FREQUENTLY ASKED QUESTIONS ON UL 300 SYSTEMS AND CLASS K EXTINGUISHERS
1. NFPA and FEMA have always promoted extinguishers as “your first line of defense” in
a fire situation. With regard to commercial kitchen cooking hazards, why are placards
now required to be posted above class “K” extinguishers stating the cooking appliance
fire suppression system is to be activated prior to using the portable fire extinguisher?
Answer: In recent years, the development of high-efficiency cooking appliances that
employ high-energy input/output rates, as well as the widespread use of
vegetable oils having high auto-ignition temperatures, results in a fire at the
onset of ignition, already being too hot! Portable extinguishers have proven to
be extremely effective but they cannot shut down the fuel source; therefore,
after their discharge duration, the appliance may not have been cooled
effectively enough to prevent reflash. The effective way to extinguish this
type of fire is to REMOVE ITS HEAT SOURCE by activating the
commercial kitchen pre-engineered suppression system. This action provides
elimination of the fuel source (gas valve or electric power off) and then
blankets the hot cooking oil with thick foam produced by the agent contained
in the extinguishing system. Activating the system FIRST places both of
these extinguishing initiatives into motion. The portable extinguisher can then
be used as follow-up in the event it is needed. (For additional information
refer to NFPA-10 and NFPA-96)
2. Statistics prove commercial kitchen pre-engineered fire suppression systems to be very
reliable and successful. If this is the case, WHY must I still provide a portable
extinguisher for these hazards?
Answer: Studies conducted by National Association of Fire Equipment Distributors
found commercial kitchen pre-engineered fire suppression systems to be 95%
reliable and successful in suppressing kitchen cooking hazard fires. Of the
5% found not to have extinguished the fire, improper installation or tampering
was determined the cause.
Having the extinguisher available in the event of a system failure is essential
and both NFPA-10 and NFPA-96 mandate their requirement. Also, the
extinguisher can be utilized in the unlikely event grease spills causing the fire
to spread outside the hazard area of protection. If cooking appliances are
moved for any reason outside such parameters of coverage or should the fire
originate as a result of a cooking media spill beyond the surface of the
appliance, having a K class extinguisher readily available is an important fire
protection consideration. (For additional information refer to NAFED
published reports, NFPA-10 and NFPA-96)
3. Is a commercial kitchen pre-engineered fire suppression system required to protect the
cooking hazard located in my church, town hall, meeting facility or other similar
occupancy?
Answer: NFPA 96, Standard for Ventilation Control and Fire Protection of
Commercial Cooking Operations, dictates that cooking equipment used in
processes producing smoke or grease-laden vapors shall be equipped with an
exhaust system that complies with all the equipment and performance
requirements of this (NFPA 96) standard. Most states have adopted NFPA 96
through their Building and Fire Prevention Codes. Compliance of these codes
and standards includes the installation of a Commercial Kitchen Cooking Pre-
engineered Fire Suppression System to protect the hood(s), duct(s) and
cooking appliance(s). Facility size or cooking capacity is NOT a factor and
does not negate this requirement. These types of occupancies often hold
socials, fund raising events and dinners that, as part of the event, utilize the
cooking facility. Cooking isn’t limited to boiling water, making soup or
warming things up. In many of these situations the food being served requires
frying, broiling, sautéing, etc. which produce smoke or grease laden vapors
and increases the potential of a kitchen cooking appliance fire in these
occupancies. (For additional information refer to NFPA-96 and your local
Building and Fire Prevention Codes)
4. For years, having a 40B:C rated sodium bicarbonate extinguisher in my cooking area
was acceptable. Why am I now being told to replace it with a new class “K” rated fire
extinguisher?
Answer: As stated in question 1, the fire hazard has simply changed and become more
difficult to control. While the old 40B:C sodium bicarbonate fire extinguisher
requirement existed for many years, it is no longer suitable for addressing
many of the newer forms of cooking appliances and cooking media
formulations commonly found in use today. Dry chemical extinguishers are
not effective in removing the tremendous heat that is generated by this type of
hazard. The fire can easily reignite or won’t be extinguished at all. Leaving
the BC sodium bicarbonate extinguisher in place provides one a FALSE sense
of fire safety. The new class “K” rated fire extinguishers are much better
suited to properly handle and address the special cooking appliance fire
hazards found in commercial kitchens. (For additional information refer to
NFPA-10, 17/17A, 96 and ANSI/UL-711 test standard).
5. If a small fire breaks out in or on the surface of my cooking appliance(s), can I first try
to use the portable fire extinguisher prior to activating the commercial kitchen pre-
engineered fire suppression system?
Answer: Kitchen fires have a long history of quickly spreading and getting out of
control. Any delay in activation of the commercial kitchen pre-engineered
fire suppression system, caused by first attempting to use a portable
extinguisher, can give a fire all the advantage it needs to go beyond the
capability and limitations of the fire suppression system. This type of fire can
quickly engulf the grease removal filters, hood plenum and ducts. Since these
areas are somewhat out of sight to the chef, it would be possible for a fire to
survive in these areas and grow without his/her knowledge. Activating the
commercial kitchen pre-engineered fire suppression system FIRST assures the
fuel source has been eliminated, as well as the application of extinguishing
agent being applied to the cooking appliance(s), hood(s) and duct(s) providing
for fire extinguishments. The extinguisher can then be used as follow-up in
the event it is needed.
6. Since there are multiple sizes of Class K extinguishers, and NFPA-10 doesn’t address
any difference in regard to size and rating, how can I, as a consumer of the AHJ, know
which size class K extinguisher would be adequate for the commercial kitchen hazards
or to meet the intent of the local Building or Fire Code?
Answer: Fire extinguishers classified for use on Class K hazards are not required to
have a number preceding the classification letter. Therefore, any extinguisher
rated for Class K hazards is acceptable from the standpoint of satisfying the
code. One needs however, also to take into consideration the size of the
hazard as cooking lines and cooking appliances vary widely. Codes require
the bigger the hazard, the bigger the extinguisher or multiple extinguishers
one must consider. As with other class rated extinguishers, Class K rated
extinguishers come in smaller and larger sizes. In hazards where multiple
fryers, wood burning appliances, or the cooking hazard is very large, multiple
extinguishers or larger Class K rated extinguishers may be required by code.
(for additional information refer to IFC sections 904.11.5 through 904.11.5.2)
For example, one 6-liter (1.5 gallon) Class K extinguisher should be provided
for up to four fryers of 80 pounds (36.3 kg) maximum capacity each. For
every additional group of four fryers having a maximum cooking medium
capacity of 80 pounds (36.3kg) each; one additional Class K portable fire
extinguisher of a minimum 1.5 gallon (6 liter) capacity shall be provided.
Solid fuel cooking appliances require a 6 liter (1.5 gallon) extinguisher as per
NFPA 10 or one 2.5 gallon (9 liter) extinguisher or two 1.5 gallon (6 liter)
Class K extinguishers as per the IFC. The advantage of the larger size unit is
having more wet chemical agent available to control/extinguish a fire should
one occur. Also, since most kitchen areas will contain Class A & B hazards,
the larger Class K extinguisher may prove to be of benefit controlling a fire of
that nature should the fire spread outside the cooking area. (For additional
information refer to International Fire Code (IFC), NFPA-10 and
Manufacturers’ Training Manuals)
IN ALL CASES ABOVE, fire extinguishers not only provide for fire fighting
capabilities, but can also be used for emergency egress situations. If a fire
were to occur that obstructed an egress path, the extinguisher may prove an
effective tool in clearing a path of egress allowing for successful evacuation.
Prepared by the members of FEMA’s Systems and Portable Divisions
Visit FEMA’s website at www.femalifesafety.org for a list of members
Revised-01/08

More Related Content

Viewers also liked

Kitchen Systems and UL 300
Kitchen Systems and UL 300Kitchen Systems and UL 300
Kitchen Systems and UL 300
Damian Regep
 

Viewers also liked (14)

Fire Hose Rack Inspection Guidelines
Fire Hose Rack Inspection GuidelinesFire Hose Rack Inspection Guidelines
Fire Hose Rack Inspection Guidelines
 
7 Simple Steps to Life Safety
7 Simple Steps to Life Safety7 Simple Steps to Life Safety
7 Simple Steps to Life Safety
 
How to Use a Portable Fire Extinguisher
How to Use a Portable Fire ExtinguisherHow to Use a Portable Fire Extinguisher
How to Use a Portable Fire Extinguisher
 
Fire Extinguisher Effectiveness - WPI Study Infographic
Fire Extinguisher Effectiveness - WPI Study InfographicFire Extinguisher Effectiveness - WPI Study Infographic
Fire Extinguisher Effectiveness - WPI Study Infographic
 
Kitchen Systems and UL 300
Kitchen Systems and UL 300Kitchen Systems and UL 300
Kitchen Systems and UL 300
 
2829 High Rise Fire Protection: A Tall Order
2829 High Rise Fire Protection: A Tall Order 2829 High Rise Fire Protection: A Tall Order
2829 High Rise Fire Protection: A Tall Order
 
A Closer Look-Portable Extinguisher
A Closer Look-Portable ExtinguisherA Closer Look-Portable Extinguisher
A Closer Look-Portable Extinguisher
 
Decision Tree for Servicing Pre-Engineered Systems
Decision Tree for Servicing Pre-Engineered SystemsDecision Tree for Servicing Pre-Engineered Systems
Decision Tree for Servicing Pre-Engineered Systems
 
A Plan to Save Lives - Building Diagram
A Plan to Save Lives - Building DiagramA Plan to Save Lives - Building Diagram
A Plan to Save Lives - Building Diagram
 
Portable Fire Extinguisher Decision Tree for Maintenance
Portable Fire Extinguisher Decision Tree for MaintenancePortable Fire Extinguisher Decision Tree for Maintenance
Portable Fire Extinguisher Decision Tree for Maintenance
 
Third-Party Training for Pre-Engineered Fire Suppression Systems
Third-Party Training for Pre-Engineered Fire Suppression SystemsThird-Party Training for Pre-Engineered Fire Suppression Systems
Third-Party Training for Pre-Engineered Fire Suppression Systems
 
Using a Fire Extinguisher - P.A.S.S. Infographic
Using a Fire Extinguisher - P.A.S.S. InfographicUsing a Fire Extinguisher - P.A.S.S. Infographic
Using a Fire Extinguisher - P.A.S.S. Infographic
 
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
 
Manufacturer Recommended Parts for Pre-Engineered Systems
Manufacturer Recommended Parts for Pre-Engineered SystemsManufacturer Recommended Parts for Pre-Engineered Systems
Manufacturer Recommended Parts for Pre-Engineered Systems
 

Similar to Frequently Asked Questions on UL 300 and Class K Fire Extinguishers

GEWINN Company Profile
GEWINN Company ProfileGEWINN Company Profile
GEWINN Company Profile
Dinesh Kumar
 
Channel partner presentation
Channel partner presentationChannel partner presentation
Channel partner presentation
Pixel
 
Pp Poultry Series
Pp Poultry SeriesPp Poultry Series
Pp Poultry Series
Jag3
 
Cleaning of Ducts & Flues
Cleaning of Ducts & FluesCleaning of Ducts & Flues
Cleaning of Ducts & Flues
Daniel Bullock
 
Buckeye Kitchen Mister
Buckeye Kitchen MisterBuckeye Kitchen Mister
Buckeye Kitchen Mister
Anjani Mishra
 

Similar to Frequently Asked Questions on UL 300 and Class K Fire Extinguishers (20)

A Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & MaintenanceA Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & Maintenance
 
Burners & fire boxes
Burners & fire boxesBurners & fire boxes
Burners & fire boxes
 
Blazemaster Fire Protection System Residential Brochure
Blazemaster Fire Protection System Residential BrochureBlazemaster Fire Protection System Residential Brochure
Blazemaster Fire Protection System Residential Brochure
 
Ansul fire suppression
Ansul fire suppressionAnsul fire suppression
Ansul fire suppression
 
Compliance awareness seminar
Compliance awareness seminarCompliance awareness seminar
Compliance awareness seminar
 
GEWINN Company Profile
GEWINN Company ProfileGEWINN Company Profile
GEWINN Company Profile
 
Firefighting equipment
Firefighting equipmentFirefighting equipment
Firefighting equipment
 
Potable Fire extinguisher
Potable Fire extinguisher Potable Fire extinguisher
Potable Fire extinguisher
 
Black diamond-brochure
Black diamond-brochureBlack diamond-brochure
Black diamond-brochure
 
Channel partner presentation
Channel partner presentationChannel partner presentation
Channel partner presentation
 
Fire Extinguisher Training by USMRA
Fire Extinguisher Training by USMRAFire Extinguisher Training by USMRA
Fire Extinguisher Training by USMRA
 
Portable-Fire-Extinguisher-for-Building-Management.ppt
Portable-Fire-Extinguisher-for-Building-Management.pptPortable-Fire-Extinguisher-for-Building-Management.ppt
Portable-Fire-Extinguisher-for-Building-Management.ppt
 
Portable-Fire-Extinguisher-for-Building-Management.ppt
Portable-Fire-Extinguisher-for-Building-Management.pptPortable-Fire-Extinguisher-for-Building-Management.ppt
Portable-Fire-Extinguisher-for-Building-Management.ppt
 
Fire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafeFire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafe
 
Pp Poultry Series
Pp Poultry SeriesPp Poultry Series
Pp Poultry Series
 
Uses of fire estinguisher
Uses of fire estinguisherUses of fire estinguisher
Uses of fire estinguisher
 
Kitchen extract fire safety & fire risk assessments
Kitchen extract fire safety & fire risk assessmentsKitchen extract fire safety & fire risk assessments
Kitchen extract fire safety & fire risk assessments
 
Cleaning of Ducts & Flues
Cleaning of Ducts & FluesCleaning of Ducts & Flues
Cleaning of Ducts & Flues
 
Refilling of fire extinguisher
Refilling of fire extinguisherRefilling of fire extinguisher
Refilling of fire extinguisher
 
Buckeye Kitchen Mister
Buckeye Kitchen MisterBuckeye Kitchen Mister
Buckeye Kitchen Mister
 

More from Fire Equipment Manufacturers' Association

More from Fire Equipment Manufacturers' Association (7)

Types of Extinguishers - Grab It & Use It!
Types of Extinguishers - Grab It & Use It!Types of Extinguishers - Grab It & Use It!
Types of Extinguishers - Grab It & Use It!
 
Division Member Infographic
Division Member InfographicDivision Member Infographic
Division Member Infographic
 
Types of Fires Infographic
Types of Fires InfographicTypes of Fires Infographic
Types of Fires Infographic
 
Rack and Reel Fire Hose Insure Dependability
Rack and Reel Fire Hose Insure DependabilityRack and Reel Fire Hose Insure Dependability
Rack and Reel Fire Hose Insure Dependability
 
FEMA Balanced Fire Protection Brochure
FEMA Balanced Fire Protection BrochureFEMA Balanced Fire Protection Brochure
FEMA Balanced Fire Protection Brochure
 
A Closer Look: Fire Suppression Systems
A Closer Look: Fire Suppression SystemsA Closer Look: Fire Suppression Systems
A Closer Look: Fire Suppression Systems
 
A Closer Look: Standpipe Fire Hose Stations
A Closer Look: Standpipe Fire Hose StationsA Closer Look: Standpipe Fire Hose Stations
A Closer Look: Standpipe Fire Hose Stations
 

Recently uploaded

1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
QucHHunhnh
 
Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.
MateoGardella
 

Recently uploaded (20)

Advance Mobile Application Development class 07
Advance Mobile Application Development class 07Advance Mobile Application Development class 07
Advance Mobile Application Development class 07
 
This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.This PowerPoint helps students to consider the concept of infinity.
This PowerPoint helps students to consider the concept of infinity.
 
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
Explore beautiful and ugly buildings. Mathematics helps us create beautiful d...
 
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
APM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAPM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across Sectors
 
psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docx
 
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
 
fourth grading exam for kindergarten in writing
fourth grading exam for kindergarten in writingfourth grading exam for kindergarten in writing
fourth grading exam for kindergarten in writing
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptx
 
Measures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SDMeasures of Dispersion and Variability: Range, QD, AD and SD
Measures of Dispersion and Variability: Range, QD, AD and SD
 
Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...
Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...
Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot Graph
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17Advanced Views - Calendar View in Odoo 17
Advanced Views - Calendar View in Odoo 17
 
Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024
 
Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.
 

Frequently Asked Questions on UL 300 and Class K Fire Extinguishers

  • 1. FREQUENTLY ASKED QUESTIONS ON UL 300 SYSTEMS AND CLASS K EXTINGUISHERS 1. NFPA and FEMA have always promoted extinguishers as “your first line of defense” in a fire situation. With regard to commercial kitchen cooking hazards, why are placards now required to be posted above class “K” extinguishers stating the cooking appliance fire suppression system is to be activated prior to using the portable fire extinguisher? Answer: In recent years, the development of high-efficiency cooking appliances that employ high-energy input/output rates, as well as the widespread use of vegetable oils having high auto-ignition temperatures, results in a fire at the onset of ignition, already being too hot! Portable extinguishers have proven to be extremely effective but they cannot shut down the fuel source; therefore, after their discharge duration, the appliance may not have been cooled effectively enough to prevent reflash. The effective way to extinguish this type of fire is to REMOVE ITS HEAT SOURCE by activating the commercial kitchen pre-engineered suppression system. This action provides elimination of the fuel source (gas valve or electric power off) and then blankets the hot cooking oil with thick foam produced by the agent contained in the extinguishing system. Activating the system FIRST places both of these extinguishing initiatives into motion. The portable extinguisher can then be used as follow-up in the event it is needed. (For additional information refer to NFPA-10 and NFPA-96) 2. Statistics prove commercial kitchen pre-engineered fire suppression systems to be very reliable and successful. If this is the case, WHY must I still provide a portable extinguisher for these hazards? Answer: Studies conducted by National Association of Fire Equipment Distributors found commercial kitchen pre-engineered fire suppression systems to be 95% reliable and successful in suppressing kitchen cooking hazard fires. Of the 5% found not to have extinguished the fire, improper installation or tampering was determined the cause.
  • 2. Having the extinguisher available in the event of a system failure is essential and both NFPA-10 and NFPA-96 mandate their requirement. Also, the extinguisher can be utilized in the unlikely event grease spills causing the fire to spread outside the hazard area of protection. If cooking appliances are moved for any reason outside such parameters of coverage or should the fire originate as a result of a cooking media spill beyond the surface of the appliance, having a K class extinguisher readily available is an important fire protection consideration. (For additional information refer to NAFED published reports, NFPA-10 and NFPA-96) 3. Is a commercial kitchen pre-engineered fire suppression system required to protect the cooking hazard located in my church, town hall, meeting facility or other similar occupancy? Answer: NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, dictates that cooking equipment used in processes producing smoke or grease-laden vapors shall be equipped with an exhaust system that complies with all the equipment and performance requirements of this (NFPA 96) standard. Most states have adopted NFPA 96 through their Building and Fire Prevention Codes. Compliance of these codes and standards includes the installation of a Commercial Kitchen Cooking Pre- engineered Fire Suppression System to protect the hood(s), duct(s) and cooking appliance(s). Facility size or cooking capacity is NOT a factor and does not negate this requirement. These types of occupancies often hold socials, fund raising events and dinners that, as part of the event, utilize the cooking facility. Cooking isn’t limited to boiling water, making soup or warming things up. In many of these situations the food being served requires frying, broiling, sautéing, etc. which produce smoke or grease laden vapors and increases the potential of a kitchen cooking appliance fire in these occupancies. (For additional information refer to NFPA-96 and your local Building and Fire Prevention Codes) 4. For years, having a 40B:C rated sodium bicarbonate extinguisher in my cooking area was acceptable. Why am I now being told to replace it with a new class “K” rated fire extinguisher? Answer: As stated in question 1, the fire hazard has simply changed and become more difficult to control. While the old 40B:C sodium bicarbonate fire extinguisher requirement existed for many years, it is no longer suitable for addressing many of the newer forms of cooking appliances and cooking media formulations commonly found in use today. Dry chemical extinguishers are not effective in removing the tremendous heat that is generated by this type of hazard. The fire can easily reignite or won’t be extinguished at all. Leaving the BC sodium bicarbonate extinguisher in place provides one a FALSE sense of fire safety. The new class “K” rated fire extinguishers are much better
  • 3. suited to properly handle and address the special cooking appliance fire hazards found in commercial kitchens. (For additional information refer to NFPA-10, 17/17A, 96 and ANSI/UL-711 test standard). 5. If a small fire breaks out in or on the surface of my cooking appliance(s), can I first try to use the portable fire extinguisher prior to activating the commercial kitchen pre- engineered fire suppression system? Answer: Kitchen fires have a long history of quickly spreading and getting out of control. Any delay in activation of the commercial kitchen pre-engineered fire suppression system, caused by first attempting to use a portable extinguisher, can give a fire all the advantage it needs to go beyond the capability and limitations of the fire suppression system. This type of fire can quickly engulf the grease removal filters, hood plenum and ducts. Since these areas are somewhat out of sight to the chef, it would be possible for a fire to survive in these areas and grow without his/her knowledge. Activating the commercial kitchen pre-engineered fire suppression system FIRST assures the fuel source has been eliminated, as well as the application of extinguishing agent being applied to the cooking appliance(s), hood(s) and duct(s) providing for fire extinguishments. The extinguisher can then be used as follow-up in the event it is needed. 6. Since there are multiple sizes of Class K extinguishers, and NFPA-10 doesn’t address any difference in regard to size and rating, how can I, as a consumer of the AHJ, know which size class K extinguisher would be adequate for the commercial kitchen hazards or to meet the intent of the local Building or Fire Code? Answer: Fire extinguishers classified for use on Class K hazards are not required to have a number preceding the classification letter. Therefore, any extinguisher rated for Class K hazards is acceptable from the standpoint of satisfying the code. One needs however, also to take into consideration the size of the hazard as cooking lines and cooking appliances vary widely. Codes require the bigger the hazard, the bigger the extinguisher or multiple extinguishers one must consider. As with other class rated extinguishers, Class K rated extinguishers come in smaller and larger sizes. In hazards where multiple fryers, wood burning appliances, or the cooking hazard is very large, multiple extinguishers or larger Class K rated extinguishers may be required by code. (for additional information refer to IFC sections 904.11.5 through 904.11.5.2) For example, one 6-liter (1.5 gallon) Class K extinguisher should be provided for up to four fryers of 80 pounds (36.3 kg) maximum capacity each. For every additional group of four fryers having a maximum cooking medium capacity of 80 pounds (36.3kg) each; one additional Class K portable fire extinguisher of a minimum 1.5 gallon (6 liter) capacity shall be provided. Solid fuel cooking appliances require a 6 liter (1.5 gallon) extinguisher as per NFPA 10 or one 2.5 gallon (9 liter) extinguisher or two 1.5 gallon (6 liter) Class K extinguishers as per the IFC. The advantage of the larger size unit is having more wet chemical agent available to control/extinguish a fire should one occur. Also, since most kitchen areas will contain Class A & B hazards, the larger Class K extinguisher may prove to be of benefit controlling a fire of
  • 4. that nature should the fire spread outside the cooking area. (For additional information refer to International Fire Code (IFC), NFPA-10 and Manufacturers’ Training Manuals) IN ALL CASES ABOVE, fire extinguishers not only provide for fire fighting capabilities, but can also be used for emergency egress situations. If a fire were to occur that obstructed an egress path, the extinguisher may prove an effective tool in clearing a path of egress allowing for successful evacuation. Prepared by the members of FEMA’s Systems and Portable Divisions Visit FEMA’s website at www.femalifesafety.org for a list of members Revised-01/08