A Rack PDU, or Rack Power Distribution Unit, is a device used in data centers and server rooms to distribute electric power to multiple devices within a server rack. It typically mounts onto the rack and provides electrical outlets or connections for servers, networking equipment, and other devices. Rack PDUs can vary in features, such as metering, remote monitoring, and power management capabilities.
Unified wired/wireless IP data networking solution designed to increase efficiency by reducing data contention. Combined with an advanced Layer 3 architecture and an IEEE802.11 enterprise wireless LAN management system, icXchange helps ensure content delivery as well as solid connectivity for the user.
An experience is a personal and emotional event we remember. Every experience is established based upon pre-determined expectations we conceive and create in our minds. It’s personal, and therefore, remains a moving and evolving target in every scenario. When our experience concludes and the moment has passed, the outcome remains in our memory. Think about what makes you happy when connecting with your own device and then think about what makes you really upset when things are hard, complicated, and slow. If the user has a bad experience in anyone of these areas (simple, fast, and smart), they are likely to leave, share their negative experience, and potentially never return. Users might forget facts or details about their computing environment but they find it difficult to forgot the feeling behind a bad network experience. When something goes wrong with the network or an application, do you always get the blame?
If the number of spine switches were to be merely doubled, the effect of a single switch failure is halved. With 8 spine switches, the effect of a single switch failure only causes a 12% reduction in available bandwidth. So, in modern data centers, people build networks with anywhere from 4 to 32 spine switches. With a leaf-spine network, every server on the network is exactly the same distance away from all other servers – three port hops, to be precise. The benefit of this architecture is that you can just add more spines and leaves as you expand the cluster and you don't have to do any recabling. Intuition Systems will also get more predictable latency between the nodes.
As a trend, disaggregation seems to be most useful for very large companies like Facebook and Google, or cloud providers. The technology does not necessarily have significant implications for small or medium sized businesses. Historically, however, technology has a way of trickling down from the pioneering phases of existing only within large companies with tremendous resources, to becoming more standardized across the board.
Large venues like stadiums or concert halls are challenging environments for Wi-Fi deployments. Most of today’s phones and tablets carry Wi-Fi interfaces. A safe assumption is that at least one device per person in a stadium carry a Wi-Fi interface. Monetizing those Wi-Fi interfaces with real time information of the event in the venue, targeted advertising, internet access, multimedia and social applications can create new revenues to the owner of the venue, if executed properly.
IGS-5225-4T2S, the smallest, fully-managed Gigabit fiber switch for harsh environments, features 4 10/100/1000Mbps copper ports, 2 100/1000X SFP ports and redundant power system in an IP30 rugged but compact-sized case. The IGS-5225-4T2S can be installed in any difficult environment as it can operate stably under the temperature range from -40 to 75 degrees C. With such a slim enclosure, it does not need a big space to install.
The switch features user-friendly yet advanced IPv6/IPv4 management interfaces, abundant L2/L4 switching functions and Layer 3 static routing capability. It allows either DIN-rail or wall mounting for efficient use of cabinet space. With 2 dual-speed SFP fiber slots, it can be flexibly applied to extend the connection distance.
Contact us
Tel: +91-7875432180 Email: sales@bbcpl.in
Website: https://www.bbcpl.in
Unified wired/wireless IP data networking solution designed to increase efficiency by reducing data contention. Combined with an advanced Layer 3 architecture and an IEEE802.11 enterprise wireless LAN management system, icXchange helps ensure content delivery as well as solid connectivity for the user.
An experience is a personal and emotional event we remember. Every experience is established based upon pre-determined expectations we conceive and create in our minds. It’s personal, and therefore, remains a moving and evolving target in every scenario. When our experience concludes and the moment has passed, the outcome remains in our memory. Think about what makes you happy when connecting with your own device and then think about what makes you really upset when things are hard, complicated, and slow. If the user has a bad experience in anyone of these areas (simple, fast, and smart), they are likely to leave, share their negative experience, and potentially never return. Users might forget facts or details about their computing environment but they find it difficult to forgot the feeling behind a bad network experience. When something goes wrong with the network or an application, do you always get the blame?
If the number of spine switches were to be merely doubled, the effect of a single switch failure is halved. With 8 spine switches, the effect of a single switch failure only causes a 12% reduction in available bandwidth. So, in modern data centers, people build networks with anywhere from 4 to 32 spine switches. With a leaf-spine network, every server on the network is exactly the same distance away from all other servers – three port hops, to be precise. The benefit of this architecture is that you can just add more spines and leaves as you expand the cluster and you don't have to do any recabling. Intuition Systems will also get more predictable latency between the nodes.
As a trend, disaggregation seems to be most useful for very large companies like Facebook and Google, or cloud providers. The technology does not necessarily have significant implications for small or medium sized businesses. Historically, however, technology has a way of trickling down from the pioneering phases of existing only within large companies with tremendous resources, to becoming more standardized across the board.
Large venues like stadiums or concert halls are challenging environments for Wi-Fi deployments. Most of today’s phones and tablets carry Wi-Fi interfaces. A safe assumption is that at least one device per person in a stadium carry a Wi-Fi interface. Monetizing those Wi-Fi interfaces with real time information of the event in the venue, targeted advertising, internet access, multimedia and social applications can create new revenues to the owner of the venue, if executed properly.
IGS-5225-4T2S, the smallest, fully-managed Gigabit fiber switch for harsh environments, features 4 10/100/1000Mbps copper ports, 2 100/1000X SFP ports and redundant power system in an IP30 rugged but compact-sized case. The IGS-5225-4T2S can be installed in any difficult environment as it can operate stably under the temperature range from -40 to 75 degrees C. With such a slim enclosure, it does not need a big space to install.
The switch features user-friendly yet advanced IPv6/IPv4 management interfaces, abundant L2/L4 switching functions and Layer 3 static routing capability. It allows either DIN-rail or wall mounting for efficient use of cabinet space. With 2 dual-speed SFP fiber slots, it can be flexibly applied to extend the connection distance.
Contact us
Tel: +91-7875432180 Email: sales@bbcpl.in
Website: https://www.bbcpl.in
2. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Index
3. Don’t settle for mediocrity when it comes to power distribution. Choose Voltz Rack for
advanced control, monitoring, and efficiency. It’s time to elevate your data center’s
power management game.
When it comes to efficient and intelligent power
distribution, look no further than the Voltz Rack.
Our cutting-edge rack PDU is more than just a power
strip; it’s a game-changer for your data center, offering a
suite of features designed to elevate your operations and
safeguard your critical equipment.
Unparalleled Control and Monitoring
The Voltz Rack PDU is the heart of your rack’s power
management. With input metering and outlet switching
capabilities, it gives you real-time insight into your power
consumption and the ability to take immediate action. No
more guesswork – our PDU puts you in the driver’s seat.
Seamless Power Optimization
Avoid overloads, optimize capacity, and minimize energy
usage effortlessly. The Voltz Rack empowers you to
make informed decisions to keep your operations running
smoothly and efficiently.
Smart Outlet Control
Take control like never before with switched outlets.
Power up your equipment in the right sequence, perform
remote reboots, and manage outlet access with ease. Your
equipment operates on your terms.
Future-Proof Technology
The Voltz Rack is designed for tomorrow’s challenges. Our
hot-swappable network management controller ensures
that you’re always ready for upgrades, reducing Mean Time
to Repair (MTTR) to a minimum.
Total Environmental Awareness
Monitoring your environment is a breeze with up to sixteen
environmental sensors. Detect temperature, humidity, and
airflow changes, allowing you to maintain ideal conditions
for your critical infrastructure.
Robust Connectivity Options
Stay connected with your equipment through a variety of
interfaces, including WebUI, SSH, SNMP, and RESTful
API. The Voltz Rack is your gateway to comprehensive
power management.
Versatile Integration
Seamlessly integrate the Voltz Rack with your existing
systems. It plays well with DCIM and BMS, making it an
essential component of your data center ecosystem.
PoE Power Sharing
Experience the convenience of optional PoE power sharing
over Ethernet cable. Simplify your setup and reduce clutter
with this innovative feature.
Fortified Security
Security is paramount. Rest easy knowing that the Voltz
Rack offers high-level network security, ensuring the safety
of your critical data.
Applications Across Industries
Experience the convenience of optional PoE power sharing
over Ethernet cable. Simplify your setup and reduce clutter
with this innovative feature.The Voltz Rack is versatile,
making it the perfect choice for various environments:
• Energy metering in environments that
require precision.
• Colocation facilities where every watt counts.
• MDF, IDF, Data Center, Computer Room,
and Data Room Environments that demand
top-tier power management.
Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
About Voltz Rack PDU
Introducing the Voltz Rack PDU:
Power Distribution Perfected
5. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP3S30S30-001
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering N/A
Outlet Switching Yes
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 71 in (1800mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 30.86 lb (14 kg)
Physical
6. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
RP3S30S30-001
Main Input Voltage 3 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 30A
Input Connection Type IEC60309 32A (3P+N+E)
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 23kVA
Rated Output Current (Phase) 30A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (6) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (24)C13 + (6)C19; Per Breaker: (4)C13 + (1)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable Offer Status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead Free Yes
Mercury Free Yes
RoHS Exemption Information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 44.00 lb (19.95 kg)
Package Units
Specs
7. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1750
55
IEC60309 3P+N+E
6H IP44
5 Cores, 6FT/1.83m
C13-24 PCS C19-6 PCS
50
1244.60
50
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240/415V 30A 3-Phase WYE configration.
SHEET 1 OF 1
REV.
01
RP3S30S30-001
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/10/27
2023/10/27
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/10/27
Rack PDU Switched, ZeroU,
17.3kW, 3 Phase, 30A,240/415V,
(24) C13, (6) C19
Drawing / Wiring Diagram
RP3S30S30-001
9. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP1S30S28-001
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering N/A
Outlet Switching Yes
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 65 in (1650mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 30.86 lb (14 kg)
Physical
10. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 1 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 30A
Input Connection Type NEMA L6-30P
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 5.0 kVA
Rated Output Current (Phase) 30A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (6) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (24)C13 + (4)C19; Per Breaker: (12)C13 + (2)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable Offer Status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead Free Yes
Mercury Free Yes
RoHS Exemption Information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 44.00 lb (19.95 kg)
Package Units
Specs RP1S30S28-001
11. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1600
55
NEMA L6-30P
3 Cores, 6FT/1.83m
C13-24 PCS C19-4 PCS
50
1244.60
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240/415V 30A 3-Phase WYE configration.
SHEET 1 OF 1
REV.
01
RP1S30S28-001
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/10/27
2023/10/27
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/10/27
Rack PDU Switched, ZeroU,
5.0kW, 1 Phase, 30A,90-240V,
(24) C13,(4)C19
Drawing / Wiring Diagram
RP1S30S28-001
13. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP3M30S36-016
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering No
Outlet Switching No
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 71 in (1650mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 28.66 lb (13 kg)
Physical
14. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 3 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 30A
Input Connection Type NEMA L22-30P
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 17.3 kVA
Rated Output Current (Phase) 30A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (6) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (24)C13 + (12)C19; Per Breaker: (4)C13 + (2)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable Offer Status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead Free Yes
Mercury Free Yes
RoHS Exemption Information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 41.78 lb (19.95 kg)
Package Units
Specs RP3M30S36-016
15. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1750
55
NEMA L22-30P
5 Cores, 6FT / 1.83M
C13-24 PCS C19-12 PCS
50
1244.60
50
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240/415V 30A 3-Phase WYE configration.
SHEET 1 OF 1
REV.
01
RP3M30S36-016
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/12/05
2023/12/05
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/12/05
Rack PDU Metering, ZeroU,
17.3kW, 3 Phase, 30A,240/415V,
(24) C13, (12) C19
Drawing / Wiring Diagram
RP3M30S36-016
17. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP3S30S24-005
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering N/A
Outlet Switching Yes
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 71 in (1800mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 30.86 lb (14 kg)
Physical
18. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 3 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 30A
Input Connection Type IEC60309 32A (3P+N+E)
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 17.3 kVA
Rated Output Current (Phase) 30A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (6) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (12)C13 + (12)C19; Per Breaker: (2)C13 + (2)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable Offer Status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead Free Yes
Mercury Free Yes
RoHS Exemption Information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 44.00 lb (19.95 kg)
Package Units
Specs RP3S30S24-005
19. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1750
55
IEC60309 3P+N+E
6H IP44
5 Cores, 6FT/1.83m
C13-12 PCS C19-12 PCS
50
1244.60
50
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240/415V 30A 3-Phase WYE configration.
SHEET 1 OF 1
REV.
01
RP3S30S24-005
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/10/27
2023/10/27
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/10/27
Rack PDU Switched, ZeroU,
17.3kW, 3 Phase, 30A,240/415V,
(12) C13, (12) C19
Drawing / Wiring Diagram
RP3S30S24-005
21. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP1P32S32-003
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Outlet Switching Yes
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 71 in (1800mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 28.66 lb (13 kg)
Physical
22. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 1 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 32A
Input Connection Type IEC60309 32A (1P+N+E)
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 7.4 kVA
Rated Output Current (Phase) 30A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (2) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (24)C13 + (8)C19; Per Breaker: (12)C13 + (4)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable Offer Status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead Free Yes
Mercury Free Yes
RoHS Exemption Information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 41.78 lb (19.95 kg)
Package Units
Specs RP1P32S32-003
23. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1750
55
IEC60309 2P+E
6H IP44
3 Cores, 6FT / 1.83M
C13-24 PCS C19-8 PCS
50
1244.60
50
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240V 32A 1-Phase.
SHEET 1 OF 1
REV.
01
RP1P32S32-003
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/12/05
2023/12/05
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/12/05
Rack PDU Metering & Switched,
ZeroU,
7.4kW, 1 Phase, 32A,240V,
(24) C13, (8) C19
Drawing / Wiring Diagram
RP1P32S32-003
25. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP3S30S24-013
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering N/A
Outlet Switching Yes
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 59 in (1500mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 30.86 lb (14 kg)
Physical
26. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 3 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 30A
Input Connection Type NEMA L22-30P
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 17.3 kVA
Rated Output Current (Phase) 30A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (6) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (24)C13 ; Per Breaker (4)C13
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable Offer Status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead Free Yes
Mercury Free Yes
RoHS Exemption Information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 44.00 lb (19.95 kg)
Package Units
Specs RP3S30S24-013
27. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1500
55
NEMA L22-30P
5 Cores, 6FT/1.83m
C13-24 PCS
50
990.60
50
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240/415V 30A 3-Phase WYE configration.
SHEET 1 OF 1
REV.
01
RP3S30S24-013
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/10/27
2023/10/27
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/10/27
Rack PDU Switched, ZeroU,
17.3kW, 3 Phase, 30A,240/415V,
(24) C13
Drawing / Wiring Diagram
RP3S30S24-013
29. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP3M30S42-021
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering N/A
Outlet Switching N/A
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 71 in (1800mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 28.66 lb (13 kg)
Physical
30. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 3 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 30A
Input Connection Type NEMA L22-30P
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 17.3 kVA
Rated Output Current (Phase) 30A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (6) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (36)C13 + (6)C19 ; Per Breaker: (6)C13 + (1)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable Offer Status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead Free Yes
Mercury Free Yes
RoHS Exemption Information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 41.78 lb (18.95 kg)
Package Units
Specs RP3M30S42-021
31. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1750
55
NEMA L22-30P
5 Cores, 6FT / 1.83M
C13-36 PCS C19-6 PCS
50
1244.60
50
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240/415V 30A 3-Phase WYE Configration.
SHEET 1 OF 1
REV.
01
RP3M30S42-021
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/12/05
2023/12/05
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/12/05
Rack PDU Metering, ZeroU,
17.3kW, 3 Phase, 30A,240/415V,
(36) C13, (6) C19
Drawing / Wiring Diagram
RP3M30S42-021
33. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP3M32S42-003
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering NO
Outlet Switching NO
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 71 in (1800mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 28.66 lb (13 kg)
Physical
34. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 3 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 30A
Input Connection Type IEC60309 3P+N+E 6H IP44
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 17.3 kVA
Rated Output Current (Phase) 20A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (6) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (30)C13 + (12)C19; Per Breaker: (6)C13 + (2)C19,
(4)C13 + (2)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable offer status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead free Yes
Mercury free Yes
RoHS exemption information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 41.78 lb (18.95 kg)
Package Units
Specs RP3M30S42-021
35. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1750
55
IEC603093P+N+E
6H IP44
5 Cores, 6FT / 1.83M
C13-30 PCS C19-12 PCS
50
1244.60
50
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240/415V 30A 3-Phase WYE Configration.
SHEET 1 OF 1
REV.
01
RP3M32S42-003
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/12/05
2023/12/05
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/12/05
Rack PDU Metering, ZeroU,
17.3kW, 3 Phase, 30A,240/415V,
(30) C13, (12) C19
Drawing / Wiring Diagram
RP3M32S42-003
37. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Specs RP1M32S42-004
Network Management Card
Network Port
2x10/100M IEE802.3 Ethernet Ports
Optional PoE PD on Port 1
Optional PoE PS on Port 2
Sensor Port
2x Slip RFC1055 over RS485 Ports
Date Rate : 19200 bps
Power Supply on Port : 5V 500mA, 12V, 300mA
Supported Sensor
• Temperature and Humidity
• Door Switch / Dry Contact
• Intelligent Handle
• Assests Management System
• Air Flow
USB Port
Mode: Host:
Supported Device:
• Serial Cable
• Ethernet Adapter
• Camera
*Supported device subject to change
Network IP Mode
• IPv4, IPv6, Dual Mode
• IP Management: DHCP, Static, IP Bridge
Management Protocols
• SNMP: v2c, v3 with SHA512/AES256
• Restful API over https with TLS1.3 supported
• RAW Json over https with TLS1.3 supported
• MQTT subscription
• SSH2 command line interface
Authorization
• Microsoft Active Directory
• LDAP
• Radius
• Tacacs+
Event Notification
• Email SMTP over TLS
• Syslog
• SNMP trap
• MQTT
Network Security
• Hardware Random Number Generator
• Hardware Crypto
• Hash: md5, sha1, sha256, sha512
• Encryption: AES, DES, RSA
• Transpoetation: TLS1.2, TLS1.3,
DTLS1.2, DTLS1.3
Function
Energy Metering Voltage (V), Current (A), Active Power (kW), Apparent power (kVA), Energy (kWh),
Power Factor(pF)
Metering Accuracy Billing grade, 1% ISO/IEC 62053-21
Outlet Level Metering N/A
Outlet Switching YES
Network Management 2x 10/100M Ethernet
Number of Rack unit 0U
High 71 in (1800mm)
Width 2.17 in (55mm)
Depth 2.17 in (55mm)
Depth t Circuit Breaker in (mm) 2.87 in (73mm)
Color Black
Net Weight 28.66 lb (13 kg)
Physical
38. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Main Input Voltage 1 Phase , 220-240 VAC, +6%, -10%
Input Current (Phase) 32A
Input Connection Type IEC603092P+E 6H IP44
Cable Length (6 FT)1.83m
Input Frequency 50/60Hz
Loading Capacity 7.4 kVA
Rated Output Current (Phase) 20A
Rated Output Current (Outlet) C13:12A, C19:16A
Overload Protection (Internal) (2) 20A, 1-pole, 10kAIC, hy-mag circuit breakers
Outlet Configuration Total: (36)C13 + (6)C19; Per Breaker: (18)C13 + (3)C19
Electrical
Ambient Air Temperature for Operation 23…140 °F (-5…60 °C)
Relative Humidity 5…95 %
Operating Altitude 0...10000 ft
Ambient Air Temperature for Storage -13…149 °F (-25…65 °C)
Storage Relative Humidity 5…95 %
Storage Altitude 0…50000 ft (0.00…15240.00 m)
Environmental
Sustainable offer status Green Premium product
REACH Regulation REACH Declaration
EU RoHS Directive EU RoHS Declaration
Lead free Yes
Mercury free Yes
RoHS exemption information Yes
Environmental Disclosure Product Environmental Profile
Offer Sustainability
Warranty Time 3 years repair or replacement
Warranty
Product
Certifications
CE, ETL
Standards FCC Part 15 Class A/ICES-003/UL 60950-1
Compliance Approve
Number of Units
in Package
1 unit
Package Length 84.61 in (214.9cm)
Package Width 8.70 in (22.0 cm)
Package Height 4.41 in (11.2 cm)
Package Weight 41.78 lb (18.95 kg)
Package Units
Specs RP1M32S42-004
39. Eatontown, NJ | Somerville, NJ | Champaign, IL | (800) 258-0129 | www.raptorpwr.com
Wiring
Wiring
Drawing
Drawing
1750
55
IEC60309 2P+E
6H IP44
5 Cores, 6FT / 1.83M
C13-36 PCS C19-6 PCS
50
1244.60
1294.60
DETAIL: G
SCALE: 1 : 1
NOTES:
1. 240V 32A 1-Phase.
SHEET 1 OF 1
REV.
01
RP1M32S42-004
DWG. NO.
PROJECT: DRAWINGS
Rain LU 2023/12/05
2023/12/05
Rain LU
DRAWN BY:
THIRD ANGLE PROJECTION ALL DIMENSIONS ARE IN MILLIMETERS [INCHES]
PROPRIETARY ITEM
THIS DRAWING AND SPECIFICATIONS HEREIN ARE
THE PROPERTY OF RAPTOR COMPANY AND SHALL
NOT BE COPIED.
THIS DRAWING IS BASED UPON LATEST AVAILABLE
INFORMATION AND IS SUBJECT TO CHANGE WITHOUT
NOTICE.
Rain LU
ENGINEER:
APPROVED BY: 2023/12/05
Rack PDU Metering, ZeroU,
7.4kW, 1 Phase, 32A,90/240V,
(36) C13, (6) C19
Drawing / Wiring Diagram
RP1M32S42-004