APPLICATION NOTE
ISOLATION TRANSFORMERS
Paul De Potter
March 2014
ECI Publication No Cu0113
Available from www.leonardo-energy.org
Publication No Cu0113
Issue Date: March 2014
Page i
Document Issue Control Sheet
Document Title: Application note – Isolation transformers
Publication No: Cu0113
Issue: 03
Release: Public
Content provider(s) Paul De Potter
Author(s): Paul De Potter
Editorial and language review Bruno De Wachter (editorial), Noel Montrucchio (English Upgrade)
Content review: Stefan Fassbinder
Document History
Issue Date Purpose
1 April 2011 Initial release
2 September
2011
Minor revision for publication in the Good Practice Guide
3 March
2014
Review in the framework of the GPG
Disclaimer
While this publication has been prepared with care, European Copper Institute and other contributors provide
no warranty with regards to the content and shall not be liable for any direct, incidental or consequential
damages that may result from the use of the information or the data contained.
Copyright© European Copper Institute.
Reproduction is authorized providing the material is unabridged and the source is acknowledged.
Publication No Cu0113
Issue Date: March 2014
Page ii
CONTENTS
Summary ........................................................................................................................................................ 1
Introduction.................................................................................................................................................... 2
Isolation transformers .................................................................................................................................... 2
Advantages of isolation transformers............................................................................................................. 4
Applications.................................................................................................................................................... 4
Human Safety—Prevention of electrical shock ......................................................................................................5
Protection by safety isolation of circuits..................................................................................................5
Electrical separation.................................................................................................................................6
Medical transformers...............................................................................................................................8
Protection of sensitive equipment .........................................................................................................................8
Construction—Cores....................................................................................................................................... 9
Conclusion .................................................................................................................................................... 10
Bibliography ................................................................................................................................................. 10
Publication No Cu0113
Issue Date: March 2014
Page 1
SUMMARY
Transformers can do more than transferring electrical energy from one voltage to another. Separation
transformers, isolation transformers, and extra isolation transformers play a major role in the protection of
people and equipment.
They come in different types and power ranges, from a few VA to a few MVA. Although they are generally
more expensive than autotransformers or transformers with conventionally separated windings, they can be
very useful in many ways, for example:
 To protect individuals against electrical shock
 To avoid losing power after a first insulation fault
 To protect sensitive equipment from electrical noise
 To create a star point for equipment
This application note discusses the working principles of isolation transformers, their advantages, and their
various application domains.
Publication No Cu0113
Issue Date: March 2014
Page 2
INTRODUCTION
A transformer is an electrical device that transfers electrical energy from one circuit to another using
induction. A current in the primary windings creates a varying magnetic flux in the transformer’s core and thus
creates a varying magnetic field in the secondary windings. Apart from some special cases, there is no
connection between the input (the primary windings) and the output (the secondary windings).
In many cases, the property of transferring electrical energy will be used to obtain a higher or lower level of
voltage.
The induced voltage in the secondary windings is in direct proportion to the primary voltage and is determined
by the ratio of the number of turns in the secondary (ns) to the number of turns in the primary (np) as follows:
Us/Un= ns / np
Electrical transformers can be configured as single-phase or three-phase; oil-filled or dry type devices. They are
used for many different applications, including control, distribution, instrumentation, current transformation
and power transformation among others. There are also many different mounting possibilities.
The special case where there is a connection between primary and secondary windings is called an
autotransformer. There is only one winding, and a part of this winding is common to both the primary and the
secondary circuits.
Figure 1 – Autotransformer
The autotransformer will generally be used as a voltage conversion of the local supply to another voltage value
that is required for a particular piece of equipment (step-up or step-down).
Although there are some benefits in the use of an autotransformer, it is obvious that there are also many
drawbacks. A major one is the fact that there is no isolation for disturbances or interferences coming from the
primary.
ISOLATION TRANSFORMERS
Usually electrical transformers are used to transform voltage from a higher level to a lower voltage or vice
versa. They do little to attenuate the passage of noise or transients from the primary to the secondary.
Transformers can also be used to change the impedance of the electrical circuit to reduce the short-circuit
current or to provide a galvanic insulation between two systems.
In theory, the definition of ‘isolation transformer’ applies to any transformer where there is no direct
connection between the primary and the secondary windings. In other words: all transformers which are not
autotransformers. The windings are connected only by the magnetic flux in the core.
Publication No Cu0113
Issue Date: March 2014
Page 3
Nevertheless, when there is only a basic separation between the primary and secondary windings, we will
speak of a separation transformer.
Figure 2 – Separation transformer
The insulation between the primary and the secondary windings provides a degree of protection against
electric shock that is equivalent to a basic insulation.
Reminder: basic insulation is the insulation required for ensuring the appropriate operation of the equipment
and of the electrical installations and for the fundamental protection against electric shock.
This separation will limit the risk in the event of accidental simultaneous contact with the exposed conductive
part and the live parts (or metals parts that can become live in the event of an insulation fault).
Taking the insulation between the primary and the secondary windings a step further, we get to the isolation
transformers.
Figure 3 – Isolation transformer
The insulation between the primary and the secondary windings provides a degree of protection against
electric shock equivalent to that of double insulation.
This separation will limit the risk in the event of accidental simultaneous contact with the exposed conductive
part and the live parts (or metals parts that can become live in the event of an insulation fault).
Reminder: double insulation is the insulation in which provision is made for separate supplementary insulation
in addition to basic insulation. It is determined by type tests.
When the no-load secondary voltage of the isolation transformer is limited to UL,where UL is the Safety Extra
Low Voltage (SELV) Limit, then we have a ‘safety transformer.’
Publication No Cu0113
Issue Date: March 2014
Page 4
Figure 4 – Safety transformers
ADVANTAGES OF ISOLATION TRANSFORMERS
Isolation transformers can be used to protect people against the dangers of electric shocks. Isolation
transformers can block transmission of DC signals from one circuit to the other, but allow AC signals to pass.
They will also block interference caused by ground loops. Isolation transformers with electrostatic shields are
used for power supplies for sensitive equipment such as medical equipment, computers or precision
laboratory measurement instruments.
There are two ways to introduce the equivalent of double isolation:
 By putting a metallic safety shield (usually copper) between the primary and secondary windings and
connecting it to the ground (protective earth). This can also be another winding or a metal strip
surrounding a winding. If the isolation breaks, the electricity flows to the ground, providing the
required safety. The shield will attenuate or filter voltage spikes and will greatly reduce the coupling
of common-mode noise by decreasing the capacitive coupling.
 By using reinforced insulation. This type of insulation is made up of multiple layers. All layers must
pass tests required by established standards. If one layer breaks, the next layer provides the required
safety.
Normally, these transformers have a lower leakage current than those that use a shield.
Electrical noise:
Common mode: between ground and the current carrying conductors, including the neutral
Normal mode: between two current carrying conductors, including line to neutral
Isolation transformers will mostly be used in a one-to-one ratio (the primary voltage rating equals the rated
secondary voltage value). The two windings will have the same number of turns. There might be a slight
difference in the number of turns to compensate for voltage drops; otherwise, the secondary voltage would be
slightly less than the primary voltage.
APPLICATIONS
Let us look at a few cases where the use of an isolation transformer is a possibility or even recommended
Isolation transformers will be mainly used to protect people from electric shock and as a power supply for
sensitive equipment (computers, medical equipment, laboratory equipment, et cetera).
Publication No Cu0113
Issue Date: March 2014
Page 5
Isolation transformers are often used to isolate the machine or equipment from the rest of the electrical
installation, to avoid loss of power in the case of a first insulation fault.
Since there is no return path to the source (the secondary winding of the transformer), in the event of a fault,
there will be no fault current flowing and no overcurrent protective device will cut off the supply. Apart from
being harmless to persons touching the conductive parts, a first fault will not cause any danger but will also
not cut off the supply.
Another application of the isolation transformer is to create a star point in grids that do not have such a point.
Quite a few applications need the neutral point for controlling purposes. When installing such a machine in a
grid without star point, the obvious remedy is to install an isolating transformer.
HUMAN SAFETY—PREVENTION OF ELECTRICAL SHOCK
The normal use for isolation transformers is to produce a zone of supply that has no reference to earth. The
majority of electric shocks are those involving contact with a live conductor while standing on, or touching an
earthed surface.
PROTECTION BY SAFETY ISOLATION OF CIRCUITS
The electrical isolation of circuits is intended to avoid electric shock that may result from contact with exposed
conductive parts liable to be made live in the event of a fault in the basic insulation of the live parts of this
circuit.
The circuit is supplied by means of a Class II isolation transformer.
The rated voltage of the secondary circuit of the isolating transformers is not more than 500 V.
The circuit supplied in this way does not have any common point with another circuit nor any point connected
to earth.
The range of the load circuit is such that the product of the voltage by the length of the wiring systems is not
more than 100,000 volt metres and that the total length of the circuit does not exceed 500 metres.
The exposed conductive parts of electrical machines and appliances used in the circuit are intentionally not
connected with earth, or with the exposed conductive parts of machines and appliances supplied by other
types of circuits.
Publication No Cu0113
Issue Date: March 2014
Page 6
If several electrical machines or appliances are connected to the same circuit, their exposed conductive parts
are connected to a protective conductor that is not connected to earth.
When the circuit supplies socket outlets, these incorporate a protective contact. These contacts with the
different sockets are arranged so that the exposed conductive parts are at the same potential, connected to
each other and to the exposed conductive part of any generator, without being earthed.
In flexible cables, the protective cover that is used as a bonding conductor is inside the same sheath as the live
conductors.
ELECTRICAL SEPARATION
Part 4-41 of IEC 60364 ‘Low voltage installations — Protection against electric shock’ specifies essential
requirements regarding protection against electric shock, including basic protection (protection against direct
contact) and fault protection (protection against indirect contact) of persons and livestock.
The following protective measures are generally permitted:
 Automatic disconnection of supply
 Double or reinforced insulation
 Electrical separation for the supply of one item of current-using equipment
 Extra-low-voltage (SELV and PELV)
Electrical separation is a protective measure in which:
 Basic protection is provided by basic insulation of live parts or by barriers and enclosures, and
 Fault protection is provided by simple separation of the separated circuit from other circuits and from
earth
Normally, this protective measure shall be limited to the supply of one item of current-using equipment
supplied from one unearthed source with simple separation.
Where more than one item of current-using equipment is supplied, the following requirements shall be met:
 The exposed-conductive-parts of the separated circuit shall be connected together by insulated, non-
earthed equipotential bonding conductors. Such conductors shall not be connected to the protective
conductors or exposed-conductive-parts of other circuits or to any extraneous-conductive-parts.
 All socket-outlets shall be provided with protective contacts which shall be connected to the
equipotential bonding system.
 Except where supplying equipment with double or reinforced insulation, all flexible cables shall
embody a protective conductor for use as an equipotential bonding conductor.
 It shall be ensured that if two faults affecting two exposed-conductive-parts occur and these are fed
by conductors of different polarity, a protective device shall disconnect the supply.
 It is recommended that the product of the nominal voltage of the circuit and length of the wiring
system should not exceed 100,000 Vm, and that the length of the wiring system should not exceed
500 metres.
Requirements for fault protection:
 The separated circuit shall be supplied through a source with at least simple separation, and the
voltage of the separated circuit shall not exceed 500 V.
 Live parts of the separated circuit shall not be connected at any point to another circuit or to earth or
to a protective conductor.
Publication No Cu0113
Issue Date: March 2014
Page 7
 To ensure electrical separation, arrangements shall be such that basic insulation is achieved between
circuits.
 The parts of flexible cables and cords liable to mechanical damage shall be visible throughout any part
of their length.
The protection by electrical separation or safety isolation can be very useful for the supply of portable and
handheld equipment.
The secondary of the isolating transformer will be floating. The current leakage path to ground is eliminated,
which helps eliminate the shock hazard.
When there is an insulation fault in a Class I machine or appliance, a person touching the enclosure under
tension, (even touching a live wire), will not be subjected to a shock as there is no current path back to the
transformer.
When using more than one Class 1 machine or piece of equipment, an unearthed equipotential bonding
should be established. This is a means of avoiding the risk of harmful pathophysiological effects on a person in
contact with simultaneously accessible exposed conductive parts in the event of two faults existing
simultaneously.
Publication No Cu0113
Issue Date: March 2014
Page 8
MEDICAL TRANSFORMERS
For the safety of the patient in hospitals, all diagnostic or therapeutic medical equipment (medical electrical
devices and non-medical electrical devices in the patient’s environment and/or areas for medical use) should
be completely isolated from the supply line (double and strengthened isolation). Complete patient/operator
safety is assured by medical isolation transformers with very low leakage current. (IEC 60601-Medical electrical
equipment; IEC 61558-2-15 ‘Safety of Power Transformers, Power Supply Units and Similar - Part 2-15:
Particular Requirements for Isolating Transformers for the Supply of Medical Locations’.)
Medical transformers are designed:
 To isolate the patient and/or the operator from an electric shock
 To protect the equipment from power surges or faulty components (see below)
Isolating transformers are used to provide a safer patient environment by minimizing the potential hazards
caused by touch voltages and by ensuring that under single fault conditions there is still continuity of supply.
The output of the isolating transformer is not connected to earth and so provides better protection from
potentially lethal shock hazards by removing the low impedance earth return path.
It should be noted that isolating transformers alone are not intended to protect against micro-shock and must
be used in conjunction with circuit integrity monitoring devices and equipotential earth bonding.
Toroidal transformers are ideal for the use in a medical environment because they are compact, can be
completely encapsulated, have low stray-fields and are therefore less likely to cause radiated electromagnetic
disturbances.
A monitoring device shall be provided to indicate the occurrence of a first fault from a live part to exposed-
conductive-parts or to earth. This device shall initiate an audible and/or visual signal that shall continue as long
as the fault persists.
If there are both audible and visible signals, it is permissible for the audible signal to be cancelled.
Nevertheless, the visual alarm shall continue as long as the fault persists.
It is recommended that a first fault be eliminated with the shortest practicable delay.
PROTECTION OF SENSITIVE EQUIPMENT
Many appliances induce high levels of interference back into their power supply. If the equipment must be
protected from this noise, isolation transformers can be used for their supply.
Extra isolating transformers are an advanced version of the isolation transformer with a different construction
method and a different method of shielding.
They will have less capacitance coupling and more noise attenuation.
They are effective for isolating sensitive equipment from any kind of power disturbance, from voltage
transients, from spikes, from DC leakage, from shocks, et cetera.
They will be used for the supply of sensitive equipment like computers, medical instrumentation, digital
communication systems, laboratory instruments, CNC machines, audio and video recording equipment, supply
of variable-frequency (variable speed) motor drives, et cetera.
Secondary neutral to ground bonding virtually eliminates common mode noise, providing an isolated neutral-
ground reference for sensitive equipment.
Publication No Cu0113
Issue Date: March 2014
Page 9
If there is multiple shielding used, it can reduce the interwinding capacitance to below 0.005 pico-farad and
increase DC isolation to over 1,000 Mega-ohm.
It acts as an efficient low pass filter and suppresses line transients, spikes, and galvanic leakage to protect
sensitive equipment.
Advantages:
 High noise attenuation level even in high frequency application
 Reduced coupling capacitance
 Suitable for higher harmonic area installation
 Longer life of the transformer because of less heat dissipation
CONSTRUCTION—CORES
The most common transformer is the laminated type. However, the more expensive toroidal type has many
advantages:
 Smaller in size for a given power level
 More efficient than the laminated types, particularly at partial load and under no-load conditions
 Lower weight
 Lower external magnetic field
 No audible noise
Apart from the price, there is another drawback: they are limited in power capacity, they have a higher inrush
current, and they are less robust.
Publication No Cu0113
Issue Date: March 2014
Page 10
CONCLUSION
We have seen that transformers can be more than just static devices that transfer electrical energy. Separation
transformers, isolation and extra isolation transformers play a major role in the protection of people and
equipment.
They come in all ranges, from very small (a few VA) to quite large (a few MVA), and although more expensive
than autotransformers or transformers with simple separate windings, they are an easy way to solve problems
that could arise concerning:
 Protecting individuals from electrical shock
 Avoiding losing power in the case of a first insulation fault
 Protecting sensitive equipment from electrical noise
 Creating a star point for equipment that require it
BIBLIOGRAPHY
 IEC 60364-4-41 ‘Low-voltage electrical installations—Part 4-41: Protection for safety—Protection
against electric shock’
 RGIE (General Regulations for Electrical Installations), Belgium
 ‘Transformers in power distribution networks’ by Stefan Fassbinder—Leonardo Energy Initiative

More Related Content

What's hot

Overload capacity of power transformers
Overload capacity of power transformersOverload capacity of power transformers
Overload capacity of power transformersLeonardo ENERGY
 
Transformers (Especially For 12th Std)
Transformers (Especially For 12th Std)Transformers (Especially For 12th Std)
Transformers (Especially For 12th Std)Atit Gaonkar
 
Transformador ideal
Transformador idealTransformador ideal
Transformador idealIván Lara
 
Basic electrical circuit theory
Basic electrical circuit theoryBasic electrical circuit theory
Basic electrical circuit theorygovind giri
 
CONDUCTORES DE MEDIA Y BAJA TENSION
CONDUCTORES DE MEDIA Y BAJA TENSIONCONDUCTORES DE MEDIA Y BAJA TENSION
CONDUCTORES DE MEDIA Y BAJA TENSIONluismairymmq
 
Hadi sadat, Power System Analysis, TMH
Hadi sadat,  Power System Analysis, TMHHadi sadat,  Power System Analysis, TMH
Hadi sadat, Power System Analysis, TMHSKIT, Jaipur
 
Basic Difference Between Wires and Cables
Basic Difference Between Wires and CablesBasic Difference Between Wires and Cables
Basic Difference Between Wires and CablesDr.Raja R
 
Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2koperundeviG
 
Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Dhrumil Maniar
 
Components of Transmission Lines
Components of Transmission LinesComponents of Transmission Lines
Components of Transmission LinesElectrical Slides
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substationEmran Ali
 
ETAP - Analisis de cortocircuito etap 11
ETAP - Analisis de cortocircuito etap 11ETAP - Analisis de cortocircuito etap 11
ETAP - Analisis de cortocircuito etap 11Himmelstern
 
Line to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power SystemLine to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power SystemSmit Shah
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSKarthik Bharadwaj
 
Transformer ppt download
Transformer ppt downloadTransformer ppt download
Transformer ppt downloadANKUSHKUMAR407
 
UNDERGROUND CABLES PRESENTATION
UNDERGROUND CABLES  PRESENTATIONUNDERGROUND CABLES  PRESENTATION
UNDERGROUND CABLES PRESENTATIONPANKAJ KUMAR
 

What's hot (20)

Transformer
TransformerTransformer
Transformer
 
Overload capacity of power transformers
Overload capacity of power transformersOverload capacity of power transformers
Overload capacity of power transformers
 
Transformers (Especially For 12th Std)
Transformers (Especially For 12th Std)Transformers (Especially For 12th Std)
Transformers (Especially For 12th Std)
 
Transformador ideal
Transformador idealTransformador ideal
Transformador ideal
 
Basic electrical circuit theory
Basic electrical circuit theoryBasic electrical circuit theory
Basic electrical circuit theory
 
CONDUCTORES DE MEDIA Y BAJA TENSION
CONDUCTORES DE MEDIA Y BAJA TENSIONCONDUCTORES DE MEDIA Y BAJA TENSION
CONDUCTORES DE MEDIA Y BAJA TENSION
 
Hadi sadat, Power System Analysis, TMH
Hadi sadat,  Power System Analysis, TMHHadi sadat,  Power System Analysis, TMH
Hadi sadat, Power System Analysis, TMH
 
Basic Difference Between Wires and Cables
Basic Difference Between Wires and CablesBasic Difference Between Wires and Cables
Basic Difference Between Wires and Cables
 
Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2
 
Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)Electrical Installation PPT (Basic Electrical Engineering)
Electrical Installation PPT (Basic Electrical Engineering)
 
Components of Transmission Lines
Components of Transmission LinesComponents of Transmission Lines
Components of Transmission Lines
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substation
 
ETAP - Analisis de cortocircuito etap 11
ETAP - Analisis de cortocircuito etap 11ETAP - Analisis de cortocircuito etap 11
ETAP - Analisis de cortocircuito etap 11
 
Line to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power SystemLine to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power System
 
PARTIAL DISCHARGES IN TRANSFORMERS
PARTIAL DISCHARGES IN TRANSFORMERSPARTIAL DISCHARGES IN TRANSFORMERS
PARTIAL DISCHARGES IN TRANSFORMERS
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTS
 
Underground cables vs overhead lines
Underground cables vs overhead linesUnderground cables vs overhead lines
Underground cables vs overhead lines
 
NS2 5.3 Basic Electricity
NS2 5.3 Basic ElectricityNS2 5.3 Basic Electricity
NS2 5.3 Basic Electricity
 
Transformer ppt download
Transformer ppt downloadTransformer ppt download
Transformer ppt download
 
UNDERGROUND CABLES PRESENTATION
UNDERGROUND CABLES  PRESENTATIONUNDERGROUND CABLES  PRESENTATION
UNDERGROUND CABLES PRESENTATION
 

Similar to Isolation transformers

Transformer and Optical isolation
Transformer and Optical isolationTransformer and Optical isolation
Transformer and Optical isolationPrasad Deshpande
 
Mohit substation
Mohit substationMohit substation
Mohit substationMohit Kumar
 
Electrical Saftey.pptx
Electrical Saftey.pptxElectrical Saftey.pptx
Electrical Saftey.pptxabell37
 
How Isolation Transformer Works - Shakti Electronics
How Isolation Transformer Works - Shakti ElectronicsHow Isolation Transformer Works - Shakti Electronics
How Isolation Transformer Works - Shakti ElectronicsShakti Electronics
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptxAsif682330
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptxAsif682330
 
IRJET- Shock Proof Wiring System
IRJET-  	  Shock Proof Wiring SystemIRJET-  	  Shock Proof Wiring System
IRJET- Shock Proof Wiring SystemIRJET Journal
 
IRJET- Shock Proof Wiring System
IRJET- Shock Proof Wiring SystemIRJET- Shock Proof Wiring System
IRJET- Shock Proof Wiring SystemIRJET Journal
 
Electrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirSheikh Shakir
 
vishal-170827171239 (1).pdf
vishal-170827171239 (1).pdfvishal-170827171239 (1).pdf
vishal-170827171239 (1).pdfSunnyYadav735981
 
PPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclPPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclVISHAL VERMA
 
TRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptx
TRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptxTRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptx
TRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptxPrabhakarTripathi16
 
Single phase transformer exp.pptx
Single phase transformer exp.pptxSingle phase transformer exp.pptx
Single phase transformer exp.pptxRamaSahityaBandaru
 
Inplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationInplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationshivashankar307
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the LightningAmeen San
 
clap switch.ppt
clap switch.pptclap switch.ppt
clap switch.pptHamed Raza
 
substation internship report
substation internship report substation internship report
substation internship report Arun Thapa
 

Similar to Isolation transformers (20)

Isolation transformers
Isolation transformersIsolation transformers
Isolation transformers
 
Transformer and Optical isolation
Transformer and Optical isolationTransformer and Optical isolation
Transformer and Optical isolation
 
11 30 kv
11 30 kv11 30 kv
11 30 kv
 
Mohit substation
Mohit substationMohit substation
Mohit substation
 
Electrical Saftey.pptx
Electrical Saftey.pptxElectrical Saftey.pptx
Electrical Saftey.pptx
 
How Isolation Transformer Works - Shakti Electronics
How Isolation Transformer Works - Shakti ElectronicsHow Isolation Transformer Works - Shakti Electronics
How Isolation Transformer Works - Shakti Electronics
 
132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx132 KV Substation Gajraula.pptx
132 KV Substation Gajraula.pptx
 
Anurag Attri.pptx
Anurag Attri.pptxAnurag Attri.pptx
Anurag Attri.pptx
 
IRJET- Shock Proof Wiring System
IRJET-  	  Shock Proof Wiring SystemIRJET-  	  Shock Proof Wiring System
IRJET- Shock Proof Wiring System
 
IRJET- Shock Proof Wiring System
IRJET- Shock Proof Wiring SystemIRJET- Shock Proof Wiring System
IRJET- Shock Proof Wiring System
 
Electrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakir
 
vishal-170827171239 (1).pdf
vishal-170827171239 (1).pdfvishal-170827171239 (1).pdf
vishal-170827171239 (1).pdf
 
PPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppclPPT on 33/11 sub-station uppcl
PPT on 33/11 sub-station uppcl
 
TRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptx
TRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptxTRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptx
TRANSMISSION AND DISTRIBUTION OF ELECTRIC POWER PROJECT.pptx
 
Pratical electricity
Pratical electricityPratical electricity
Pratical electricity
 
Single phase transformer exp.pptx
Single phase transformer exp.pptxSingle phase transformer exp.pptx
Single phase transformer exp.pptx
 
Inplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substationInplant training about 110kv/11kv substation
Inplant training about 110kv/11kv substation
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
clap switch.ppt
clap switch.pptclap switch.ppt
clap switch.ppt
 
substation internship report
substation internship report substation internship report
substation internship report
 

More from Bruno De Wachter

Transient overvoltages and currents: ferroresonance effects
Transient overvoltages and currents: ferroresonance effectsTransient overvoltages and currents: ferroresonance effects
Transient overvoltages and currents: ferroresonance effectsBruno De Wachter
 
Transient overvoltages and currents: mitigation and protection techniques
Transient overvoltages and currents: mitigation and protection techniquesTransient overvoltages and currents: mitigation and protection techniques
Transient overvoltages and currents: mitigation and protection techniquesBruno De Wachter
 
Transient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurementTransient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurementBruno De Wachter
 
Transient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipmentTransient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipmentBruno De Wachter
 
Transient overvoltages and currents: TOVs and swells
Transient overvoltages and currents: TOVs and swellsTransient overvoltages and currents: TOVs and swells
Transient overvoltages and currents: TOVs and swellsBruno De Wachter
 
Transient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesTransient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesBruno De Wachter
 
Introduction to transients and overvoltages
Introduction to transients and overvoltagesIntroduction to transients and overvoltages
Introduction to transients and overvoltagesBruno De Wachter
 
Introduction to industrial electrical process heating
Introduction to industrial electrical process heatingIntroduction to industrial electrical process heating
Introduction to industrial electrical process heatingBruno De Wachter
 
Stochastic life cycle costing
Stochastic life cycle costingStochastic life cycle costing
Stochastic life cycle costingBruno De Wachter
 
Life cycle costing (LCC): the basics
Life cycle costing (LCC): the basicsLife cycle costing (LCC): the basics
Life cycle costing (LCC): the basicsBruno De Wachter
 
Generator set design parameters
Generator set design parametersGenerator set design parameters
Generator set design parametersBruno De Wachter
 
UPS power system design parameters
UPS power system design parameters  UPS power system design parameters
UPS power system design parameters Bruno De Wachter
 
Replacement decisions for ageing physical assets
Replacement decisions for ageing physical assetsReplacement decisions for ageing physical assets
Replacement decisions for ageing physical assetsBruno De Wachter
 
Developing preventive maintenance plans with RCM
Developing preventive maintenance plans with RCMDeveloping preventive maintenance plans with RCM
Developing preventive maintenance plans with RCMBruno De Wachter
 
Electrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetimeElectrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetimeBruno De Wachter
 
Design for electrical safety
Design for electrical safetyDesign for electrical safety
Design for electrical safetyBruno De Wachter
 
Electricity systems for hospitals
Electricity systems for hospitalsElectricity systems for hospitals
Electricity systems for hospitalsBruno De Wachter
 

More from Bruno De Wachter (20)

Transient overvoltages and currents: ferroresonance effects
Transient overvoltages and currents: ferroresonance effectsTransient overvoltages and currents: ferroresonance effects
Transient overvoltages and currents: ferroresonance effects
 
Transient overvoltages and currents: mitigation and protection techniques
Transient overvoltages and currents: mitigation and protection techniquesTransient overvoltages and currents: mitigation and protection techniques
Transient overvoltages and currents: mitigation and protection techniques
 
Transient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurementTransient overvoltages and currents: detection and measurement
Transient overvoltages and currents: detection and measurement
 
Transient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipmentTransient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipment
 
Transient overvoltages and currents: TOVs and swells
Transient overvoltages and currents: TOVs and swellsTransient overvoltages and currents: TOVs and swells
Transient overvoltages and currents: TOVs and swells
 
Transient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surgesTransient overvoltages and currents: lightning surges
Transient overvoltages and currents: lightning surges
 
Introduction to transients and overvoltages
Introduction to transients and overvoltagesIntroduction to transients and overvoltages
Introduction to transients and overvoltages
 
Infrared heating
Infrared heatingInfrared heating
Infrared heating
 
Induction heating
Induction heatingInduction heating
Induction heating
 
Dielectric heating
Dielectric heatingDielectric heating
Dielectric heating
 
Introduction to industrial electrical process heating
Introduction to industrial electrical process heatingIntroduction to industrial electrical process heating
Introduction to industrial electrical process heating
 
Stochastic life cycle costing
Stochastic life cycle costingStochastic life cycle costing
Stochastic life cycle costing
 
Life cycle costing (LCC): the basics
Life cycle costing (LCC): the basicsLife cycle costing (LCC): the basics
Life cycle costing (LCC): the basics
 
Generator set design parameters
Generator set design parametersGenerator set design parameters
Generator set design parameters
 
UPS power system design parameters
UPS power system design parameters  UPS power system design parameters
UPS power system design parameters
 
Replacement decisions for ageing physical assets
Replacement decisions for ageing physical assetsReplacement decisions for ageing physical assets
Replacement decisions for ageing physical assets
 
Developing preventive maintenance plans with RCM
Developing preventive maintenance plans with RCMDeveloping preventive maintenance plans with RCM
Developing preventive maintenance plans with RCM
 
Electrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetimeElectrical storage systems: efficiency and lifetime
Electrical storage systems: efficiency and lifetime
 
Design for electrical safety
Design for electrical safetyDesign for electrical safety
Design for electrical safety
 
Electricity systems for hospitals
Electricity systems for hospitalsElectricity systems for hospitals
Electricity systems for hospitals
 

Recently uploaded

HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 

Recently uploaded (20)

HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 

Isolation transformers

  • 1. APPLICATION NOTE ISOLATION TRANSFORMERS Paul De Potter March 2014 ECI Publication No Cu0113 Available from www.leonardo-energy.org
  • 2. Publication No Cu0113 Issue Date: March 2014 Page i Document Issue Control Sheet Document Title: Application note – Isolation transformers Publication No: Cu0113 Issue: 03 Release: Public Content provider(s) Paul De Potter Author(s): Paul De Potter Editorial and language review Bruno De Wachter (editorial), Noel Montrucchio (English Upgrade) Content review: Stefan Fassbinder Document History Issue Date Purpose 1 April 2011 Initial release 2 September 2011 Minor revision for publication in the Good Practice Guide 3 March 2014 Review in the framework of the GPG Disclaimer While this publication has been prepared with care, European Copper Institute and other contributors provide no warranty with regards to the content and shall not be liable for any direct, incidental or consequential damages that may result from the use of the information or the data contained. Copyright© European Copper Institute. Reproduction is authorized providing the material is unabridged and the source is acknowledged.
  • 3. Publication No Cu0113 Issue Date: March 2014 Page ii CONTENTS Summary ........................................................................................................................................................ 1 Introduction.................................................................................................................................................... 2 Isolation transformers .................................................................................................................................... 2 Advantages of isolation transformers............................................................................................................. 4 Applications.................................................................................................................................................... 4 Human Safety—Prevention of electrical shock ......................................................................................................5 Protection by safety isolation of circuits..................................................................................................5 Electrical separation.................................................................................................................................6 Medical transformers...............................................................................................................................8 Protection of sensitive equipment .........................................................................................................................8 Construction—Cores....................................................................................................................................... 9 Conclusion .................................................................................................................................................... 10 Bibliography ................................................................................................................................................. 10
  • 4. Publication No Cu0113 Issue Date: March 2014 Page 1 SUMMARY Transformers can do more than transferring electrical energy from one voltage to another. Separation transformers, isolation transformers, and extra isolation transformers play a major role in the protection of people and equipment. They come in different types and power ranges, from a few VA to a few MVA. Although they are generally more expensive than autotransformers or transformers with conventionally separated windings, they can be very useful in many ways, for example:  To protect individuals against electrical shock  To avoid losing power after a first insulation fault  To protect sensitive equipment from electrical noise  To create a star point for equipment This application note discusses the working principles of isolation transformers, their advantages, and their various application domains.
  • 5. Publication No Cu0113 Issue Date: March 2014 Page 2 INTRODUCTION A transformer is an electrical device that transfers electrical energy from one circuit to another using induction. A current in the primary windings creates a varying magnetic flux in the transformer’s core and thus creates a varying magnetic field in the secondary windings. Apart from some special cases, there is no connection between the input (the primary windings) and the output (the secondary windings). In many cases, the property of transferring electrical energy will be used to obtain a higher or lower level of voltage. The induced voltage in the secondary windings is in direct proportion to the primary voltage and is determined by the ratio of the number of turns in the secondary (ns) to the number of turns in the primary (np) as follows: Us/Un= ns / np Electrical transformers can be configured as single-phase or three-phase; oil-filled or dry type devices. They are used for many different applications, including control, distribution, instrumentation, current transformation and power transformation among others. There are also many different mounting possibilities. The special case where there is a connection between primary and secondary windings is called an autotransformer. There is only one winding, and a part of this winding is common to both the primary and the secondary circuits. Figure 1 – Autotransformer The autotransformer will generally be used as a voltage conversion of the local supply to another voltage value that is required for a particular piece of equipment (step-up or step-down). Although there are some benefits in the use of an autotransformer, it is obvious that there are also many drawbacks. A major one is the fact that there is no isolation for disturbances or interferences coming from the primary. ISOLATION TRANSFORMERS Usually electrical transformers are used to transform voltage from a higher level to a lower voltage or vice versa. They do little to attenuate the passage of noise or transients from the primary to the secondary. Transformers can also be used to change the impedance of the electrical circuit to reduce the short-circuit current or to provide a galvanic insulation between two systems. In theory, the definition of ‘isolation transformer’ applies to any transformer where there is no direct connection between the primary and the secondary windings. In other words: all transformers which are not autotransformers. The windings are connected only by the magnetic flux in the core.
  • 6. Publication No Cu0113 Issue Date: March 2014 Page 3 Nevertheless, when there is only a basic separation between the primary and secondary windings, we will speak of a separation transformer. Figure 2 – Separation transformer The insulation between the primary and the secondary windings provides a degree of protection against electric shock that is equivalent to a basic insulation. Reminder: basic insulation is the insulation required for ensuring the appropriate operation of the equipment and of the electrical installations and for the fundamental protection against electric shock. This separation will limit the risk in the event of accidental simultaneous contact with the exposed conductive part and the live parts (or metals parts that can become live in the event of an insulation fault). Taking the insulation between the primary and the secondary windings a step further, we get to the isolation transformers. Figure 3 – Isolation transformer The insulation between the primary and the secondary windings provides a degree of protection against electric shock equivalent to that of double insulation. This separation will limit the risk in the event of accidental simultaneous contact with the exposed conductive part and the live parts (or metals parts that can become live in the event of an insulation fault). Reminder: double insulation is the insulation in which provision is made for separate supplementary insulation in addition to basic insulation. It is determined by type tests. When the no-load secondary voltage of the isolation transformer is limited to UL,where UL is the Safety Extra Low Voltage (SELV) Limit, then we have a ‘safety transformer.’
  • 7. Publication No Cu0113 Issue Date: March 2014 Page 4 Figure 4 – Safety transformers ADVANTAGES OF ISOLATION TRANSFORMERS Isolation transformers can be used to protect people against the dangers of electric shocks. Isolation transformers can block transmission of DC signals from one circuit to the other, but allow AC signals to pass. They will also block interference caused by ground loops. Isolation transformers with electrostatic shields are used for power supplies for sensitive equipment such as medical equipment, computers or precision laboratory measurement instruments. There are two ways to introduce the equivalent of double isolation:  By putting a metallic safety shield (usually copper) between the primary and secondary windings and connecting it to the ground (protective earth). This can also be another winding or a metal strip surrounding a winding. If the isolation breaks, the electricity flows to the ground, providing the required safety. The shield will attenuate or filter voltage spikes and will greatly reduce the coupling of common-mode noise by decreasing the capacitive coupling.  By using reinforced insulation. This type of insulation is made up of multiple layers. All layers must pass tests required by established standards. If one layer breaks, the next layer provides the required safety. Normally, these transformers have a lower leakage current than those that use a shield. Electrical noise: Common mode: between ground and the current carrying conductors, including the neutral Normal mode: between two current carrying conductors, including line to neutral Isolation transformers will mostly be used in a one-to-one ratio (the primary voltage rating equals the rated secondary voltage value). The two windings will have the same number of turns. There might be a slight difference in the number of turns to compensate for voltage drops; otherwise, the secondary voltage would be slightly less than the primary voltage. APPLICATIONS Let us look at a few cases where the use of an isolation transformer is a possibility or even recommended Isolation transformers will be mainly used to protect people from electric shock and as a power supply for sensitive equipment (computers, medical equipment, laboratory equipment, et cetera).
  • 8. Publication No Cu0113 Issue Date: March 2014 Page 5 Isolation transformers are often used to isolate the machine or equipment from the rest of the electrical installation, to avoid loss of power in the case of a first insulation fault. Since there is no return path to the source (the secondary winding of the transformer), in the event of a fault, there will be no fault current flowing and no overcurrent protective device will cut off the supply. Apart from being harmless to persons touching the conductive parts, a first fault will not cause any danger but will also not cut off the supply. Another application of the isolation transformer is to create a star point in grids that do not have such a point. Quite a few applications need the neutral point for controlling purposes. When installing such a machine in a grid without star point, the obvious remedy is to install an isolating transformer. HUMAN SAFETY—PREVENTION OF ELECTRICAL SHOCK The normal use for isolation transformers is to produce a zone of supply that has no reference to earth. The majority of electric shocks are those involving contact with a live conductor while standing on, or touching an earthed surface. PROTECTION BY SAFETY ISOLATION OF CIRCUITS The electrical isolation of circuits is intended to avoid electric shock that may result from contact with exposed conductive parts liable to be made live in the event of a fault in the basic insulation of the live parts of this circuit. The circuit is supplied by means of a Class II isolation transformer. The rated voltage of the secondary circuit of the isolating transformers is not more than 500 V. The circuit supplied in this way does not have any common point with another circuit nor any point connected to earth. The range of the load circuit is such that the product of the voltage by the length of the wiring systems is not more than 100,000 volt metres and that the total length of the circuit does not exceed 500 metres. The exposed conductive parts of electrical machines and appliances used in the circuit are intentionally not connected with earth, or with the exposed conductive parts of machines and appliances supplied by other types of circuits.
  • 9. Publication No Cu0113 Issue Date: March 2014 Page 6 If several electrical machines or appliances are connected to the same circuit, their exposed conductive parts are connected to a protective conductor that is not connected to earth. When the circuit supplies socket outlets, these incorporate a protective contact. These contacts with the different sockets are arranged so that the exposed conductive parts are at the same potential, connected to each other and to the exposed conductive part of any generator, without being earthed. In flexible cables, the protective cover that is used as a bonding conductor is inside the same sheath as the live conductors. ELECTRICAL SEPARATION Part 4-41 of IEC 60364 ‘Low voltage installations — Protection against electric shock’ specifies essential requirements regarding protection against electric shock, including basic protection (protection against direct contact) and fault protection (protection against indirect contact) of persons and livestock. The following protective measures are generally permitted:  Automatic disconnection of supply  Double or reinforced insulation  Electrical separation for the supply of one item of current-using equipment  Extra-low-voltage (SELV and PELV) Electrical separation is a protective measure in which:  Basic protection is provided by basic insulation of live parts or by barriers and enclosures, and  Fault protection is provided by simple separation of the separated circuit from other circuits and from earth Normally, this protective measure shall be limited to the supply of one item of current-using equipment supplied from one unearthed source with simple separation. Where more than one item of current-using equipment is supplied, the following requirements shall be met:  The exposed-conductive-parts of the separated circuit shall be connected together by insulated, non- earthed equipotential bonding conductors. Such conductors shall not be connected to the protective conductors or exposed-conductive-parts of other circuits or to any extraneous-conductive-parts.  All socket-outlets shall be provided with protective contacts which shall be connected to the equipotential bonding system.  Except where supplying equipment with double or reinforced insulation, all flexible cables shall embody a protective conductor for use as an equipotential bonding conductor.  It shall be ensured that if two faults affecting two exposed-conductive-parts occur and these are fed by conductors of different polarity, a protective device shall disconnect the supply.  It is recommended that the product of the nominal voltage of the circuit and length of the wiring system should not exceed 100,000 Vm, and that the length of the wiring system should not exceed 500 metres. Requirements for fault protection:  The separated circuit shall be supplied through a source with at least simple separation, and the voltage of the separated circuit shall not exceed 500 V.  Live parts of the separated circuit shall not be connected at any point to another circuit or to earth or to a protective conductor.
  • 10. Publication No Cu0113 Issue Date: March 2014 Page 7  To ensure electrical separation, arrangements shall be such that basic insulation is achieved between circuits.  The parts of flexible cables and cords liable to mechanical damage shall be visible throughout any part of their length. The protection by electrical separation or safety isolation can be very useful for the supply of portable and handheld equipment. The secondary of the isolating transformer will be floating. The current leakage path to ground is eliminated, which helps eliminate the shock hazard. When there is an insulation fault in a Class I machine or appliance, a person touching the enclosure under tension, (even touching a live wire), will not be subjected to a shock as there is no current path back to the transformer. When using more than one Class 1 machine or piece of equipment, an unearthed equipotential bonding should be established. This is a means of avoiding the risk of harmful pathophysiological effects on a person in contact with simultaneously accessible exposed conductive parts in the event of two faults existing simultaneously.
  • 11. Publication No Cu0113 Issue Date: March 2014 Page 8 MEDICAL TRANSFORMERS For the safety of the patient in hospitals, all diagnostic or therapeutic medical equipment (medical electrical devices and non-medical electrical devices in the patient’s environment and/or areas for medical use) should be completely isolated from the supply line (double and strengthened isolation). Complete patient/operator safety is assured by medical isolation transformers with very low leakage current. (IEC 60601-Medical electrical equipment; IEC 61558-2-15 ‘Safety of Power Transformers, Power Supply Units and Similar - Part 2-15: Particular Requirements for Isolating Transformers for the Supply of Medical Locations’.) Medical transformers are designed:  To isolate the patient and/or the operator from an electric shock  To protect the equipment from power surges or faulty components (see below) Isolating transformers are used to provide a safer patient environment by minimizing the potential hazards caused by touch voltages and by ensuring that under single fault conditions there is still continuity of supply. The output of the isolating transformer is not connected to earth and so provides better protection from potentially lethal shock hazards by removing the low impedance earth return path. It should be noted that isolating transformers alone are not intended to protect against micro-shock and must be used in conjunction with circuit integrity monitoring devices and equipotential earth bonding. Toroidal transformers are ideal for the use in a medical environment because they are compact, can be completely encapsulated, have low stray-fields and are therefore less likely to cause radiated electromagnetic disturbances. A monitoring device shall be provided to indicate the occurrence of a first fault from a live part to exposed- conductive-parts or to earth. This device shall initiate an audible and/or visual signal that shall continue as long as the fault persists. If there are both audible and visible signals, it is permissible for the audible signal to be cancelled. Nevertheless, the visual alarm shall continue as long as the fault persists. It is recommended that a first fault be eliminated with the shortest practicable delay. PROTECTION OF SENSITIVE EQUIPMENT Many appliances induce high levels of interference back into their power supply. If the equipment must be protected from this noise, isolation transformers can be used for their supply. Extra isolating transformers are an advanced version of the isolation transformer with a different construction method and a different method of shielding. They will have less capacitance coupling and more noise attenuation. They are effective for isolating sensitive equipment from any kind of power disturbance, from voltage transients, from spikes, from DC leakage, from shocks, et cetera. They will be used for the supply of sensitive equipment like computers, medical instrumentation, digital communication systems, laboratory instruments, CNC machines, audio and video recording equipment, supply of variable-frequency (variable speed) motor drives, et cetera. Secondary neutral to ground bonding virtually eliminates common mode noise, providing an isolated neutral- ground reference for sensitive equipment.
  • 12. Publication No Cu0113 Issue Date: March 2014 Page 9 If there is multiple shielding used, it can reduce the interwinding capacitance to below 0.005 pico-farad and increase DC isolation to over 1,000 Mega-ohm. It acts as an efficient low pass filter and suppresses line transients, spikes, and galvanic leakage to protect sensitive equipment. Advantages:  High noise attenuation level even in high frequency application  Reduced coupling capacitance  Suitable for higher harmonic area installation  Longer life of the transformer because of less heat dissipation CONSTRUCTION—CORES The most common transformer is the laminated type. However, the more expensive toroidal type has many advantages:  Smaller in size for a given power level  More efficient than the laminated types, particularly at partial load and under no-load conditions  Lower weight  Lower external magnetic field  No audible noise Apart from the price, there is another drawback: they are limited in power capacity, they have a higher inrush current, and they are less robust.
  • 13. Publication No Cu0113 Issue Date: March 2014 Page 10 CONCLUSION We have seen that transformers can be more than just static devices that transfer electrical energy. Separation transformers, isolation and extra isolation transformers play a major role in the protection of people and equipment. They come in all ranges, from very small (a few VA) to quite large (a few MVA), and although more expensive than autotransformers or transformers with simple separate windings, they are an easy way to solve problems that could arise concerning:  Protecting individuals from electrical shock  Avoiding losing power in the case of a first insulation fault  Protecting sensitive equipment from electrical noise  Creating a star point for equipment that require it BIBLIOGRAPHY  IEC 60364-4-41 ‘Low-voltage electrical installations—Part 4-41: Protection for safety—Protection against electric shock’  RGIE (General Regulations for Electrical Installations), Belgium  ‘Transformers in power distribution networks’ by Stefan Fassbinder—Leonardo Energy Initiative