 per MW per year over an
                                               6,000
         equivalent data centre with a PUE of 2.5




© Ark Continuity 2010             Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Sustainable Design - Power Usage Efficiency (PUE)

         PUE presented so far has been to 1 decimal place because:
         • It varies with IT load, time of day and time of year.
                                 ,           y             y
         • PUEs quoted have been unqualified in terms of support systems.

         At low PUEs the UPS efficiency and ancillary l d h
            l   PUE th        ffi i       d    ill    loads have a significant i
                                                                    i ifi    t impact:
                                                                                    t




© Ark Continuity 2010             Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Benefits of Efficient Operation by Sustainable Design

         • Operations, Design, Implementation and Research are all linked in a
           virtual circle.
         • Development effort is focussed at the appropriate stages in the project life
           cycle to obtain maximum benefit for cost incurred
         • Sustainable design means we are focussed on minimising our impact on
           the planet
         • Risk management and the use of incentivised contracts mean we deliver
           to cost and programme




© Ark Continuity 2010             Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

         Benefits to Government ICT

         Sustainable Operations on the Government Estate
         (SOGE), have the following targets:
         • Reduce Carbon Emissions on 1999/2000 levels by
           12.5% in 2010 and 30% in 2020
         • Increase energy efficiency p m2 on 1999/2000 levels
                        gy          y per
           by 15% in 2010 and 30% in 2020
         • Reduce water consumption on 2004/5 levels by 25%
           in 2020
         • Reduce waste arisings on 2004/5 levels by 5% in
           2010 and 25% in 2020
         • Increase recycling to 40% in 2010 and 75% in 2020
         The Ark SQ17 Facility:
         • With a PUE of 1.4 – 1.5 reduces data centre carbon
           emissions, over a 1999/2000 facility by more than
                                               y y
           30%, i.e. 2020 target delivered in 2010.
         • Sustainable design and operating practices mean that
           we are already delivering the water consumption and
           waste reduction targets identified above
               t    d ti t       t id tifi d b

© Ark Continuity 2010               Presentation to GGG   Thursday16th September 2010
Low Carbon Data Centres without compromise
                                   p

 Our mission is to continuously deliver scalable and
 predictable mission critical i f t t
    di t bl   i i      iti l infrastructure…




 that is the most secure resilient & sustainable in Europe
                  secure,                           Europe.

 Thank you

 www.arkcontinuity.co.uk
                 y



© Ark Continuity 2010   Presentation to GGG   Thursday16th September 2010

More Related Content

What's hot

Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...
Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...
Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...IEA-ETSAP
 
ITM Power Results Presentation
ITM Power Results PresentationITM Power Results Presentation
ITM Power Results PresentationITM Power
 
District Heat - Powerpoint presentation
District Heat - Powerpoint presentationDistrict Heat - Powerpoint presentation
District Heat - Powerpoint presentationmontpelier
 
Impact of technology availability on the transition to a net-zero industry
Impact of technology availability on the transition to a net-zero industryImpact of technology availability on the transition to a net-zero industry
Impact of technology availability on the transition to a net-zero industryIEA-ETSAP
 
Developing district heating in ireland presentations
Developing district heating in ireland presentationsDeveloping district heating in ireland presentations
Developing district heating in ireland presentationsCodema
 
The National Energy Services Framework
The National Energy Services FrameworkThe National Energy Services Framework
The National Energy Services FrameworkCodema
 
Modelling of offshore wind
Modelling of offshore windModelling of offshore wind
Modelling of offshore windIEA-ETSAP
 
Mitigation Pathways to well below 2C in ETSAP-TIAM
Mitigation Pathways to well below 2C in ETSAP-TIAMMitigation Pathways to well below 2C in ETSAP-TIAM
Mitigation Pathways to well below 2C in ETSAP-TIAMIEA-ETSAP
 
Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...
Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...
Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...Global CCS Institute
 
Zero carbon projects
Zero carbon projectsZero carbon projects
Zero carbon projectsPeter Mumford
 
BBP BL Case Study
BBP BL Case StudyBBP BL Case Study
BBP BL Case StudyEPTUK
 
COHEAT @ BEIS May 2017
COHEAT @ BEIS May 2017COHEAT @ BEIS May 2017
COHEAT @ BEIS May 2017Marko Cosic
 
Residential heat pumps in the future Danish energy system
Residential heat pumps in the future Danish energy systemResidential heat pumps in the future Danish energy system
Residential heat pumps in the future Danish energy systemIEA-ETSAP
 
Green Hydrogen Financial Model Toolkit LCOH V6
Green Hydrogen Financial Model Toolkit LCOH V6Green Hydrogen Financial Model Toolkit LCOH V6
Green Hydrogen Financial Model Toolkit LCOH V6Fadi Maalouf, PMP
 
Pushing the limits of TIAM - Achieving well-below 2 degrees scenarios
Pushing the limits of TIAM - Achieving well-below 2 degrees scenariosPushing the limits of TIAM - Achieving well-below 2 degrees scenarios
Pushing the limits of TIAM - Achieving well-below 2 degrees scenariosIEA-ETSAP
 
Cost of EV charging infrastructure
Cost of EV charging infrastructureCost of EV charging infrastructure
Cost of EV charging infrastructureLeonardo ENERGY
 
Europe User Conference: BP - implementing and supporting a multi-model, multi...
Europe User Conference: BP - implementing and supporting a multi-model, multi...Europe User Conference: BP - implementing and supporting a multi-model, multi...
Europe User Conference: BP - implementing and supporting a multi-model, multi...KBC (A Yokogawa Company)
 

What's hot (20)

Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...
Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...
Project update on Enhancing Flexibility in TIMES: Introducing Ancillary Servi...
 
ITM Power Results Presentation
ITM Power Results PresentationITM Power Results Presentation
ITM Power Results Presentation
 
District Heat - Powerpoint presentation
District Heat - Powerpoint presentationDistrict Heat - Powerpoint presentation
District Heat - Powerpoint presentation
 
Impact of technology availability on the transition to a net-zero industry
Impact of technology availability on the transition to a net-zero industryImpact of technology availability on the transition to a net-zero industry
Impact of technology availability on the transition to a net-zero industry
 
Coal Fleet Overview 2010
Coal Fleet Overview   2010Coal Fleet Overview   2010
Coal Fleet Overview 2010
 
Developing district heating in ireland presentations
Developing district heating in ireland presentationsDeveloping district heating in ireland presentations
Developing district heating in ireland presentations
 
The National Energy Services Framework
The National Energy Services FrameworkThe National Energy Services Framework
The National Energy Services Framework
 
Chp presentation 1st july 2015
Chp presentation 1st july 2015Chp presentation 1st july 2015
Chp presentation 1st july 2015
 
Modelling of offshore wind
Modelling of offshore windModelling of offshore wind
Modelling of offshore wind
 
Mitigation Pathways to well below 2C in ETSAP-TIAM
Mitigation Pathways to well below 2C in ETSAP-TIAMMitigation Pathways to well below 2C in ETSAP-TIAM
Mitigation Pathways to well below 2C in ETSAP-TIAM
 
Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...
Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...
Emirates Steel Industry Carbon Capture Usage & Storage Project and ADNOC Ruma...
 
Zero carbon projects
Zero carbon projectsZero carbon projects
Zero carbon projects
 
BBP BL Case Study
BBP BL Case StudyBBP BL Case Study
BBP BL Case Study
 
COHEAT @ BEIS May 2017
COHEAT @ BEIS May 2017COHEAT @ BEIS May 2017
COHEAT @ BEIS May 2017
 
Residential heat pumps in the future Danish energy system
Residential heat pumps in the future Danish energy systemResidential heat pumps in the future Danish energy system
Residential heat pumps in the future Danish energy system
 
Green Hydrogen Financial Model Toolkit LCOH V6
Green Hydrogen Financial Model Toolkit LCOH V6Green Hydrogen Financial Model Toolkit LCOH V6
Green Hydrogen Financial Model Toolkit LCOH V6
 
Pushing the limits of TIAM - Achieving well-below 2 degrees scenarios
Pushing the limits of TIAM - Achieving well-below 2 degrees scenariosPushing the limits of TIAM - Achieving well-below 2 degrees scenarios
Pushing the limits of TIAM - Achieving well-below 2 degrees scenarios
 
Energy and GHG emission balances: CTBE´s proposal
Energy and GHG emission balances: CTBE´s proposalEnergy and GHG emission balances: CTBE´s proposal
Energy and GHG emission balances: CTBE´s proposal
 
Cost of EV charging infrastructure
Cost of EV charging infrastructureCost of EV charging infrastructure
Cost of EV charging infrastructure
 
Europe User Conference: BP - implementing and supporting a multi-model, multi...
Europe User Conference: BP - implementing and supporting a multi-model, multi...Europe User Conference: BP - implementing and supporting a multi-model, multi...
Europe User Conference: BP - implementing and supporting a multi-model, multi...
 

Viewers also liked

Poster 1 Whispering Sand New
Poster 1  Whispering Sand NewPoster 1  Whispering Sand New
Poster 1 Whispering Sand NewIan Kenworthy
 
Screen Masters Print Ad
Screen Masters Print Ad Screen Masters Print Ad
Screen Masters Print Ad carlandl
 
T6 karajeh case study-egyptsudan(3)
T6 karajeh case study-egyptsudan(3)T6 karajeh case study-egyptsudan(3)
T6 karajeh case study-egyptsudan(3)NENAwaterscarcity
 
Short case...Arterial embolic hemorrhagic infarction
Short case...Arterial embolic hemorrhagic infarctionShort case...Arterial embolic hemorrhagic infarction
Short case...Arterial embolic hemorrhagic infarctionProfessor Yasser Metwally
 
세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!
세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!
세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!cbs15min
 
Creating Personas by focusing on your website users
Creating Personas by focusing on your website usersCreating Personas by focusing on your website users
Creating Personas by focusing on your website usersPrescient Digital Media
 
Peder Mork Monsted 1859 - 1941
Peder Mork Monsted 1859 - 1941Peder Mork Monsted 1859 - 1941
Peder Mork Monsted 1859 - 1941John *
 
Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA
Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA
Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA haeuslerbernhard
 
Why GSCOS Introductory Presentation Final (Pp Tminimizer)
Why GSCOS Introductory Presentation  Final (Pp Tminimizer)Why GSCOS Introductory Presentation  Final (Pp Tminimizer)
Why GSCOS Introductory Presentation Final (Pp Tminimizer)gogisangha
 
Ks. Misiniec - Zakliczyn
Ks. Misiniec - ZakliczynKs. Misiniec - Zakliczyn
Ks. Misiniec - Zakliczyngm55
 

Viewers also liked (17)

Poster 1 Whispering Sand New
Poster 1  Whispering Sand NewPoster 1  Whispering Sand New
Poster 1 Whispering Sand New
 
Screen Masters Print Ad
Screen Masters Print Ad Screen Masters Print Ad
Screen Masters Print Ad
 
T6 karajeh case study-egyptsudan(3)
T6 karajeh case study-egyptsudan(3)T6 karajeh case study-egyptsudan(3)
T6 karajeh case study-egyptsudan(3)
 
Short case...Arterial embolic hemorrhagic infarction
Short case...Arterial embolic hemorrhagic infarctionShort case...Arterial embolic hemorrhagic infarction
Short case...Arterial embolic hemorrhagic infarction
 
세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!
세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!
세바시 15 김원철 아키텍트4라이프 대표 - 청년들이여, 아프리카로 가자!
 
Creating Personas by focusing on your website users
Creating Personas by focusing on your website usersCreating Personas by focusing on your website users
Creating Personas by focusing on your website users
 
Health wellness villages_28
Health wellness villages_28Health wellness villages_28
Health wellness villages_28
 
SSC2011_Mell Henderson PPT
SSC2011_Mell Henderson PPTSSC2011_Mell Henderson PPT
SSC2011_Mell Henderson PPT
 
Somos bang
Somos bangSomos bang
Somos bang
 
Peder Mork Monsted 1859 - 1941
Peder Mork Monsted 1859 - 1941Peder Mork Monsted 1859 - 1941
Peder Mork Monsted 1859 - 1941
 
концепт
концептконцепт
концепт
 
Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA
Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA
Der Transatlantische Wahnsinn und seine fette Beute, CETA, TTIP und TiSA
 
Why GSCOS Introductory Presentation Final (Pp Tminimizer)
Why GSCOS Introductory Presentation  Final (Pp Tminimizer)Why GSCOS Introductory Presentation  Final (Pp Tminimizer)
Why GSCOS Introductory Presentation Final (Pp Tminimizer)
 
Ks. Misiniec - Zakliczyn
Ks. Misiniec - ZakliczynKs. Misiniec - Zakliczyn
Ks. Misiniec - Zakliczyn
 
TIC
TICTIC
TIC
 
yeso velmix
yeso velmixyeso velmix
yeso velmix
 
ch1
ch1ch1
ch1
 

Similar to Low Carbon Data Centres without Compromise

David Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET Power
David Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET PowerDavid Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET Power
David Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET PowerELEEP Network
 
Life Cycle Assessment & Environmental Product Declarations: What You Need to ...
Life Cycle Assessment & Environmental Product Declarations: What You Need to ...Life Cycle Assessment & Environmental Product Declarations: What You Need to ...
Life Cycle Assessment & Environmental Product Declarations: What You Need to ...Irish Green Building Council
 
Green it vmug presentation v1
Green it vmug presentation v1Green it vmug presentation v1
Green it vmug presentation v1subtitle
 
Sustainable development in the Utility Sector
Sustainable development in the Utility SectorSustainable development in the Utility Sector
Sustainable development in the Utility Sector lancashire county council
 
Energy benoit hood(iea) ccxg gf sep2014
Energy benoit hood(iea) ccxg gf sep2014Energy benoit hood(iea) ccxg gf sep2014
Energy benoit hood(iea) ccxg gf sep2014OECD Environment
 
Sample energy saving proposal
Sample energy saving proposalSample energy saving proposal
Sample energy saving proposalRoyal Mail
 
Andrew Houghton - Green ICT in the European Union
Andrew Houghton - Green ICT in the European UnionAndrew Houghton - Green ICT in the European Union
Andrew Houghton - Green ICT in the European UnioniMinds conference
 
Terry McGivern MEGS-KT lecture 14th November 2012
Terry McGivern MEGS-KT lecture 14th November 2012Terry McGivern MEGS-KT lecture 14th November 2012
Terry McGivern MEGS-KT lecture 14th November 2012Andrea Wheeler
 
Early Replacement of Notebooks Considering Environmental Impacts
Early Replacement of Notebooks Considering Environmental ImpactsEarly Replacement of Notebooks Considering Environmental Impacts
Early Replacement of Notebooks Considering Environmental ImpactsOeko-Institut
 
Hydrogen PowerPoint Presentation.pdf
Hydrogen PowerPoint Presentation.pdfHydrogen PowerPoint Presentation.pdf
Hydrogen PowerPoint Presentation.pdfJudeDimaalihan3
 
GreenTouch: Putting Energy Into Making Networks More Efficient
GreenTouch: Putting Energy Into Making Networks More Efficient GreenTouch: Putting Energy Into Making Networks More Efficient
GreenTouch: Putting Energy Into Making Networks More Efficient GreenTouch
 
Project management presentation 27th november 2013
Project management presentation 27th november 2013Project management presentation 27th november 2013
Project management presentation 27th november 2013Building Sustainability Ltd
 
Counting for Large Property Portfolios | Sean Lockie
Counting for Large Property Portfolios | Sean Lockie Counting for Large Property Portfolios | Sean Lockie
Counting for Large Property Portfolios | Sean Lockie icarb
 
Cut Carbon Symposium: Capital Carbon Inventory Seedcorn Project
Cut Carbon Symposium: Capital Carbon Inventory Seedcorn ProjectCut Carbon Symposium: Capital Carbon Inventory Seedcorn Project
Cut Carbon Symposium: Capital Carbon Inventory Seedcorn ProjectDecarboN8
 

Similar to Low Carbon Data Centres without Compromise (20)

David Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET Power
David Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET PowerDavid Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET Power
David Freed (8 Rivers Capital), ELEEP Virtual Discussion on NET Power
 
Life Cycle Assessment & Environmental Product Declarations: What You Need to ...
Life Cycle Assessment & Environmental Product Declarations: What You Need to ...Life Cycle Assessment & Environmental Product Declarations: What You Need to ...
Life Cycle Assessment & Environmental Product Declarations: What You Need to ...
 
Green it vmug presentation v1
Green it vmug presentation v1Green it vmug presentation v1
Green it vmug presentation v1
 
Sustainable development in the Utility Sector
Sustainable development in the Utility SectorSustainable development in the Utility Sector
Sustainable development in the Utility Sector
 
Building the UK carbon capture and storage sector by 2030 – Scenarios and act...
Building the UK carbon capture and storage sector by 2030 – Scenarios and act...Building the UK carbon capture and storage sector by 2030 – Scenarios and act...
Building the UK carbon capture and storage sector by 2030 – Scenarios and act...
 
Energy benoit hood(iea) ccxg gf sep2014
Energy benoit hood(iea) ccxg gf sep2014Energy benoit hood(iea) ccxg gf sep2014
Energy benoit hood(iea) ccxg gf sep2014
 
Sample energy saving proposal
Sample energy saving proposalSample energy saving proposal
Sample energy saving proposal
 
Andrew Houghton - Green ICT in the European Union
Andrew Houghton - Green ICT in the European UnionAndrew Houghton - Green ICT in the European Union
Andrew Houghton - Green ICT in the European Union
 
Terry McGivern MEGS-KT lecture 14th November 2012
Terry McGivern MEGS-KT lecture 14th November 2012Terry McGivern MEGS-KT lecture 14th November 2012
Terry McGivern MEGS-KT lecture 14th November 2012
 
Early Replacement of Notebooks Considering Environmental Impacts
Early Replacement of Notebooks Considering Environmental ImpactsEarly Replacement of Notebooks Considering Environmental Impacts
Early Replacement of Notebooks Considering Environmental Impacts
 
Hydrogen PowerPoint Presentation.pdf
Hydrogen PowerPoint Presentation.pdfHydrogen PowerPoint Presentation.pdf
Hydrogen PowerPoint Presentation.pdf
 
GreenTouch: Putting Energy Into Making Networks More Efficient
GreenTouch: Putting Energy Into Making Networks More Efficient GreenTouch: Putting Energy Into Making Networks More Efficient
GreenTouch: Putting Energy Into Making Networks More Efficient
 
Project management presentation 27th november 2013
Project management presentation 27th november 2013Project management presentation 27th november 2013
Project management presentation 27th november 2013
 
Green Networking
Green NetworkingGreen Networking
Green Networking
 
Greening DECC - The CIO as Champion
Greening DECC - The CIO as ChampionGreening DECC - The CIO as Champion
Greening DECC - The CIO as Champion
 
Counting for Large Property Portfolios | Sean Lockie
Counting for Large Property Portfolios | Sean Lockie Counting for Large Property Portfolios | Sean Lockie
Counting for Large Property Portfolios | Sean Lockie
 
Siemens
SiemensSiemens
Siemens
 
Cut Carbon Symposium: Capital Carbon Inventory Seedcorn Project
Cut Carbon Symposium: Capital Carbon Inventory Seedcorn ProjectCut Carbon Symposium: Capital Carbon Inventory Seedcorn Project
Cut Carbon Symposium: Capital Carbon Inventory Seedcorn Project
 
Kiev presentations validation workshop 24 september
Kiev   presentations validation workshop 24 septemberKiev   presentations validation workshop 24 september
Kiev presentations validation workshop 24 september
 
Kiev presentations validation workshop 24 september
Kiev   presentations validation workshop 24 septemberKiev   presentations validation workshop 24 september
Kiev presentations validation workshop 24 september
 

Low Carbon Data Centres without Compromise

  • 1. Low Carbon Data Centres without compromise Th d 16th S t b 2010 Thursday September Pip Squire, Engineering & Project Director p q g g j delivered by: Ark Continuity - Continuously Delivering high integrity data centres
  • 2. Low Carbon Data Centres without compromise p Introduction Since this conference last year we: • have completed SQ17 Module 1 1.4 testing • have demonstrated a PUE of 1 4 during IST testing* • are now operational with a capacity of: – 800 kW of IT Load – 600m2 of supported Data Suite space – Tier III – Security to IL4 This presentation will look at: • Wh l Life C l D t C t C t Whole Lif Cycle Data Centre Costs • Our focus on reducing carbon through efficient operation by sustainable design • The benefits arising from this approach © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 3. Low Carbon Data Centres without compromise p Definitions Data Centre A Facility that is dedicated to Data Centre operations Whole Life 26 years from start of design to decommissioning and disposal Whole Life Costing ‘... the systematic consideration of all relevant costs associated with the development and ownership of an asset’ Whole Life Stages Design, Build, Operate, Refresh, Decommission. © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 4. Low Carbon Data Centres without compromise p Definitions Power Usage Effectiveness (PUE) This is a metric for characterising and reporting overall data centre infrastructure efficiency based on annual energy consumption data as follows: y gy p PUE = Total Data Centre energy consumption/IT energy consumption. Total Data Centre Energy Consumption is measured in kWh and is the sum of the kWh recorded on the utility company bills IT Energy Consumption is measured in kWh. It is the sum of the kWh recorded at the PDUs supplying the IT load. pp y g PDU Power Distribution Unit UPS Uninterruptible Power Supply Autonomy Time the UPS can supply the technical load without an incoming supply. © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 5. Low Carbon Data Centres without compromise p Whole Life Cycle Data Centre Costs Only 44% of IT Managers see their Data Centre Energy Bills (Institute of Engineering and Technology, November 2009) © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 6. Low Carbon Data Centres without compromise p Whole Life Cycle Data Centre Costs © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 7. Low Carbon Data Centres without compromise p Implementation and Impact on Whole Lif C l D t C t C t Wh l Life Cycle Data Centre Costs Focus on continuous improvement in terms of: - Design with sustainability at its core - Operations © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 8. Low Carbon Data Centres without compromise p The Cycle of Continuous Improvement – The Virtual Circle Driven by our systems that are accredited to: - BS 25999–2:2007, Business Continuity Management - ISO/IEC 27001:2005, Information Security Management y g - ISO 14001:2004, Environmental Management © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 9. Low Carbon Data Centres without compromise p Linking Carbon Impacts with Whole Life Cycle Costs In our SQ17 Facility we have: 1. 1 Measured our Construction Carbon Footprint, where we can: • Our M&E Suppliers are still working on their embedded carbon calculations • Shell & Core has 1,111 tonnes of CO2 equivalent • Anticipate a total of 3,000 tonnes of CO2 equivalent including the g M&E data • Embedded CO2 is 3,000 t per MW of IT Load © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 10. Low Carbon Data Centres without compromise p Linking Carbon Impacts with Whole Life Cycle Costs In our SQ17 Facility we have: 2. 2 Calculated our Operating Carbon Footprint: • At full load • With an annual operating PUE of between 1.4 and 1.5 p g • Based on the total UK electricity mix of coal, nuclear, oil, gas and renewable generation mix and the 5 year rolling grid average of 0.54 t CO2 equivalent p kWh. q per As 6,600 to 7,000 tonnes CO2 equivalent per year This provides: a) A saving of 3,500 to 4,000 t CO2 equivalent a year over a data centre with a PUE of 2.5 b) The basis on which to build a carbon accounting tool for compliance with: - the CRC Energy Efficiency Scheme - the EU Code of Conduct on Data Centres © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 11. Low Carbon Data Centres without compromise p Sustainable Design - local renewable energy and water conservation d t ti Sustainable Design - local renewable energy and water conservation © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 12. Low Carbon Data Centres without compromise p Sustainable Design - local renewable energy and water conservation l l bl d t ti We anticipate that this will enable the site to achieve a PUE of around 1.2 and provide an annual saving of around 6 000 t of CO2 per MW per year over an 6,000 equivalent data centre with a PUE of 2.5 © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 13. Low Carbon Data Centres without compromise p Sustainable Design - Power Usage Efficiency (PUE) PUE presented so far has been to 1 decimal place because: • It varies with IT load, time of day and time of year. , y y • PUEs quoted have been unqualified in terms of support systems. At low PUEs the UPS efficiency and ancillary l d h l PUE th ffi i d ill loads have a significant i i ifi t impact: t © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 14. Low Carbon Data Centres without compromise p Benefits of Efficient Operation by Sustainable Design • Operations, Design, Implementation and Research are all linked in a virtual circle. • Development effort is focussed at the appropriate stages in the project life cycle to obtain maximum benefit for cost incurred • Sustainable design means we are focussed on minimising our impact on the planet • Risk management and the use of incentivised contracts mean we deliver to cost and programme © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 15. Low Carbon Data Centres without compromise p Benefits to Government ICT Sustainable Operations on the Government Estate (SOGE), have the following targets: • Reduce Carbon Emissions on 1999/2000 levels by 12.5% in 2010 and 30% in 2020 • Increase energy efficiency p m2 on 1999/2000 levels gy y per by 15% in 2010 and 30% in 2020 • Reduce water consumption on 2004/5 levels by 25% in 2020 • Reduce waste arisings on 2004/5 levels by 5% in 2010 and 25% in 2020 • Increase recycling to 40% in 2010 and 75% in 2020 The Ark SQ17 Facility: • With a PUE of 1.4 – 1.5 reduces data centre carbon emissions, over a 1999/2000 facility by more than y y 30%, i.e. 2020 target delivered in 2010. • Sustainable design and operating practices mean that we are already delivering the water consumption and waste reduction targets identified above t d ti t t id tifi d b © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010
  • 16. Low Carbon Data Centres without compromise p Our mission is to continuously deliver scalable and predictable mission critical i f t t di t bl i i iti l infrastructure… that is the most secure resilient & sustainable in Europe secure, Europe. Thank you www.arkcontinuity.co.uk y © Ark Continuity 2010 Presentation to GGG Thursday16th September 2010