EE 369
POWER SYSTEM ANALYSIS
Lecture 18
Fault Analysis
Tom Overbye and Ross Baldick
1
Announcements
Read Chapter 7.
Homework 12 is 6.59, 6.61, 12.19, 12.22,
12.24, 12.26, 12.28, 7.1, 7.3, 7.4, 7.5, 7.6,
7.9, 7.12, 7.16; due Thursday, 12/3.
2
Transmission Fault Analysis
The cause of electric power system faults is
insulation breakdown/compromise.
This breakdown can be due to a variety of
different factors:
– Lightning ionizing air,
– Wires blowing together in the wind,
– Animals or plants coming in contact with the
wires,
– Salt spray or pollution on insulators.
3
Transmission Fault Types
There are two main types of faults:
– symmetric faults: system remains balanced;
these faults are relatively rare, but are the
easiest to analyze so we’ll consider them first.
– unsymmetric faults: system is no longer
balanced; very common, but more difficult to
analyze (considered in EE 368L).
The most common type of fault on a three
phase system by far is the single line-to-
ground (SLG), followed by the line-to-line
faults (LL), double line-to-ground (DLG)
faults, and balanced three phase faults. 4
Lightning Strike Event Sequence
1. Lighting hits line, setting up an ionized path to
ground
 30 million lightning strikes per year in US!
 a single typical stroke might have 25,000 amps,
with a rise time of 10 s, dissipated in 200 s.
 multiple strokes can occur in a single flash, causing
the lightning to appear to flicker, with the total
event lasting up to a second.
2. Conduction path is maintained by ionized air
after lightning stroke energy has dissipated,
resulting in high fault currents (often > 25,000
amps!) 5
Lightning Strike Sequence, cont’d
3. Within one to two cycles (16 ms) relays at both
ends of line detect high currents, signaling
circuit breakers to open the line:
 nearby locations see decreased voltages
4. Circuit breakers open to de-energize line in an
additional one to two cycles:
 breaking tens of thousands of amps of fault current
is no small feat!
 with line removed voltages usually return to near
normal.
5. Circuit breakers may reclose after several
seconds, trying to restore faulted line to service.
6
Fault Analysis
Fault currents cause equipment damage due
to both thermal and mechanical processes.
Goal of fault analysis is to determine the
magnitudes of the currents present during
the fault:
– need to determine the maximum current to
ensure devices can survive the fault,
– need to determine the maximum current the
circuit breakers (CBs) need to interrupt to
correctly size the CBs.
7
RL Circuit Analysis
To understand fault analysis we need to
review the behavior of an RL circuit
( )
2 cos( )
v t
V t
 


(Note text uses sinusoidal voltage instead of cos!)
Before the switch is closed, i(t) = 0.
When the switch is closed at t=0 the current will
have two components: 1) a steady-state value
2) a transient value.
R L
8
RL Circuit Analysis, cont’d
2 2 2 2
1
1. Steady-state current component (from standard
phasor analysis)
Steady-state phasor current magnitude is ,
where ( )
and current phasor angle is , tan ( / )
Corresponding in
ac
Z Z
V
I
Z
Z R L R X
L R

  


   
 
ac
stantaneous current is:
2 cos( )
( ) Z
V t
i t
Z
  
 

9
RL Circuit Analysis, cont’d
1
1
ac dc 1
1
2. Exponentially decaying dc current component
( )
where is the time constant,
The value of is determined from the initial
conditions:
2
(0) 0 ( ) ( ) cos( )
2
t
T
dc
t
T
Z
i t C e
L
T T
R
C
V
i i t i t t C e
Z
V
C
Z
  




      
  cos( ) which depends on
Z
  

10
Time varying current
i(t)
time
Superposition of steady-state component and
exponentially decaying dc offset.
11
RL Circuit Analysis, cont’d
dc
Hence ( ) is a sinusoidal superimposed on a decaying
dc current. The magnitude of (0) depends on when
the switch is closed. For fault analysis we're just
concerned with the worst case.
Highest DC c
i t
i
Z 1
2
urrent occurs for: = ,
( ) ( ) ( )
2 2
( ) cos( )
2
( cos( ) )
ac dc
t
T
t
T
V
C
Z
i t i t i t
V V
i t t e
Z Z
V
t e
Z
  




 
 
  
   12
RMS for Fault Current
The interrupting capability of a circuit breaker is
specified in terms of the RMS current it can interrupt.
2
The function ( ) ( cos( ) ) is
not periodic, so we can't formally define an RMS value
t
T
V
i t t e
Z


  
.
However, if then we can approximate the current
as a sinusoid plus a time-invarying dc offset.
The RMS value of such a current is equal to the
square root of the sum of the squares of the
indivi
T t
dual RMS values of the two current components.
13
RMS for Fault Current
2 2
RMS
2
2 2
I ,
2
where , 2 ,
2
This function has a maximum value of 3 .
Therefore the worst case effect of the dc
component is included simply by
mu
ac dc
t t
T T
ac dc ac
t
T
ac ac
ac
I I
V V
I I e I e
Z Z
I I e
I
 

 
  
 
ltiplying the ac fault currents by 3.
14
Generator Modeling During Faults
During a fault the only devices that can
contribute fault current are those with energy
storage.
Thus the models of generators (and other
rotating machines) are very important since they
contribute the bulk of the fault current.
Generators can be approximated as a constant
voltage behind a time-varying reactance:
'
a
E
15
Generator Modeling, cont’d
"
d
'
d
d
The time varying reactance is typically approximated
using three different values, each valid for a different
time period:
X direct-axis subtransient reactance
X direct-axis transient reactance
X dire


 ct-axis synchronous reactance
Can then estimate currents using circuit theory:
For example, could calculate steady-state current
that would occur after a three-phase short-circuit
if no circuit breakers interrupt current. 16
Generator Modeling, cont’d
'
"
'
'
ac
" '
"
For a balanced three-phase fault on the generator
terminal the ac fault current is (see page 362)
1 1 1
( ) 2 sin( )
1 1
where
direct-axis su
d
d
t
T
d d
d
a t
T
d d
d
e
X X
X
i t E t
e
X X
T
 


 
 
  
 
 
 
 
 
 
 
 

 
 
 
 

'
btransient time constant ( 0.035sec)
direct-axis transient time constant ( 1sec)
d
T

  17
Generator Modeling, cont'd
'
"
'
'
ac
" '
'
DC "
The phasor current is then
1 1 1
1 1
The maximum DC offset is
2
( )
where is the armature time constant ( 0.2 seconds)
d
d
A
t
T
d d
d
a t
T
d d
t
T
a
d
A
e
X X
X
I E
e
X X
E
I t e
X
T



 
 
  
 
 
 
 
  
 
 

 
 
 
 


18
Generator Short Circuit Currents
19
Generator Short Circuit Currents
20
Generator Short Circuit Example
A 500 MVA, 20 kV, 3 is operated with an
internal voltage of 1.05 pu. Assume a solid
3 fault occurs on the generator's terminal
and that the circuit breaker operates after
three cycles. Determine the fault current.
Assume
" '
" '
0.15, 0.24, 1.1 (all per unit)
0.035 seconds, 2.0 seconds
0.2 seconds
d d d
d d
A
X X X
T T
T
  
 

21
Generator S.C. Example, cont'd
2.0
ac
0.035
ac
6
base ac
3
0.2
DC
Substituting in the values
1 1 1
1.1 0.24 1.1
( ) 1.05
1 1
0.15 0.24
1.05
(0) 7 p.u.
0.15
500 10
14,433 A (0) 101,000 A
3 20 10
(0) 101 kA 2 143 k
t
t
t
e
I t
e
I
I I
I e


 
 
  
 
 
 
  
 
 

 
 
 
 
 

  

   RMS
A (0) 175 kA
I 
22
Generator S.C. Example, cont'd
0.05
2.0
ac 0.05
0.035
ac
0.05
0.2
DC
RMS
Evaluating at t = 0.05 seconds for breaker opening
1 1 1
1.1 0.24 1.1
(0.05) 1.05
1 1
0.15 0.24
(0.05) 70.8 kA
(0.05) 143 kA 111 k A
(0.05
e
I
e
I
I e
I



 
 
  
 
 
 
  
 
 

 
 
 
 

  
2 2
) 70.8 111 132 kA
  
23
Network Fault Analysis Simplifications
 To simplify analysis of fault currents in
networks we'll make several simplifications:
1. Transmission lines are represented by their series
reactance
2. Transformers are represented by their leakage
reactances
3. Synchronous machines are modeled as a
constant voltage behind direct-axis subtransient
reactance
4. Induction motors are ignored or treated as
synchronous machines
5. Other (nonspinning) loads are ignored 24
Network Fault Example
For the following network assume a fault on the
terminal of the generator; all data is per unit
except for the transmission line reactance
2
19.5
Convert to per unit: 0.1 per unit
138
100
line
X  
generator has 1.05
terminal voltage &
supplies 100 MVA
with 0.95 lag pf
25
Network Fault Example, cont'd
Faulted network per unit diagram
*
'
To determine the fault current we need to first estimate
the internal voltages for the generator and motor
For the generator 1.05, 1.0 18.2
1.0 18.2
0.952 18.2 1.103 7.1
1.05
T G
Gen a
V S
I E
   

 
       
 
  26
Network Fault Example, cont'd
The motor's terminal voltage is then
1.05 0-(0.9044 - 0.2973) 0.3 1.00 15.8
The motor's internal voltage is
1.00 15.8 (0.9044 - 0.2973) 0.2
1.008 26.6
We can then solve as a linear circuit:
1
f
j j
j j
I
     
    
   

.103 7.1 1.008 26.6
0.15 0.5
7.353 82.9 2.016 116.6 9.09
j j
j
    

        
27
Fault Analysis Solution Techniques
 Circuit models used during the fault allow the
network to be represented as a linear circuit
 There are two main methods for solving for fault
currents:
1. Direct method: Use prefault conditions to solve for
the internal machine voltages; then apply fault and
solve directly.
2. Superposition: Fault is represented by two opposing
voltage sources; solve system by superposition:
– first voltage just represents the prefault operating point
– second system only has a single voltage source. 28
Superposition Approach
Faulted Condition
Exact Equivalent to Faulted Condition
Fault is represented
by two equal and
opposite voltage
sources, each with
a magnitude equal
to the pre-fault voltage
29
Superposition Approach, cont’d
Since this is now a linear network, the faulted voltages
and currents are just the sum of the pre-fault conditions
[the (1) component] and the conditions with just a single
voltage source at the fault location [the (2) component]
Pre-fault (1) component equal to the pre-fault
power flow solution
Obvious the
pre-fault
“fault current”
is zero!
30
Superposition Approach, cont’d
Fault (1) component due to a single voltage source
at the fault location, with a magnitude equal to the
negative of the pre-fault voltage at the fault location.
(1) (2) (1) (2)
(1) (2) (2)
0
g
g g m m m
f f f f
I I I I I I
I I I I
   
   
31
Two Bus Superposition Solution
f
(1) (1)
(2) f
(2) f
(2)
Before the fault we had E 1.05 0 ,
0.952 18.2 and 0.952 18.2
Solving for the (2) network we get
E 1.05 0
7
j0.15 j0.15
E 1.05 0
2.1
j0.5 j0.5
7 2.1 9.1
0.952
g m
g
m
f
g
I I
I j
I j
I j j j
I
  
        
 
   
 
   
    
  18.2 7 7.35 82.9
j
      
This matches
what we
calculated
earlier
32
Extension to Larger Systems
bus
bus
The superposition approach can be easily extended
to larger systems. Using the we have
For the second (2) system there is only one voltage
source so is all zeros except at the fault loca

Y
Y V I
I tion
0
0
f
I
 
 
 

 

 
 
 
 
I
However to use this
approach we need to
first determine If
33
Determination of Fault Current
bus
1
bus bus
(2)
1
(2)
11 1 2
(2)
1 1
(2)
(1)
f
Define the bus impedance matrix as
0
Then
0
For a fault a bus i we get -I
bus
n
f
n nn n
n
ii f i
V
Z Z V
I
Z Z V
V
Z V V



 
 
 
 
   
 
   

  
   
 
   
   
 
 
   
 
   
Z
Z Y V Z I
34
Determination of Fault Current
(1)
(1) (2) (1)
Hence
Where
driving point impedance
( ) transfer point imepdance
Voltages during the fault are also found by superposition
are prefault values
i
f
ii
ii
ij
i i i i
V
I
Z
Z
Z i j
V V V V


 
35

More Related Content

Similar to Lecture_18.ppt

symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfShanmukhSaiR
 
ECE4762011_Lect10.ppt
ECE4762011_Lect10.pptECE4762011_Lect10.ppt
ECE4762011_Lect10.pptbabu717541
 
ECE4762011_Lect10.ppt
ECE4762011_Lect10.pptECE4762011_Lect10.ppt
ECE4762011_Lect10.pptThomasNikola
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharingVivek Arun
 
Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems SafetyTalia Carbis
 
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITUNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITAbinaya Saraswathy T
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guideSlides Hub
 
Dc97 -------intech-modeling of-dc_dc_converters
Dc97 -------intech-modeling of-dc_dc_convertersDc97 -------intech-modeling of-dc_dc_converters
Dc97 -------intech-modeling of-dc_dc_convertersmaheswaran_m
 
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...Manmeet Singh
 
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...eSAT Journals
 
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...eSAT Publishing House
 
Power System Analysis and Design
Power System Analysis and DesignPower System Analysis and Design
Power System Analysis and DesignZainUlAbdeen41
 
Resonant Response of RLC Circuits
Resonant Response of RLC Circuits Resonant Response of RLC Circuits
Resonant Response of RLC Circuits Sachin Mehta
 
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...IAES-IJPEDS
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
Ies electrical-engineering-paper-2-2006
Ies electrical-engineering-paper-2-2006Ies electrical-engineering-paper-2-2006
Ies electrical-engineering-paper-2-2006Venugopala Rao P
 

Similar to Lecture_18.ppt (20)

symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdf
 
ECE4762011_Lect10.ppt
ECE4762011_Lect10.pptECE4762011_Lect10.ppt
ECE4762011_Lect10.ppt
 
ECE4762011_Lect10.ppt
ECE4762011_Lect10.pptECE4762011_Lect10.ppt
ECE4762011_Lect10.ppt
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharing
 
Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems Safety
 
Balanced faults
Balanced faultsBalanced faults
Balanced faults
 
3059
30593059
3059
 
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUITUNIT -I per unit calculation,EQUIVALENT CIRCUIT
UNIT -I per unit calculation,EQUIVALENT CIRCUIT
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Dc97 -------intech-modeling of-dc_dc_converters
Dc97 -------intech-modeling of-dc_dc_convertersDc97 -------intech-modeling of-dc_dc_converters
Dc97 -------intech-modeling of-dc_dc_converters
 
Buck converter design
Buck converter designBuck converter design
Buck converter design
 
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
 
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
 
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
Mitigation of harmonics using thyristor based 12 pulse voltage source pwm rec...
 
Power System Analysis and Design
Power System Analysis and DesignPower System Analysis and Design
Power System Analysis and Design
 
Resonant Response of RLC Circuits
Resonant Response of RLC Circuits Resonant Response of RLC Circuits
Resonant Response of RLC Circuits
 
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
 
Lecture 2
Lecture 2Lecture 2
Lecture 2
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
 
Ies electrical-engineering-paper-2-2006
Ies electrical-engineering-paper-2-2006Ies electrical-engineering-paper-2-2006
Ies electrical-engineering-paper-2-2006
 

Recently uploaded

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 

Recently uploaded (20)

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 

Lecture_18.ppt

  • 1. EE 369 POWER SYSTEM ANALYSIS Lecture 18 Fault Analysis Tom Overbye and Ross Baldick 1
  • 2. Announcements Read Chapter 7. Homework 12 is 6.59, 6.61, 12.19, 12.22, 12.24, 12.26, 12.28, 7.1, 7.3, 7.4, 7.5, 7.6, 7.9, 7.12, 7.16; due Thursday, 12/3. 2
  • 3. Transmission Fault Analysis The cause of electric power system faults is insulation breakdown/compromise. This breakdown can be due to a variety of different factors: – Lightning ionizing air, – Wires blowing together in the wind, – Animals or plants coming in contact with the wires, – Salt spray or pollution on insulators. 3
  • 4. Transmission Fault Types There are two main types of faults: – symmetric faults: system remains balanced; these faults are relatively rare, but are the easiest to analyze so we’ll consider them first. – unsymmetric faults: system is no longer balanced; very common, but more difficult to analyze (considered in EE 368L). The most common type of fault on a three phase system by far is the single line-to- ground (SLG), followed by the line-to-line faults (LL), double line-to-ground (DLG) faults, and balanced three phase faults. 4
  • 5. Lightning Strike Event Sequence 1. Lighting hits line, setting up an ionized path to ground  30 million lightning strikes per year in US!  a single typical stroke might have 25,000 amps, with a rise time of 10 s, dissipated in 200 s.  multiple strokes can occur in a single flash, causing the lightning to appear to flicker, with the total event lasting up to a second. 2. Conduction path is maintained by ionized air after lightning stroke energy has dissipated, resulting in high fault currents (often > 25,000 amps!) 5
  • 6. Lightning Strike Sequence, cont’d 3. Within one to two cycles (16 ms) relays at both ends of line detect high currents, signaling circuit breakers to open the line:  nearby locations see decreased voltages 4. Circuit breakers open to de-energize line in an additional one to two cycles:  breaking tens of thousands of amps of fault current is no small feat!  with line removed voltages usually return to near normal. 5. Circuit breakers may reclose after several seconds, trying to restore faulted line to service. 6
  • 7. Fault Analysis Fault currents cause equipment damage due to both thermal and mechanical processes. Goal of fault analysis is to determine the magnitudes of the currents present during the fault: – need to determine the maximum current to ensure devices can survive the fault, – need to determine the maximum current the circuit breakers (CBs) need to interrupt to correctly size the CBs. 7
  • 8. RL Circuit Analysis To understand fault analysis we need to review the behavior of an RL circuit ( ) 2 cos( ) v t V t     (Note text uses sinusoidal voltage instead of cos!) Before the switch is closed, i(t) = 0. When the switch is closed at t=0 the current will have two components: 1) a steady-state value 2) a transient value. R L 8
  • 9. RL Circuit Analysis, cont’d 2 2 2 2 1 1. Steady-state current component (from standard phasor analysis) Steady-state phasor current magnitude is , where ( ) and current phasor angle is , tan ( / ) Corresponding in ac Z Z V I Z Z R L R X L R             ac stantaneous current is: 2 cos( ) ( ) Z V t i t Z       9
  • 10. RL Circuit Analysis, cont’d 1 1 ac dc 1 1 2. Exponentially decaying dc current component ( ) where is the time constant, The value of is determined from the initial conditions: 2 (0) 0 ( ) ( ) cos( ) 2 t T dc t T Z i t C e L T T R C V i i t i t t C e Z V C Z                 cos( ) which depends on Z     10
  • 11. Time varying current i(t) time Superposition of steady-state component and exponentially decaying dc offset. 11
  • 12. RL Circuit Analysis, cont’d dc Hence ( ) is a sinusoidal superimposed on a decaying dc current. The magnitude of (0) depends on when the switch is closed. For fault analysis we're just concerned with the worst case. Highest DC c i t i Z 1 2 urrent occurs for: = , ( ) ( ) ( ) 2 2 ( ) cos( ) 2 ( cos( ) ) ac dc t T t T V C Z i t i t i t V V i t t e Z Z V t e Z                  12
  • 13. RMS for Fault Current The interrupting capability of a circuit breaker is specified in terms of the RMS current it can interrupt. 2 The function ( ) ( cos( ) ) is not periodic, so we can't formally define an RMS value t T V i t t e Z      . However, if then we can approximate the current as a sinusoid plus a time-invarying dc offset. The RMS value of such a current is equal to the square root of the sum of the squares of the indivi T t dual RMS values of the two current components. 13
  • 14. RMS for Fault Current 2 2 RMS 2 2 2 I , 2 where , 2 , 2 This function has a maximum value of 3 . Therefore the worst case effect of the dc component is included simply by mu ac dc t t T T ac dc ac t T ac ac ac I I V V I I e I e Z Z I I e I           ltiplying the ac fault currents by 3. 14
  • 15. Generator Modeling During Faults During a fault the only devices that can contribute fault current are those with energy storage. Thus the models of generators (and other rotating machines) are very important since they contribute the bulk of the fault current. Generators can be approximated as a constant voltage behind a time-varying reactance: ' a E 15
  • 16. Generator Modeling, cont’d " d ' d d The time varying reactance is typically approximated using three different values, each valid for a different time period: X direct-axis subtransient reactance X direct-axis transient reactance X dire    ct-axis synchronous reactance Can then estimate currents using circuit theory: For example, could calculate steady-state current that would occur after a three-phase short-circuit if no circuit breakers interrupt current. 16
  • 17. Generator Modeling, cont’d ' " ' ' ac " ' " For a balanced three-phase fault on the generator terminal the ac fault current is (see page 362) 1 1 1 ( ) 2 sin( ) 1 1 where direct-axis su d d t T d d d a t T d d d e X X X i t E t e X X T                                      ' btransient time constant ( 0.035sec) direct-axis transient time constant ( 1sec) d T    17
  • 18. Generator Modeling, cont'd ' " ' ' ac " ' ' DC " The phasor current is then 1 1 1 1 1 The maximum DC offset is 2 ( ) where is the armature time constant ( 0.2 seconds) d d A t T d d d a t T d d t T a d A e X X X I E e X X E I t e X T                                     18
  • 19. Generator Short Circuit Currents 19
  • 20. Generator Short Circuit Currents 20
  • 21. Generator Short Circuit Example A 500 MVA, 20 kV, 3 is operated with an internal voltage of 1.05 pu. Assume a solid 3 fault occurs on the generator's terminal and that the circuit breaker operates after three cycles. Determine the fault current. Assume " ' " ' 0.15, 0.24, 1.1 (all per unit) 0.035 seconds, 2.0 seconds 0.2 seconds d d d d d A X X X T T T       21
  • 22. Generator S.C. Example, cont'd 2.0 ac 0.035 ac 6 base ac 3 0.2 DC Substituting in the values 1 1 1 1.1 0.24 1.1 ( ) 1.05 1 1 0.15 0.24 1.05 (0) 7 p.u. 0.15 500 10 14,433 A (0) 101,000 A 3 20 10 (0) 101 kA 2 143 k t t t e I t e I I I I e                                          RMS A (0) 175 kA I  22
  • 23. Generator S.C. Example, cont'd 0.05 2.0 ac 0.05 0.035 ac 0.05 0.2 DC RMS Evaluating at t = 0.05 seconds for breaker opening 1 1 1 1.1 0.24 1.1 (0.05) 1.05 1 1 0.15 0.24 (0.05) 70.8 kA (0.05) 143 kA 111 k A (0.05 e I e I I e I                                     2 2 ) 70.8 111 132 kA    23
  • 24. Network Fault Analysis Simplifications  To simplify analysis of fault currents in networks we'll make several simplifications: 1. Transmission lines are represented by their series reactance 2. Transformers are represented by their leakage reactances 3. Synchronous machines are modeled as a constant voltage behind direct-axis subtransient reactance 4. Induction motors are ignored or treated as synchronous machines 5. Other (nonspinning) loads are ignored 24
  • 25. Network Fault Example For the following network assume a fault on the terminal of the generator; all data is per unit except for the transmission line reactance 2 19.5 Convert to per unit: 0.1 per unit 138 100 line X   generator has 1.05 terminal voltage & supplies 100 MVA with 0.95 lag pf 25
  • 26. Network Fault Example, cont'd Faulted network per unit diagram * ' To determine the fault current we need to first estimate the internal voltages for the generator and motor For the generator 1.05, 1.0 18.2 1.0 18.2 0.952 18.2 1.103 7.1 1.05 T G Gen a V S I E                    26
  • 27. Network Fault Example, cont'd The motor's terminal voltage is then 1.05 0-(0.9044 - 0.2973) 0.3 1.00 15.8 The motor's internal voltage is 1.00 15.8 (0.9044 - 0.2973) 0.2 1.008 26.6 We can then solve as a linear circuit: 1 f j j j j I                 .103 7.1 1.008 26.6 0.15 0.5 7.353 82.9 2.016 116.6 9.09 j j j                27
  • 28. Fault Analysis Solution Techniques  Circuit models used during the fault allow the network to be represented as a linear circuit  There are two main methods for solving for fault currents: 1. Direct method: Use prefault conditions to solve for the internal machine voltages; then apply fault and solve directly. 2. Superposition: Fault is represented by two opposing voltage sources; solve system by superposition: – first voltage just represents the prefault operating point – second system only has a single voltage source. 28
  • 29. Superposition Approach Faulted Condition Exact Equivalent to Faulted Condition Fault is represented by two equal and opposite voltage sources, each with a magnitude equal to the pre-fault voltage 29
  • 30. Superposition Approach, cont’d Since this is now a linear network, the faulted voltages and currents are just the sum of the pre-fault conditions [the (1) component] and the conditions with just a single voltage source at the fault location [the (2) component] Pre-fault (1) component equal to the pre-fault power flow solution Obvious the pre-fault “fault current” is zero! 30
  • 31. Superposition Approach, cont’d Fault (1) component due to a single voltage source at the fault location, with a magnitude equal to the negative of the pre-fault voltage at the fault location. (1) (2) (1) (2) (1) (2) (2) 0 g g g m m m f f f f I I I I I I I I I I         31
  • 32. Two Bus Superposition Solution f (1) (1) (2) f (2) f (2) Before the fault we had E 1.05 0 , 0.952 18.2 and 0.952 18.2 Solving for the (2) network we get E 1.05 0 7 j0.15 j0.15 E 1.05 0 2.1 j0.5 j0.5 7 2.1 9.1 0.952 g m g m f g I I I j I j I j j j I                                18.2 7 7.35 82.9 j        This matches what we calculated earlier 32
  • 33. Extension to Larger Systems bus bus The superposition approach can be easily extended to larger systems. Using the we have For the second (2) system there is only one voltage source so is all zeros except at the fault loca  Y Y V I I tion 0 0 f I                   I However to use this approach we need to first determine If 33
  • 34. Determination of Fault Current bus 1 bus bus (2) 1 (2) 11 1 2 (2) 1 1 (2) (1) f Define the bus impedance matrix as 0 Then 0 For a fault a bus i we get -I bus n f n nn n n ii f i V Z Z V I Z Z V V Z V V                                                      Z Z Y V Z I 34
  • 35. Determination of Fault Current (1) (1) (2) (1) Hence Where driving point impedance ( ) transfer point imepdance Voltages during the fault are also found by superposition are prefault values i f ii ii ij i i i i V I Z Z Z i j V V V V     35