SlideShare a Scribd company logo
1 of 2
Download to read offline
Sample coolers are small shell and tube heat exchangers that are used to cool hot fluids or
to condense vapors such as steam to a point at which they pose no concern for personnel
safety. These are usually used to cool the fluid as it is being collect for analysis.
Sample coolers are not only used to cool samples but also
to temper the sample to the appropriate temperature for
the analysis being performed. This is important as some
analysis procedures can be affected by interferences
directly or indirectly due to the fluid temperature.
For example, when sampling steam condensate in order to
check the pH of the water, the samples should be cooled
sufficiently for safe collection and handling while avoiding
overcooling. A relatively common recommendation for
analysis of steam condensate pH is for the cooled sample
to be in the range of 100 to 105 degrees F. It is extremely
important that pH measurements be made on cooled
samples. If the sample is hot, carbon dioxide in the water
sample will be liberated from the sample and escape into
the atmosphere, which results in artificially or falsely high
pH measurements. Cooling will minimize the carbon
dioxide that will flash off from the sample. When the
carbon dioxide flashes off from the sample, it is no longer
present in the condensate sample which will result in this
measurement to be falsely high. The difference between
in-line cooled steam condensate samples and condensate
cooled at atmospheric ambient temperatures and exposed
to the atmosphere can be 2.0 pH units or more. Obviously,
this difference in pH could have implications to correctly
applying treatment to the steam condensate system and
the corrosion rates experienced.
It is sometimes also argued that over-cooled samples,
particularly if they are left exposed to the atmosphere, can
result in some atmospheric carbon dioxide and oxygen to
be absorbed into solution from the atmosphere, again
potentially resulting in false results. With regard to oxygen
for example, oxygen is more soluble in cold water than in
hot water. Therefore, it can be argued that some amount
of oxygen can potentially be absorbed in over-cooled
samples.
In applications such as described above, the practice of
local conditioning or cooling and analysis is often
exercised. This means that the sample is cooled with the
use of an in-line sample cooler relatively close to the point
of extraction from the process and the analysis is
performed at the sample cooler using a continuously
flowing sample from the cooler. This minimizes the
potential for interferences as a result of prolonged
exposure of the sample to the atmosphere when the
analysis is performed and as while the analytical
equipment acclimates to the sample and compensates for
the temperature of the sample.
Proper conditioning, collection and storage of samples
collected for remote analysis also needs to be considered.
Where samples are collected in containers so that they can
be transported to a remote location for analysis, diligence
regarding the manner in which the sample is collected is
also important. Depending on the type of analysis to be
performed, how the sample is collected can impact the
degree of interferences and the accuracy of results. Some
considerations may include but are not necessarily limited
to the following.
The correct sample temperature should be
considered for laboratory instruments and
procedures utilized.
The duration of time elapsed from when the
sample is collected to when the analysis is
performed.
Completely filling the container to the brim to
displace atmospheric gasses from the container.
Immediately capping the container to reduce
sample exposure to atmospheric conditions or
contamination.
Adequate purging of sample line is necessary to
assure a representative and “fresh” sample.
Minimize splashing, agitation and exposure to
atmosphere. Some methods for analysis
recommended that the sampling tube be long
enough to extend to the bottom of the sample
container and for the end of the sampling tube
to remain immersed in the collected sample fluid
until the required volume is obtained. This
reduces exposure to atmospheric gasses.
Another consideration for the temperature of conditioned
or cooled samples is the desired temperature of the
analytical equipment and procedures being utilized. Some
analytical equipment for instance has an optimal
temperature of 77 degrees F. The degree of deviation from
the desired temperature may affect the accuracy of the
measurement and/or the time required for the equipment
to compensate for the difference in temperature. These
factors should also be considered regarding the
appropriate temperature of samples conditioned or cooled
for analysis.
The Proper Use and Benefits of Sample
Coolers in Steam Plant Applications $
When purchasing or installing a sample cooler, the
conditions and application for which the cooler will be
utilized should be considered. Sample coolers are designed
and specified in various sizes and with varying rates of
heat removal. Identifying the correct sample cooler for the
application will be useful in assuring the following.
Safety of the personnel collecting samples.
The appropriate degrees of conditioning/cooling
of samples for the specific analysis to be
performed or instruments utilized.
Minimize the potential for interferences that
may result in inaccurate analysis results.
Minimizing waste from excessive amounts of
cooling water being required.
Adjustment of the cooling water flow to the sample cooler
can result in the appropriate temperature for the analysis
being performed. This can be done by installing an
additional valve which is used to throttle the flow to
achieve the desired temperature. The same may also be
accomplished by installing an orifice or flow restrictor.
Both of these methods can be employed to achieve the
desired sample temperature if the conditions, such as
temperature and pressure of the stream being sampled
and the cooling water remains stable and unchanged. This
can also minimize the variability in sample conditioning
and analytical results when tests are performed by
numerous individuals.
Additionally, diligence in understanding the importance of
employing proper sample conditioning techniques also can
reveal potential for water savings. Restricting or
controlling cooling water flows to sample coolers for the
degree of cooling required for the analysis performed can
reduce water usage. Furthermore, identifying alternative
sources of water for cooling of samples can result in even
greater water savings.
One example of an alternative cooling water source for
sample conditioning is the use of open recirculating
cooling system water. This is often available with
pressures and temperatures sufficient for sample cooling
and has the added benefit that it has been treated for
scale and corrosion inhibition that will protect the
internals of the sample cooler and result in increased
longevity of the heat exchanger for sample cooling.
Sample coolers are available in numerous sizes and
configurations depending on the application that they will
be used in. Cooling water flows can range from less than
one gallon per minute to greater than 20 gallons per
minute. It is also not uncommon for a single facility to
have multiple sample coolers used in various applications.
When one considers the amount of water potentially used
in sample cooling applications, it is easy to perceive that
there may be appreciable potential for water savings.
Recognizing the benefits of employing proper controlled
conditioning of samples is important for safe and efficient
operation of steam plants as well as numerous other
industries. System operations can be optimized resulting in
increased output, on-stream time, longevity of equipment,
personnel safety and water savings.
By Robert Jewell
Robert has 30 years of career experience in industrial utilities. He specializes in and has extensive
experience in the operation and management of steam plants, central plants, cooling and
refrigeration systems, potable (drinking) water systems, water treatment, wastewater treatment,
and facility management.
He is an advocate of water conservation, energy conservation and protecting our environment while
also incorporating those advocacies into sustainable water and energy efficiency activities and
programs that positively impact the organization and local community by finding efficiency and
savings in existing processes and procedures through creative solutions.
Connect with Robert on Linkedin at http://www.linkedin.com/pub/bob-jewell/26/810/32a

More Related Content

What's hot

Relief and blowdown in
Relief and blowdown           inRelief and blowdown           in
Relief and blowdown inAkshay Kotkar
 
Cold water supply and pipe sizing
Cold water supply and pipe sizingCold water supply and pipe sizing
Cold water supply and pipe sizingHumphrey Samati
 
Intevras Company Overview Jan 09
Intevras Company Overview   Jan 09Intevras Company Overview   Jan 09
Intevras Company Overview Jan 09tlucario
 
3 Best Practices for 100% Regulatory Compliant Testing
3 Best Practices for 100% Regulatory Compliant Testing3 Best Practices for 100% Regulatory Compliant Testing
3 Best Practices for 100% Regulatory Compliant TestingMarcus & Millichap
 
Module 2 familiarization with laboratory wares and equipment
Module 2 familiarization with laboratory wares and equipmentModule 2 familiarization with laboratory wares and equipment
Module 2 familiarization with laboratory wares and equipmentMansiBhavsar10
 
Oxygen planning and management- Hospitals
Oxygen planning and management- HospitalsOxygen planning and management- Hospitals
Oxygen planning and management- HospitalsLallu Joseph
 
Vapor Compression Refrigeration System
Vapor Compression Refrigeration System Vapor Compression Refrigeration System
Vapor Compression Refrigeration System Abduljalil Al-Abidi
 
Basic Manual Water Level Measurement
Basic Manual Water Level MeasurementBasic Manual Water Level Measurement
Basic Manual Water Level MeasurementHydroG Resources
 
SRU Troubleshooting
SRU TroubleshootingSRU Troubleshooting
SRU TroubleshootingAhmed Omran
 
Water-Gas-Shift Reactor Loading & Unloading Considerations
Water-Gas-Shift Reactor Loading & Unloading ConsiderationsWater-Gas-Shift Reactor Loading & Unloading Considerations
Water-Gas-Shift Reactor Loading & Unloading ConsiderationsGerard B. Hawkins
 
FORBLUE sunsep™ Membranes for Gas Drying and Humidification
FORBLUE sunsep™ Membranes for Gas Drying and HumidificationFORBLUE sunsep™ Membranes for Gas Drying and Humidification
FORBLUE sunsep™ Membranes for Gas Drying and HumidificationAGC Chemicals Americas
 
Tips to Perform Pipette Calibration
Tips to Perform Pipette CalibrationTips to Perform Pipette Calibration
Tips to Perform Pipette CalibrationEdword Simpson
 

What's hot (20)

Pipeline drying
Pipeline dryingPipeline drying
Pipeline drying
 
Relief and blowdown in
Relief and blowdown           inRelief and blowdown           in
Relief and blowdown in
 
Cold water supply and pipe sizing
Cold water supply and pipe sizingCold water supply and pipe sizing
Cold water supply and pipe sizing
 
Intevras Company Overview Jan 09
Intevras Company Overview   Jan 09Intevras Company Overview   Jan 09
Intevras Company Overview Jan 09
 
3 Best Practices for 100% Regulatory Compliant Testing
3 Best Practices for 100% Regulatory Compliant Testing3 Best Practices for 100% Regulatory Compliant Testing
3 Best Practices for 100% Regulatory Compliant Testing
 
Adm apn051-en
Adm apn051-enAdm apn051-en
Adm apn051-en
 
Chapter 03
Chapter 03Chapter 03
Chapter 03
 
Module 2 familiarization with laboratory wares and equipment
Module 2 familiarization with laboratory wares and equipmentModule 2 familiarization with laboratory wares and equipment
Module 2 familiarization with laboratory wares and equipment
 
Oxygen planning and management- Hospitals
Oxygen planning and management- HospitalsOxygen planning and management- Hospitals
Oxygen planning and management- Hospitals
 
Vapor Compression Refrigeration System
Vapor Compression Refrigeration System Vapor Compression Refrigeration System
Vapor Compression Refrigeration System
 
Basic Manual Water Level Measurement
Basic Manual Water Level MeasurementBasic Manual Water Level Measurement
Basic Manual Water Level Measurement
 
SRU Troubleshooting
SRU TroubleshootingSRU Troubleshooting
SRU Troubleshooting
 
Chapter 12
Chapter 12Chapter 12
Chapter 12
 
Water-Gas-Shift Reactor Loading & Unloading Considerations
Water-Gas-Shift Reactor Loading & Unloading ConsiderationsWater-Gas-Shift Reactor Loading & Unloading Considerations
Water-Gas-Shift Reactor Loading & Unloading Considerations
 
FORBLUE sunsep™ Membranes for Gas Drying and Humidification
FORBLUE sunsep™ Membranes for Gas Drying and HumidificationFORBLUE sunsep™ Membranes for Gas Drying and Humidification
FORBLUE sunsep™ Membranes for Gas Drying and Humidification
 
Lecture notes
Lecture notesLecture notes
Lecture notes
 
Tips to Perform Pipette Calibration
Tips to Perform Pipette CalibrationTips to Perform Pipette Calibration
Tips to Perform Pipette Calibration
 
Plumbing training
Plumbing training Plumbing training
Plumbing training
 
Steralization
SteralizationSteralization
Steralization
 
Piping design sheets
Piping design sheetsPiping design sheets
Piping design sheets
 

Similar to Proper Use and Benefits of Sample Coolers

ce_332 Environmental Engineering- Lab I.pdf
ce_332 Environmental Engineering- Lab I.pdfce_332 Environmental Engineering- Lab I.pdf
ce_332 Environmental Engineering- Lab I.pdfAli Al-naqa
 
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17PerkinElmer, Inc.
 
Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17PerkinElmer, Inc.
 
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17PerkinElmer, Inc.
 
An Innovative Approach for Humidity Control by Using Deliquescent Materials i...
An Innovative Approach for Humidity Control by Using Deliquescent Materials i...An Innovative Approach for Humidity Control by Using Deliquescent Materials i...
An Innovative Approach for Humidity Control by Using Deliquescent Materials i...IJMER
 
EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)
EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)
EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)Shikha Popali
 
Thermal techniques- DSC- Durgashree Diwakar
Thermal techniques- DSC- Durgashree DiwakarThermal techniques- DSC- Durgashree Diwakar
Thermal techniques- DSC- Durgashree DiwakarDurgashree Diwakar
 
World Of Biotechnology
World Of BiotechnologyWorld Of Biotechnology
World Of BiotechnologyVaibhav Dubey
 
Humidication in NICU - Dr Padmesh - Neonatology
Humidication in NICU - Dr Padmesh - NeonatologyHumidication in NICU - Dr Padmesh - Neonatology
Humidication in NICU - Dr Padmesh - NeonatologyDr Padmesh Vadakepat
 
DSC | DIFFERENTIAL SCANNING CALORIMETRY
DSC | DIFFERENTIAL SCANNING CALORIMETRYDSC | DIFFERENTIAL SCANNING CALORIMETRY
DSC | DIFFERENTIAL SCANNING CALORIMETRYKarthic27
 
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report     7Midterm Lab ReportIntroductionCell.docxMidterm Lad Report     7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docxroushhsiu
 
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report     7Midterm Lab ReportIntroductionCell.docxMidterm Lad Report     7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docxjessiehampson
 
Seminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahilSeminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahilsahilhusen
 
Seminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahilSeminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahilsahilhusen
 
IRJET- An Experimental Study of the Effect of Capillary Tube in Different...
IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...
IRJET- An Experimental Study of the Effect of Capillary Tube in Different...IRJET Journal
 
Design of electric stirrer.
Design of electric stirrer.Design of electric stirrer.
Design of electric stirrer.rohan deshmukh
 

Similar to Proper Use and Benefits of Sample Coolers (20)

ce_332 Environmental Engineering- Lab I.pdf
ce_332 Environmental Engineering- Lab I.pdfce_332 Environmental Engineering- Lab I.pdf
ce_332 Environmental Engineering- Lab I.pdf
 
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
 
Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using U.S. EPA Method TO-17
 
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
Analysis of Volatile Organic Compounds (VOCs) in Air Using US EPA Method TO-17
 
An Innovative Approach for Humidity Control by Using Deliquescent Materials i...
An Innovative Approach for Humidity Control by Using Deliquescent Materials i...An Innovative Approach for Humidity Control by Using Deliquescent Materials i...
An Innovative Approach for Humidity Control by Using Deliquescent Materials i...
 
EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)
EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)
EXPERIMENT PARAMETERS OF DIFFERENTIAL SCANNING CALORIMETRY (DSC)
 
TGA and DSC ppt
TGA and DSC ppt   TGA and DSC ppt
TGA and DSC ppt
 
Presentation of industrial pharmacy 2
Presentation  of industrial pharmacy 2Presentation  of industrial pharmacy 2
Presentation of industrial pharmacy 2
 
Thermal techniques- DSC- Durgashree Diwakar
Thermal techniques- DSC- Durgashree DiwakarThermal techniques- DSC- Durgashree Diwakar
Thermal techniques- DSC- Durgashree Diwakar
 
World Of Biotechnology
World Of BiotechnologyWorld Of Biotechnology
World Of Biotechnology
 
Presentation of industrial pharmacy 2
Presentation of industrial pharmacy 2Presentation of industrial pharmacy 2
Presentation of industrial pharmacy 2
 
Humidication in NICU - Dr Padmesh - Neonatology
Humidication in NICU - Dr Padmesh - NeonatologyHumidication in NICU - Dr Padmesh - Neonatology
Humidication in NICU - Dr Padmesh - Neonatology
 
DSC | DIFFERENTIAL SCANNING CALORIMETRY
DSC | DIFFERENTIAL SCANNING CALORIMETRYDSC | DIFFERENTIAL SCANNING CALORIMETRY
DSC | DIFFERENTIAL SCANNING CALORIMETRY
 
Mpat presentation
Mpat presentationMpat presentation
Mpat presentation
 
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report     7Midterm Lab ReportIntroductionCell.docxMidterm Lad Report     7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docx
 
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report     7Midterm Lab ReportIntroductionCell.docxMidterm Lad Report     7Midterm Lab ReportIntroductionCell.docx
Midterm Lad Report 7Midterm Lab ReportIntroductionCell.docx
 
Seminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahilSeminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahil
 
Seminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahilSeminor on accelerated stability testing of dosage forms sahil
Seminor on accelerated stability testing of dosage forms sahil
 
IRJET- An Experimental Study of the Effect of Capillary Tube in Different...
IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...
IRJET- An Experimental Study of the Effect of Capillary Tube in Different...
 
Design of electric stirrer.
Design of electric stirrer.Design of electric stirrer.
Design of electric stirrer.
 

More from Bob Jewell

MN DLI CCAC 20160411
MN DLI CCAC 20160411MN DLI CCAC 20160411
MN DLI CCAC 20160411Bob Jewell
 
Bob Jewell Deaerator Operations Letter
Bob Jewell Deaerator Operations LetterBob Jewell Deaerator Operations Letter
Bob Jewell Deaerator Operations LetterBob Jewell
 
Solenis Letter 20150605
Solenis Letter 20150605Solenis Letter 20150605
Solenis Letter 20150605Bob Jewell
 
boiler_legislature08
boiler_legislature08boiler_legislature08
boiler_legislature08Bob Jewell
 
CCAC Appointment 2009
CCAC Appointment 2009CCAC Appointment 2009
CCAC Appointment 2009Bob Jewell
 
CCAC Reappointment 2012
CCAC Reappointment 2012CCAC Reappointment 2012
CCAC Reappointment 2012Bob Jewell
 
Arise Inspections Sept 2015
Arise Inspections Sept 2015Arise Inspections Sept 2015
Arise Inspections Sept 2015Bob Jewell
 
Solenis Letter 20150605
Solenis Letter 20150605Solenis Letter 20150605
Solenis Letter 20150605Bob Jewell
 
AUG 2015 Ethanol Producer Magazine Operations Leader
AUG 2015 Ethanol Producer Magazine Operations LeaderAUG 2015 Ethanol Producer Magazine Operations Leader
AUG 2015 Ethanol Producer Magazine Operations LeaderBob Jewell
 
Water Well Operation and Yeild
Water Well Operation and YeildWater Well Operation and Yeild
Water Well Operation and YeildBob Jewell
 

More from Bob Jewell (10)

MN DLI CCAC 20160411
MN DLI CCAC 20160411MN DLI CCAC 20160411
MN DLI CCAC 20160411
 
Bob Jewell Deaerator Operations Letter
Bob Jewell Deaerator Operations LetterBob Jewell Deaerator Operations Letter
Bob Jewell Deaerator Operations Letter
 
Solenis Letter 20150605
Solenis Letter 20150605Solenis Letter 20150605
Solenis Letter 20150605
 
boiler_legislature08
boiler_legislature08boiler_legislature08
boiler_legislature08
 
CCAC Appointment 2009
CCAC Appointment 2009CCAC Appointment 2009
CCAC Appointment 2009
 
CCAC Reappointment 2012
CCAC Reappointment 2012CCAC Reappointment 2012
CCAC Reappointment 2012
 
Arise Inspections Sept 2015
Arise Inspections Sept 2015Arise Inspections Sept 2015
Arise Inspections Sept 2015
 
Solenis Letter 20150605
Solenis Letter 20150605Solenis Letter 20150605
Solenis Letter 20150605
 
AUG 2015 Ethanol Producer Magazine Operations Leader
AUG 2015 Ethanol Producer Magazine Operations LeaderAUG 2015 Ethanol Producer Magazine Operations Leader
AUG 2015 Ethanol Producer Magazine Operations Leader
 
Water Well Operation and Yeild
Water Well Operation and YeildWater Well Operation and Yeild
Water Well Operation and Yeild
 

Proper Use and Benefits of Sample Coolers

  • 1. Sample coolers are small shell and tube heat exchangers that are used to cool hot fluids or to condense vapors such as steam to a point at which they pose no concern for personnel safety. These are usually used to cool the fluid as it is being collect for analysis. Sample coolers are not only used to cool samples but also to temper the sample to the appropriate temperature for the analysis being performed. This is important as some analysis procedures can be affected by interferences directly or indirectly due to the fluid temperature. For example, when sampling steam condensate in order to check the pH of the water, the samples should be cooled sufficiently for safe collection and handling while avoiding overcooling. A relatively common recommendation for analysis of steam condensate pH is for the cooled sample to be in the range of 100 to 105 degrees F. It is extremely important that pH measurements be made on cooled samples. If the sample is hot, carbon dioxide in the water sample will be liberated from the sample and escape into the atmosphere, which results in artificially or falsely high pH measurements. Cooling will minimize the carbon dioxide that will flash off from the sample. When the carbon dioxide flashes off from the sample, it is no longer present in the condensate sample which will result in this measurement to be falsely high. The difference between in-line cooled steam condensate samples and condensate cooled at atmospheric ambient temperatures and exposed to the atmosphere can be 2.0 pH units or more. Obviously, this difference in pH could have implications to correctly applying treatment to the steam condensate system and the corrosion rates experienced. It is sometimes also argued that over-cooled samples, particularly if they are left exposed to the atmosphere, can result in some atmospheric carbon dioxide and oxygen to be absorbed into solution from the atmosphere, again potentially resulting in false results. With regard to oxygen for example, oxygen is more soluble in cold water than in hot water. Therefore, it can be argued that some amount of oxygen can potentially be absorbed in over-cooled samples. In applications such as described above, the practice of local conditioning or cooling and analysis is often exercised. This means that the sample is cooled with the use of an in-line sample cooler relatively close to the point of extraction from the process and the analysis is performed at the sample cooler using a continuously flowing sample from the cooler. This minimizes the potential for interferences as a result of prolonged exposure of the sample to the atmosphere when the analysis is performed and as while the analytical equipment acclimates to the sample and compensates for the temperature of the sample. Proper conditioning, collection and storage of samples collected for remote analysis also needs to be considered. Where samples are collected in containers so that they can be transported to a remote location for analysis, diligence regarding the manner in which the sample is collected is also important. Depending on the type of analysis to be performed, how the sample is collected can impact the degree of interferences and the accuracy of results. Some considerations may include but are not necessarily limited to the following. The correct sample temperature should be considered for laboratory instruments and procedures utilized. The duration of time elapsed from when the sample is collected to when the analysis is performed. Completely filling the container to the brim to displace atmospheric gasses from the container. Immediately capping the container to reduce sample exposure to atmospheric conditions or contamination. Adequate purging of sample line is necessary to assure a representative and “fresh” sample. Minimize splashing, agitation and exposure to atmosphere. Some methods for analysis recommended that the sampling tube be long enough to extend to the bottom of the sample container and for the end of the sampling tube to remain immersed in the collected sample fluid until the required volume is obtained. This reduces exposure to atmospheric gasses. Another consideration for the temperature of conditioned or cooled samples is the desired temperature of the analytical equipment and procedures being utilized. Some analytical equipment for instance has an optimal temperature of 77 degrees F. The degree of deviation from the desired temperature may affect the accuracy of the measurement and/or the time required for the equipment to compensate for the difference in temperature. These factors should also be considered regarding the appropriate temperature of samples conditioned or cooled for analysis. The Proper Use and Benefits of Sample Coolers in Steam Plant Applications $
  • 2. When purchasing or installing a sample cooler, the conditions and application for which the cooler will be utilized should be considered. Sample coolers are designed and specified in various sizes and with varying rates of heat removal. Identifying the correct sample cooler for the application will be useful in assuring the following. Safety of the personnel collecting samples. The appropriate degrees of conditioning/cooling of samples for the specific analysis to be performed or instruments utilized. Minimize the potential for interferences that may result in inaccurate analysis results. Minimizing waste from excessive amounts of cooling water being required. Adjustment of the cooling water flow to the sample cooler can result in the appropriate temperature for the analysis being performed. This can be done by installing an additional valve which is used to throttle the flow to achieve the desired temperature. The same may also be accomplished by installing an orifice or flow restrictor. Both of these methods can be employed to achieve the desired sample temperature if the conditions, such as temperature and pressure of the stream being sampled and the cooling water remains stable and unchanged. This can also minimize the variability in sample conditioning and analytical results when tests are performed by numerous individuals. Additionally, diligence in understanding the importance of employing proper sample conditioning techniques also can reveal potential for water savings. Restricting or controlling cooling water flows to sample coolers for the degree of cooling required for the analysis performed can reduce water usage. Furthermore, identifying alternative sources of water for cooling of samples can result in even greater water savings. One example of an alternative cooling water source for sample conditioning is the use of open recirculating cooling system water. This is often available with pressures and temperatures sufficient for sample cooling and has the added benefit that it has been treated for scale and corrosion inhibition that will protect the internals of the sample cooler and result in increased longevity of the heat exchanger for sample cooling. Sample coolers are available in numerous sizes and configurations depending on the application that they will be used in. Cooling water flows can range from less than one gallon per minute to greater than 20 gallons per minute. It is also not uncommon for a single facility to have multiple sample coolers used in various applications. When one considers the amount of water potentially used in sample cooling applications, it is easy to perceive that there may be appreciable potential for water savings. Recognizing the benefits of employing proper controlled conditioning of samples is important for safe and efficient operation of steam plants as well as numerous other industries. System operations can be optimized resulting in increased output, on-stream time, longevity of equipment, personnel safety and water savings. By Robert Jewell Robert has 30 years of career experience in industrial utilities. He specializes in and has extensive experience in the operation and management of steam plants, central plants, cooling and refrigeration systems, potable (drinking) water systems, water treatment, wastewater treatment, and facility management. He is an advocate of water conservation, energy conservation and protecting our environment while also incorporating those advocacies into sustainable water and energy efficiency activities and programs that positively impact the organization and local community by finding efficiency and savings in existing processes and procedures through creative solutions. Connect with Robert on Linkedin at http://www.linkedin.com/pub/bob-jewell/26/810/32a