SlideShare a Scribd company logo
1 of 23
AIR CONDITIONING FOR LARGE MULTISTORY BUILDINGS PREPARED BY NOOR AZILA BINTI JAMARI LECTURER CIVIL ENGINEERING DEPARTMENT
Most large multistory buildings use highly centralized air conditioning equipment.  The roof and basement are the usual choice for these central station systems.   The basement has the advantage of easy utility connections, noise isolation, not being valuable rental area and the fact that structural loads are not a problem. INTRODUCTION
The roof is the ideal location for fresh air intakes and heat rejection to the atmosphere. Cooling tower are noisy, produce very hot and humid exhaust air, so the best location for cooling rower is placed on the roof. SECTION OF A TYPICAL MULTISTORY BUILDING WITH A ROOFTOP CENTRAL STATION MECHANICAL SYSTEM
In most buildings, the mechanical equipment is shown to be on the roof.  This section shows an all-air system served by a single central air handling unit on the roof. To avoid the large vertical ducts, separate air handling units can be placed on each floor and only water circulates vertically.  This saves much energy because moving air great distances requires much power.   MECHANICAL EQUIPMENT IS STILL ON THE ROOF, EACH FLOOR HAS A SEPARATE AHU
The advantage of all-air system is complete control over air quality is possible.  The disadvantage is that all-air systems are very bulky and a significant part of the building volume must be devoted to them.   There are 5 system in all-air system categories. i.   Central Plants      ii.  Variable Air Volume (V.A.V)     iii.  Terminal Reheat System      iv.  Multizone System       v.  Double Duct System   ALL-AIR SYSTEM
The central air conditioning system has the limitation of the same air quality being delivered throughout the building. If the structure is zoned or divided and compartmented into several different functions such as offices, workshops, canteen. The temperature of each element can be controlled with zoned thermostats. The fan precedes the chiller and reheater coils and blow air through the air-handling unit. Several ducts radiate from the unit to designated zones within the building.  CENTRAL PLANTS SYSTEM
CENTRAL PLANTS SYSTEM
This is a single duct system that can easily have many zones.  A variable air volume control box is located wherever a duct enters a separate zone. A thermostat in each zone controls the air flow by operating a damper in the V.A.V control box.  More cooling is required, more cool air is allowed to enter the zone.    ii. VARIABLE AIR VOLUME SYSTEMS
VAV system. Floor plan of a VAV system. VAV control box.
At the first the terminal reheat system looks just like the V.A.V system but in fact it is very different.   This system has terminal reheat boxes in which electric strip heaters or hot water coils reheat air previously cooled. All others zones will reheat the cold air to the desired temperature. iii. TERMINAL REHEAT SYSTEM Terminal reheat system.
In this system, every zone receives air at the required temperature through a separate duct. These ducts are supplied by a special multizone air handling unit that custom mixes hot and cold air for each zone.   This is accomplished by motorized dampers located in the air handling unit but controlled by thermostats in each zone. Depending on the temperature, the ratio of hot and cold air varies but the total amount of air is constant.   iv. MULTIZONE SYSTEM
The multizone unit is supplied with hot water, chilled water and a small amount of fresh air. Each multizone unit can handle about 8 zones. Because moderate air temperatures are created by mixing hot and cold air, this system also wasteful of energy. Disadvantage this system are costs relatively high while the thermal control is relatively poor.
Like the multizone system, the double duct system mixes hot and cold air to achieve the required air temperature. Instead of mixing the air at a central air handling unit, mixing boxes are dispersed throughout the building. The double duct system creates a high level of thermal comfort and allows for great zoning flexibility, it is very expensive, requires much building space and its wasteful of energy. v. DOUBLE DUCT SYSTEM Double duct system.
To reduce the size of the ducts, a high-velocity version of this system High-velocity air systems (6000 feet/minute) consume more fan power than normal velocity systems(2000 feet/minute). Because of these problem and because V.A.V system are a good alternative, dual duct systems are not used much anymore.
These system supply both airand water to each zone of a building. It greatly decreases the size of the equipment because of the immense heart-carrying capacity of water as opposed to air. Air is supplied mainly because of the need for ventilation. There are 2 system in air-water system categories. i.  Induction System      ii.  Fan- coil with supplementary air But in this topic is cover induction system only AIR-WATER SYSTEM
A small quantity of high-velocity air is supplied to each zone to supply the required fresh air and to induce room air to circulate. Most induction terminal units are found under windows where they can effectively neutralize the heat gain.   As the high-velocity air shoots into the room it induces a large amount of room air to circulates. This combination of room air and fresh air, then passes over heating or cooling coils. INDUCTION SYSTEM
Local thermostats regulate the temperature by controlling the flow of either hot or cold water through the coils. It takes a lot of fan power to circulate air at high velocity throughout a building. Because of the high cost of energy and the expense of high-velocity ductwork, the use of induction systems is limited. Induction system.
Induction system.  Induction unit with cooling or heating coils
These systems supply no air. There are 2 system in all-water system categories. i.  Fan-coil System      ii.  Water Loop Heat Pump System But in this topic is cover Fan-coil system only. ALL-WATER SYSTEM
The fan-coil unit basically consists of a fan and a coil within water circulates.  The units are in the form of cabinets for placement under windows. The fan blows room air across coils containing  either hot or cold water. Thermostatically controlled valves regulate the flow of water through the coils.   A 4 pipe system, which is has 2 pipes for hot water supply and return and another 2 pipes for cold water supply and return. FAN-COIL SYSTEM
Condensation on the cooling coils must be collected in a pan and drained away. When the fan-coil unit is on an outside wall, it is possible to have an outdoor air intake connected to the unit. A three-speed fan switch allows occupants of the zone to have some control over the temperature. Fan-coil units are most appropriate for air conditioning buildings with small zones (eg. Apartments, condominiums, motels, hotels, hospitals and schools). Fan coil units also located above windows, in small closets or in the dropped ceiling above a bathroom.
Fan Coil System. Schematic diagram of an under window FCU ( 4 pipe system).
FCU placed in a small closet. FCU placed above a dropped ceiling.

More Related Content

What's hot

central air conditioning system
central air conditioning systemcentral air conditioning system
central air conditioning system
UiTM Shah Alam
 
Air conditioning of small buildings
Air conditioning of small buildingsAir conditioning of small buildings
Air conditioning of small buildings
Noor Azila
 
Centralized ac system
Centralized ac systemCentralized ac system
Centralized ac system
Febin Siby
 
All water, air water systems
All water, air water systemsAll water, air water systems
All water, air water systems
Asan Ibrahim
 

What's hot (20)

Ventilation system
Ventilation systemVentilation system
Ventilation system
 
Ventilation System
Ventilation System Ventilation System
Ventilation System
 
National Building Code : Building Services
National Building Code : Building ServicesNational Building Code : Building Services
National Building Code : Building Services
 
Vertical Transportation Systems in Buildings by Ramesh Nayaka
Vertical Transportation Systems in Buildings by Ramesh NayakaVertical Transportation Systems in Buildings by Ramesh Nayaka
Vertical Transportation Systems in Buildings by Ramesh Nayaka
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) ppt
 
Building Service Project 2 Case Study Report
Building Service Project 2 Case Study ReportBuilding Service Project 2 Case Study Report
Building Service Project 2 Case Study Report
 
B.services case-study
B.services case-studyB.services case-study
B.services case-study
 
central air conditioning system
central air conditioning systemcentral air conditioning system
central air conditioning system
 
Building services 2 final (final)
Building services 2 final (final)Building services 2 final (final)
Building services 2 final (final)
 
Air conditioning system
Air conditioning systemAir conditioning system
Air conditioning system
 
Air conditioning of small buildings
Air conditioning of small buildingsAir conditioning of small buildings
Air conditioning of small buildings
 
Heating Ventilation & Air Conditioning (HVAC)
Heating Ventilation & Air Conditioning (HVAC)Heating Ventilation & Air Conditioning (HVAC)
Heating Ventilation & Air Conditioning (HVAC)
 
Building services & Standards For Institutional Building
Building services & Standards For Institutional BuildingBuilding services & Standards For Institutional Building
Building services & Standards For Institutional Building
 
Centralized ac system
Centralized ac systemCentralized ac system
Centralized ac system
 
AIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGINGAIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGING
 
All water, air water systems
All water, air water systemsAll water, air water systems
All water, air water systems
 
Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System
 
Basements light and ventilation
Basements light and ventilationBasements light and ventilation
Basements light and ventilation
 
Air conditioning system
Air conditioning system Air conditioning system
Air conditioning system
 
BUILDING SERVICES-II (ELECTRICAL)
BUILDING SERVICES-II (ELECTRICAL)BUILDING SERVICES-II (ELECTRICAL)
BUILDING SERVICES-II (ELECTRICAL)
 

Similar to Air conditioning for large multistory buildings

Air conditioning of small buildings
Air conditioning of small buildingsAir conditioning of small buildings
Air conditioning of small buildings
Noor Azila
 
1589184349-cac.pptx
1589184349-cac.pptx1589184349-cac.pptx
1589184349-cac.pptx
JulieDash5
 
Air conditining system
Air conditining systemAir conditining system
Air conditining system
Yashh Pandya
 

Similar to Air conditioning for large multistory buildings (20)

Air conditioning of small buildings
Air conditioning of small buildingsAir conditioning of small buildings
Air conditioning of small buildings
 
Air Conditioning and Security Installations
Air Conditioning and Security InstallationsAir Conditioning and Security Installations
Air Conditioning and Security Installations
 
HVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDINGHVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDING
 
LECTURE 6 ZONING IN HVAC.ppt
LECTURE  6 ZONING IN HVAC.pptLECTURE  6 ZONING IN HVAC.ppt
LECTURE 6 ZONING IN HVAC.ppt
 
Air conditioning (1)
Air conditioning (1)Air conditioning (1)
Air conditioning (1)
 
1589184349-cac.pptx
1589184349-cac.pptx1589184349-cac.pptx
1589184349-cac.pptx
 
Air conditining system
Air conditining systemAir conditining system
Air conditining system
 
Air condition.pptx
Air condition.pptxAir condition.pptx
Air condition.pptx
 
Central ac
Central ac Central ac
Central ac
 
Energy efficient hvac
Energy efficient hvac Energy efficient hvac
Energy efficient hvac
 
HVAC
HVACHVAC
HVAC
 
Intro and career opportunities in HVACR
Intro and career opportunities in HVACRIntro and career opportunities in HVACR
Intro and career opportunities in HVACR
 
Air conditioning-system
Air conditioning-systemAir conditioning-system
Air conditioning-system
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system
 
Centralized AC System- S Menon & S Dayakar
Centralized AC System-  S Menon & S DayakarCentralized AC System-  S Menon & S Dayakar
Centralized AC System- S Menon & S Dayakar
 
Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system Overview and Maintenanaces of HVAC system
Overview and Maintenanaces of HVAC system
 
Central ac system
Central ac system Central ac system
Central ac system
 
HEATING VENTILATION AND AIR CONDITIONING SYSTEMS
HEATING VENTILATION AND AIR CONDITIONING SYSTEMSHEATING VENTILATION AND AIR CONDITIONING SYSTEMS
HEATING VENTILATION AND AIR CONDITIONING SYSTEMS
 
HVAC
HVACHVAC
HVAC
 
Bs mechanical-and-air-conditioning
Bs mechanical-and-air-conditioningBs mechanical-and-air-conditioning
Bs mechanical-and-air-conditioning
 

Air conditioning for large multistory buildings

  • 1. AIR CONDITIONING FOR LARGE MULTISTORY BUILDINGS PREPARED BY NOOR AZILA BINTI JAMARI LECTURER CIVIL ENGINEERING DEPARTMENT
  • 2. Most large multistory buildings use highly centralized air conditioning equipment. The roof and basement are the usual choice for these central station systems. The basement has the advantage of easy utility connections, noise isolation, not being valuable rental area and the fact that structural loads are not a problem. INTRODUCTION
  • 3. The roof is the ideal location for fresh air intakes and heat rejection to the atmosphere. Cooling tower are noisy, produce very hot and humid exhaust air, so the best location for cooling rower is placed on the roof. SECTION OF A TYPICAL MULTISTORY BUILDING WITH A ROOFTOP CENTRAL STATION MECHANICAL SYSTEM
  • 4. In most buildings, the mechanical equipment is shown to be on the roof. This section shows an all-air system served by a single central air handling unit on the roof. To avoid the large vertical ducts, separate air handling units can be placed on each floor and only water circulates vertically. This saves much energy because moving air great distances requires much power. MECHANICAL EQUIPMENT IS STILL ON THE ROOF, EACH FLOOR HAS A SEPARATE AHU
  • 5. The advantage of all-air system is complete control over air quality is possible. The disadvantage is that all-air systems are very bulky and a significant part of the building volume must be devoted to them. There are 5 system in all-air system categories. i. Central Plants ii. Variable Air Volume (V.A.V) iii. Terminal Reheat System iv. Multizone System v. Double Duct System ALL-AIR SYSTEM
  • 6. The central air conditioning system has the limitation of the same air quality being delivered throughout the building. If the structure is zoned or divided and compartmented into several different functions such as offices, workshops, canteen. The temperature of each element can be controlled with zoned thermostats. The fan precedes the chiller and reheater coils and blow air through the air-handling unit. Several ducts radiate from the unit to designated zones within the building. CENTRAL PLANTS SYSTEM
  • 8. This is a single duct system that can easily have many zones. A variable air volume control box is located wherever a duct enters a separate zone. A thermostat in each zone controls the air flow by operating a damper in the V.A.V control box. More cooling is required, more cool air is allowed to enter the zone. ii. VARIABLE AIR VOLUME SYSTEMS
  • 9. VAV system. Floor plan of a VAV system. VAV control box.
  • 10. At the first the terminal reheat system looks just like the V.A.V system but in fact it is very different. This system has terminal reheat boxes in which electric strip heaters or hot water coils reheat air previously cooled. All others zones will reheat the cold air to the desired temperature. iii. TERMINAL REHEAT SYSTEM Terminal reheat system.
  • 11. In this system, every zone receives air at the required temperature through a separate duct. These ducts are supplied by a special multizone air handling unit that custom mixes hot and cold air for each zone. This is accomplished by motorized dampers located in the air handling unit but controlled by thermostats in each zone. Depending on the temperature, the ratio of hot and cold air varies but the total amount of air is constant. iv. MULTIZONE SYSTEM
  • 12. The multizone unit is supplied with hot water, chilled water and a small amount of fresh air. Each multizone unit can handle about 8 zones. Because moderate air temperatures are created by mixing hot and cold air, this system also wasteful of energy. Disadvantage this system are costs relatively high while the thermal control is relatively poor.
  • 13. Like the multizone system, the double duct system mixes hot and cold air to achieve the required air temperature. Instead of mixing the air at a central air handling unit, mixing boxes are dispersed throughout the building. The double duct system creates a high level of thermal comfort and allows for great zoning flexibility, it is very expensive, requires much building space and its wasteful of energy. v. DOUBLE DUCT SYSTEM Double duct system.
  • 14. To reduce the size of the ducts, a high-velocity version of this system High-velocity air systems (6000 feet/minute) consume more fan power than normal velocity systems(2000 feet/minute). Because of these problem and because V.A.V system are a good alternative, dual duct systems are not used much anymore.
  • 15. These system supply both airand water to each zone of a building. It greatly decreases the size of the equipment because of the immense heart-carrying capacity of water as opposed to air. Air is supplied mainly because of the need for ventilation. There are 2 system in air-water system categories. i. Induction System ii. Fan- coil with supplementary air But in this topic is cover induction system only AIR-WATER SYSTEM
  • 16. A small quantity of high-velocity air is supplied to each zone to supply the required fresh air and to induce room air to circulate. Most induction terminal units are found under windows where they can effectively neutralize the heat gain. As the high-velocity air shoots into the room it induces a large amount of room air to circulates. This combination of room air and fresh air, then passes over heating or cooling coils. INDUCTION SYSTEM
  • 17. Local thermostats regulate the temperature by controlling the flow of either hot or cold water through the coils. It takes a lot of fan power to circulate air at high velocity throughout a building. Because of the high cost of energy and the expense of high-velocity ductwork, the use of induction systems is limited. Induction system.
  • 18. Induction system. Induction unit with cooling or heating coils
  • 19. These systems supply no air. There are 2 system in all-water system categories. i. Fan-coil System ii. Water Loop Heat Pump System But in this topic is cover Fan-coil system only. ALL-WATER SYSTEM
  • 20. The fan-coil unit basically consists of a fan and a coil within water circulates. The units are in the form of cabinets for placement under windows. The fan blows room air across coils containing either hot or cold water. Thermostatically controlled valves regulate the flow of water through the coils. A 4 pipe system, which is has 2 pipes for hot water supply and return and another 2 pipes for cold water supply and return. FAN-COIL SYSTEM
  • 21. Condensation on the cooling coils must be collected in a pan and drained away. When the fan-coil unit is on an outside wall, it is possible to have an outdoor air intake connected to the unit. A three-speed fan switch allows occupants of the zone to have some control over the temperature. Fan-coil units are most appropriate for air conditioning buildings with small zones (eg. Apartments, condominiums, motels, hotels, hospitals and schools). Fan coil units also located above windows, in small closets or in the dropped ceiling above a bathroom.
  • 22. Fan Coil System. Schematic diagram of an under window FCU ( 4 pipe system).
  • 23. FCU placed in a small closet. FCU placed above a dropped ceiling.