Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0601 -
Nov '15J.DN.C
1:1000@A1
OVERALL VILLAGE 2 LAYOUT PLAN
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
V-2
0602 0603
0604 0605
CONNECT TO DEEP GRAVITY SEWER
REFER TO AREA 10 DRAWINGS
CONNECT TO DEEP GRAVITY SEWER
REFER TO AREA 10 DRAWINGS
CONNECT TO DEEP GRAVITY SEWER
REFER TO AREA 10 DRAWINGS
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED MAIN PIPELINE shown thus
SECTION No. & DIRECTION shown thus
LATERAL SEWER & CHAMBER shown thus
NOTE's :
FOUL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0606 to 0609
LATERAL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0610 to 0619
STANDARD DETAILS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR
MANHOLE REPORT & CHAMBER DETAILS.
No.1
200mm@1:?
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
?
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0602 -
Nov '15J.DN.C
1:500@A1
SHEET 1 of 4
VILLAGE 2 LAYOUT PLAN
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
No.1
No.1
No.1 No.1
No.2
No.3
No.1
No.4
No.6
No.5
No.5
No.5
No.7
No.7
No.8
No.18
No.18
No.13
No.12
No.12
No.14
No.14
No.14
No.14
No.15
No.16
No.28
35
1
36
37
38
39 44
43
41
42
2 40 3
45
46
47
48
80
79
78
77
76
18
114
115 116 118
119
86
87
90 91
88
8483
8213
81
12
15 89
171
172
173
102
103
100
95
104 93
90
90
9594
61
57
56
54
55
58
59
60
63
64
8
62
10
9
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED MAIN PIPELINE shown thus
SECTION No. & DIRECTION shown thus
LATERAL SEWER & CHAMBER shown thus
NOTE's :
FOUL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0606 to 0609
LATERAL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0610 to 0619
STANDARD DETAILS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR
MANHOLE REPORT & CHAMBER DETAILS.
No.1
200mm@1:?
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
?
117
93
6
5 52
49
464
51
50
7
204
53
96
205
169
170
2TX
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0603 -
Nov '15J.DN.C
1:500@A1
SHEET 2 of 4
VILLAGE 2 LAYOUT PLAN
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
No.11
No.11
No.9
No.9
No.9
No.10
No.8
No.14
No.33
Deep
Gravity Sewer
to East Sitra Pumphouse
CONNECT TO DEEP GRAVITY SEWER
SEE AREA 10 DRAWINGS FOR DETAILS
98
99 106
16
28170
169
168
17
33
74
75
70
69
67
68 72 73
71
11
66
20610
65
111
112
109
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED MAIN PIPELINE shown thus
SECTION No. & DIRECTION shown thus
LATERAL SEWER & CHAMBER shown thus
NOTE's :
FOUL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0606 to 0609
LATERAL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0610 to 0619
STANDARD DETAILS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR
MANHOLE REPORT & CHAMBER DETAILS.
No.1
200mm@1:?
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
?
No.1
No.3
No.1
No.4
No.6
No.5
No.5
No.5
No.7
No.7
No.8
No.14
No.14
No.14
No.14
No.15
No.16
No.28
46
48
119
86
87
90 91
88
84
15 89
171
172
173
102
103
100
95
104 93
90
9594
61
57
56
54
55
58
59
60
63
64
8
62
9
93
6
5 52
49
464
51
50
7
204
53
96
205
105
108
110
Deep
Gravity Sewer
to East Sitra Pumphouse
2 2TX
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0604 -
Nov '15J.DN.C
1:500@A1
SHEET 3 of 4
VILLAGE 2 LAYOUT PLAN
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
No.18
No.18
No.18
No.18
No.18
No.19
No.20
No.20
No.20
No.21
No.22
No.24
No.24 No.24
No.24
No.24
No.23
No.25
No.26
No.28
No.28
No.28
No.28
No.32
No.32
No.30
19 120
115 116
117 119
118
121
22
138
140
139
130
131
143
137
136
135
134
133
21 13220
122
123
124
125
126
127
128
129
24
144
145
146
147
148
149
150
151
158
152
153
155
154
156
157162
163
159
160
164
26
166
165
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED MAIN PIPELINE shown thus
SECTION No. & DIRECTION shown thus
LATERAL SEWER & CHAMBER shown thus
NOTE's :
FOUL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0606 to 0609
LATERAL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0610 to 0619
STANDARD DETAILS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR
MANHOLE REPORT & CHAMBER DETAILS.
No.1
200mm@1:?
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
?
23 141
142
No.24
30
179
14
85
188
32
189
191
190
90
No.17
34
161
25
No.28
15
89
173
172
171 169
170
178175
174 177
184
183
182180
181
193
192 203
97
206
2TX
3TX
2 2TX
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0605 -
Nov '15J.DN.C
1:500@A1
SHEET 4 of 4
VILLAGE 2 LAYOUT PLAN
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
No.18
No.18
No.18
No.27
No.24
No.23
No.28
No.28
No.28
No.28
No.29
No.33
No.33
No.30
No.30
No.32
No.32
No.20
Deep
Gravity Sewer
to East Sitra Pumphouse
CONNECT TO DEEP GRAVITY SEWER
see AREA 10 DRAWINGS FOR DETAILS
15
89
173
172
171 169
170 28
168
178175
174 177
176
90
195
196
197
31
185
186
187
184
183
182180
181
30
179
14
85
188
32
189
191
190
192
193
203
201
202 200
199
198
33
194
27
167
151
141
142
159
140
130
131
143
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED MAIN PIPELINE shown thus
SECTION No. & DIRECTION shown thus
LATERAL SEWER & CHAMBER shown thus
NOTE's :
FOUL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0606 to 0609
LATERAL SECTIONS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0610 to 0619
STANDARD DETAILS
REFER TO DRAWING's
JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR
MANHOLE REPORT & CHAMBER DETAILS.
No.1
200mm@1:?
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
?
No.24
No.24
No.17
No.26
152
153
155
154
156
157
162
34
161
163
164
26
166
165
97
No.18
No.24
No.24
No.24
No.25
158
25
160
206
CONNECT TO DEEP
GRAVITY
SEWER
see AREA 10
DRAWINGS FOR DETAILS
No.31
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0606 -
Nov '15J.DN.C
1:1000@A1
SHEET 1 of 4
VILLAGE 2 SECTION
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
SCALE = 1:1000 HORIZONTAL
1:100 VERTICAL
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED PIPELINE shown thus
LATERAL SEWER CONNECTION shown thus
V 2 - F - N o .
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0607 -
Nov '15J.DN.C
As Shown@A1
SHEET 2 of 4
VILLAGE 2 SECTION
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
SCALE = 1:1000 HORIZONTAL
1:100 VERTICAL
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED PIPELINE shown thus
LATERAL SEWER CONNECTION shown thus
V 2 - F - N o .
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0608 -
Nov '15J.DN.C
As Shown@A1
SHEET 3 of 4
VILLAGE 2 SECTION
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
SCALE = 1:1000 HORIZONTAL
1:100 VERTICAL
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED PIPELINE shown thus
LATERAL SEWER CONNECTION shown thus
V 2 - F - N o .
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.
Project
Stage
Title
Design Consultant
Checked Approved Date
Rev
Prepared
Job No.
Rev Description Prep Chkd Appd Date
PJH
10011
DETAIL DESIGN
SOCIAL HOUSING PROJECT
AT EAST SITRA
Client
JOD-10011-C-CD-00-FS-PL-0609 -
Nov '15J.DN.C
As Shown@A1
SHEET 4 of 4
VILLAGE 2 SECTION
EAST SITRA FOUL SEWER
PJHJDNCDraft DETAIL DESIGN IssueA
SCALE = 1:1000 HORIZONTAL
1:100 VERTICAL
LEGEND:
PROPOSED MANHOLE shown thus
PROPOSED PIPELINE shown thus
LATERAL SEWER CONNECTION shown thus
V 2 - F - N o .
Notes
1. This Drawing is to be read in conjunction with all other relevant
documentation.
2. Do not scale from this drawing, use only printed dimensions.
3. All dimensions in millimetres, all chainages, levels and coordinates
are in metres unless defined otherwise.
4. This drawing is to be read in conjunction with the project Health and
Safety File for any identified potential risks.
5. All materials to be approved by EWA/SEPPD prior to installation.
6. Installation to be in accordance with SEPPD standards and best
practices and in accordance with the utility cross sections.
7. All works to be carried out by a SEPPD approved contractor.
8. Pipe diameters up to 450mm, shall be of uPVC.
9. Pipe diameters above 450mm, shall be of GRP material.
10. Minimum clear cover from finish grade level to the top of pipe shall
be minimum 1200mm.

More Related Content

What's hot

71 Constable PROPOSAL LAYOUT
71 Constable PROPOSAL LAYOUT71 Constable PROPOSAL LAYOUT
71 Constable PROPOSAL LAYOUTKensonSunBernade
 
Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15Sean Roper
 
M.BERG- ARCH201-CD-SET
M.BERG- ARCH201-CD-SETM.BERG- ARCH201-CD-SET
M.BERG- ARCH201-CD-SETMarcia Berg
 
Building Information Modeling - Residential Fall 2014
Building Information Modeling -  Residential Fall 2014Building Information Modeling -  Residential Fall 2014
Building Information Modeling - Residential Fall 2014Martin Pauly
 
SHOP_DRAWING Hand Grinder
SHOP_DRAWING Hand GrinderSHOP_DRAWING Hand Grinder
SHOP_DRAWING Hand GrinderRussell Cantos
 
24hrs fitness escondido for fabrication
24hrs fitness escondido  for fabrication24hrs fitness escondido  for fabrication
24hrs fitness escondido for fabricationWuillian Medrano
 
NO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSAL
NO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSALNO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSAL
NO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSALKensonSunBernade
 
Bedingfield Assessment Report, blank
Bedingfield Assessment Report, blankBedingfield Assessment Report, blank
Bedingfield Assessment Report, blankWally Dutcher
 

What's hot (14)

71 Constable PROPOSAL LAYOUT
71 Constable PROPOSAL LAYOUT71 Constable PROPOSAL LAYOUT
71 Constable PROPOSAL LAYOUT
 
Akberet's Residence
Akberet's ResidenceAkberet's Residence
Akberet's Residence
 
Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15
 
M.BERG- ARCH201-CD-SET
M.BERG- ARCH201-CD-SETM.BERG- ARCH201-CD-SET
M.BERG- ARCH201-CD-SET
 
Plan addendum sheets
Plan addendum  sheetsPlan addendum  sheets
Plan addendum sheets
 
Woodward12-3.pdf
Woodward12-3.pdfWoodward12-3.pdf
Woodward12-3.pdf
 
Building Information Modeling - Residential Fall 2014
Building Information Modeling -  Residential Fall 2014Building Information Modeling -  Residential Fall 2014
Building Information Modeling - Residential Fall 2014
 
SHOP_DRAWING Hand Grinder
SHOP_DRAWING Hand GrinderSHOP_DRAWING Hand Grinder
SHOP_DRAWING Hand Grinder
 
24hrs fitness escondido for fabrication
24hrs fitness escondido  for fabrication24hrs fitness escondido  for fabrication
24hrs fitness escondido for fabrication
 
Eden Price List
Eden Price ListEden Price List
Eden Price List
 
Drafting and Design
Drafting and DesignDrafting and Design
Drafting and Design
 
NO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSAL
NO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSALNO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSAL
NO DIMENSION 1945 BELAIR KITCHEN RENOVATION PROPOSAL
 
Bedingfield Assessment Report, blank
Bedingfield Assessment Report, blankBedingfield Assessment Report, blank
Bedingfield Assessment Report, blank
 
Jacobs I
Jacobs IJacobs I
Jacobs I
 

Similar to Village 2 foul sewer layout plans

Southland colonial pedestrianoverpass_tre0003-g_11x17plans
Southland colonial pedestrianoverpass_tre0003-g_11x17plansSouthland colonial pedestrianoverpass_tre0003-g_11x17plans
Southland colonial pedestrianoverpass_tre0003-g_11x17plansBrendan O'Connor
 
Brisbane ferries project drawings
Brisbane ferries project drawingsBrisbane ferries project drawings
Brisbane ferries project drawingsGirish Ravikumar
 
SAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITA
SAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITASAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITA
SAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITASunit Dhingra
 
C&I July-2022.pptx
C&I July-2022.pptxC&I July-2022.pptx
C&I July-2022.pptxPowerMurugan
 
MISSION STATMENT 2015
MISSION STATMENT 2015MISSION STATMENT 2015
MISSION STATMENT 2015Alauddin Alam
 
BUSTUBE JIG DESIGN SHEET 1
BUSTUBE JIG DESIGN SHEET 1BUSTUBE JIG DESIGN SHEET 1
BUSTUBE JIG DESIGN SHEET 1Rochelle Abrie
 
45 in beam mAIN ASSEM 05-05-2015
45 in beam mAIN ASSEM 05-05-201545 in beam mAIN ASSEM 05-05-2015
45 in beam mAIN ASSEM 05-05-2015Javier Pena
 
PSG WPSR Generator Refurbishment
PSG WPSR Generator RefurbishmentPSG WPSR Generator Refurbishment
PSG WPSR Generator RefurbishmentJamie Emmart
 
Lcl users manual electrical drawings
Lcl users manual electrical drawingsLcl users manual electrical drawings
Lcl users manual electrical drawingsbibimisael
 
Red Reedbuck Bush Lodge
Red Reedbuck Bush LodgeRed Reedbuck Bush Lodge
Red Reedbuck Bush LodgeGrant Hepburn
 
Royal Museum Alor Setar
Royal Museum Alor SetarRoyal Museum Alor Setar
Royal Museum Alor Setarshacjhow
 

Similar to Village 2 foul sewer layout plans (20)

final presentation.pdf
final presentation.pdffinal presentation.pdf
final presentation.pdf
 
Southland colonial pedestrianoverpass_tre0003-g_11x17plans
Southland colonial pedestrianoverpass_tre0003-g_11x17plansSouthland colonial pedestrianoverpass_tre0003-g_11x17plans
Southland colonial pedestrianoverpass_tre0003-g_11x17plans
 
ProcContSite
ProcContSiteProcContSite
ProcContSite
 
Brisbane ferries project drawings
Brisbane ferries project drawingsBrisbane ferries project drawings
Brisbane ferries project drawings
 
SAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITA
SAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITASAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITA
SAMPLE REVIT DRAWINGS-SUNIT K DHINGRA-COMPLETE - CAPITA
 
disel tank.PDF
disel tank.PDFdisel tank.PDF
disel tank.PDF
 
C&I July-2022.pptx
C&I July-2022.pptxC&I July-2022.pptx
C&I July-2022.pptx
 
may-lanh
may-lanhmay-lanh
may-lanh
 
MISSION STATMENT 2015
MISSION STATMENT 2015MISSION STATMENT 2015
MISSION STATMENT 2015
 
BUSTUBE JIG DESIGN SHEET 1
BUSTUBE JIG DESIGN SHEET 1BUSTUBE JIG DESIGN SHEET 1
BUSTUBE JIG DESIGN SHEET 1
 
IC3D example dwgs
IC3D example dwgsIC3D example dwgs
IC3D example dwgs
 
Anchor Progress Drawing 20_03_13
Anchor Progress Drawing 20_03_13Anchor Progress Drawing 20_03_13
Anchor Progress Drawing 20_03_13
 
AWNING_SK1_A1
AWNING_SK1_A1AWNING_SK1_A1
AWNING_SK1_A1
 
YD-CTS-06
YD-CTS-06YD-CTS-06
YD-CTS-06
 
45 in beam mAIN ASSEM 05-05-2015
45 in beam mAIN ASSEM 05-05-201545 in beam mAIN ASSEM 05-05-2015
45 in beam mAIN ASSEM 05-05-2015
 
PSG WPSR Generator Refurbishment
PSG WPSR Generator RefurbishmentPSG WPSR Generator Refurbishment
PSG WPSR Generator Refurbishment
 
Lcl users manual electrical drawings
Lcl users manual electrical drawingsLcl users manual electrical drawings
Lcl users manual electrical drawings
 
M1.pdf
M1.pdfM1.pdf
M1.pdf
 
Red Reedbuck Bush Lodge
Red Reedbuck Bush LodgeRed Reedbuck Bush Lodge
Red Reedbuck Bush Lodge
 
Royal Museum Alor Setar
Royal Museum Alor SetarRoyal Museum Alor Setar
Royal Museum Alor Setar
 

Village 2 foul sewer layout plans

  • 1. 2TX 2TX 3TX 2TX 2 6 2TX V-6 Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0601 - Nov '15J.DN.C 1:1000@A1 OVERALL VILLAGE 2 LAYOUT PLAN EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA V-2 0602 0603 0604 0605 CONNECT TO DEEP GRAVITY SEWER REFER TO AREA 10 DRAWINGS CONNECT TO DEEP GRAVITY SEWER REFER TO AREA 10 DRAWINGS CONNECT TO DEEP GRAVITY SEWER REFER TO AREA 10 DRAWINGS LEGEND: PROPOSED MANHOLE shown thus PROPOSED MAIN PIPELINE shown thus SECTION No. & DIRECTION shown thus LATERAL SEWER & CHAMBER shown thus NOTE's : FOUL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0606 to 0609 LATERAL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0610 to 0619 STANDARD DETAILS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR MANHOLE REPORT & CHAMBER DETAILS. No.1 200mm@1:? Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm. ?
  • 2. Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0602 - Nov '15J.DN.C 1:500@A1 SHEET 1 of 4 VILLAGE 2 LAYOUT PLAN EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA No.1 No.1 No.1 No.1 No.2 No.3 No.1 No.4 No.6 No.5 No.5 No.5 No.7 No.7 No.8 No.18 No.18 No.13 No.12 No.12 No.14 No.14 No.14 No.14 No.15 No.16 No.28 35 1 36 37 38 39 44 43 41 42 2 40 3 45 46 47 48 80 79 78 77 76 18 114 115 116 118 119 86 87 90 91 88 8483 8213 81 12 15 89 171 172 173 102 103 100 95 104 93 90 90 9594 61 57 56 54 55 58 59 60 63 64 8 62 10 9 LEGEND: PROPOSED MANHOLE shown thus PROPOSED MAIN PIPELINE shown thus SECTION No. & DIRECTION shown thus LATERAL SEWER & CHAMBER shown thus NOTE's : FOUL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0606 to 0609 LATERAL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0610 to 0619 STANDARD DETAILS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR MANHOLE REPORT & CHAMBER DETAILS. No.1 200mm@1:? Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm. ? 117 93 6 5 52 49 464 51 50 7 204 53 96 205 169 170
  • 3. 2TX Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0603 - Nov '15J.DN.C 1:500@A1 SHEET 2 of 4 VILLAGE 2 LAYOUT PLAN EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA No.11 No.11 No.9 No.9 No.9 No.10 No.8 No.14 No.33 Deep Gravity Sewer to East Sitra Pumphouse CONNECT TO DEEP GRAVITY SEWER SEE AREA 10 DRAWINGS FOR DETAILS 98 99 106 16 28170 169 168 17 33 74 75 70 69 67 68 72 73 71 11 66 20610 65 111 112 109 LEGEND: PROPOSED MANHOLE shown thus PROPOSED MAIN PIPELINE shown thus SECTION No. & DIRECTION shown thus LATERAL SEWER & CHAMBER shown thus NOTE's : FOUL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0606 to 0609 LATERAL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0610 to 0619 STANDARD DETAILS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR MANHOLE REPORT & CHAMBER DETAILS. No.1 200mm@1:? Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm. ? No.1 No.3 No.1 No.4 No.6 No.5 No.5 No.5 No.7 No.7 No.8 No.14 No.14 No.14 No.14 No.15 No.16 No.28 46 48 119 86 87 90 91 88 84 15 89 171 172 173 102 103 100 95 104 93 90 9594 61 57 56 54 55 58 59 60 63 64 8 62 9 93 6 5 52 49 464 51 50 7 204 53 96 205 105 108 110 Deep Gravity Sewer to East Sitra Pumphouse
  • 4. 2 2TX Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0604 - Nov '15J.DN.C 1:500@A1 SHEET 3 of 4 VILLAGE 2 LAYOUT PLAN EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA No.18 No.18 No.18 No.18 No.18 No.19 No.20 No.20 No.20 No.21 No.22 No.24 No.24 No.24 No.24 No.24 No.23 No.25 No.26 No.28 No.28 No.28 No.28 No.32 No.32 No.30 19 120 115 116 117 119 118 121 22 138 140 139 130 131 143 137 136 135 134 133 21 13220 122 123 124 125 126 127 128 129 24 144 145 146 147 148 149 150 151 158 152 153 155 154 156 157162 163 159 160 164 26 166 165 LEGEND: PROPOSED MANHOLE shown thus PROPOSED MAIN PIPELINE shown thus SECTION No. & DIRECTION shown thus LATERAL SEWER & CHAMBER shown thus NOTE's : FOUL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0606 to 0609 LATERAL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0610 to 0619 STANDARD DETAILS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR MANHOLE REPORT & CHAMBER DETAILS. No.1 200mm@1:? Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm. ? 23 141 142 No.24 30 179 14 85 188 32 189 191 190 90 No.17 34 161 25 No.28 15 89 173 172 171 169 170 178175 174 177 184 183 182180 181 193 192 203 97 206
  • 5. 2TX 3TX 2 2TX Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0605 - Nov '15J.DN.C 1:500@A1 SHEET 4 of 4 VILLAGE 2 LAYOUT PLAN EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA No.18 No.18 No.18 No.27 No.24 No.23 No.28 No.28 No.28 No.28 No.29 No.33 No.33 No.30 No.30 No.32 No.32 No.20 Deep Gravity Sewer to East Sitra Pumphouse CONNECT TO DEEP GRAVITY SEWER see AREA 10 DRAWINGS FOR DETAILS 15 89 173 172 171 169 170 28 168 178175 174 177 176 90 195 196 197 31 185 186 187 184 183 182180 181 30 179 14 85 188 32 189 191 190 192 193 203 201 202 200 199 198 33 194 27 167 151 141 142 159 140 130 131 143 LEGEND: PROPOSED MANHOLE shown thus PROPOSED MAIN PIPELINE shown thus SECTION No. & DIRECTION shown thus LATERAL SEWER & CHAMBER shown thus NOTE's : FOUL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0606 to 0609 LATERAL SECTIONS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0610 to 0619 STANDARD DETAILS REFER TO DRAWING's JOD-10011-C-CD-00-FS-PL-0620 to 0624 FOR MANHOLE REPORT & CHAMBER DETAILS. No.1 200mm@1:? Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm. ? No.24 No.24 No.17 No.26 152 153 155 154 156 157 162 34 161 163 164 26 166 165 97 No.18 No.24 No.24 No.24 No.25 158 25 160 206 CONNECT TO DEEP GRAVITY SEWER see AREA 10 DRAWINGS FOR DETAILS No.31
  • 6. Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0606 - Nov '15J.DN.C 1:1000@A1 SHEET 1 of 4 VILLAGE 2 SECTION EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA SCALE = 1:1000 HORIZONTAL 1:100 VERTICAL LEGEND: PROPOSED MANHOLE shown thus PROPOSED PIPELINE shown thus LATERAL SEWER CONNECTION shown thus V 2 - F - N o . Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm.
  • 7. Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0607 - Nov '15J.DN.C As Shown@A1 SHEET 2 of 4 VILLAGE 2 SECTION EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA SCALE = 1:1000 HORIZONTAL 1:100 VERTICAL LEGEND: PROPOSED MANHOLE shown thus PROPOSED PIPELINE shown thus LATERAL SEWER CONNECTION shown thus V 2 - F - N o . Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm.
  • 8. Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0608 - Nov '15J.DN.C As Shown@A1 SHEET 3 of 4 VILLAGE 2 SECTION EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA SCALE = 1:1000 HORIZONTAL 1:100 VERTICAL LEGEND: PROPOSED MANHOLE shown thus PROPOSED PIPELINE shown thus LATERAL SEWER CONNECTION shown thus V 2 - F - N o . Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm.
  • 9. Project Stage Title Design Consultant Checked Approved Date Rev Prepared Job No. Rev Description Prep Chkd Appd Date PJH 10011 DETAIL DESIGN SOCIAL HOUSING PROJECT AT EAST SITRA Client JOD-10011-C-CD-00-FS-PL-0609 - Nov '15J.DN.C As Shown@A1 SHEET 4 of 4 VILLAGE 2 SECTION EAST SITRA FOUL SEWER PJHJDNCDraft DETAIL DESIGN IssueA SCALE = 1:1000 HORIZONTAL 1:100 VERTICAL LEGEND: PROPOSED MANHOLE shown thus PROPOSED PIPELINE shown thus LATERAL SEWER CONNECTION shown thus V 2 - F - N o . Notes 1. This Drawing is to be read in conjunction with all other relevant documentation. 2. Do not scale from this drawing, use only printed dimensions. 3. All dimensions in millimetres, all chainages, levels and coordinates are in metres unless defined otherwise. 4. This drawing is to be read in conjunction with the project Health and Safety File for any identified potential risks. 5. All materials to be approved by EWA/SEPPD prior to installation. 6. Installation to be in accordance with SEPPD standards and best practices and in accordance with the utility cross sections. 7. All works to be carried out by a SEPPD approved contractor. 8. Pipe diameters up to 450mm, shall be of uPVC. 9. Pipe diameters above 450mm, shall be of GRP material. 10. Minimum clear cover from finish grade level to the top of pipe shall be minimum 1200mm.