SlideShare a Scribd company logo
1 of 4
Good Practice Note:      Applying Human Factors to Procedure Writing: Part A, Action
                         Steps -General

1. Use simple command statements.

   a. Begin the sentence with an action verb (highlighted) followed by the direct object
      of the action (usually the equipment name). Active statements usually are
      clearer and more succinct. Placing the highlighted verb first directs attention to
      the key word and increases comprehension and retention (short term memory).

                                   EXAMPLE:
      Preferred:    START “A” Booster Pump.

      Instead of:   The Booster Pump must be started.

   b. Omit the subject “you” in the sentence; it is implied. Recommended practice is
      to write procedures for a specific job position, such as “Operator”, “A-Side
      Operator”, or “Senior Operator”, who is the “primary actor” performing the
      overall task that is the subject of the procedure. (See Item 3 below for team
      performance.)

   c. Omit unnecessary articles (a, an, the).

   d. Add objectives and location information as necessary to convey the appropriate
      instructions.

2. In team performance, identify the person who is to take the action.

   a. If an input is required from someone other than the primary actor, identify that
      person by the position, e.g. “A-Side Operator”, “Outside Operator”, “Controller”.

                                  EXAMPLE:
      Preferred:    OBTAIN Lead Controller’s permission to bypass an alarm.

      Instead of:   You need permission from the lead controller to bypass an alarm.

   b. If someone other than the primary actor is to perform the step, identify that
      person by position title.

                                  EXAMPLE:
      Preferred:    NOTIFY B Operator to sample T-354.

      Instead of:   The B Operator shall sample T-354.
3. Limit the number of actions per step.

   a. In most cases, use one action statement per step. A small number of closely
      related actions can be put in one step, but use the “standard” form.

                                        EXAMPLE:
             OPEN Discharge Valve.
             VERIFY flow increases.

   b. Do not place hidden action instructions in a step.

                                  EXAMPLE
      Preferred:     START Compressor.
                     ENSURE Discharge Valve Opens.

      Instead of:    START Compressor. The discharge valve should open. If it
                     doesn’t open, stop compressor and report to supervisor

4. When there are multiple objects for a single action verb list each object
   vertically. Use bullets as appropriate.

                                    EXAMPLE:
      Preferred:     OPEN breakers for the following valves:
                     •    MO-10-5A at E-124-R-C
                     •      MO-10-5B at E-224-R-B
                     •      MO-10-5C at E-324-R-B
                     •      MO-10-5D at E-424-W-A

      Instead of:    OPEN breakers for MO-10-5A at E-124-R-C, MO-10-5-B at E-224-
                     R-B, MO-10-5C at E-324-R-B, and MO-10-5D at E-424-W-A.

   If the list is long, leave a vertical space every four or five items to aid place-keeping.
   For a very long list, consider using a table or a separate checklist.

5. Use positive rather than negative forms whenever possible.

                                        EXAMPLE:
      Preferred:     IF the Inlet valves are OPEN,
                     GO TO Step 23.
Instead of:   DO NOT proceed to Step 23 unless Inlet Valves are open.

6. Add useful information appropriate for the experience/knowledge level of the
   user, but don’t overdo it.

   a. Do not state the expected results of tasks that are so routine or obvious as to be
      almost trivial. Clearly, this requires judgment on what is “trivial” and what is
      useful as an aid to a qualified operator. A rule of thumb is to target the material
      for the least experienced (fully qualified) operator.

                                   EXAMPLE:
      Preferred:    START Line A primary pump.
                    VERIFY discharge pressure 60 to 90 psig.

      Instead of:   START the Line A primary pump.
                    VERIFY green “Pump On” light is lit.
                    VERIFY discharge pressure 60 to 90 psig.

   b. When actions are required based on receipt of an annunciated alarm, list the
      alarm setpoint for ease of verification.

                                      EXAMPLE
                    IF “High Outlet Temperature” alarm sounds (Setpoint = 720°F)
                    REDUCE inlet flow to 250 gpm.
                    AND VERIFY auxiliary cooling system has auto-started.

   c. Where it would be help the user, identify expected system behavior, time for
      response, etc., a note preceding the action step. Don’t overuse notes; a
      procedure is a user aid to guide action, not a training document.

                                      EXAMPLE:

NOTE: There is a time delay of approximately 1-1/2 minutes before Booster
      Pump Discharge Valve begins to open.


                    START “B” Booster Pump,”
                    AND VERIFY discharge valve is open.
d. If the expected system response may adversely affect instrument indications,
     use a note to describe the conditions that may cause instrument error.

                                    EXAMPLE:

NOTE: The actions of the following step may cause temperature drop in the
       product. This will result in inaccurate flow indications.

  e. If additional confirmation of system response is necessary, state the backup
     readings to be taken.

                                    EXAMPLE:
                  IF Inlet Temperature ≤600°F,
                  VERIFY Outlet Temperature > 450°F,
                  AND VERIFY Inlet Flow Rate ≥ 200 gpm.

More Related Content

Similar to Hf procedure writing part a

Sop for total_power_failure.[1]
Sop for total_power_failure.[1]Sop for total_power_failure.[1]
Sop for total_power_failure.[1]dastak
 
Basic_Pump_Operations_Class_BHFD.pptx
Basic_Pump_Operations_Class_BHFD.pptxBasic_Pump_Operations_Class_BHFD.pptx
Basic_Pump_Operations_Class_BHFD.pptxMunicipalDistrictSmo
 
helium porosimeter (Reservoir lab)
helium porosimeter (Reservoir lab)helium porosimeter (Reservoir lab)
helium porosimeter (Reservoir lab)Bakhtiar Mahmood
 
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak DetectorHow to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak DetectorBuyobdtoolShop
 
BP_Waterline Hydrostatic
BP_Waterline HydrostaticBP_Waterline Hydrostatic
BP_Waterline HydrostaticScott Nunn
 
Hazard operability study - in Industires and plant
Hazard operability study - in Industires and plantHazard operability study - in Industires and plant
Hazard operability study - in Industires and plantJayaKarthic1
 
Pump Performance Presentation.pptx
Pump Performance Presentation.pptxPump Performance Presentation.pptx
Pump Performance Presentation.pptxAzharBudiman5
 
Heavy Duty Gear Pumps / AERN Series Pumps
Heavy Duty Gear Pumps / AERN Series PumpsHeavy Duty Gear Pumps / AERN Series Pumps
Heavy Duty Gear Pumps / AERN Series PumpsAnivarya pumps
 
RAC-050 Engineer Training V1.0e-202202.ppt
RAC-050 Engineer Training V1.0e-202202.pptRAC-050 Engineer Training V1.0e-202202.ppt
RAC-050 Engineer Training V1.0e-202202.pptArnoldoFelix3
 
Competency Training Evidence for Panel Operator Answers
Competency Training Evidence for Panel Operator AnswersCompetency Training Evidence for Panel Operator Answers
Competency Training Evidence for Panel Operator Answersmark robertson
 
Automationforum Interview Questions
Automationforum  Interview QuestionsAutomationforum  Interview Questions
Automationforum Interview Questionsautomationforum
 
HAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh Rajput
HAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh RajputHAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh Rajput
HAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh RajputGaurav Singh Rajput
 
A guide for firetube boiler testes
A guide for firetube boiler   testesA guide for firetube boiler   testes
A guide for firetube boiler testesederpitapeva
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13-
 

Similar to Hf procedure writing part a (20)

Sop for total_power_failure.[1]
Sop for total_power_failure.[1]Sop for total_power_failure.[1]
Sop for total_power_failure.[1]
 
Basic_Pump_Operations_Class_BHFD.pptx
Basic_Pump_Operations_Class_BHFD.pptxBasic_Pump_Operations_Class_BHFD.pptx
Basic_Pump_Operations_Class_BHFD.pptx
 
helium porosimeter (Reservoir lab)
helium porosimeter (Reservoir lab)helium porosimeter (Reservoir lab)
helium porosimeter (Reservoir lab)
 
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak DetectorHow to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
How to use Auto Smoke Detector AUTOOL SDT-206 Smoke Leak Detector
 
BP_Waterline Hydrostatic
BP_Waterline HydrostaticBP_Waterline Hydrostatic
BP_Waterline Hydrostatic
 
Hazard operability study - in Industires and plant
Hazard operability study - in Industires and plantHazard operability study - in Industires and plant
Hazard operability study - in Industires and plant
 
HAZOP.ppt
HAZOP.pptHAZOP.ppt
HAZOP.ppt
 
Pump Performance Presentation.pptx
Pump Performance Presentation.pptxPump Performance Presentation.pptx
Pump Performance Presentation.pptx
 
Heavy Duty Gear Pumps / AERN Series Pumps
Heavy Duty Gear Pumps / AERN Series PumpsHeavy Duty Gear Pumps / AERN Series Pumps
Heavy Duty Gear Pumps / AERN Series Pumps
 
RAC-050 Engineer Training V1.0e-202202.ppt
RAC-050 Engineer Training V1.0e-202202.pptRAC-050 Engineer Training V1.0e-202202.ppt
RAC-050 Engineer Training V1.0e-202202.ppt
 
Ins and Outs of I/P Transducers
Ins and Outs of I/P TransducersIns and Outs of I/P Transducers
Ins and Outs of I/P Transducers
 
Air Duct Leakage
Air Duct LeakageAir Duct Leakage
Air Duct Leakage
 
Hazop steps
Hazop stepsHazop steps
Hazop steps
 
Competency Training Evidence for Panel Operator Answers
Competency Training Evidence for Panel Operator AnswersCompetency Training Evidence for Panel Operator Answers
Competency Training Evidence for Panel Operator Answers
 
Automationforum Interview Questions
Automationforum  Interview QuestionsAutomationforum  Interview Questions
Automationforum Interview Questions
 
HAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh Rajput
HAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh RajputHAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh Rajput
HAZOP I Hazard and operability study I Risk Assessment I Gaurav Singh Rajput
 
A guide for firetube boiler testes
A guide for firetube boiler   testesA guide for firetube boiler   testes
A guide for firetube boiler testes
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13
 
The Consultants Role
The Consultants RoleThe Consultants Role
The Consultants Role
 
Tab Fire Pump Testing
Tab Fire Pump TestingTab Fire Pump Testing
Tab Fire Pump Testing
 

More from PMHaas

Twelve tips to improve procedure usage
Twelve tips to improve procedure usageTwelve tips to improve procedure usage
Twelve tips to improve procedure usagePMHaas
 
NPRA-042899
NPRA-042899NPRA-042899
NPRA-042899PMHaas
 
HPE Summary PowerPoint 2000
HPE Summary PowerPoint 2000HPE Summary PowerPoint 2000
HPE Summary PowerPoint 2000PMHaas
 
ConOps: A control system ...
ConOps: A control system ...ConOps: A control system ...
ConOps: A control system ...PMHaas
 
Five Steps to Excellence
Five Steps to ExcellenceFive Steps to Excellence
Five Steps to ExcellencePMHaas
 
Good practice note procedure validation
Good practice note   procedure validationGood practice note   procedure validation
Good practice note procedure validationPMHaas
 
Good practice note ojt
Good practice note ojtGood practice note ojt
Good practice note ojtPMHaas
 
Hf procedure writing part c
Hf procedure writing part cHf procedure writing part c
Hf procedure writing part cPMHaas
 
Hpe program rating #6 measurement system
Hpe program rating #6 measurement systemHpe program rating #6 measurement system
Hpe program rating #6 measurement systemPMHaas
 
Hpe program rating #5 ops performance feedback
Hpe program rating #5 ops performance feedbackHpe program rating #5 ops performance feedback
Hpe program rating #5 ops performance feedbackPMHaas
 
Hpe program rating #4 human factors engineering
Hpe program rating #4 human factors engineeringHpe program rating #4 human factors engineering
Hpe program rating #4 human factors engineeringPMHaas
 
Hpe program rating #3 training
Hpe program rating #3 trainingHpe program rating #3 training
Hpe program rating #3 trainingPMHaas
 
Hpe program rating #2 procedures
Hpe program rating #2 proceduresHpe program rating #2 procedures
Hpe program rating #2 proceduresPMHaas
 
Hpe program rating #1 con ops
Hpe program rating #1 con opsHpe program rating #1 con ops
Hpe program rating #1 con opsPMHaas
 
Good practice note procedure validation
Good practice note   procedure validationGood practice note   procedure validation
Good practice note procedure validationPMHaas
 
Twelve Things ... Use Procedures
Twelve Things ... Use ProceduresTwelve Things ... Use Procedures
Twelve Things ... Use ProceduresPMHaas
 

More from PMHaas (16)

Twelve tips to improve procedure usage
Twelve tips to improve procedure usageTwelve tips to improve procedure usage
Twelve tips to improve procedure usage
 
NPRA-042899
NPRA-042899NPRA-042899
NPRA-042899
 
HPE Summary PowerPoint 2000
HPE Summary PowerPoint 2000HPE Summary PowerPoint 2000
HPE Summary PowerPoint 2000
 
ConOps: A control system ...
ConOps: A control system ...ConOps: A control system ...
ConOps: A control system ...
 
Five Steps to Excellence
Five Steps to ExcellenceFive Steps to Excellence
Five Steps to Excellence
 
Good practice note procedure validation
Good practice note   procedure validationGood practice note   procedure validation
Good practice note procedure validation
 
Good practice note ojt
Good practice note ojtGood practice note ojt
Good practice note ojt
 
Hf procedure writing part c
Hf procedure writing part cHf procedure writing part c
Hf procedure writing part c
 
Hpe program rating #6 measurement system
Hpe program rating #6 measurement systemHpe program rating #6 measurement system
Hpe program rating #6 measurement system
 
Hpe program rating #5 ops performance feedback
Hpe program rating #5 ops performance feedbackHpe program rating #5 ops performance feedback
Hpe program rating #5 ops performance feedback
 
Hpe program rating #4 human factors engineering
Hpe program rating #4 human factors engineeringHpe program rating #4 human factors engineering
Hpe program rating #4 human factors engineering
 
Hpe program rating #3 training
Hpe program rating #3 trainingHpe program rating #3 training
Hpe program rating #3 training
 
Hpe program rating #2 procedures
Hpe program rating #2 proceduresHpe program rating #2 procedures
Hpe program rating #2 procedures
 
Hpe program rating #1 con ops
Hpe program rating #1 con opsHpe program rating #1 con ops
Hpe program rating #1 con ops
 
Good practice note procedure validation
Good practice note   procedure validationGood practice note   procedure validation
Good practice note procedure validation
 
Twelve Things ... Use Procedures
Twelve Things ... Use ProceduresTwelve Things ... Use Procedures
Twelve Things ... Use Procedures
 

Hf procedure writing part a

  • 1. Good Practice Note: Applying Human Factors to Procedure Writing: Part A, Action Steps -General 1. Use simple command statements. a. Begin the sentence with an action verb (highlighted) followed by the direct object of the action (usually the equipment name). Active statements usually are clearer and more succinct. Placing the highlighted verb first directs attention to the key word and increases comprehension and retention (short term memory). EXAMPLE: Preferred: START “A” Booster Pump. Instead of: The Booster Pump must be started. b. Omit the subject “you” in the sentence; it is implied. Recommended practice is to write procedures for a specific job position, such as “Operator”, “A-Side Operator”, or “Senior Operator”, who is the “primary actor” performing the overall task that is the subject of the procedure. (See Item 3 below for team performance.) c. Omit unnecessary articles (a, an, the). d. Add objectives and location information as necessary to convey the appropriate instructions. 2. In team performance, identify the person who is to take the action. a. If an input is required from someone other than the primary actor, identify that person by the position, e.g. “A-Side Operator”, “Outside Operator”, “Controller”. EXAMPLE: Preferred: OBTAIN Lead Controller’s permission to bypass an alarm. Instead of: You need permission from the lead controller to bypass an alarm. b. If someone other than the primary actor is to perform the step, identify that person by position title. EXAMPLE: Preferred: NOTIFY B Operator to sample T-354. Instead of: The B Operator shall sample T-354.
  • 2. 3. Limit the number of actions per step. a. In most cases, use one action statement per step. A small number of closely related actions can be put in one step, but use the “standard” form. EXAMPLE: OPEN Discharge Valve. VERIFY flow increases. b. Do not place hidden action instructions in a step. EXAMPLE Preferred: START Compressor. ENSURE Discharge Valve Opens. Instead of: START Compressor. The discharge valve should open. If it doesn’t open, stop compressor and report to supervisor 4. When there are multiple objects for a single action verb list each object vertically. Use bullets as appropriate. EXAMPLE: Preferred: OPEN breakers for the following valves: • MO-10-5A at E-124-R-C • MO-10-5B at E-224-R-B • MO-10-5C at E-324-R-B • MO-10-5D at E-424-W-A Instead of: OPEN breakers for MO-10-5A at E-124-R-C, MO-10-5-B at E-224- R-B, MO-10-5C at E-324-R-B, and MO-10-5D at E-424-W-A. If the list is long, leave a vertical space every four or five items to aid place-keeping. For a very long list, consider using a table or a separate checklist. 5. Use positive rather than negative forms whenever possible. EXAMPLE: Preferred: IF the Inlet valves are OPEN, GO TO Step 23.
  • 3. Instead of: DO NOT proceed to Step 23 unless Inlet Valves are open. 6. Add useful information appropriate for the experience/knowledge level of the user, but don’t overdo it. a. Do not state the expected results of tasks that are so routine or obvious as to be almost trivial. Clearly, this requires judgment on what is “trivial” and what is useful as an aid to a qualified operator. A rule of thumb is to target the material for the least experienced (fully qualified) operator. EXAMPLE: Preferred: START Line A primary pump. VERIFY discharge pressure 60 to 90 psig. Instead of: START the Line A primary pump. VERIFY green “Pump On” light is lit. VERIFY discharge pressure 60 to 90 psig. b. When actions are required based on receipt of an annunciated alarm, list the alarm setpoint for ease of verification. EXAMPLE IF “High Outlet Temperature” alarm sounds (Setpoint = 720°F) REDUCE inlet flow to 250 gpm. AND VERIFY auxiliary cooling system has auto-started. c. Where it would be help the user, identify expected system behavior, time for response, etc., a note preceding the action step. Don’t overuse notes; a procedure is a user aid to guide action, not a training document. EXAMPLE: NOTE: There is a time delay of approximately 1-1/2 minutes before Booster Pump Discharge Valve begins to open. START “B” Booster Pump,” AND VERIFY discharge valve is open.
  • 4. d. If the expected system response may adversely affect instrument indications, use a note to describe the conditions that may cause instrument error. EXAMPLE: NOTE: The actions of the following step may cause temperature drop in the product. This will result in inaccurate flow indications. e. If additional confirmation of system response is necessary, state the backup readings to be taken. EXAMPLE: IF Inlet Temperature ≤600°F, VERIFY Outlet Temperature > 450°F, AND VERIFY Inlet Flow Rate ≥ 200 gpm.