Technical Datasheet
TD 00025E/24/EN/01.13
•	 Detect up to five level limits with
one probe
•	 Flexible instrumentation (compact/
separate)
•	 No moving parts
•	 No calibration required
Complete product information:
www.e-direct.us/ftw31_32
Specs at a glance:
•	Product: liquids as of 5 µS/cm
•	Approval: ATEX II 2G EEx ia
•	Measuring points:
up to 4 measuring points with
5 rods or ropes
•	Product temperature:
-40 to + 212 °F
(-40 to +100 °C)
•	Process pressure:
-14.5 to +145 psi
(-1 to +10 bar)
Conductivity point level switch for multiple point detection
Liquipoint T FTW31 / FTW32
$ 139.00
Probes with integrated electronic insert
(compact instrument version)
The measuring system consists of:
•	 FTW31, FTW32 with two/three rods or
ropes and an electronic insert
•	 Control units, switches or signal transmitters,
e.g. process control systems PLC, relays or
NAMUR isolating amplifier according to IEC
60947-5-6
Probes without integrated electronic insert
(separate instrument version)
The measuring system consists of:
•	 FTW31, FTW32 with two to five rods or ropes
•	 Nivotester FTW325 or FTW470 Z
•	 Control units, switches or signal transmitters,
e.g. process control systems PLC, relays, etc.
The number of Nivotester depends on the
number of measuring points (e.g. 4 measuring
points with 2 Nivotester FTW).
Ex Ex Ex Ex
4
5
6
71
[Ex ia ]
CH1
CH1
FTW 32
T
5
7
8
9
01
Liquipoint T FTW31 / FTW32 2
Overview Technical data Dimensions
Electrical connection Price table Contact
Go to
shop
Application / Function
Application Liquipoint T sensors are
used in conductive liquids for
determining point levels. Depending
on the number of measuring points,
measuring tasks such as overspill
protection, dry running protection,
two-point control of pumps or
multiple point detection can be
implemented within an existing
process connection.
Application exampleFunction An alternating voltage
exists between the rod probes in an
empty tank. As soon as the conductive
liquid in the tank creates a connection
between the ground rod probe and the
maximum rod probe, for example, a
measurable current flows and the
Liquipoint T switches.
By using alternating voltage, corrosion
of the probe ends and electroytic
destruction of the product is avoided.
As the system is designed as a closed
potential-free circuit between the
probe rods and the electronics, the
materials used in the tank walls is
unimportant and there is no danger if
the probe rods are touched during
operation.
Liquipoint T FTW31 / FTW32 3
Application / FunctionOverview
Electrical connection Price table Contact
Go to
shop
Technical data Dimensions
General
Version Compact version:
two/three (Always ∆S-mode – only three
rod-/rope versions) rods or ropes;
Separate version (With integrated line
monitoring – in combination with level limit
switch FTW325):
two/three/five rods or ropes
Sensor length Rod: 100 to 4000 mm (4” to 157”);
rope: 250 to 15000 mm (10” to 590”)
Minimum
conductivity
Compact version ≥ 10 µS/cm
Separate version (FTW325) ≥ 5 µS/cm
Cable specification Use standard cable (25 Ω per core)
Operating conditions
Medium temp. -40 to +212 °F (-40 to +100 °C)
Ambient temp. -40 to +158 °F (-40 to +70 °C)
Pressure -14.5 to +145 psi (-1 to +10 bar)
Ingress Protection IP 66
Process connection G 1½"
Material
Electrodes Rods: 1.4404 (316L)/insulation: PP;
ropes: 1.4571 (316TI)/insulation: FEP;
weight: 1.4435 (316L)
Process connection PPS
Housing F16 For compact instrument version;
housing: PBT;
hat: PPS;
adapter: PBT
Housing F24 For separate instrument version;
housing: PPS;
hat: PBT
Approvals (Compact instrument version)
Ex approval ATEX II 2G EEx ia IIC T6 with FEW58
WHG approval WHG Z-65.40-360 (DIBt)
Approvals (Separate instrument version)
Ex approval ATEX II 2G EEx ia IIC T6
Technical data Dimensions (in inches)
FTW32 (Rope version)FTW31 (Rod version)
Installation according to instruction manual
Rod and rope version with G 1½"
(compact instrument version with electronic insert)
max. 2.99
Ø 3.35
max. 2.99
Ø 3.35
Ø 0.20
Ø 0.16
1.10
5.71
0.87
1.46
0.87
1.46
G 1½
Ø 0.10
5.71
Ø 0.40
3.94
ProbelengthL
4"to160"
ProbelengthL10"to590"
AF 55
G 1½
AF 55
FTW32 (Rope version)FTW31 (Rod version)
Installation according to instruction manual
Rod and rope version with G 1½"
(separate instrument version without electronic insert)
2.52
G 1½
max. 2.48
Ø 2.60
AF 55
G 1½
AF 55
0.87
1.46
2.52
max. 2.48
Ø 2.60
0.87
1.46
Ø 0.20
Ø 0.16
1.10
Ø 0.10
Ø 0.40
3.94
ProbelengthL
4"to160"
ProbelengthL10"to590"
Liquipoint T FTW31 / FTW32 4
Application / FunctionOverview Technical data Dimensions
Price table Contact
Go to
shopElectrical connection
Electrical connection – Probes with electronic insert (compact instrument version) Electrical connection – Probes without integrated
electronic insert (separate-instrument version)
FEW52
Mains
M
1 2
L+
F R
–
(+)
L–
3
Electronic insert FEW54
Supply voltage 20 to 55 V DC or
20 to 253 V AC, 50/60 Hz
Current consumption 60 mA
Peak inrush current Max. 2 A, max. 400 µs
Pulse frequency Approx. 1.5 s
Output Two potential-free changeover contacts
(DPDT)
Contact load capacity U~ max. 253 V, I~ max. 4 A,
U = 30 V/4 A; 150 V/ 0.2 A
Power consumption < 2.0 W
Electronic insert FEW58
Supply voltage see Technical data of connected isolating amplifier
according to IEC 60947-5-6 (NAMUR).
Use with a separate contactor according to IEC 60947-5-6 (NAMUR);
output signal leap of high to low electricity on limit (H-L-flank).
Two-wire signal transfer: H-L-edge 2.2 to 6.5 mA/0.4 to 1.0 mA
Output signal of damaged sensor: < 1.0 mA
On access to a multiplexer the cycle time is to adjust on min. 2 sec.
Electronic insert FEW52
Supply voltage U = 10.8 to 45 V
Current consumption Max. 25 mA
Load connection Open collector; PNP
Switching voltage Max. 45 V
Connectable load Temporary (max. 1 sec): max. 2 A
Continuous: max. 200 mA
Protected against
reverse polarity
Yes
FEW54
Mains
+ –
L1
F1
F2
F2
N PE
a u r a u
M
r
1 2 3 4 5 6 7 8
Potential-free change-over contacts Vessel
–
1
+
2
FEW58
EX
EX
I
IEC 60947-5-6 (NAMUR) e.g. FTL325N
Connecting the FEW52 electronic
insert
F: Fine-wire fuse, dependent on
connected load
R: Connected load, e.g. PLC, PLS,
relay
M: Ground connection to
protective earth (PE)
For evaluation one or more
FTW325 processor units are
needed.
Separate instrumentation for
three-rod- or rope-probes with
cable monitoring.
*1 = Printed circuit board for
cable monitoring
Connecting the
FEW52 electronic
insert
F1: Fine-wire fuse,
200 mA,
semi-time lag
F2: Fine-wire fuse to
protect the relay
contact,
load-dependent
M: Ground
connection to PE
(protective earth)
7 8 9
d4 b2 d2
z4
CH1
FTW325
CH2
*1
1 3 2
Min
Max
b4 z2
Liquipoint T FTW31 / FTW32 5
Application / FunctionOverview Technical data Dimensions
Electrical connection Contact
Go to
shopPrice table
Price table
More products to complete your measuring point …
Liquipoint T FTW31 Order no. Price/pcs. in USD
Approval Electronics; Output Sensing Point 1 to 5 6 to 10 11 to 35
Non-hazardous
area
Separate instrumentation 3x rod, 316L FTW31-A2A3EB0A 176.00 164.00 155.00
5x rod, 316L FTW31-A2A5EB0A 204.00 190.00 180.00
FEW54; relay 20-253VAC; 20-55VDC 3x rod, 316L FTW31-A2A3EB4A 306.00 285.00 269.00
Liquipoint T FTW32 Order no. Price/pcs. in USD
Approval Electronics; Output Sensing Point 1 to 5 6 to 10 11 to 35
Non-hazardous
area
Separate instrumentation 2x rope, 316Ti FTW32-A2D2EB0A 158.00 147.00 139.00
5x rope, 316Ti FTW32-A2D5EB0A 392.00 365.00 345.00
Prices valid until 09.30.2013 in U.S. dollars per unit (not including shipping and applicable sales tax).
See Endress+Hauser, Inc. Terms and Conditions of Sale for shipping, tax, and payment terms.
Complete product information:
www.e-direct.us/ftw31_32
Temperature switch
Thermophant T TTR31
Switching unit
Nivotester FTW325
Capacitive probe
Liquicap T FMI21
Application / FunctionOverview Technical data Dimensions
Electrical connection Price table Contact
Go to
shop
Contact
E-direct
Endress+Hauser, Inc.
2350 Endress Place
Greenwood, IN 46143
Direct order
Internet	www.e-direct.us
by phone	 888-EH-DIRECT
(343-4732)
per Fax	 317-535-8498
E-Mail	e-direct@us.endress.com

More Related Content

Similar to FTW31 - FTW32

Comac cal flow38
Comac cal flow38Comac cal flow38
Comac cal flow38
Arve
 
Katalog fluke-1621-earth-ground-tester-by-tridinamika
Katalog fluke-1621-earth-ground-tester-by-tridinamikaKatalog fluke-1621-earth-ground-tester-by-tridinamika
Katalog fluke-1621-earth-ground-tester-by-tridinamika
PT. Tridinamika Jaya Instrument
 
Drager Polytron 5700 Fixed Gas Detector - Spec Sheet
Drager Polytron 5700 Fixed Gas Detector - Spec SheetDrager Polytron 5700 Fixed Gas Detector - Spec Sheet
Drager Polytron 5700 Fixed Gas Detector - Spec Sheet
Thorne & Derrick UK
 
Automated pH Sensor Cleaning and Calibration
Automated pH Sensor Cleaning and CalibrationAutomated pH Sensor Cleaning and Calibration
Automated pH Sensor Cleaning and Calibration
Alliance Technical Sales, Inc.
 
Solar Edge Load Switching Devices
Solar Edge Load Switching Devices Solar Edge Load Switching Devices
Solar Edge Load Switching Devices
Optimus Energy Philippines
 
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec SheetDrager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
Thorne & Derrick UK
 
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
PT. Siwali Swantika
 
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled PipesKrohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
Instrument Specialties, Inc.
 
Drager Polytron 8310 Fixed Gas Detector - Spec Sheet
Drager Polytron 8310 Fixed Gas Detector - Spec SheetDrager Polytron 8310 Fixed Gas Detector - Spec Sheet
Drager Polytron 8310 Fixed Gas Detector - Spec Sheet
Thorne & Derrick UK
 
Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618
PT. Siwali Swantika
 
Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...
Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...
Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...Thorne & Derrick UK
 
LV live feeder and phase identifier
LV live feeder and phase identifierLV live feeder and phase identifier
LV live feeder and phase identifier
Al Buraq Hardware & Tools L.L.C
 
Vibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for LiquidsVibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for Liquids
Trumen Technologies Pvt. Ltd. India
 
Vibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for LiquidsVibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for Liquids
Trumen Technologies Pvt. Ltd. India
 

Similar to FTW31 - FTW32 (20)

FTM20 - FTM21
FTM20 - FTM21FTM20 - FTM21
FTM20 - FTM21
 
Comac cal flow38
Comac cal flow38Comac cal flow38
Comac cal flow38
 
Katalog fluke-1621-earth-ground-tester-by-tridinamika
Katalog fluke-1621-earth-ground-tester-by-tridinamikaKatalog fluke-1621-earth-ground-tester-by-tridinamika
Katalog fluke-1621-earth-ground-tester-by-tridinamika
 
FTC260 - FTC262
FTC260 - FTC262FTC260 - FTC262
FTC260 - FTC262
 
DTT31
DTT31DTT31
DTT31
 
FTW325
FTW325FTW325
FTW325
 
Drager Polytron 5700 Fixed Gas Detector - Spec Sheet
Drager Polytron 5700 Fixed Gas Detector - Spec SheetDrager Polytron 5700 Fixed Gas Detector - Spec Sheet
Drager Polytron 5700 Fixed Gas Detector - Spec Sheet
 
Automated pH Sensor Cleaning and Calibration
Automated pH Sensor Cleaning and CalibrationAutomated pH Sensor Cleaning and Calibration
Automated pH Sensor Cleaning and Calibration
 
Solar Edge Load Switching Devices
Solar Edge Load Switching Devices Solar Edge Load Switching Devices
Solar Edge Load Switching Devices
 
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec SheetDrager Polytron 5720 Fixed Gas Detector - Spec Sheet
Drager Polytron 5720 Fixed Gas Detector - Spec Sheet
 
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
 
DTT35
DTT35DTT35
DTT35
 
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled PipesKrohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
Krohne TIDALFLUX Electromagnetic Flow Sensor for Partially Filled Pipes
 
Drager Polytron 8310 Fixed Gas Detector - Spec Sheet
Drager Polytron 8310 Fixed Gas Detector - Spec SheetDrager Polytron 8310 Fixed Gas Detector - Spec Sheet
Drager Polytron 8310 Fixed Gas Detector - Spec Sheet
 
Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1750. Hubungi PT. Siwali Swantika 021-45850618
 
Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...
Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...
Kamstrup ultraflow 54 ultrasonic flow meter, multical heat meter, thermal hea...
 
LV live feeder and phase identifier
LV live feeder and phase identifierLV live feeder and phase identifier
LV live feeder and phase identifier
 
FMI21
FMI21FMI21
FMI21
 
Vibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for LiquidsVibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for Liquids
 
Vibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for LiquidsVibrating Fork Point Level Switch for Liquids
Vibrating Fork Point Level Switch for Liquids
 

More from E-direct, Division of Endress+Hauser (20)

TTR35
TTR35TTR35
TTR35
 
TTR31
TTR31TTR31
TTR31
 
TST487
TST487TST487
TST487
 
TST187
TST187TST187
TST187
 
TSM487
TSM487TSM487
TSM487
 
TSM187
TSM187TSM187
TSM187
 
TMT127-187-128-188
TMT127-187-128-188TMT127-187-128-188
TMT127-187-128-188
 
TMT80
TMT80TMT80
TMT80
 
TMR35
TMR35TMR35
TMR35
 
TMR31
TMR31TMR31
TMR31
 
RTA421
RTA421RTA421
RTA421
 
RSG30
RSG30RSG30
RSG30
 
RNS221
RNS221RNS221
RNS221
 
RN221N
RN221NRN221N
RN221N
 
RMA42
RMA42RMA42
RMA42
 
RIA452
RIA452RIA452
RIA452
 
RIA2
RIA2RIA2
RIA2
 
RIA46
RIA46RIA46
RIA46
 
RIA45
RIA45RIA45
RIA45
 
RIA14 - RIA16
RIA14 - RIA16RIA14 - RIA16
RIA14 - RIA16
 

FTW31 - FTW32

  • 1. approval Products Solutions Services Application / FunctionOverview Technical data Dimensions Electrical connection Price table Contact Go to shop Technical Datasheet TD 00025E/24/EN/01.13 • Detect up to five level limits with one probe • Flexible instrumentation (compact/ separate) • No moving parts • No calibration required Complete product information: www.e-direct.us/ftw31_32 Specs at a glance: • Product: liquids as of 5 µS/cm • Approval: ATEX II 2G EEx ia • Measuring points: up to 4 measuring points with 5 rods or ropes • Product temperature: -40 to + 212 °F (-40 to +100 °C) • Process pressure: -14.5 to +145 psi (-1 to +10 bar) Conductivity point level switch for multiple point detection Liquipoint T FTW31 / FTW32 $ 139.00
  • 2. Probes with integrated electronic insert (compact instrument version) The measuring system consists of: • FTW31, FTW32 with two/three rods or ropes and an electronic insert • Control units, switches or signal transmitters, e.g. process control systems PLC, relays or NAMUR isolating amplifier according to IEC 60947-5-6 Probes without integrated electronic insert (separate instrument version) The measuring system consists of: • FTW31, FTW32 with two to five rods or ropes • Nivotester FTW325 or FTW470 Z • Control units, switches or signal transmitters, e.g. process control systems PLC, relays, etc. The number of Nivotester depends on the number of measuring points (e.g. 4 measuring points with 2 Nivotester FTW). Ex Ex Ex Ex 4 5 6 71 [Ex ia ] CH1 CH1 FTW 32 T 5 7 8 9 01 Liquipoint T FTW31 / FTW32 2 Overview Technical data Dimensions Electrical connection Price table Contact Go to shop Application / Function Application Liquipoint T sensors are used in conductive liquids for determining point levels. Depending on the number of measuring points, measuring tasks such as overspill protection, dry running protection, two-point control of pumps or multiple point detection can be implemented within an existing process connection. Application exampleFunction An alternating voltage exists between the rod probes in an empty tank. As soon as the conductive liquid in the tank creates a connection between the ground rod probe and the maximum rod probe, for example, a measurable current flows and the Liquipoint T switches. By using alternating voltage, corrosion of the probe ends and electroytic destruction of the product is avoided. As the system is designed as a closed potential-free circuit between the probe rods and the electronics, the materials used in the tank walls is unimportant and there is no danger if the probe rods are touched during operation.
  • 3. Liquipoint T FTW31 / FTW32 3 Application / FunctionOverview Electrical connection Price table Contact Go to shop Technical data Dimensions General Version Compact version: two/three (Always ∆S-mode – only three rod-/rope versions) rods or ropes; Separate version (With integrated line monitoring – in combination with level limit switch FTW325): two/three/five rods or ropes Sensor length Rod: 100 to 4000 mm (4” to 157”); rope: 250 to 15000 mm (10” to 590”) Minimum conductivity Compact version ≥ 10 µS/cm Separate version (FTW325) ≥ 5 µS/cm Cable specification Use standard cable (25 Ω per core) Operating conditions Medium temp. -40 to +212 °F (-40 to +100 °C) Ambient temp. -40 to +158 °F (-40 to +70 °C) Pressure -14.5 to +145 psi (-1 to +10 bar) Ingress Protection IP 66 Process connection G 1½" Material Electrodes Rods: 1.4404 (316L)/insulation: PP; ropes: 1.4571 (316TI)/insulation: FEP; weight: 1.4435 (316L) Process connection PPS Housing F16 For compact instrument version; housing: PBT; hat: PPS; adapter: PBT Housing F24 For separate instrument version; housing: PPS; hat: PBT Approvals (Compact instrument version) Ex approval ATEX II 2G EEx ia IIC T6 with FEW58 WHG approval WHG Z-65.40-360 (DIBt) Approvals (Separate instrument version) Ex approval ATEX II 2G EEx ia IIC T6 Technical data Dimensions (in inches) FTW32 (Rope version)FTW31 (Rod version) Installation according to instruction manual Rod and rope version with G 1½" (compact instrument version with electronic insert) max. 2.99 Ø 3.35 max. 2.99 Ø 3.35 Ø 0.20 Ø 0.16 1.10 5.71 0.87 1.46 0.87 1.46 G 1½ Ø 0.10 5.71 Ø 0.40 3.94 ProbelengthL 4"to160" ProbelengthL10"to590" AF 55 G 1½ AF 55 FTW32 (Rope version)FTW31 (Rod version) Installation according to instruction manual Rod and rope version with G 1½" (separate instrument version without electronic insert) 2.52 G 1½ max. 2.48 Ø 2.60 AF 55 G 1½ AF 55 0.87 1.46 2.52 max. 2.48 Ø 2.60 0.87 1.46 Ø 0.20 Ø 0.16 1.10 Ø 0.10 Ø 0.40 3.94 ProbelengthL 4"to160" ProbelengthL10"to590"
  • 4. Liquipoint T FTW31 / FTW32 4 Application / FunctionOverview Technical data Dimensions Price table Contact Go to shopElectrical connection Electrical connection – Probes with electronic insert (compact instrument version) Electrical connection – Probes without integrated electronic insert (separate-instrument version) FEW52 Mains M 1 2 L+ F R – (+) L– 3 Electronic insert FEW54 Supply voltage 20 to 55 V DC or 20 to 253 V AC, 50/60 Hz Current consumption 60 mA Peak inrush current Max. 2 A, max. 400 µs Pulse frequency Approx. 1.5 s Output Two potential-free changeover contacts (DPDT) Contact load capacity U~ max. 253 V, I~ max. 4 A, U = 30 V/4 A; 150 V/ 0.2 A Power consumption < 2.0 W Electronic insert FEW58 Supply voltage see Technical data of connected isolating amplifier according to IEC 60947-5-6 (NAMUR). Use with a separate contactor according to IEC 60947-5-6 (NAMUR); output signal leap of high to low electricity on limit (H-L-flank). Two-wire signal transfer: H-L-edge 2.2 to 6.5 mA/0.4 to 1.0 mA Output signal of damaged sensor: < 1.0 mA On access to a multiplexer the cycle time is to adjust on min. 2 sec. Electronic insert FEW52 Supply voltage U = 10.8 to 45 V Current consumption Max. 25 mA Load connection Open collector; PNP Switching voltage Max. 45 V Connectable load Temporary (max. 1 sec): max. 2 A Continuous: max. 200 mA Protected against reverse polarity Yes FEW54 Mains + – L1 F1 F2 F2 N PE a u r a u M r 1 2 3 4 5 6 7 8 Potential-free change-over contacts Vessel – 1 + 2 FEW58 EX EX I IEC 60947-5-6 (NAMUR) e.g. FTL325N Connecting the FEW52 electronic insert F: Fine-wire fuse, dependent on connected load R: Connected load, e.g. PLC, PLS, relay M: Ground connection to protective earth (PE) For evaluation one or more FTW325 processor units are needed. Separate instrumentation for three-rod- or rope-probes with cable monitoring. *1 = Printed circuit board for cable monitoring Connecting the FEW52 electronic insert F1: Fine-wire fuse, 200 mA, semi-time lag F2: Fine-wire fuse to protect the relay contact, load-dependent M: Ground connection to PE (protective earth) 7 8 9 d4 b2 d2 z4 CH1 FTW325 CH2 *1 1 3 2 Min Max b4 z2
  • 5. Liquipoint T FTW31 / FTW32 5 Application / FunctionOverview Technical data Dimensions Electrical connection Contact Go to shopPrice table Price table More products to complete your measuring point … Liquipoint T FTW31 Order no. Price/pcs. in USD Approval Electronics; Output Sensing Point 1 to 5 6 to 10 11 to 35 Non-hazardous area Separate instrumentation 3x rod, 316L FTW31-A2A3EB0A 176.00 164.00 155.00 5x rod, 316L FTW31-A2A5EB0A 204.00 190.00 180.00 FEW54; relay 20-253VAC; 20-55VDC 3x rod, 316L FTW31-A2A3EB4A 306.00 285.00 269.00 Liquipoint T FTW32 Order no. Price/pcs. in USD Approval Electronics; Output Sensing Point 1 to 5 6 to 10 11 to 35 Non-hazardous area Separate instrumentation 2x rope, 316Ti FTW32-A2D2EB0A 158.00 147.00 139.00 5x rope, 316Ti FTW32-A2D5EB0A 392.00 365.00 345.00 Prices valid until 09.30.2013 in U.S. dollars per unit (not including shipping and applicable sales tax). See Endress+Hauser, Inc. Terms and Conditions of Sale for shipping, tax, and payment terms. Complete product information: www.e-direct.us/ftw31_32 Temperature switch Thermophant T TTR31 Switching unit Nivotester FTW325 Capacitive probe Liquicap T FMI21
  • 6. Application / FunctionOverview Technical data Dimensions Electrical connection Price table Contact Go to shop Contact E-direct Endress+Hauser, Inc. 2350 Endress Place Greenwood, IN 46143 Direct order Internet www.e-direct.us by phone 888-EH-DIRECT (343-4732) per Fax 317-535-8498 E-Mail e-direct@us.endress.com