SlideShare a Scribd company logo
1 of 2
Download to read offline
www.acornfiresecurity.com



                       LaserFOCUS
                                                          TM
                                                                                VLF-500

                                                                                Features
                                                                                •	 Out-of-the-Box Installation and
                                                                                	 Commissioning
                                                                                •	 Ultrasonic Airflow Sensing
                                                                                •	 Laser-Based Absolute Smoke Detection
                                                                                •	 Pre-engineered pipe network designs
                                                                                •	 Programmable Alarm Thresholds
                                                                                •	 Dual Stage Air Filtration
                                                                                •	 Instant Recognition Display
                                                                                •	 Instant Fault Finder™
                                                                                •	 AutoLearn™ Smoke
                                                                                •	 AutoLearn™ Flow
                                                                                •	 Field Service Access Door
                                                                                •	 Multiple Event Logging in separate logs
                                                                                •	 Event log – up to 18000 events
                                                                                •	 Offline/online configuration capability
The VESDA LaserFOCUS detector is a very early warning smoke                     •	 Up to 500 m2 (5000 sq. ft.) coverage*
detector designed to protect small, business-critical environments of less
than 500 m2 (5000 sq. ft.)
The detector works by continually drawing air into sample holes in a pipe       Listings/Approvals
network. The air is filtered and passed into a detection chamber where light    •	 UL 268 listed
scattering technology detects the presence of very small amounts of smoke.      •	 UL 268A Duct listed
Detector status information is communicated on the detector display and via
relays or optional interface cards.                                             •	 FM approved
                                                                                •	 FM approved for Hazardous Locations,
Out-of-the-box operation                                                        	 Class I, Div. 2
The VESDA LaserFOCUS can be installed and commissioned out-of-the-box           •	 CCCF approved
without the need for a special interface or software programming tools.         •	 LPCB approved
In operation, the unique Smoke Dial display provides the user with an instant   •	 VdS approved
understanding of a smoke event, even from a distance. Should a fault occur,
the user simply opens the field service door and activates the Instant Fault
Finder feature to determine the specific fault condition. This information
can then be passed onto their fire service company, ensuring that service
technicians arrive onsite fully prepared.

Ultrasonic Flow Sensing
The patent-pending Ultrasonic Flow Sensing used in the LaserFOCUS
provides a direct reading of the sampling pipe flow rate. The system is
immune to air temperature and pressure changes and is unaffected by
contamination. VESDA is the first air sampling smoke detector to use
ultrasonic flow sensing.




                                             www.acornfiresecurity.com
www.acornfiresecurity.com



                              LaserFOCUS
                                                                         TM
                                                                                                  VLF-500
Specifications                                                                                    Display:
                                                                                                  The display provided to the user includes a
Input Power
                                                                                                  Smoke Dial and alarm and status indicators.
Voltage:	                             24V DC Nominal (18-30 V DC)
Current @ 24 VDC: 	                   410 mA nominal, 490 mA in alarm
Dimensions (W x H x D)	               255 mm x 185 mm x 90 mm (97/8 in x 71/8 in x 31/2 in)
Weight	                               Approx. 2 kg (4.4 lbs)
IP Rating	                            IP30
Mounting	                             Upright, inverted or horizontal
Operating Conditions†
Detector Ambient:	                    0 °C to 40 °C (32 °F to 104 °F)
Sampled Air:	                         0 °C to 40 °C (32 °F to 104 °F)
Humidity:	                            5% to 95% (non-condensing)
Sampling Network                                                                                                                        FIRE 2             RESET
Maximum pipe lengths:	            1 x 50 m (150 ft) (Max. 24 holes)
	                                 2 x 30 m (90 ft) per branch (Max. 12 holes per branch)                                                FIRE 1             FAULT
Sampling Hole Options: 	          Pre-Engineered Option or Maximum Pipe length in
	                                 accordance with Pipe Modelling Design Tool (ASPIRE2™)           When the field service access door is open,
                                                                                                                                   ACTION        DISABLE(D)
	                                                                                                 the user has access to the RESET ,RESET
                                                                                                                                 FIRE 2


Air Inlet Pipe                                                                                    DISABLE , Fire Test         , AutoLearn FAULT AUTOLEARN
                                                                                                                                   ALERT
                                                                                                                                 FIRE 1

Accepts both metric and American standard pipe sizes.                                             and Instant Fault Finder functions.
                                                                                                                                 ACTION   DISABLE(D)
Metric: 25 mm American Pipe: IPS ¾ in.                                                            When the Instant Fault Finder function is
                                                                                                  activated, the Smoke Dial converts to a fault
                                                                                                                                 ALERT    AUTOLEARN
Area Coverage
                                                                                                  indicator, with the dial segment numbers
Up to 500 m2 (5000 sq. ft.) depending on local codes and standards
                                                                                                  corresponding to the faults listed below.
Relay Outputs
3 changeover relays (Fire 1, Action, Fault), Contacts rated 2A @ 30 VDC (max). NO/NC Contacts
Cable Access                                                                                      Legend of fault indicators:
3 x 25 mm (11/16 in.) cable entries (1 rear entry, 2 top entry)                                   1
                                                                                                  	 	 Filter	           6	 External Device/PSU
Cable Termination                                                                                 2
                                                                                                  	 	Aspirator	         7	 Interface card
Screw Terminals 0.2-2.5 mm2 (30-12 AWG)                                                           3
                                                                                                  	 	 High flow	        8	 Field wiring
                                                                                                  4
                                                                                                  	 	 Low flow	         9	 AutoLearn Fail
Interfaces
                                                                                                  5
                                                                                                  	 	 n/a	             10	 Detector failure
Shown in Terminal Block Connections diagram, to right, plus an RS232 Programming Port.
General Purpose Input (GPI) interface offers: Reset, Disable, Standby, Alarm set 1, Alarm set 2
and External Input functions.
                                                                                                  Terminal Block Connections:
Alarm Threshold Setting Range
Alert, Action, 	                      0.025 - 2.00% obs/m (0.008 - 0.625% obs/ft)                           	 1	 GPI
Fire 1, Fire 2	                       0.025 - 20.00% obs/m (0.008 - 6.25% obs/ft)                           	 2	 GPI
Individual Alarm Delays	              0 – 60 seconds                                                        	 3	 Display TX
Two Alarm Threshold Settings 	        Either time or GPI based                                              	 4	 Display RX

Display                                                                                                     	 5	 Display Common Ground

• 4 Alarm State Indicators	         • Fault and Disabled Indicators                                         	 6	 Display Power -
• Smoke Level Indicator	            • Instant Fault Finder                                                  	 7	 Display Power +
• Reset, Disable and Test Controls	 • Smoke and Flow AutoLearn Controls                                     	 8	 Power Return 0 VDC    From power
                                                                                                                                       supply unit
                                                                                                            	 9	 Power In 24 VDC
Event Log
                                                                                                                                       To next detector
Up to 18000 events, time and date stamped in separate, non-volatile, logs for:                              	 10	 Power Return 0 VDC
                                                                                                                                       (if more than 1 detector
Smoke Level, Flow Level, Detector Status and Faults                                                         	 11	 Power Out 24 VDC     per Power Supply Unit)
                                                                                                            	 12	 NC
AutoLearn Smoke & Flow
                                                                                                            	 13	 Common               Fault relay
• Automatically set acceptable alarm thresholds for both smoke and flow levels
                                                                                                            	 14	 NO
• Minimum 15 minutes, maximum 15 days (default 14 days)
• During AutoLearn, thresholds are NOT changed from pre-set values                                          	 15	 NC
                                                                                                            	 16	 Common               Action relay
Warranty Period
                                                                                                            	 17	 NO
2 years
                                                                                                            	 18	 NC
Ordering Information:                                                                                       	 19	 Common               Fire 1 relay
VLF-500-00 VESDA LaserFOCUS. European language set. English display labels                                  	 20	 NO
VLF-500-01 VESDA LaserFOCUS. European language set. International display labels
VLF-500-02 VESDA LaserFOCUS. English + Asian language set. International display labels
VIC-010 VESDAnet Interface Card
VSP-005 Filter Cartridge
VSP-715 Aspirator




                                                           www.acornfiresecurity.com

More Related Content

What's hot

What's hot (13)

Testo 340 datasheet 2012
Testo 340 datasheet 2012Testo 340 datasheet 2012
Testo 340 datasheet 2012
 
Laser Science Services (I) Pvt. Ltd
Laser Science Services (I) Pvt. LtdLaser Science Services (I) Pvt. Ltd
Laser Science Services (I) Pvt. Ltd
 
Senscient ELDS Laser Gas Detection System
Senscient ELDS Laser Gas Detection SystemSenscient ELDS Laser Gas Detection System
Senscient ELDS Laser Gas Detection System
 
Up 15 K Brochure
Up 15 K BrochureUp 15 K Brochure
Up 15 K Brochure
 
Drager Polytron 8720 Fixed Gas Detector - Spec Sheet
Drager Polytron 8720 Fixed Gas Detector - Spec SheetDrager Polytron 8720 Fixed Gas Detector - Spec Sheet
Drager Polytron 8720 Fixed Gas Detector - Spec Sheet
 
Entry Scan3e Rev B April 06
Entry Scan3e Rev B April 06Entry Scan3e Rev B April 06
Entry Scan3e Rev B April 06
 
Brosur Total Station Sokkia Cx series
Brosur Total Station Sokkia Cx seriesBrosur Total Station Sokkia Cx series
Brosur Total Station Sokkia Cx series
 
Et traffic b ox brochure 2pp
Et traffic b ox brochure 2ppEt traffic b ox brochure 2pp
Et traffic b ox brochure 2pp
 
Bi osingle(sbs series)
Bi osingle(sbs series)Bi osingle(sbs series)
Bi osingle(sbs series)
 
Honeywell 5898-data-sheet
Honeywell 5898-data-sheetHoneywell 5898-data-sheet
Honeywell 5898-data-sheet
 
Rx 40 qz
Rx 40 qzRx 40 qz
Rx 40 qz
 
Ds g-700
Ds g-700Ds g-700
Ds g-700
 
Et pms leaflet
Et pms leafletEt pms leaflet
Et pms leaflet
 

Similar to Vesda laser focus vlf500 data sheet

Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...Hile Controls of Alabama, Inc.
 
Vesda vls laser scanner data sheet
Vesda vls laser scanner data sheetVesda vls laser scanner data sheet
Vesda vls laser scanner data sheetsanzen enterprises
 
Honeywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetHoneywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetAlarm Grid
 
CPM-700 Deluxe datasheet
CPM-700 Deluxe datasheetCPM-700 Deluxe datasheet
CPM-700 Deluxe datasheetMartin Quaife
 
Technical Data Fluke ii900 Sonic Industrial Imager
Technical Data Fluke ii900 Sonic Industrial ImagerTechnical Data Fluke ii900 Sonic Industrial Imager
Technical Data Fluke ii900 Sonic Industrial ImagerPT. Siwali Swantika
 
Sound level meters
Sound level metersSound level meters
Sound level meterslink2013
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishHans Bronkhorst
 
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamikaKatalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamikaPT. Tridinamika Jaya Instrument
 

Similar to Vesda laser focus vlf500 data sheet (20)

D2
D2D2
D2
 
G vlp 400 data sheet
G vlp 400 data sheetG vlp 400 data sheet
G vlp 400 data sheet
 
D4120
D4120D4120
D4120
 
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
 
Vesda vls laser scanner data sheet
Vesda vls laser scanner data sheetVesda vls laser scanner data sheet
Vesda vls laser scanner data sheet
 
Intro to x ray
Intro to x rayIntro to x ray
Intro to x ray
 
Vt Dat A4 Nov 07 Rev
Vt Dat A4 Nov 07 RevVt Dat A4 Nov 07 Rev
Vt Dat A4 Nov 07 Rev
 
Honeywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetHoneywell 5806w3-data-sheet
Honeywell 5806w3-data-sheet
 
Optical smokedetectoreco1003
Optical smokedetectoreco1003Optical smokedetectoreco1003
Optical smokedetectoreco1003
 
Dn 7112 pdf
Dn 7112 pdfDn 7112 pdf
Dn 7112 pdf
 
CPM-700 Deluxe datasheet
CPM-700 Deluxe datasheetCPM-700 Deluxe datasheet
CPM-700 Deluxe datasheet
 
Technical Data Fluke ii900 Sonic Industrial Imager
Technical Data Fluke ii900 Sonic Industrial ImagerTechnical Data Fluke ii900 Sonic Industrial Imager
Technical Data Fluke ii900 Sonic Industrial Imager
 
Dnr
DnrDnr
Dnr
 
Introduction to FIRElink.pptx
Introduction to FIRElink.pptxIntroduction to FIRElink.pptx
Introduction to FIRElink.pptx
 
Sound level meters
Sound level metersSound level meters
Sound level meters
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet english
 
Fire Fighting Enterprises Presentation
Fire Fighting Enterprises PresentationFire Fighting Enterprises Presentation
Fire Fighting Enterprises Presentation
 
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamikaKatalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
Katalog fluke-oscilloscope-the-toughest-scopes-ever-built-by-tridinamika
 
Ia r6000-c-r1-1
Ia r6000-c-r1-1Ia r6000-c-r1-1
Ia r6000-c-r1-1
 
Ia r6000-c-r1-1
Ia r6000-c-r1-1Ia r6000-c-r1-1
Ia r6000-c-r1-1
 

More from sanzen enterprises (20)

Odyssey 3
Odyssey 3Odyssey 3
Odyssey 3
 
Vm3240va ce cb1e
Vm3240va ce cb1eVm3240va ce cb1e
Vm3240va ce cb1e
 
Vm 3240 e
Vm 3240 eVm 3240 e
Vm 3240 e
 
Sv200ma mi1e
Sv200ma mi1eSv200ma mi1e
Sv200ma mi1e
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
 
Cs154 cs1e
Cs154 cs1eCs154 cs1e
Cs154 cs1e
 
Bs678 cs1e tei rev1
Bs678 cs1e tei rev1Bs678 cs1e tei rev1
Bs678 cs1e tei rev1
 
Bs633a data sheet
Bs633a data sheetBs633a data sheet
Bs633a data sheet
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
 
Data sheet en_us_1911721995
Data sheet en_us_1911721995Data sheet en_us_1911721995
Data sheet en_us_1911721995
 
La1 uw24 x column loudspeakers
La1 uw24 x column loudspeakersLa1 uw24 x column loudspeakers
La1 uw24 x column loudspeakers
 
Bgt 4139 ts
Bgt 4139 tsBgt 4139 ts
Bgt 4139 ts
 
Bgt 5504 a
Bgt 5504 aBgt 5504 a
Bgt 5504 a
 
Bgt 5140 a
Bgt 5140 aBgt 5140 a
Bgt 5140 a
 
Bgt 9120 ts
Bgt 9120 tsBgt 9120 ts
Bgt 9120 ts
 
Bgt 9119 as
Bgt 9119 asBgt 9119 as
Bgt 9119 as
 
Bgt 720 tos
Bgt 720 tosBgt 720 tos
Bgt 720 tos
 
Bgt 5221 as
Bgt 5221 asBgt 5221 as
Bgt 5221 as
 

Vesda laser focus vlf500 data sheet

  • 1. www.acornfiresecurity.com LaserFOCUS TM VLF-500 Features • Out-of-the-Box Installation and Commissioning • Ultrasonic Airflow Sensing • Laser-Based Absolute Smoke Detection • Pre-engineered pipe network designs • Programmable Alarm Thresholds • Dual Stage Air Filtration • Instant Recognition Display • Instant Fault Finder™ • AutoLearn™ Smoke • AutoLearn™ Flow • Field Service Access Door • Multiple Event Logging in separate logs • Event log – up to 18000 events • Offline/online configuration capability The VESDA LaserFOCUS detector is a very early warning smoke • Up to 500 m2 (5000 sq. ft.) coverage* detector designed to protect small, business-critical environments of less than 500 m2 (5000 sq. ft.) The detector works by continually drawing air into sample holes in a pipe Listings/Approvals network. The air is filtered and passed into a detection chamber where light • UL 268 listed scattering technology detects the presence of very small amounts of smoke. • UL 268A Duct listed Detector status information is communicated on the detector display and via relays or optional interface cards. • FM approved • FM approved for Hazardous Locations, Out-of-the-box operation Class I, Div. 2 The VESDA LaserFOCUS can be installed and commissioned out-of-the-box • CCCF approved without the need for a special interface or software programming tools. • LPCB approved In operation, the unique Smoke Dial display provides the user with an instant • VdS approved understanding of a smoke event, even from a distance. Should a fault occur, the user simply opens the field service door and activates the Instant Fault Finder feature to determine the specific fault condition. This information can then be passed onto their fire service company, ensuring that service technicians arrive onsite fully prepared. Ultrasonic Flow Sensing The patent-pending Ultrasonic Flow Sensing used in the LaserFOCUS provides a direct reading of the sampling pipe flow rate. The system is immune to air temperature and pressure changes and is unaffected by contamination. VESDA is the first air sampling smoke detector to use ultrasonic flow sensing. www.acornfiresecurity.com
  • 2. www.acornfiresecurity.com LaserFOCUS TM VLF-500 Specifications Display: The display provided to the user includes a Input Power Smoke Dial and alarm and status indicators. Voltage: 24V DC Nominal (18-30 V DC) Current @ 24 VDC: 410 mA nominal, 490 mA in alarm Dimensions (W x H x D) 255 mm x 185 mm x 90 mm (97/8 in x 71/8 in x 31/2 in) Weight Approx. 2 kg (4.4 lbs) IP Rating IP30 Mounting Upright, inverted or horizontal Operating Conditions† Detector Ambient: 0 °C to 40 °C (32 °F to 104 °F) Sampled Air: 0 °C to 40 °C (32 °F to 104 °F) Humidity: 5% to 95% (non-condensing) Sampling Network FIRE 2 RESET Maximum pipe lengths: 1 x 50 m (150 ft) (Max. 24 holes) 2 x 30 m (90 ft) per branch (Max. 12 holes per branch) FIRE 1 FAULT Sampling Hole Options: Pre-Engineered Option or Maximum Pipe length in accordance with Pipe Modelling Design Tool (ASPIRE2™) When the field service access door is open, ACTION DISABLE(D) the user has access to the RESET ,RESET FIRE 2 Air Inlet Pipe DISABLE , Fire Test , AutoLearn FAULT AUTOLEARN ALERT FIRE 1 Accepts both metric and American standard pipe sizes. and Instant Fault Finder functions. ACTION DISABLE(D) Metric: 25 mm American Pipe: IPS ¾ in. When the Instant Fault Finder function is activated, the Smoke Dial converts to a fault ALERT AUTOLEARN Area Coverage indicator, with the dial segment numbers Up to 500 m2 (5000 sq. ft.) depending on local codes and standards corresponding to the faults listed below. Relay Outputs 3 changeover relays (Fire 1, Action, Fault), Contacts rated 2A @ 30 VDC (max). NO/NC Contacts Cable Access Legend of fault indicators: 3 x 25 mm (11/16 in.) cable entries (1 rear entry, 2 top entry) 1 Filter 6 External Device/PSU Cable Termination 2 Aspirator 7 Interface card Screw Terminals 0.2-2.5 mm2 (30-12 AWG) 3 High flow 8 Field wiring 4 Low flow 9 AutoLearn Fail Interfaces 5 n/a 10 Detector failure Shown in Terminal Block Connections diagram, to right, plus an RS232 Programming Port. General Purpose Input (GPI) interface offers: Reset, Disable, Standby, Alarm set 1, Alarm set 2 and External Input functions. Terminal Block Connections: Alarm Threshold Setting Range Alert, Action, 0.025 - 2.00% obs/m (0.008 - 0.625% obs/ft) 1 GPI Fire 1, Fire 2 0.025 - 20.00% obs/m (0.008 - 6.25% obs/ft) 2 GPI Individual Alarm Delays 0 – 60 seconds 3 Display TX Two Alarm Threshold Settings Either time or GPI based 4 Display RX Display 5 Display Common Ground • 4 Alarm State Indicators • Fault and Disabled Indicators 6 Display Power - • Smoke Level Indicator • Instant Fault Finder 7 Display Power + • Reset, Disable and Test Controls • Smoke and Flow AutoLearn Controls 8 Power Return 0 VDC From power supply unit 9 Power In 24 VDC Event Log To next detector Up to 18000 events, time and date stamped in separate, non-volatile, logs for: 10 Power Return 0 VDC (if more than 1 detector Smoke Level, Flow Level, Detector Status and Faults 11 Power Out 24 VDC per Power Supply Unit) 12 NC AutoLearn Smoke & Flow 13 Common Fault relay • Automatically set acceptable alarm thresholds for both smoke and flow levels 14 NO • Minimum 15 minutes, maximum 15 days (default 14 days) • During AutoLearn, thresholds are NOT changed from pre-set values 15 NC 16 Common Action relay Warranty Period 17 NO 2 years 18 NC Ordering Information: 19 Common Fire 1 relay VLF-500-00 VESDA LaserFOCUS. European language set. English display labels 20 NO VLF-500-01 VESDA LaserFOCUS. European language set. International display labels VLF-500-02 VESDA LaserFOCUS. English + Asian language set. International display labels VIC-010 VESDAnet Interface Card VSP-005 Filter Cartridge VSP-715 Aspirator www.acornfiresecurity.com