Firestop Filler Boards4 Hour rated
VEDAFEU FBB
S
Y
S
T
E
M
Form
work
-Fire
barrier
Therm
aland
acoustic
insulation
ALL-IN-ONE
2. © All rights reserved - Non contractual drawings - 01/2016
2
Description
VEDAFEU FB©
firestop filler boards are made of high density mineral wool and are used as fire barrier for
expansion joints.
Packaging
Delivered in 1200 mm long boards with a standard height of 200 mm (other heigths available upon request).
VEDAFEU FB
©
FIRESTOP FILLER BOARDS
All-in-one system : formwork, fire barrier,
thermal and acoustic insulation
1. Attach the anchoring springs at 30 mm from
a long edge of the VEDAFEU FB©
firestop
filler board on Side A.
4. Attach the anchoring springs at 30 mm from
the other long edge of the VEDAFEU FB©
firestop
filler board on Side B.
2. Install the VEDAFEU FB©
firestop filler board
along the wooden formwork.
3. Concrete slab sideupoured.
5. Concrete slab sidevpoured.
u
u
v
v
Side A
u
u
vv
Side B
Side A
Installation instructions
Technical Data
100%
PATENTED
Initial opening 20 to 60 mm
Orientation Horizontal and vertical
Fire resistance EI 240 (4 hours) in compliance with applicable European regulations (EN 1366-4 and EN 13501-2)
Movement Opening up to +20 % - Closing up to -60 %
Minimum height Certified from a 140 mm height
Installation Anchoring springs on one side, springs or adhesive on the other
Thermal conductivity (Lambda) 0,039 W.m-1
K-1
(Report n° RA.15.36.EB-V2 dated 25/10/2015)
Sound attenuation Up to 43 dB (Report n°BEB2.F.6023 dated 09/07/2015)
In case of installation with adhesive, glue
the upper part of the board to the dry
concrete on a 40 mm height and resume
to step 4.
3. ILLUSTRATIONS
Concrete slab
sidevto be poured.
Positioning at the base of the formwork Installation of anchoring springs
VEDAFEU FB©
firestop filler boards
ready for
concrete pouring
Concrete slab
sideupoured.
4. © All rights reserved - Non contractual drawings - 01/2016
4
OFFICIAL CLASSIFICATION OF
VEDAFEU FB©
FIRESTOP FILLER BOARDS
■ Tested in horizontal configuration with movement (also valid without or less
movement) for a minimum height of 140 mm (also valid for superior heights)
■ Certified movements : +20% for openings up to 40 mm
+15% for openings up to 60 mm
■ Installation method : anchoring springs on both sides
■ Tested in vertical configuration with movement (also valid without or less movement)
for a minimum height of 160 mm (also valid for superior heights)
■ Certified movements : +20% for a 20 mm opening
+7.5% for openings up to 60 mm
■ Installation method : anchoring springs on one side and adhesive on the other
Classification Report n° 13-F-131441 dated 16/04/2014
VERTICAL
EI 240 – V – M7,5 – B – W 20 to 60EI 240 – V – M20 – B – W 20
Classification Report n° 12-F-148 dated 01/03/2012
HORIZONTAL
EI 240 – H – M15 – B – W 20 to 60EI 240 – H – M20 – B – W 20 to 40
5. EI : E = Firestop Integrity I = thermal insulation. EI expressed in minutes.
H or V : H = horizontal construction support. V = vertical construction support.
M or X : M = movement. X = no movement. M and X expressed in percentage.
B or F : junction type. B = factory and on-site manufactured. F = on-site manufactured.
W = tested joint width. Expressed in millimeters.
Fire resistance according to standard EN 13501-2.
Fireproofing
& Thermal
insulation
in minutes
Horizontal
support
H
Movement
of
+50 %
Initial approved
joint
560 mm
240
minutes
Vertical
support
V
Junction
type
EI 240 - V - M20 - B - W 20 to 120 mm
EI 240 - H - M50 - B - W 560
VALID for width
from
20 to 120 mm
HOW TO READ A CLASSIFICATION REPORT ?
Example of classification
E 60 - H - X - F - W 60
VALID for a
gap of 60 mm
ONLY.
Not valid for
a range
Failed after
60 minutes
NO «I»
NO THERMAL
INSULATION
HORIZONTAL
SUPPORT
ONLY
Tested
WITHOUT MOVEMENT
6. © All rights reserved - Non contractual drawings - 01/2016
6
ADVANTAGES OF THE ALL-IN-ONE
VEDAFEU FB©
SYSTEM
■ VEDAFEU FB©
firestop filler boards are an all-in-one system :
- They replace the expansion joint formwork usually used on site (alveolar cardboard,
polystyrene…)
- They make the joint fireproof (EI 240 – 4-hour fire resistance) on the whole thickness
of the slab or the wall. Fire can thus come from any side.
■ The use of VEDAFEU FB©
firestop filler boards allows to skip steps in the making and
fireproofing of expansion joints as shown on the below chart :
On top of the savings on material and labor, the use of VEDAFEU FB©
firestop filler boards in
expansion joints allows a better environmental impact : they reduce the carbon footprint, increase
productivity, remove waste and its management as well as the removing of the formwork.
Standard
method
Removing formwork
Cleaning
(waste management…)
Fireproofing
with another solution
Expansion joint formwork
Concrete pouring
Fireproof expansion joint
Alveolar cardboard,
polystyrene…
VEDAFEU FB©
+
springs
+
adhesive
VEDAFEU FB©
firestop
filler boards
{STEPS SKIPPED WITH
THE USE OF
VEDAFEU FB© FIRESTOP
FILLER BOARDS
FAST
ECOLOGICAL
ECONOMICAL
7. OTHER ADVANTAGES
Junction between two boards
The patented linking system guarantees the integrity
of the product at junctions. It also guarantees the same
acoustic and fire performance on the whole length, eases
installation and improves airtightness.
Thermal and acoustic insulation
VEDAFEU FB©
firestop filler boards allow a good
thermal (lambda 0.039 as per report n° RA.15.36-EB-V2
dated october 25th
2015) and acoustic (up to 43 dB
reduction as per report n° BEB2.F.6023 dated July 9th
2015) insulation. They can therefore be used in High
Environmental Quality buildings. Official reports are
available upon request.
Adhesion to concrete
As per their installation method, concrete is always
poured on at least one side of the VEDAFEU FB©
firestop
filler boards which guarantees a perfect adhesion with
no risk to see the product fall with time. Moreover, the
high density of the wool gives an excellent resistance
to infiltration and physical agressions.
Ancillary products
No ancillary product is mandatory to ensure fire
resistance.
8. GV2 - VEDA FRANCE - CS 63052 - 95972 Roissy CDG Cedex - France