Seaward Digital Readout High Voltage Indicators are used as a potential indicator to determine presence of voltage or as a voltmeter. The high voltage detectors have a robust display housing, no switches and low battery indicator. The Seaward digital indicator also provides direct reading of voltage measurements. Seaward digital high voltage indicators are supplied with a battery charger and a specifically designed carrying case for unit and accessories.
Seaward KD1E Digital High Voltage Indicator & Detector Specifications:
Use as a potential indicator to determine presence of voltage or as a voltmeter
Robust display housing
No switches
Provides direct reading of voltage measurements
Low battery indicator
Supplied with battery charger
Specifically designed carrying case for unit and accessories
Seaward KD1E/15D 15kV Digital High Voltage Indicator & Detector
Seaward KD1E/15D digital high voltage detector is a digital HV potential indicator which can be used to indicate the presence of voltage or make voltage measurements on earthed neutral systems up to 15kV.
Seaward KD1E/15D 15kV Digital High Voltage Indicator & Detector Features:
Maximum System Voltage: 15kV
KD1E/15D Resolution: 10V
Maximum Voltage to Earth: 8.6kV
Seaward KD1E/15D Part No - 109A910
Seaward KD1E/15D Digital High Voltage Indicator Dimensions: Length: 600mm Diameter: 25mm Handle Length: 235mm Hand Guard Height: 23.5mm
Seaward KD1E/33D 33kV Digital High Voltage Indicator & Detector
Seaward KD1E/33D digital high voltage detector is a digital HV potential indicator which can be used to indicate the presence of voltage or make voltage measurements on earthed neutral systems up to 33kV.
Seaward KD1E/33D 33kV Digital High Voltage Indicator & Detector Features:
Maximum System Voltage: 33kV
KD1E/33D Resolution: 100V
Maximum Voltage to Earth: 19kV
Seaward KD1E/33D Part No - 109A911
Seaward KD1E/33D Digital High Voltage Indicator Dimensions: Length: 600mm Diameter: 25mm Handle Length: 235mm Hand Guard Height: 23.5mm
Seaward KD1E Digital High Voltage Indicator Accessories
Seaward PH3 Unit
Proving Unit for proof testing high voltage indicators
High Voltage output 1200V-1500DC
Self Test Facility
Avoids use of known supply points or bulky test equipment
Seaward Bent End Adaptors
90 degrees Standard, 120 degrees on request
Suitable for use on vertical typre switchgear
Seaward Extension Rod
1.5m extension rod for use on overhead lines
Suitable for use with KDIE/15D, KDIE/33D, PR15D & PR33D
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Seaward KD1E Digital High Voltage HV Indicators & Detectors - KD1E/15D 15kV & KD1E/33D 33kV
1. Seaward
Bracken Hill,
South West Industrial Estate,
Peterlee, SR8 2SW
Tel: +44 (0) 191 5863511
Fax: +44 (0) 191 5860227Web: www.seaward.co.uk Email: sales@seaward.co.uk
HV INDICATORS
These instruments let you confirm the presence of voltage on earthed neutral electrical
systems. They conform in design lengths to the recommended creepage and safety
standards. Each model features high grade PVC tubing and incorporates encapsulated
resistor chains. There’s a PH3 proving unit for additional safety and should be used
before and after the voltage indicator’s used.
The digital reading instruments provide voltage measurements and are supplied with
detachable earth lead, battery charger and PH3 proving unit.
Portable, neon and digital potential
indicators for confirming voltage
on earthed neutral systems.
Neon Indication
Digital Readout
Digital Readout Accessories
Unit Features Part No.
I Proving unit for proof testing
high voltage indicators
I High voltage output
1200V -1500DC
I Self test facility
I Avoids use of known supply
points or bulky test equipment
I 90O
standard, 120O
on request
I Suitable for use on vertical
type switchgear
I 1.5m extension rod for use on
overhead lines
I Suitable for use with KDIE/15D,
KDIE/33D, PR15D and PR33D
PH3
Bent End
Adaptors
Extension
Rod
112A913
141A900
(specify degree)
141A901
Teflon Polyester jacket
Thermal Insulation
Flap for Filler Access
Can be used with HSSD, HISD or HBD
Standard sizes 25L, 50L, 105L, 200L
Bespoke Sizes Made to Order
Water Resistant
Easy Installation
Ex-stock
Type HIJD Insulation Jacket
olroyd Components Ltd.
hire Hill Industrial Estate,
ffron Walden, Essex
B11 3AQ United Kingdom
el: +44 (0) 1799 523177
x: +44 (0) 1799 513714
les@holroydcomponents.com
ww.holroydcomponents.com
Technical Datasheet
Construction:
High performance ceramic fibre thermal insulation contained
within layers of Teflon coated polyester give the jacket a durable
and industrial feel.
Easy to fit with Velcro fixing strips and a moveable flap for ease
of access makes the HIJD jacket the most convenient way to
keep your products warm.
Technical Data:
Jacket Material: 1100 deitex texturised Nylon
Polyurethane coated
Insulation: Glass filament blanket
Fixing: Velcro Fixing
Custom Made:
All HIJD heater jackets are manufactured to conform to the EEC
low voltage and EMC directives and CE marked accordingly.
Health and Safety:
All HIJD heater jackets are manufactured to conform to the EEC
low voltage and EMC directives and CE marked accordingly.
Tel: +44 (0)191 490 1547
Fax: +44 (0)191 477 5371
Email: northernsales@thorneandderrick.co.uk
Website: www.cablejoints.co.uk
www.thorneanderrick.co.uk
2. Cropico
Hampton Road,
Croydon,
Surrey, United Kingdom, CR9 2RU
Tel: +44 (0) 20 86844025
Fax: +44 (0) 20 86844094Web: www.cropico.com Email: info@cropico.com
WORLD LEADERs IN SAFETY TEST AND MEASUREMENT
G R O U P
SEAWARD
PRECISION INSTRUMENTS
CROPICO
MEDICAL
RIGEL
INDUSTRIAL SAFETY INSTRUMENTS
CLARE
PORTABLE ELECTRICAL SAFETY INSTRUMENTS
SEAWARD
Seaward test and measurement companies include:
Maximum System voltage
Maximum Voltage to earth
Threshold voltage
Measuring Range
Resolution
Sensitivity
Circuit current
(IEC 61234-2)
Dielectric leakage current
(IEC 61234-2)
Length (mm)
Diameter (mm)
Handle length (mm)
Hand guard height (mm)
Contact Electrode Type
Neon Indication
KD1E
Indicator Type
KD1E/19 KD1E/19S KDE1/22 KDE1/33 KD1E/15D KD1E/33D
Digital Reading
11kV
6.6kV
300V
AC/DC
2.3mA nominal
@6.6kV
7µA nominal
@13.8kV
330
25
105
23.5
Domed
19kV
11kV
300V
AC/DC
0.7mA nominal
@11kV
11µA nominal
@ 22.8kV
330
25
105
23.5
Flat
19kV
11kV
300V
AC Only
0.9mA nominal
@11kV
12µA nominal
@ 22.8kV
330
25
105
23.5
Flat
22kV
12.5kV
300V
AC/DC
3.5mA nominal
@12.5kV
12µA nominal
@ 26.4kV
665
25
90
23.5
Domed
33kV
19kV
300V
AC/DC
1.1mA nominal
@19kV
17µA nominal
@ 40kV
670
25
250
23.5
Domed
15kV
8.6kV
0.00kV-8.6kV
10V
AC/DC
0.5mA nominal
@8.6kV
9µA nominal
@ 18V
600
25
235
23.5
Domed
33kV
19kV
0.00kV-19.0kV
100V
AC/DC
1.1mA nominal
@19kV
17µA nominal
@ 140kV
600
25
235
23.5
Domed
L
Indicator Type
L
Digital Readout Specifications
Features
I Use as a potential indicator to determine presence of voltage
or as a voltmeter
I Robust display housing
I No switches
I Provides direct reading of voltage measurements
I Low battery indicator
I Supplied with battery charger
I Specifically designed carrying case for unit and accessories
Unit System Voltage* Features Part No.
*Earthed neutral system
15KV max
33KV max
KDIE/15D
KDIE/33D
Resolution-10V
Resolution-100V
109A910
109A911
Neon Indication Specifications
Features
I Duplicate neon indicators within shock resistant sleeves
I Permanently connected earth cable
I Hand guards on all elements
I Direct access to vertical or horizontal metal clad switch gear
I UK Electricity Council Approval list G9
Unit System Voltage* Features Part No.
IKV-11.5KV
IKV-11.5KV
1.5KV-19KV
1.5KV-19KV
3KV-22KV
3KV-33KV
KDIE
KDIE/KAD
KDIE/19
KDIE/19S
KDIE/22
KDIE/33
KAD Audio Alarm
AC Voltage
113A916
113A915
113A914
113A913
113A912
113A911
Extension Rods
L
120O
1.5m Straight 90O
Maximum System voltage
Dielectric leakage current
Length (mm)
Diameter (mm)
Contact Electrode Type
33kV
140µA nominal @ 40kV
1.5m
25
“V” form
15kV
50µA nominal @ 18kV
780
25
Domed
33kV
130µA nominal @ 40kV
780
25
Domed
HV INDICATORS SPECIFICATIONS