Abstract
For the last 15 years, cutting extinguishers and the cutting extinguisher method have been used in thousands and yet thousands of fire interventions by municipal firefighters around the globe.
The numbers of cutting extinguishers installed on ships are few in comparison to the numbers in use by the fire and rescue services. Adding the higher level of safety awareness on-board naval vessels, compared to the general public, naval shipboard fires, and thus experience, tend to be scarce. It’s hard to find real cases.
However, in many areas, special units from municipal fire and rescue services, such as Maritime Intervention Response Groups and similar teams, are assigned to shipboard firefighting when vessels are near or alongside quays. These units are trained to fight fires on board ships and have great routine and experience in fighting fires, on-board as well as on shore.
Cross discipline learning is crucial to reach high efficiency in introducing new technology and methods. This paper will describe and illuminate the experiences, procedures and methods from fighting real fires on-board ships using the cutting extinguisher and its method. It will also conclude in lessons learned from the actual incidents.
Beginners Guide to TikTok for Search - Rachel Pearson - We are Tilt __ Bright...
160621 experience of shipboard firefighting with cutting extinguishers (v 1.0)
1. MAST 2016, v1.0 Amsterdam, the Netherlands, 21st
of June, 2016
Experience of Shipboard
firefighting with Cutting
Extinguishers
Integrating the cutting extinguisher with existing naval firefighting Standard
Operating Procedures
A discussion on the practical results of the Swedish Navy; onboard traditional mild steel naval vessels as
well as light weight composite stealth vessels
3. MAST 2016, v1.0 Amsterdam, the Netherlands, 21st
of June, 2016
EXPERIENCE OF SHIPBOARD FIREFIGHTING WITH CUTTING EXTINGUISHERS 1
Abstract 1
Key words 1
INTRODUCTION 1
BACKGROUND 1
Cold Cut Systems 1
Marine implementations of cutting extinguishers 2
Swedish Navy 2
Risk reduction management on HMS Queen Elizabeth Aircraft Carrier Class 2
Fire and rescue services, MIRGs and Salvage companies 3
THE FEATURES OF WATER IN FIRE FIGHTING 4
The Cutting Extinguisher 4
Water Mist 5
Adding piercing capability; suspension vs entrainment 7
Suspension system 7
Entrainment system 7
Doing the job: Gas cooling, oxygen depletion, radiation shielding 8
THE CUTTING EXTINGUISHER METHOD ON SWEDISH NAVY VESSELS 10
Royal Swedish Navy Shipboard Firefighting enhanced with cutting extinguisher method 12
Future developments 16
FIRES ON MERCHANT VESSELS AND THE USE OF CUTTING EXTINGUISHERS 16
Container vessel Yang Ming Green, 2006, Singapore 17
RO‐PAX Vincenzo Florio, 2009, Palermo, IT and Lisco Gloria, 2010, Fehmarn Belt 17
M/V Charlotte Maersk, 2010, off Port Klang, MY 18
MSC Flaminia, 2012, Atlantic Ocean – Wilhelmshaven, DE 19
4. MAST 2016, v1.0 Amsterdam, the Netherlands, 21st
of June, 2016
Fishing trawler Johanna Maria (SCH118), 2014, Scheveningen NL 21
Dieppe Seaways, 2014, Dover, UK 24
Reference cases on shore 28
Industrial Fire, Corby, Northampton shire, UK 28
Domestic House Fire, Halmstad, SE 29
SUMMARY AND DISCUSSION OF INCIDENTS 29
Container vessels 30
RO‐PAX vessels 30
Fishing trawler 32
CONCLUSIONS 32
Knowledge, training (exercise) and capabilities 33
Thinking outside the box 34
Redundancy in firefighting systems 34
REFERENCES 36
35. MAST 2016, v1.0 Amsterdam, the Netherlands, 21st
of June, 2016
Anders Trewe
Cold Cut Systems Svenska AB
P.O. Box 10181
SE‐434 22 Kungsbacka, SWEDEN
Phone: +46 300 40 41 00
Fax: +46 300 40 41 19
anders.trewe@coldcutsystems.com
www.coldcutsystems.com
31
Figure 16 Vincenzo Florio at Palermo (2009) and Lisco Gloria at Fehmarn Belt (2010)
In essence, this made it possible for the salvor to enter the car deck on the Vincenzo Florio once it was
alongside in Palermo, to fight off the fires in the vehicles using the cobra, and finally save 75% of the
property, at a loss of €20 000 000. The Lisco Gloria was a 100% loss, at €60 000 000. Johan Luijks, one of
the contracted salvors of Yang Ming Green and Vincenzo Florio, later said that if there had been a cobra
onboard the Lisco Gloria, the fire could have been limited to the truck that originally caused the fire.46
This was also one of the driving facts for the German Havariekommando to invest in five marine cobra
units in 2011 for their MIRG’s operating out of five coastal cities in the Baltic Sea and the North Sea.
The Dieppe Seaways incident originated from an oil leakage in a boiler furnace. As the situation evolved,
the fire spread through expansion of hot fire gasses from the furnace into the surrounding compartment.
The situation deteriorated due to preconceived conclusions of the ship’s chief engineer, lack of or
misinterpreted liaisons between the ship master and the command of the FRS. The situation prior to
opening the door was not assessed properly. If the risk of back draft had been on the agenda, one would
probably not been content with the dry power action and one would probably had checked whether the
fixed water mist system had been activated automatically – after all, water mist is the best extinguishing
media to mitigate risk of back draft.47
However, immediately after the backdraft, proper liaisons were set up, thorough risk assessments were
made and evaluations of available actions were done. In the course of this work, it became apparent that
the automatic function of the fixed high pressure firefighting had not gone off. This was engaged
manually, but did not have significant effect based on the monitoring of the exhaust temperature from
the furnace. Eventually, a firefighter suggested that the cobra should be used, which, when finally
engaged, showed significant temperature drop of the exhaust temperature. Again, suggesting and using
the cutting extinguisher at this situation, requires knowledge and understanding of the efficiency of the
46
(Luijks, 2011)
47
(Gottuk, Peatross, Farley, & Williams, 1999)