SlideShare a Scribd company logo
www.btcables.com 
 
Cables for
BUILDING INFRASTRUCTURE
SYSTEMS
Edition 1 2015
CONTENTS
CABLE FINDER
BT CABLES – BELDEN EQUIVALENTS
SECTION 1 BT BMS-TECTM
- Paired Cables
SECTION 2 BT BMS-TECTM
- Multi-Conductor Cables
SECTION 3 BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables
SECTION 4 BT FIREPRO-TEC™ – Fire Resistant Cables
SECTION 5 BT Security-Tec ™– Coaxial Cables
SECTION 6 BT Data-Tec™ - Category LAN Cables
SECTION 7 BT Industrial-Tec™ - DEF Standard Cables
SECTION 8 BT Industrial-Tec™ - Industrial Cables
SECTION 9 BT Industrial-Tec™ – Control Cables
GENERALTECHNICAL INFORMATION
COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS
CONVERSIONS
GLOSSARY
BT CABLES PART NUMBER INDEX
 
 
 
info.btcables@bt.com 2
Cable Finder
BT BMS-TECTM
- Paired Cables
Application
Cond.-
Size ↓
No. of pairs →
1 2 3 4 5 6 7 8 § Page
Screen Sheath
RS-485
24 AWG
Foil+
braid
PVC C1189 C1190 C1191 C1192 1.1
24 AWG HFFR C1318 C1319 C1320 C1321 1.1
22 AWG PVC C1080 C1295 C1296 C1297 1.1
22AWG HFFR C1401 C1402 C1403 C1404 1.1
RS-422 24 AWG every
pair
a foil
PVC C1382 C1383 C1384 C1386 1.2
G.P.
Bus
22 AWG PVC C1196 C1197 C1298 C1299 C1214 1.6
22 AWG HFFR C1281 C1282 C1314 1.6
RS-232 24 AWG Foil PVC C1181 C1182 C1183 C1184 C1185 C1186 C1187 C1188 1.3
Lon
Works
0.64 mm no scrn HFFR C1346 C1347 1.5
0.64 mm
every
pair a foil
HFFR C1348 C1349 1.5
KNX
0.8 mm
Foil
PVC C1219 C1217 1.4
0.8 mm HFFR C1220 C1218 1.4
Security &
Alarm
18 AWG
Foil HFFR C1171 C1172 C1173 C1174 C1175 C1176 1.8
Foil +
Braid
HFFR C1418 C1419 C1420 C1421 C1422 C1423 1.8
BMS 0.6 mm² Foil PVC C1381 1.9
Application
No. of
pairs ↓
AWG conductor size →
22 20 18 16 14 12 Section Page
Screen ↓ Sheath ↓
G.P Bus
1 Yes PVC C1199 C1195 C1193 C1213 C1224 C1313 1.7
1 Yes HFFR C1310 C1308 C1272 C1270 C1305 C1303 1.7
1 No PVC C1301 C1300 C1203 C1198 C1222 C1302 1.7
1 No HFFR C1311 C1309 C1271 C1307 C1306 C1304 1.7
BT BMS-TECTM
- Multi-Conductor Cables
Cond. Size
AWG↓
No. of conductors →
2 3 4 6 8 Section Page
Sheath ↓ Screen
22
PVC
Yes C1226 C1228 C1230 C1264 C1232 2.1
No C1227 C1278 C1231 C1265 C1233 2.1
HFFR
Yes C1741 C1743 C1745 C1747 C1749 2.2
No C1742 C1744 C1746 C1748 C1750 2.2
20
PVC
Yes C1019 C1021 C1023 C1260 C1262 2.1
No C1020 C1022 C1024 C1261 C1263 2.1
HFFR
Yes C1731 C1733 C1735 C1737 C1739 2.2
No C1732 C1734 C1736 C1738 C1740 2.2
18
PVC
Yes C1013 C1015 C1017 C1211 C1258 2.1
No C1014 C1016 C1018 C1212 C1259 2.1
HFFR
Yes C1721 C1723 C1725 C1727 C1729 2.2
No C1722 C1724 C1726 C1728 C1730 2.2
UV-HFFR Yes C1351 C1352 C1353 C1354 C1355 2.3
16
PVC
Yes C1007 C1009 C1011 C1252 C1254 2.1
No C1008 C1010 C1012 C1253 C1255 2.1
HFFR
Yes C1711 C1713 C1715 C1717 C1719 2.2
No C1712 C1714 C1716 C1718 C1720 2.2
UV-HFFR Yes C1391 C1392 C1393 C1394 C1395 2.3
14
PVC
Yes C1001 C1003 C1005 C1248 C1250 2.1
No C1002 C1004 C1006 C1249 C1251 2.1
HFFR
Yes C1701 C1703 C1705 C1707 C1709 2.2
No C1702 C1704 C1706 C1708 C1710 2.2
12
PVC
Yes C1322 C1324 C1326 C1330 C1332 2.1
No C1323 C1325 C1327 C1331 C1333 2.1
HFFR
Yes C1334 C1336 C1338 C1342 C1344 2.2
No C1335 C1337 C1339 C1343 C1345 2.2
No. of
conductors
Conductor size →
22 AWG 20 AWG 18 AWG Section Page
Sheath ↓ Screen
3 PVC Yes C1215 C1245 C1225 ?
Multi-Conductor Power Limited Tray Cables (PLTC) are available on request
 
 
 
info.btcables@bt.com 3
BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables
Application
No. of
pairs ↓
Cond. size → AWG
18
AWG
16
AWG
14
AWG
12
Section Page
Screen ↓ Sheath ↓
Fire Alarm
1 Yes PVC C1040 C1041 C1042 C1043 3
1 No PVC C1135 C1136 C1137 C1138 3
BT FIREPRO-TEC™ – Fire Resistant Cables
Application
No. of
cores ↓
Cond. size → 0.75
mm
2
1.0
mm
2
1.5
mm
2
2.5
mm
2
4.0
mm
2 Section Page
Screen ↓ Sheath ↓
Circuit integrity
1 No HFFR C1760 C1761 4
2 Yes HFFR C1284 C1283 C1044 C1045 C1289 4
2 No HFFR C1139 C1140 C1141 C1142 C1143 4
3 Yes HFFR C1159 C1160 C1161 C1162 C1163 4
3 No HFFR C1149 C1150 1151 C1152 C1153 4
BT Security-Tec ™– Coaxial Cables
Application
Inner
Conductor
Screen Sheath RG-59 RG-6 RG-11 Section Page
CCTV
Solid BC Braid BC PVC C1028 C1029 C1030 5.1
Solid BC Braid BC HFFR C1428 C1429 C1430 5.1
Flex BC Braid BC PVC C1275 C1276 C1277 5.1
SMATV
CATV
CCS Foil+Alu Braid PVC C1025 C1026 C1027 5.2
CCS Quad screen PVC C1256 C1257 C1241 5.2
HDTV
Solid BC Foil+TC Braid PVC C1229 C1279 C1280 5.3
Solid BC Foil+TC Braid HFFR C1378 C1379 C1380 5.3
50 Ohm Coaxial cables are available on request
BT Data-Tec™ - Category LAN Cables
Cat. type Sheath 2 pairs 6 prs 12 prs 25 prs 50 prs 100 prs 150 prs 200 prs section Page
Cat 3 PVC C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269 6.4
Cat. types Sheath UTP UTP-UL FTP FTP-UL U-FTP S-FTP Section Page
Cat 5e
PVC C1035 C1285 C1036 C1286 6.1
HFFR C1235 C1236 6.1
Cat 5e-
patch
PVC C1500 C1520 6.3
HFFR C1510 C1530 6.3
Cat 6
PVC C1037 C1287 C1038 C1288 6.1
HFFR C1237 C1238 6.1
Cat 6-patch PVC C1540 C1560 6.3
HFFR C1550 C1570 6.3
Cat 6a
PVC C1055 C1056 C1057 6.2
HFFR C1200 C1052 C1053 6.2
Cat 7 HFFR C1039 6.2
Cat 7a HFFR C1201 6.2
 
 
 
info.btcables@bt.com 4
BT Industrial-Tec™ - DEF Standard Cables
Conductor 7 x 0.1 mm = 0.055 mm²
No. of cores 2 3 4 6 9 15 25 36 50 section Page
Screened C1164 C1165 C1166 C1168 C1169 C1365 7
Unscreened C1360 C1361 C1362 C1144 C1145 C1146 C1147 C1148 C1364 7
Conductor 7 x 0.2mm = 0.22 mm²
No. of cores 2 3 4 6 8 12 20 36 section Page
Screened C1171 C1172 C1173 C1174 C1175 C1176 7
Unscreened C1366 C1367 C1368 C1369 C1154 C1155 C1156 C1157 7
Conductor 16 x 0.2mm = 0.5 mm²
No. of cores 2 3 4 6 12 18 section Page
Screened C1177 C1178 C1375 C1180 7
Unscreened C1158 C1370 C1371 C1372 C1373 C1374 7
BT Industrial-Tec™ - Industrial Cables
BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Unarmoured cables
No. of pairs 1 2 5 10 20 section Page
Conductor 0.5 mm² (16x0.2 mm) C1081 C1082 C1083 C1084 C1085 8
Conductor 0.75 mm² (24x0.2 mm) C1086 C1087 C1088 C1089 C1090 8
Conductor 1.5 mm² (7x0.53 mm) C1091 C1092 C1093 C1094 C1095 8
BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Armoured cables
No. of pairs 1 2 5 10 20 section Page
Conductor 0.5 mm² (16x0.2 mm) C1096 C1097 C1098 C1099 C1100 8
Conductor 0.75 mm² (24x0.2 mm) C1101 C1102 C1103 C1104 C1105 8
Conductor 1.5 mm² (7x0.53 mm) C1106 C1107 C1108 C1109 C1110 8
BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Unarmoured cables
No. of pairs 2 5 10 20 section Page
Conductor 0.5 mm² (16x0.2 mm) C1111 C1112 C1113 C1114 8
Conductor 0.75 mm² (24x0.2 mm) C1115 C1116 C1117 C1118 8
Conductor 1.5 mm² (7x0.53 mm) C1119 C1120 C1121 C1122 8
BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Armoured cable
No. of pairs 2 5 10 20 section Page
Conductor 0.5 mm² (16x0.2 mm) C1123 C1124 C1125 C1126 8
Conductor 0.75 mm² (24x0.2 mm) C1127 C1128 C1129 C1130 8
Conductor 1.5 mm² (7x0.53 mm) C1131 C1132 C1133 C1134 8
 
 
 
info.btcables@bt.com 5
BT Industrial-Tec™ - Control Cables
YY Series (N stranded cores surrounded by a PVC sheath)
No. of cores 3 4 5 7 8 12 18 section Page
Conductor 0.75 mm² (24x0.2 mm) C1631 C1635 C1645 C1648 9
Conductor 1.0 mm² (32x0.2 mm) C1632 C1636 9
Conductor 1.5 mm² (30x0.24 mm) C1633 C1637 C1639 C1641 C1643 C1646 C649 9
Conductor 2.5 mm² (50x0.24 mm) C1634 C1638 C1640 C1642 C1644 C1647 C1650 9
CY Series (N stranded cores surrounded by a braiding plus a PVC sheath)
No. of cores 3 4 5 section Page
Conductor 0.75 mm² (24x0.2 mm) C1620 C1624 9
Conductor 1.0 mm² (32x0.2 mm) C1621 C1625 9
Conductor 1.5 mm² (30x0.24 mm) C1622 C1626 C1628 9
Conductor 2.5 mm² (50x0.24 mm) C1623 C1627 C1629 9
SY Series (N stranded cores surrounded by Steel Wire Armouring plus a PVC sheath)
No. of cores 2 3 4 5 7 12 18 25 section Page
Conductor 0.75 mm² (24x0.2 mm) C1655 9
Conductor 1.0 mm² (32x0.2 mm) C1651 C1656 C1660 C1665 C1669 C1671 C1673 C1675 9
No. of cores 2 3 4 5 6 7 12 18
Conductor 1.5 mm² (30x0.24 mm) C1652 C1657 C1661 C1666 C1668 C1670 C1672 C1674 9
Conductor 2.5 mm² (50x0.24 mm) C1658 C1662 9
Conductor 4.0 mm² (56x0.29 mm) C1659 C1663 9
Conductor 6.0 mm² (84x0.29 mm) C1664 9
 
 
 
info.btcables@bt.com 6
BT Cables - Belden equivalents
Belden P/N BT Cables P/N Conductor Size
No. of
Conductors
No. of
Pairs
Individually
shielded
pairs
Collective
shield
Jacket BT Cables Brand and Additional Data
1030A C1223 16(7*24) AWG 1 Yes PVC 300V PL Tray Cable
1043A C1078 16 (7*24) AWG 16 Yes Yes PVC 600V Tray Cable
1044A C1077 16 (7*24) AWG 20 Yes Yes PVC 600V Tray Cable
1064A C1076 18 (7*26) AWG 4 Yes Yes PVC 600V Tray Cable
1067A C1074 18 (7*26) AWG 16 Yes Yes PVC 600V Tray Cable
1467A C1075 18 (7*26) AWG 8 Yes Yes PVC 300V PL Tray Cable
1505A C1229 20 AWG 1 Yes PVC RG-59 Coaxial Cable (BC)
1523A C1027 14 AWG 1 Yes PVC RG11 Coaxial Cable (CCS)
1583A C1035 24 AWG 4 CAT 5E UTP Cable
1617A C1241 14 AWG 1 Yes PVC RG-11 Quad Shield Coaxial Cable (CCS)
1633E C1036 24 AWG 4 yes PVC CAT 5E FTP Cable
1694A C1279 18 AWG 1 Yes PVC RG-6 Coaxial Cable (BC)
1885ENH C1039 23 AWG 4 Yes Yes PVC CAT 7 ISTP Cable
3079E C1315 22 (7*30) AWG 1 Yes PVC Profibus DP
3105A C1080 22 (7*30) AWG 2 Yes PVC RS-485 Computer Cable
3107A C1295 22 (7*30) AWG 2 Yes PVC RS-485 Low Cap Computer Cable
3108A C1296 22 (7*30) AWG 3 Yes PVC RS-485 Computer Cable
3109A C1297 22 (7*30) AWG 4 Yes PVC RS-485 Computer Cable
4000FE C1334 12 (19*25) AWG 2 Yes HFFR BMS-HFFR cables
4000UE C1335 12 (19*25) AWG 2 HFFR BMS-HFFR cables
4001UE C1337 12 (19*25) AWG 3 HFFR BMS-HFFR cables
4100FE C1701 14 (19*27) AWG 2 Yes HFFR BMS-HFFR cables
4100UE C1702 14 (19*27) AWG 3 HFFR BMS-HFFR cables
4101UE C1704 14 (19*27) AWG 3 HFFR BMS-HFFR cables
4102UE C1706 14 (19*27) AWG 4 HFFR BMS-HFFR cables
4200FE C1711 16 (19*29) AWG 2 Yes HFFR BMS-HFFR cables
4200UE C1712 16 (19*29) AWG 2 HFFR BMS-HFFR cables
4201FE C1713 16 (19*29) AWG 3 Yes HFFR BMS-HFFR cables
4201UE C1714 16 (19*29) AWG 3 HFFR BMS-HFFR cables
4202FE C1715 16 (19*29) AWG 4 Yes HFFR BMS-HFFR cables
4202UE C1716 16 (19*29) AWG 4 HFFR BMS-HFFR cables
4300FE C1721 18 (7*26) AWG 2 Yes HFFR BMS-HFFR cables
4300UE C1722 18 (7*26) AWG 2 HFFR BMS-HFFR cables
4301FE C1723 18 (7*26) AWG 3 Yes HFFR BMS-HFFR cables
4301UE C1724 18 (7*26) AWG 3 HFFR BMS-HFFR cables
4302FE C1725 18 (7*26) AWG 4 Yes HFFR BMS-HFFR cables
4302UE C1726 18 (7*26) AWG 4 HFFR BMS-HFFR cables
4304FE C1727 18 (7*26) AWG 6 Yes HFFR BMS-HFFR cables
4304UE C1728 18 (7*26) AWG 6 HFFR BMS-HFFR cables
4306FE C1729 18 (7*26) AWG 8 Yes HFFR BMS-HFFR cables
4306UE C1730 18 (7*26) AWG 8 HFFR BMS-HFFR cables
4400FE C1731 20 (7*28) AWG 2 Yes HFFR BMS-HFFR cables
4400UE C1732 20 (7*28) AWG 2 HFFR BMS-HFFR cables
4401FE C1733 20 (7*28) AWG 3 Yes HFFR BMS-HFFR cables
4402FE C1735 20 (7*28) AWG 4 Yes HFFR BMS-HFFR cables
4402UE C1736 20 (7*28) AWG 4 HFFR BMS-HFFR cables
4500FE C1741 22 (7*30) AWG 2 Yes HFFR BMS-HFFR cables
4500UE C1742 22 (7*30) AWG 2 HFFR BMS-HFFR cables
4501FE C1743 22 (7*30) AWG 3 Yes HFFR BMS-HFFR cables
4501UE C1744 22 (7*30) AWG 3 HFFR BMS-HFFR cables
4502FE C1745 22 (7*30) AWG 4 Yes HFFR BMS-HFFR cables
4502UE C1746 22 (7*30) AWG 4 HFFR BMS-HFFR cables
4504FE C1747 22 (7*30) AWG 6 Yes HFFR BMS-HFFR cables
4504UE C1748 22 (7*30) AWG 6 HFFR BMS-HFFR cables
4506FE C1749 22 (7*30) AWG 8 Yes HFFR BMS-HFFR cables
4506UE C1750 22 (7*30) AWG 8 HFFR BMS-HFFR cables
5100FE C1001 14 (19*27) AWG 2 Yes PVC BMS-PVC cables
5100UE C1002 14 (19*27) AWG 2 PVC BMS-PVC cables
5101FE C1003 14 (19*27) AWG 3 Yes PVC BMS-PVC cables
5101UE C1004 14 (19*27) AWG 3 PVC BMS-PVC cables
5102FE C1005 14 (19*27) AWG 4 Yes PVC BMS-PVC cables
5102UE C1006 14 (19*27) AWG 4 PVC BMS-PVC cables
5200FE C1007 16 (19*29) AWG 2 Yes PVC BMS-PVC cables
5200UE C1008 16 (19*29) AWG 2 PVC BMS-PVC cables
5201FE C1009 16 (19*29) AWG 3 Yes PVC BMS-PVC cables
5201UE C1010 16 (19*29) AWG 3 PVC BMS-PVC cables
5202FE C1011 16 (19*29) AWG 4 Yes PVC BMS-PVC cables
5202UE C1012 16 (19*29) AWG 4 PVC BMS-PVC cables
5300FE C1013 18 (7*26) AWG 2 Yes PVC BMS-PVC cables
5300UE C1014 18 (7*26) AWG 2 PVC BMS-PVC cables
5301FE C1015 18 (7*26) AWG 3 Yes PVC BMS-PVC cables
5301UE C1016 18 (7*26) AWG 3 PVC BMS-PVC cables
5302FE C1017 18 (7*26) AWG 4 Yes PVC BMS-PVC cables
5302UE C1018 18 (7*26) AWG 4 PVC BMS-PVC cables
5305FE C1239 18 (7*26) AWG 7 PVC BMS-PVC cables
5400FE C1019 20 (7*28) AWG 2 Yes PVC BMS-PVC cables
5400UE C1020 20 (7*28) AWG 2 PVC BMS-PVC cables
5401FE C1021 20 (7*28) AWG 3 Yes PVC BMS-PVC cables
5401UE C1022 20 (7*28) AWG 3 PVC BMS-PVC cables
5402FE C1023 20 (7*28) AWG 4 Yes PVC BMS-PVC cables
5402UE C1024 20 (7*28) AWG 4 PVC BMS-PVC cables
7731A C1280 14 AWG 1 Yes PVC RG-11 Coaxial Cable (BC)
7860E C1038 23 AWG 4 Yes CAT6 FTP Cable
7965E C1037 23 AWG 4 CAT 6 UTP Cable
8205 C1300 20 (7*28) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable
8205NH C1415 20 (7*28) AWG 1 HFFR High Conductivity Speaker and BMS-PVC-TC Cable
8259 C1046 20 (10*33) AWG 1 Yes PVC RG-58 Coaxial Cable
8442 C1301 22 (7*30) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable
8442NH C1416 22 (7*30) AWG 1 HFFR BMS-HFFR cables
8471 C1198 16 (19*29) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable
8471NH C1307 16 (19*29) AWG 1 HFFR BMS-HFFR cables
8473 C1222 14 (19*27) AWG 2 PVC High Conductivity Speaker and BMS-PVC-TC Cable
8473NH C1306 14 (19*27) AWG 2 HFFR BMS-HFFR cables
 
 
 
info.btcables@bt.com 7
BT Cables - Belden equivalents
Belden P/N BT Cables P/N Conductor Size
No. of
Conductors
No. of
Pairs
Individually
shielded
pairs
Collective
shield
Jacket BT Cables Brand and Additional Data
8477 C1302 12 (19*25) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable
8477NH C1417 12 (19*25) AWG 1 HFFR BMS-HFFR cables
8718NH C1303 12 (19*25) AWG 1 Yes HFFR BMS-HFFR cables
8719 C1213 16 (19*29) AWG 2 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable
8719NH C1270 16 (19*29) AWG 2 HFFR BMS-HFFR cables
8720 C1224 14 (19*27) AWG 2 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable
8720NH C1305 14 (19*27) AWG 2 Yes HFFR BMS-HFFR cables
8723 C1196 22 (7*30) AWG 2 Yes PVC Individually Shielded TP BMS-PVC-TC Cable
8723NH C1281 22 (7*30) AWG 2 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable
8723PE C1316 22 (7*30) AWG 2 Yes PE Individually Shielded TP BMS-PE-TC Cable
8760 C1193 18 (7*26) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable
8760NH C1272 18 (7*26) AWG 1 Yes HFFR BMS-HFFR cables
8761 C1199 22 (7*30) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable
8761NH C1310 22 (7*30) AWG 1 Yes HFFR BMS-HFFR cables
8762 C1195 20 (7*28) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable
8762NH C1308 20 (7*28) AWG 1 Yes HFFR BMS-HFFR cables
8770 C1225 18 (7*26) AWG 3 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable
8772 C1245 20 (7*28) AWG 3 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable
8777 C1197 22 (7*30) AWG 3 Yes PVC Individually Shielded TP BMS-PVC-TC Cable
8777NH C1282 22 (7*30) AWG 3 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable
8777PE C1317 22 (7*30) AWG 3 Yes PE Individually Shielded TP BMS-PE-TC Cable
8778 C1214 22 (7*30) AWG 6 Yes PVC Individually Shielded TP BMS-PVC-TC Cable
8778NH C1314 22 (7*30) AWG 6 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable
9100 C1025 20 AWG 1 Yes PVC RG-59 Coaxial Cable (CCS)
9116 C1026 18 AWG 1 Yes PVC RG-6 Coaxial Cable (CCS)
9259 C1275 20 (19*33) 1 Yes PVC RG-59 Coaxial CCTV cable
9463F C1079 20 (42*36) AWG 1 Yes PVC Twinax - Blue Hose cable
9501 C1181 24 (7*32) AWG 1 Yes PVC RS-232 Computer Cable
9501NH C1441 24 (7*32) AWG 1 Yes HFFR RS-232 Computer Cable
9501PE C1451 24 (7*32) AWG 1 Yes PE RS-232 Computer Cable
9502 C1182 24 (7*32) AWG 2 Yes PVC RS-232 Computer Cable
9502NH C1442 24 (7*32) AWG 2 Yes HFFR RS-232 Computer Cable
9502PE C1452 24 (7*32) AWG 2 Yes PE RS-232 Computer Cable
9503 C1183 24 (7*32) AWG 3 Yes PVC RS-232 Computer Cable
9503NH C1443 24 (7*32) AWG 3 Yes HFFR RS-232 Computer Cable
9503PE C1453 24 (7*32) AWG 3 Yes PE RS-232 Computer Cable
9504 C1184 24 (7*32) AWG 4 Yes PVC RS-232 Computer Cable
9504NH C1444 24 (7*32) AWG 4 Yes HFFR RS-232 Computer Cable
9504PE C1454 24 (7*32) AWG 4 Yes PE RS-232 Computer Cable
9505 C1185 24 (7*32) AWG 5 Yes PVC RS-232 Computer Cable
9505NH C1445 24 (7*32) AWG 5 Yes HFFR RS-232 Computer Cable
9505PE C1455 24 (7*32) AWG 5 Yes PE RS-232 Computer Cable
9506 C1186 24 (7*32) AWG 6 Yes PVC RS-232 Computer Cable
9506NH C1446 24 (7*32) AWG 6 Yes HFFR RS-232 Computer Cable
9506PE C1456 24 (7*32) AWG 6 Yes PE RS-232 Computer Cable
9507 C1187 24 (7*32) AWG 7 Yes PVC RS-232 Computer Cable
9507NH C1447 24 (7*32) AWG 7 Yes HFFR RS-232 Computer Cable
9507PE C1457 24 (7*32) AWG 7 Yes PE RS-232 Computer Cable
9508 C1188 24 (7*32) AWG 8 Yes PVC RS-232 Computer Cable
9508NH C1448 24 (7*32) AWG 8 Yes HFFR RS-232 Computer Cable
9508PE C1458 24 (7*32) AWG 8 Yes PE RS-232 Computer Cable
9510NH C1206 24 (7*32) AWG 10 Yes PVC RS-232 Computer Cable
9510NH C1449 24 (7*32) AWG 10 Yes HFFR RS-232 Computer Cable
9536 NH C1358 24 (7*32) AWG 6 Yes HFFR RS-232 Computer Cable
9536 C1398 24 (7*32) AWG 6 Yes PVC RS-232 Computer Cable
9538 C1399 24 (7*32) AWG 8 Yes PVC RS-232 Computer Cable
9538NH C1359 24 (7*32) AWG 8 Yes HFFR RS-232 Computer Cable
9540 C1400 24 (7*32) AWG 10 Yes PVC RS-232 Computer Cable
9571 C1135 18 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9572 C1136 16 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9574 C1040 18 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9575 C1041 16 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9580 C1137 14 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9581 C1042 14 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9582 C1138 12 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9583 C1043 12 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed
9728 C1384 24 (7*32) AWG 4 Yes PVC Low Cap Computer Cable
9729 C1382 24 (7*32) AWG 2 Yes PVC Low Cap Computer Cable
9730 C1383 24 (7*32) AWG 1 Yes PVC Low Cap Computer Cable
9740 C1203 18 (7*26) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable
9740NH C1271 18 (7*26) AWG 1 HFFR BMS-HFFR cables
9773 C1298 22 (7*30) AWG 4 Yes PVC Individually Shielded TP BMS-PVC-TC Cable
9774 C1299 22 (7*30) AWG 5 Yes PVC Individually Shielded TP BMS-PVC-TC Cable
9841 C1189 24 (7*32) AWG 1 PVC RS-485 Low Cap Computer Cable
9841NH C1318 24 (7*32) AWG 1 HFFR RS-485 Low Cap Computer Cable
9841PE C1409 24 (7*32) AWG 1 PE RS-485 Low Cap Computer Cable
9842 C1190 24 (7*32) AWG 2 PVC RS-485 Low Cap Computer Cable
9842NH C1319 24 (7*32) AWG 2 HFFR RS-485 Low Cap Computer Cable
9843 C1191 24 (7*32) AWG 3 PVC RS-485 Low Cap Computer Cable
9843NH C1320 24 (7*32) AWG 3 HFFR RS-485 Low Cap Computer Cable
9844 C1192 24 (7*32) AWG 4 PVC RS-485 Low Cap Computer Cable
9844NH C1321 24 (7*32) AWG 4 HFFR RS-485 Low Cap Computer Cable
9913 C1047 10 AWG 1 Yes PVC RG-8 Series Coaxial Cable
1227A1 C1031 24 AWG 2 PVC CAT 3 UTP Cable
1232A1 C1032 24 AWG 25 PVC CAT 3 UTP Cable
43051 C1208 0.4 mm 8 Yes PVC 8 Pair/0.4 Braided Telecoms Cable
43113 C1207 26 AWG 1 Yes HFFR TELCO 75 Ohm Coaxial Cable
513945 C1030 14 AWG 1 Yes PVC RG-11 Coaxial Cable (BC)
533945 C1029 18 AWG 1 Yes PVC RG6 Series Coaxial Cable (BC)
543945 C1028 20 AWG 1 Yes PVC RG-59 Coaxial Cable (BC)
9842NH C1319 24 (7*32) AWG 2 Yes HFFR 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket
9842PE C1410 24 (7*32) AWG 2 Yes PE 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket
9843NH C1320 24 (7*32) AWG 3 Yes HFFR 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket
 
 
 
info.btcables@bt.com 8
BT Cables - Belden equivalents
Belden P/N BT Cables P/N Conductor Size
No. of
Conductors
No. of
Pairs
Individually
shielded
pairs
Collective
shield
Jacket BT Cables Brand and Additional Data
9843PE C1411 24 (7*32) AWG 3 Yes PE 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket
9844NH C1321 24 (7*32) AWG 4 Yes HFFR 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket
9844PE C1412 24 (7*32) AWG 4 Yes PE 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket
MRG2130 C1048 2.25 (7*0.75) mm 1 Yes PVC RG213 Series Coaxial cable
MRG214 C1049 2.25 (7*0.75) mm 1 Yes PVC RG214 Series Coaxial Cable
YE00819 C1219 0.8 1 Yes PVC KNX (was EIB) CABLE
YE00820 C1217 0.8 2 Yes PVC KNX (was EIB) CABLE
YE00905 C1220 0.8 1 Yes HFFR KNX (was EIB) CABLE
YE00906 C1218 0.8 2 Yes HFFR KNX (was EIB) CABLE
 
 
 
info.btcables@bt.com 9
Section 1 - BT BMS-TECTM
- Paired Cables
PVC, PE or HFFR sheathed cables for BUS and Interface Systems
1. Application
RS-232, RS-422, RS-485, KNX (EIB or Instabus), LonWorks, ModBus, M-Bus, CAN-bus, BACnet, BMS (Building Management
Systems) or general interface systems.
2. Basic Construction of the cables
Wire = conductor without or with insulation. With insulation sometimes also indicated as core.
Conductor: may be solid = one single rod or flexible = twisted bare or tinned copper strands, ranging from 12 to 24AWG.
Conductor
(AWG)
Configuration
(AWG)
Configuration
(mm)
DC Resistance
(Ohm/km)
24 7 x 32 7 x 0.20 ≤ 88
22 7 x 30 7 x 0.25 ≤ 57.4
20 7 x 28 7 x 0.32 ≤ 32.16
18 7 x 26 7 x 0.40 ≤ 22.7
16 19 x 29 19 x 0.28 ≤ 15.47
14 19 x 27 19 x 0.36 ≤ 9.36
12 19 x 25 19 x 0.45 ≤ 5.61
Insulation: Polyethylene (PE) or Foam PE (FPE) for PVC (Polyvinyl Chloride) or Halogen-Free (HFFR) sheathed cables. And
Halogen-Free (HFFR) for HFFR sheathed cables. All insulations are in accordance with BS EN 50290-2, good strippable and
coloured. The colours are not interchangeable.
Pair = two twisted – colour coded – wires.
Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire.
Cable core: two or more (individually screened) pairs stranded.
Good twisting (lay-length < 30 ~ 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends.
Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that
drain wires are tinned.
Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically
applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend.
Braiding (if applicable): tinned copper wires.
Sheath: grey PVC , black PE or purple HFFR, all in accordance with BS EN 50290-2.
Cable Configuration Cable
Retardancy
Low
Smoke
Halogen-free
(non acid, non toxic)
RoHS
compliantInsulation Sheath
PE, FPE or PVC PVC
according to
IEC 60332-1
No No Yes
PE, FPE or PVC PE No No Only with (F)PE insulation Yes
PE, FPE or HFFR HFFR
according to
IEC 60332-3-24
according to IEC
61034-1-2
according to
IEC 60754-1 & 2
Yes
Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms
 
 
 
info.btcables@bt.com 10
RS-232: Hand shake interface used for low data rates. Computer to printer or to modem or to another device.
RS-422: Balanced digital circuit. Medium speed data exchange. Long line modems and Daisy chain configuration.
RS-485: Balanced digital circuit. Medium speed fieldbus interfaces.
RS-232 RS-422 RS-485
Differential no yes yes
Max. number of drivers
Max. number of receivers
1
1
1
10
1
32
Modes of operation full duplex half duplex half duplex
Network topology point-to-point multidrop multidrop
Max. distance acc. to standard 15 m 1200 m 1200 m
Max. speed at 12 m.
Max. speed at 1200 m.
20 kbs
1 kbs
10 Mbs
100 kbs
35 Mbs
100 kbs
Cables used
Conductor size mainly 24 AWG mainly 24 AWG mainly 24 AWG
Number of conductors 6 to 25 2 pairs or more 1 pair or more
Impedance not defined 100 Ohm 120 Ohm
BT Cables main part numbers see section 1.3 section 1.2 section 1.1
KNX is a standardised (EN 50090, ISO/IEC 14543), OSI-based network communications protocol for intelligent buildings. KNX is
the successor to, and convergence of, three previous standards: the European Home Systems Protocol (EHS), BatiBUS, and the
European Installation Bus (EIB or Instabus).
BT Cables main part numbers for KNX cables: C1217 (quad – PVC) – C1218 (quad – HFFR) – C1219 (1 pair – PVC) – C1220 (1
pair – HFFR).
LonWorks is a networking platform specifically created to address the needs of control applications. The platform is built on a
protocol created by Echelon Corporation for networking devices over media such as twisted pair, power lines, fibre optics, and
RF. It is used for the automation of various functions within buildings such as lighting and HVAC.
BT Cables main part numbers for LonWorks: C1198 (PVC) - C1203 (PVC) – C1307 (HFFR) – C1271 (HFFR) –
C1346 (HFFR) – C1347 (HFFR) – C1348 (HFFR) and C1349 (HFFR).
Modbus is a serial communications protocol published by Modicon in 1979 for use with its programmable logic controllers
(PLCs). Simple and robust, it has since become one of the de facto standard communications protocols in the industry.
BT Cables main part numbers for Modbus: C1197 (PVC) - C1193 (PVC) – C1282 (HFFR) – C1272 (HFFR).
M-Bus (Meter-Bus) is a European standard (EN 13757-2 physical and link layer, EN 13757-3 application layer) for the remote
reading of gas or electricity meters. M-Bus is also usable for other types of consumption meters.
BT Cables main part number for M-bus: C1020 – C1193.
Controller–area network (CAN or CAN-bus) is a vehicle bus standard designed specifically for automotive applications but now
also used in other areas such as industrial automation and medical equipment.
CAN bus utilize TIA/EIA-485 cables.
BT Cables main part numbers for CAN-bus: C1080 - C1189 – C1190 – C1191 – C1192 – C1295 – C1296 – C1297 and HFFR
cables C1318 – C1319 – C1320 – C1321.
BACnet is a communications protocol for building automation and control networks. It is was designed to allow communication
of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting
control, access control, and fire detection systems and their associated equipment. BACnet over IP can utilize Cat 6.
BT Cables main part numbers for BACnet: C1228 (PVC) – C1189 (PVC) – C1190 (PVC) - C1318 (HFFR)
and C1319 (HFFR).
 
 
 
info.btcables@bt.com 11
Section 1.1
Paired Cables for TIA/EIA-485 = RS-485 applications
22 and 24AWG conductors – PE or FPE insulation – Dual Screen - PVC or HFFR sheath
CABLE DESCRIPTION
1. Conductor
Flexible Tinned Copper
2. Insulation
Polyethylene (PE) or
Foam PE (FPE)
3. Pair
Impedance 120 Ω
4. Tinned Copper Drain Wire
24 AWG(7 x 32)
5. Screen
Aluminium/Polyester
6. Braiding
Tinned Copper wires
7. Sheath Material
Grey PVC or
Purple HFFR
Standard Put Up Length
305 or 500 meters
Standard References
TIA/EIA-485
(BS) EN 50290-2
IEC 60332-1 (PVC sheath) or
IEC 60332-3-24 (3C) (HFFR sheath)
IEC 61034 (HFFR sheath)
IEC 60754-1 & 2 (HFFR sheath)
RoHS directives
Cables with 24 AWG conductors – PE insulation - PVC sheath
BTCL
Part
Number
No of
pairs
Conductor
(AWG)
Max. DC
Resistance
Conductor
(Ω/km)
Coverage
braiding
(%)
Sheath
Overall
Diameter
(mm)
Capacitance
(pF/m)
Weight
(kg/km)
C1189 1 24 (7 x 32) 88 90 PVC 5.9 41 49
C1190 2 24 (7 x 32) 88 90 PVC 8.5 41 80.5
C1191 3 24 (7 x 32) 88 90 PVC 9.0 41 92.6
C1192 4 24 (7 x 32) 88 90 PVC 9.9 41 114.4
C1318 1 24 (7 x 32) 88 90 HFFR 5.9 41 49
C1319 2 24 (7 x 32) 88 90 HFFR 8.5 42 80.5
C1320 3 24 (7 x 32) 88 90 HFFR 9.0 42 92.6
C1321 4 24 (7 x 32) 88 90 HFFR 9.9 42 114.4
Cables with 22 AWG conductors – Foam PE insulation - Halogen-free (HFFR) sheath
BTCL
Part
Number
No of
pairs
Conductor
(AWG)
Max. DC
Resistance
Conductor
(Ω/km)
Coverage
braiding
(%)
Sheath
Overall
Diameter
(mm)
Capacitance
(pF/m)
Weight
(kg/km)
C1080 1 22 (7 x 30) 57.4 65 PVC 6.1 36 63.7
C1295 2 22 (7 x 30) 57.4 65 PVC 9.1 37 75.6
C1296 3 22 (7 x 30) 57.4 65 PVC 10.5 38 97
C1297 4 22 (7 x 30) 57.4 65 PVC 11.4 38 119.1
C1401 1 22 (7 x 30) 57.4 65 HFFR 6.1 36 63.7
C1402 2 22 (7 x 30) 57.4 65 HFFR 9.1 37 75.6
C1403 3 22 (7 x 30) 57.4 65 HFFR 10.5 38 97
C1404 4 22 (7 x 30) 57.4 65 HFFR 11.4 38 119.1
Colour scheme Pair 1 Pair 2 Pair 3 Pair 4
Wire a (insulation colour / colour of stripe) White / blue White / orange White / green White / brown
Wire b (insulation colour / colour of stripe) Blue / white Orange / white Green / white Brown /white
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 12
Section 1.2
Cables with 2 to 6 pairs for RS-422 applications
24AWG conductors – FPE insulation – every pair screened - PVC sheath
CABLE DESCRIPTION
1. Conductor
Flexible Tinned Copper
2. Insulation
Foam Polyethylene (FPE)
3. Pair
Two twisted wires
4. Drain Wire
Flexible Tinned Copper
24 AWG (7 x 32)
5. Screen
Aluminium/Polyester
Wrapped around each
Pair
6. Cable core
2 or more individually
screened pairs stranded
7. Sheath Material
Grey PVC
Standard Put Up Length
305 or 500 metres
Standard References
ANSI/TIA/EIA-422-B
(BS) EN 50290-2
IEC 60332-1
RoHS directives
Cables with 24 AWG conductors – PE insulation – PVC sheath
BTCL Part
Number
No.
of
Pairs
Conductor
and
Drain Wire
(AWG)
Max. DC
Resistance
Conductor
(Ω/km)
Overall
Diameter
(mm)
Capacitance
(pF/m)
Impedance
(Ohm)
Weight
(kg/km)
C1382 2 24 (7 x 32) 88 6.7 41 100 41.8
C1383 3 24 (7 x 32) 88 8.4 41 100 59.4
C1384 4 24 (7 x 32) 88 9.2 41 100 75.5
C1386 6 24 (7 x 32) 88 10.6 41 100 104.8
Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6
C1382 to C1386 Black/Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 13
Section 1.3
Cables with 2 to 8 pairs for RS-232 applications
24AWG conductors – PVC insulation – overall screen – PVC, PE or HFFR sheath
CABLE DESCRIPTION
1. Conductor
Flexible Tinned Copper
24AWG(7x32)
2. Insulation
PVC or HFFR
3. Pair
Two twisted wires
4. Cable core
2 or more pairs stranded
5. Tinned Copper Drain Wire
24 AWG(7 x 32)
6. Screen
Aluminium/Polyester
7. Sheath Material
Grey PVC
Purple HFFR
Black PE
Standard Put Up Length
305 or 500 metres
Standard References
ANSI/TIA/EIA-232-F
(BS) EN 50290-2
IEC 60332-1 (PVC sheath)
IEC 60332-3-24 (3C) (HFFR sheath)
IEC 61034 (HFFR sheath)
RoHS directives
BTCL Part
Number
No. of
Pairs
Insulation Sheath
Conductor
and
Drain Wire
Max. DCR
Conductor
(Ω/km)
Overall
Diameter
Capacitance Weight
C1181 1 PVC PVC 24 (7 x 32) 88 4.0 135 18
C1182 2 PVC PVC 24 (7 x 30) 88 5.6 76 28
C1183 3 PVC PVC 24 (7 x 30) 88 5.9 76 39
C1184 4 PVC PVC 24 (7 x 30) 88 6.7 80 48
C1185 5 PVC PVC 24 (7 x 30) 88 7.3 80 57
C1186 6 PVC PVC 24 (7 x 30) 88 7.4 80 65
C1187 7 PVC PVC 24 (7 x 30) 88 7.5 80 68
C1188 8 PVC PVC 24 (7 x 30) 88 8.3 80 76
BTCL Part
Number
No. of
Pairs
Insulation Sheath
Conductor
and
Drain Wire
Max. DCR
Conductor
(Ω/km)
Overall
Diameter
Capacitance Weight
C1441 1 HFFR HFFR 24 (7 x 32) 88 4.0 95 18
C1442 2 HFFR HFFR 24 (7 x 30) 88 5.6 55 28
C1443 3 HFFR HFFR 24 (7 x 30) 88 5.9 55 39
C1444 4 HFFR HFFR 24 (7 x 30) 88 6.7 60 48
C1445 5 HFFR HFFR 24 (7 x 30) 88 7.3 60 57
C1446 6 HFFR HFFR 24 (7 x 30) 88 7.4 60 65
C1447 7 HFFR HFFR 24 (7 x 30) 88 7.5 60 73
C1448 8 HFFR HFFR 24 (7 x 30) 88 8.3 60 85
C1449 10 HFFR HFFR 24 (7 x 30) 88 9.2 60 95
BTCL Part
Number
No. of
Pairs
Insulation Sheath
Conductor
and
Drain Wire
Max. DCR
Conductor
(Ω/km)
Overall
Diameter
Capacitance Weight
C1451 1 PVC PE 24 (7 x 32) 88 4.0 135 14.5
C1452 2 PVC PE 24 (7 x 30) 88 5.6 76 24.5
C1453 3 PVC PE 24 (7 x 30) 88 5.9 76 31
C1454 4 PVC PE 24 (7 x 30) 88 6.7 80 39
C1455 5 PVC PE 24 (7 x 30) 88 7.3 80 47
C1456 6 PVC PE 24 (7 x 30) 88 7.4 80 55
C1457 7 PVC PE 24 (7 x 30) 88 7.5 80 59
C1458 8 PVC PE 24 (7 x 30) 88 8.3 80 67
Colour scheme of the pairs
Pair number Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6 Pair 7 Pair 8 Pair 10
Wire a Black Black Black Black Black Black Black Red Red
Wire b Red White Green Blue Yellow Brown Orange White Blue
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 14
Section 1.4
Cables for KNX (was EIB or Instabus) applications
0.8 mm conductors – PE insulation – overall screen - PVC or HFFR sheath
CABLE DESCRIPTION
1. Conductor
Solid Bare Copper
0.8 mm = 0.5 mm2
2. Insulation
Polyethylene (PE)
Black-Red-
White-Green
3. Cable Core
Quad or Pair
4. Polyester tape
5. Drain Wire
0.4 mm Tinned Copper
6. Screen
Aluminium/Polyester
7 Sheath Material
Green PVC or
Green HFFR
Standard Put Up Length
305 or 500 metres
Standard References
EN 50090
(BS) EN 50290-2
IEC 60332-1 (PVC sheath)
or IEC 60332-3-24 (3C) (HFFR sheath)
IEC 61034 (HFFR sheath)
IEC 60754-1 & 2 (HFFR sheath)
RoHS directives
BTCL Part
Number
No. of
wires
Lay-Up
Sheath
Material
Diameter
Insulation
(mm)
Overall
Diameter
(mm)
Max. DC
Resistance
Conductor
(Ω/km)
Capacitance
(pF/m)
Weight
(kg/km)
C1217 1 x 4 quad PVC 1.45 6.1 37 ≤ 100 51
C1218 1 x 4 quad HFFR 1.45 6.1 37 ≤ 100 53
C1219 1 x 2 pair PVC 1.45 5.5 37 ≤ 100 37
C1220 1 x 2 pair HFFR 1.45 5.5 37 ≤ 100 39
BTCL Part
Number
Wire a Wire b Wire c Wire d
C1217 Black White Red Green
C1218 Black White Red Green
C1219 Black White
C1220 Black White
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 15
Section 1.5
Cables for LonWorks applications
0.64 mm conductors – PE or FPE insulation
Individually screened pairs or unscreened pairs - HFFR sheath
CABLE DESCRIPTION
1. Conductor
Solid Bare Copper
0.64 mm = 0.32 mm²
2. Insulation
Polyethylene (PE) or
Foam Polyethylene (FPE)
3. Pairs with no screen
two twisted wires
4. Individually screened
pair
two twisted wires
plus drain wire
wrapped with an
Aluminium/Polyester
foil
5. Cable core
one pair or two
pairs stranded
6 Sheath Material
Purple HFFR
Standard Put Up Length
305 or 500 metres
Standard References
EN 50090
(BS) EN 50290-2
IEC 60332-3C
IEC 61034
IEC 60754-1 & 2
RoHS directives
BTCL Part
Number
No.
of
pairs
Insulation
Material
Indiv.
screened
pairs
Overall
Diameter
(mm)
Max. DC
Resistance
Conductor
(Ω/km)
Capacitance
(pF/m)
Weight
(kg/km)
C1346 1 Solid PE No 3.5 61 46 17.1
C1347 2 Solid PE No 5.2 61 46 27.7
C1348 1 Foam PE Yes 4.6 61 46 24.2
C1349 2 Foam PE Yes 7.6 61 46 56.1
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 16
Section 1.6
Cables for General Interface applications
2 to 6 pairs – 22AWG conductors – PE or HFFR insulation
Individually screened pairs – PVC or HFFR sheath
CABLE DESCRIPTION
1. Conductor
Flexible Tinned Copper
22AWG(7 x 30)
2. Insulation
Polyethylene (PE) or
Halogen-free (HFFR)
3. Pair
Two twisted wires
4. Tinned Copper Drain Wire
24 AWG(7 x 32)
5. Screen
Aluminium/Polyester foil
wrapped around each
pair
6. Cable core
2 or more individually
screened pairs stranded
7. Sheath Material
Grey PVC or
Purple HFFR
Standard Put Up Length
305 or 500 metres
Standard References
(BS) EN 50290-2
IEC 60332-1 (PVC sheath)
IEC 60332-3-24 (3C) (HFFR sheath)
IEC 61034 (HFFR sheath)
IEC 60754-1 & 2 (HFFR sheath)
RoHS directives
BTCL Part
Number
No.
of
pairs
Insulation
Material
Sheath
Material
Overall
Diameter
(mm)
Max. DC
Resistance
Conductor
(Ω/km)
Capacitance
(pF/m)
Weight
(kg/km)
C1196 2 PE PVC 6.0 57.4 90 36.1
C1281 2 HFFR HFFR 6.5 57.4 150 50.8
C1197 3 PE PVC 6.5 57.4 98 49.1
C1282 3 HFFR HFFR 7.5 57.4 155 67.4
C1298 4 PE PVC 7.0 57.4 98 62
C1299 5 PE PVC 7.7 57.4 99 74.2
C1214 6 PE PVC 8.9 57.4 99 87.2
C1314 6 HFFR HFFR 9.5 57.4 155 115.6
Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6
C1196 and C1281 Black/ Red Green/White
C1197 and C1282 Black/ Red Black/White Black/Green
C1298 Black/ Red Black/White Black/Green Black/Blue
C1299 Black/ Red Black/White Black/Green Black/Blue Black/Yellow
C1214 and C1314 Black/ Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 17
Section 1.7
Cables for General Interface applications
One pair – 22 to 12AWG conductors – PE insulation
Collective (overall) screen – PVC or HFFR sheath
CABLE DESCRIPTION
1. Conductor
Flexible Tinned Copper
2. Insulation
PVC or
Polyethylene (PE) or
Halogen-free (HFFR)
3. Pair
Two wires twisted
4. T.C. Drain Wire
(only with screen)
24 AWG(7 x 32)
5. Screen (if applicable)
Aluminium/Polyester
6. Sheath Material
Grey PVC or
Purple HFFR
Standard Put Up Length
305 or 500 metres
Standard References
(BS) EN 50290-2
IEC 60332-1 (PVC sheath)
IEC 60332-3-24 (3C) (HFFR sheath)
IEC 61034 (HFFR sheath)
IEC 60754-1 & 2 (HFFR sheath)
RoHS directives
DC Resistance 12 to 22 AWG conductors
Conductor AWG 22 20 18 16 14 12
No. of strands x gauge AWG 7 x 30 7 x 28 7 x 26 19 x 29 19 x 27 19 x 25
No. of strands x mm Mm 7 x 0.25 7 x 0.32 7 x 0.40 19 x 0.28 19 x 0.36 19 x 0.45
Max. DC resistance conductor Ω/km 57.4 35.75 22.7 15.47 9.36 5.61
One pair cables with PE insulation and PVC sheath
Screened Unscreened
BTCL Part
Number
Cond.
(AWG)
Overall
Diameter
(mm)
Capacity
(pF/m)
Weight
(kg/km)
BTCL Part
Number
Cond.
(AWG)
Overall
Diameter
(mm)
Capacity
(pF/m)
Weight
(kg/km)
C1199 22 4.4 75 25 C1301 22 4.0 70 19.5
C1195 20 5.0 75 36.4 C1300 20 4.3 80 23
C1193 18 5.6 75 43.2 C1203 18 5.1 85 38.6
C1213 16 7.9 60 75.7 C1198 16 6.9 90 63.3
C1224 14 9.0 76 104.9 C1222 14 8.6 108 91.8
C1313 12 10.2 77 124.7 C1302 12 9.8 115 115
One pair cables with HFFR insulation and HFFR sheath
Screened Unscreened
BTCL Part
Number
Cond.
(AWG)
Overall
Diameter
(mm)
Capacity
(pF/m)
Weight
(kg/km)
BTCL Part
Number
Cond.
(AWG)
Overall
Diameter
(mm)
Capacity
(pF/m)
Weight
(kg/km)
C1310 22 4.8 140 27.1 C1311 22 4.7 48 24.7
C1308 20 5.3 158 37.2 C1309 20 5,2 52 34.7
C1272 18 6.0 165 48.4 C1271 18 5.9 65 45.9
C1270 16 7.8 150 74.3 C1307 16 7.7 48 71.8
C1305 14 8.8 180 97.9 C1306 14 8.7 55 95.3
C1303 12 9.8 195 132.6 C1304 12 9.7 57 128.2
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 18
Section 1.8
Cables for Security & Alarm applications
1 to 6 pairs – 18AWG conductors – polyolefin insulation
foil or foil + braid overall screen –HFFR sheath
CABLE DESCRIPTION
Design
1. Conductor
Flexible Bare Copper
2. Insulation
Polyolefin
3. Pair
Two twisted wires
4. Cable core
N pairs stranded
5. Drain Wire
Flexible Tinned Copper
24 AWG (7 x 32)
6. Overall Screen 1
Aluminium/Polyester foil
7. Overall Screen 2
braid
coverage
8. Sheath Material
Purple Halogen-free (HFFR)
Standard Put Up Length
305 or 500 metres
Standard References
(BS) EN 50290-2
IEC 60332-3-24
IEC 61034
IEC 60754-1 & 2
RoHS directives
Cables with 18AWG conductors – Polyolefin insulation – Collective Screen and HFFR sheath
BTCL Part
Number
No.
of
Pairs
Conductor
(AWG)
Screen
Max. DC
Resistance
Conductor
(Ω/km)
Overall
Diameter
(mm)
Capacitance
(pF/m)
Weight
(kg/km)
C1171 1 18 (7 x 26) foil 22.7 5.1 115 4.1
C1172 2 18 (7 x 26) foil 22.7 7.7 115 7.41
C1173 3 18 (7 x 26) foil 22.7 8.1 115 9.64
C1174 4 18 (7 x 26) foil 22.7 8.9 115 12.37
C1175 5 18 (7 x 26) foil 22.7 9.9 115 14.92
C1176 6 18 (7 x 26) foil 22.7 10.2 115 17.11
BTCL Part
Number
No.
of
Pairs
Conductor
(AWG)
Screen
Max. DC
Resistance
Conductor
(Ω/km)
Overall
Diameter
(mm)
Capacitance
(pF/m)
Weight
(kg/km)
C1418 1 18 (7 x 26) foil + braid 22.7 5.8 115 4.7
C1419 2 18 (7 x 26) foil + braid 22.7 8.4 115 10.5
C1420 3 18 (7 x 26) foil + braid 22.7 8.8 115 11.6
C1421 4 18 (7 x 26) foil + braid 22.7 9.6 115 13.7
C1422 5 18 (7 x 26) foil + braid 22.7 10.5 115 16.5
C1423 6 18 (7 x 26) foil + braid 22.7 10.9 115 18.6
Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6
C1171 to C1176 Black/Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 19
Section 1.9
Cable for Building Management Systems
1 pair – 0.6 mm² conductors – polyolefin insulation
Collective overall screen –PVC sheath
CABLE DESCRIPTION
1. Conductor
Flexible Bare Copper
7 x 0.35 mm = 0.6 mm²
2. Insulation
Polyolefin
Core 1: Black
Core 2: Red
3. Pairs
two twisted wires
4. Tinned Copper Drain Wirer
7 x 0.20 mm
5. Screen
Aluminium/Polyester
foil
6 Sheath Material
Grey PVC
Standard Put Up Length
305 or 500 metres
Standard References
(BS) EN 50290-2
IEC 60332-1
RoHS directives
BTCL Part
Number
No. of
pairs
Overall
Diameter
(mm)
Max. DC Resistance
Conductor
(Ω/km)
Capacitance
(pF/m)
Weight
(kg/km)
C1381 1 3.9 61 110 14.6
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 20
Section 2 - BT BMS-TECTM
- Multi-Conductor Cables
Application and Construction
1. Application
All PVC and HFFR sheathed multi-conductor cables are suitable for Building Management Systems (BMS), Sound, Audio,
Security, Safety, Control and Instrumentation.
2. Basic Construction of the cables
Wire = Conductor without or with insulation. With insulation sometimes also indicated as core.
Conductor: flexible = twisted bare or tinned copper strands, ranging from 12 to 22AWG.
Conductor
(AWG)
configuration
(AWG)
configuration
(mm)
DC Resistance
(Ohm/km)
24 7 x 32 7 x 0.2 ≤ 88
22 7 x 30 7 x 0.25 ≤ 57.4
20 7 x 28 7 x 0.32 ≤ 32.16
18 7 x 26 7 x 0.40 ≤ 22.7
16 19 x 29 19 x 0.28 ≤ 15.47
14 19 x 27 19 x 0.36 ≤ 9.36
12 19 x 25 19 x 0.45 ≤ 5.61
Insulation: Polypropylene (PP) for PVC (Polyvinyl Chloride) sheathed cables and Halogen-Free (HFFR) for HFFR sheathed cables.
Both insulations are in accordance with BS EN 50290-2. Good strippable and coloured insulation. The colours are not
interchangeable.
Colour scheme of wires with 12 or 14 AWG conductors: black-white-red-green-brown-blue-orange-yellow-purlpe-grey-pink-
tan.
Colour scheme of wires with ≥ 16AWG conductors: black-red-white-green-brown-blue-orange-yellow-purlpe-grey-pink-tan.
Cable core: two or more wires, twisted.
Good twisting (lay-length < 30 – 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends.
Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that
drain wires are tinned.
Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically
applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend.
Sheath: grey PVC or purple HFFR or black UV-resistant HFFR, all in accordance with BS EN 50290-2.
Cable configurations Cables with PVC sheath Halogen-Free cables
Insulation PP acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2
Sheath PVC acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2
Retardancy Flame Retardant Fire Retardant
Retardant acc. to IEC 60332-1 / UL1581 IEC 60332-3-24 / UL 1685
Low Smoke emission acc. to Not applicable IEC 61034
Halogen-free acc. to Not applicable IEC 60754
RoHS compliant Yes yes
Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms.
Non-standard cable constructions, colours, details and/or additional information are available on request.
For more details, please see the respective detailed datasheet(s).
Please note that technical specifications are subject to change without notice.
 
 
 
info.btcables@bt.com 21
Section 2.1 – Multi-Conductor Cables
PVC sheathed cables with 12AWG to 22AWG conductors for
Audio, Control, Instrumentation and Building Management Systems (BMS)
CABLE DESCRPTION
Design
1. Conductor
Stranded
Bare Copper
2. Insulation
Polypropylene (PP)
3 Cable Core
Two or more wires
stranded
4 Drain Wire (only with screen)
24 AWG (7 x 32)
Tinned Copper
5 Screen (if applicable)
Aluminium/Polyester
> 100% Coverage
6. Sheath Material
Grey PVC
Standard Put Up Length
305 and 500 metres
Standard References
(BS) EN 50290-2
IEC 60332-1
RoHS directives
No of
wires
Cond.
(AWG)
BT Cables
Part
Number
Scrn
Diam.
(mm)
Weight
(kg/km)
BT Cables
Part
Number
Scrn
Diam.
(mm)
Weight
(kg/km)
2 22 C1226 Yes 3.3 16.5 C1227 No 3.3 14.6
3 22 C1228 Yes 3.5 21.4 C1278 No 3.5 19.7
4 22 C1230 Yes 3.8 26 C1231 No 3.8 23.9
6 22 C1264 Yes 4.5 35.7 C1265 No 4.5 33.6
8 22 C1232 Yes 4.9 45.1 C1233 No 4.9 43
2 20 C1019 Yes 3.5 22 C1020 No 3.4 19.7
3 20 C1021 Yes 3.7 28.5 C1022 No 3.6 26.2
4 20 C1023 Yes 4.1 35.4 C1024 No 4.0 33.1
6 20 C1260 Yes 5.0 49.9 C1261 No 4.9 47.9
8 20 C1262 Yes 5.4 62.9 C1263 No 5.3 60.6
2 18 C1013 Yes 4.0 29.6 C1014 No 3.9 27.3
3 18 C1015 Yes 4.2 39.2 C1016 No 4.1 36.9
4 18 C1017 Yes 4.6 49.4 C1018 No 4.55 47.2
6 18 C1211 Yes 5.75 70.9 C1212 No 5.7 68.2
8 18 C1258 Yes 6.0 89.5 C1259 No 5.9 87
2 16 C1007 Yes 4.6 37.3 C1008 No 4.5 35
3 16 C1009 Yes 4.9 50 C1010 No 4.75 47.7
4 16 C1011 Yes 5.3 63.5 C1012 No 5.25 61.1
6 16 C1252 Yes 6.8 91.6 C1253 No 6.7 89
8 16 C1254 Yes 7.6 120.8 C1255 No 7.5 118.1
2 14 C1001 Yes 6.0 57 C1002 No 5.75 53.3
3 14 C1003 Yes 6.5 77.9 C1004 No 6.35 72.5
4 14 C1005 Yes 6.9 102.5 C1006 No 6.75 97.1
6 14 C1248 Yes 8.6 151 C1249 No 8.4 148.2
8 14 C1250 Yes 9.8 197.3 C1251 No 9.7 194.5
2 12 C1322 Yes 6.9 85.7 C1323 No 6.7 79.8
3 12 C1324 Yes 7.4 118.1 C1325 No 7.2 112.1
4 12 C1326 Yes 8.2 151.1 C1327 No 8.0 145.3
6 12 C1330 Yes 9.8 215.5 C1331 No 9.6 209.7
8 12 C1332 Yes 10.7 279.5 C1333 No 10.5 273.7
Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s
 
 
 
info.btcables@bt.com 22
Section 2.2 – Multi-Conductor Cables
Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for
Audio, Control, Instrumentation and Building Management Systems (BMS)
CABLE DESCRIPTION
Design
1. Conductor
Stranded
Bare Copper
2. Insulation
HFFR
3. Drain Wire
(only with screen)
24 AWG (7 x 32)
Tinned Copper
4. Screen (if applicable)
Aluminium/Polyester
> 100% Coverage
5. Ripcord
6. Sheath Material
Purple Halogen-Free
(HFFR)
Standard Put Up Length
305 metres
Standard References
(BS) EN 50290-2
IEC 60332-3C
IEC 61034
IEC 60754-1 & 2
RoHS directives
No of
wires
Cond.
(AWG)
BT Cables
Part
Number
Scrn
Diam.
(mm)
Weight
(kg/km)
BT Cables
Part
Number
Scrn
Diam.
(mm)
Weight
(kg/km)
2 22 C1741 Yes 3.9 22.4 C1742 No 3.9 20.5
3 22 C1743 Yes 4.1 27.6 C1744 No 4.1 26.0
4 22 C1745 Yes 4.4 33.7 C1746 No 4.4 31.7
6 22 C1747 Yes 5.2 45.8 C1748 No 5.2 43.9
8 22 C1749 Yes 5.6 56.4 C1750 No 5.6 54.4
2 20 C1731 Yes 4.7 32.6 C1732 No 4.6 30.1
3 20 C1733 Yes 4.9 40.2 C1734 No 4.8 37.7
4 20 C1735 Yes 5.3 48.7 C1736 No 5.2 46.2
6 20 C1737 Yes 6.2 66.2 C1738 No 6.1 63.7
8 20 C1739 Yes 6.7 81.9 C1740 No 6.6 79.4
2 18 C1721 Yes 5.1 41.0 C1722 No 5.0 38.5
3 18 C1723 Yes 5.4 52.3 C1724 No 5.3 49.8
4 18 C1725 Yes 5.8 64.1 C1726 No 5.7 61.6
6 18 C1727 Yes 6.8 88.6 C1728 No 6.7 86.1
8 18 C1729 Yes 7.3 110.8 C1730 No 7.2 108.2
2 16 C1711 Yes 5.4 49.3 C1712 No 5.4 46.8
3 16 C1713 Yes 5.7 63.8 C1714 No 5.7 61.3
4 16 C1715 Yes 6.2 79.3 C1716 No 6.2 78.2
6 16 C1717 Yes 7.3 108.2 C1718 No 7.3 107.0
8 16 C1719 Yes 7.9 137.0 C1720 No 7.9 135.9
2 14 C1701 Yes 6.5 67.7 C1702 No 6.4 65.2
3 14 C1703 Yes 6.9 92.8 C1704 No 6.8 89.1
4 14 C1705 Yes 7.5 115.4 C1706 No 7.4 112.9
6 14 C1707 Yes 8.9 163.7 C1708 No 8.8 162.8
8 14 C1709 Yes 9.6 210.8 C1710 No 9.5 208.3
2 12 C1334 Yes 7.7 102.2 C1335 No 7.5 97.0
3 12 C1336 Yes 8.1 135.0 C1337 No 7.9 129.7
4 12 C1338 Yes 8.9 170.9 C1339 No 8.7 165.7
6 12 C1342 Yes 10.6 243.3 C1343 No 10.4 237.1
8 12 C1344 Yes 11.6 314.6 C1345 No 11.4 306.2
Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s
 
 
 
info.btcables@bt.com 23
Section 2.3 – Multi-Conductor Cables
UV-Resistant Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors
for Audio, Control, Instrumentation and Building Management Systems (BMS)
CABLE DESCRIPTION
Design
1. Conductor
Stranded
Bare Copper
2. Insulation
HFFR
3. Drain Wire
(only with screen)
24 AWG (7 x 32)
Tinned Copper
4. Screen (if applicable)
Aluminium/Polyester
> 100% Coverage
5. Ripcord
6. Sheath Material
Black UV-resistant
Halogen-Free (HFFR)
Standard Put Up Length
305 metres
Standard References
(BS) EN 50290-2
IEC 60332-3C
IEC 61034
IEC 60754-1 & 2
RoHS directives
No of
wires
Cond.
(AWG)
BT Cables
Part
Number
Screen
Diameter
(mm)
Weight
(kg/km)
2 18 C1351 Yes 5.1 41.0
3 18 C1352 Yes 5.4 52.3
4 18 C1353 Yes 5.8 64.1
6 18 C1354 Yes 6.8 88.6
8 18 C1355 Yes 7.3 110.8
10 18 C1356 Yes 8.4 135.7
20 18 C1357 Yes 10.7 249.6
No of
wires
Cond.
(AWG)
BT Cables
Part
Number
Screen
Diameter
(mm)
Weight
(kg/km)
2 16 C1391 Yes 5.5 49.3
3 16 C1392 Yes 5.8 63.8
4 16 C1393 Yes 6.3 79.3
6 16 C1394 Yes 7.4 108.2
8 16 C1395 Yes 8.0 137.0
10 16 C1396 Yes 9.5 173.1
20 16 C1397 Yes 12.1 316.6
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 24
Section 3 - BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables
Bare Copper 12 to 18AWG, one pair, PVC insulation and Sheath,
Screened and Unscreened
©UL Certification: type FPLR rated 105°C - ©UL listed
APPLICATION
Fire Detection and Alarm Systems
Fire Retardancy: UL 1666
Operating temperature range: -40 to +105 °C and Rated Voltage: 300 Vrms
CABLE DESCRIPTION
1. Conductor
Solid Bare Copper
2. Insulation
PVC acc. to UL444
Black and Red
3. Pair
Two wires twisted
4. TC Drain Wire
(only under screen)
22 AWG (7 x 30)
5. Screen (if applicable)
Aluminium/Polyester
> 100% Coverage
6. Sheath Material
Red PVC
acc. to UL444
Standard Put Up Length
305 metres
Standard References
UL1424
UL444
UL1666
RoHS directives
BT Cables
Part
Number
No.
of
Pairs
Conductor
(
AWG)
Screen
Overall
Diameter
(mm)
Max. DC
Resistance
Conductor
(Ω/km)
Capacitance
(pF/m)
Weight
(kg/km)
C1040 1 18 Yes 5.9 22.7 160 19.2
C1135 1 18 No 5.8 22.7 60 16.0
C1041 1 16 Yes 6.1 15.47 189 28.5
C1136 1 16 No 6.0 15.47 71 25.0
C1042 1 14 Yes 7.8 9.36 160 43.0
C1137 1 14 No 7.7 9.36 69 40.0
C1043 1 12 Yes 8.7 5.61 216 66.0
C1138 1 12 No 8.6 5.61 65 63.0
Non-standard cable constructions, colours, details and/or additional information are available on request.
For more details, please see the respective detailed datasheet(s).
Please note that technical specifications are subject to change without notice.
POWER-LIMITED
CIRCUIT CABLE
NO. 000001
1000 FEET F ORM 3
 
 
 
info.btcables@bt.com 25
Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables
Bare and Flexible Copper Conductors 0.75 to 4.0 mm2
,
Silicon insulation and Halogen-free Sheath, Screened and Unscreened
1. Application
All Fire Resistant cables are suitable for Security, Safety, Control and Instrumentation with special requirements for circuit
integrity in case of a fire.
2. Fire Resistance confirming with BS6387 CWZ:
Fire Resistant to BS 6387, Cat. C: exposed to fire at 950°C for 3 hours
Fire Resistant to BS 6387, Cat. W: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with water for 15
minutes
Fire Resistant to BS 6387, Cat. Z: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with mechanical shock
for 15 minutes
3. Fire Retardancy confirming with IEC 60332-3-24 (was 3C)
4. Basic Construction of the cables
Wire = Conductor with Insulation
Conductor: solid bare copper wires, ranging from 0.75 to 2.5 mm² and the 4.0 mm² conductor consists of stranded bare copper
wires = flexible
Cross Section
(mm²)
Diameter
(mm)
DC Resistance
(Ohm/km)
Recommended
Current
(Amp)
0.75 1 x 1.0 ≤ 24.5 ≤ 12
1.0 1 x 1.13 ≤ 18.1 ≤ 18
1.5 1 x 1.4 ≤ 12.1 ≤ 21
2.5 1 x 1.8 ≤ 7.41 ≤ 30
4.0 7 x 0.85 = 2.55 ≤ 4.61 ≤ 40
Insulation: Silicon Rubber blends acc. to BS 7655. Good strippable and coloured insulation. The colours are not interchangeable.
Colour scheme:
2 cores: brown – blue,
3 cores: brown – black – grey,
4 and more cores: brown – blue – black – grey – others black numbered.
Cable core: two or more cores, twisted.
Good twisting is necessary otherwise the cable can hardly be bending and will break after a few bends.
Drain wire (only in combination with a screen): solid bare copper.
Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically
applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend.
Sheath: red HFFR in accordance with BS EN 50290-2
Operating temperature range: -20 to +90 °C.
Rated Voltage: 300/500 Vrms
Non-standard cable constructions, colours, details and/or additional information are available on request.
For more details, please see the respective detailed datasheet(s).
Please note that technical specifications are subject to change without notice.
 
 
 
info.btcables@bt.com 26
Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables
CABLE DESCRIPTION
1. Conductor
Solid or Flexible
Bare Copper
2. Insulation
Silicon Rubber blend
3. Cable core
Two or three wires
Twisted
4. BC Drain Wire
(only under screen)
5. Screen (if applicable)
Aluminium/Polyester
> 100% Coverage
6. Sheath Material
Red HFFR
Standard Put Up Length
305 and 500 metres
Standard References
BS 6387 CWZ
BS 7655
IEC 60332-3C
IEC 60754-1 & 2
RoHS directives
BT Cables
Part
Number
No. of
wires
Conductor
(mm²)
Screen
Drain Wire
(mm²)
Overall
Diameter
(mm)
Max. DC
Resistance
Conductor
(Ω/km)
Weight
(kg/km)
C1284 2 0.75 Yes 0.75 7.5 24.5 67.0
C1139 2 0.75 No 7.4 24.5 61.7
C1159 3 0.75 Yes 0.75 7.9 24.5 83
C1149 3 0.75 No 7.8 24.5 75
C1283 2 1.0 Yes 1.0 7.8 18.1 73.4
C1140 2 1.0 No 7.7 18.1 65.5
C1160 3 1.0 Yes 1.0 8.1 18.1 93
C1150 3 1.0 No 8.0 18.1 83
C1044 2 1.5 Yes 1.5 8.7 12.1 98.1
C1141 2 1.5 No 8.6 12.1 87.6
C1161 3 1.5 Yes 1.5 8.95 12.1 123
C1151 3 1.5 No 8.85 12.1 108
C1045 2 2.5 Yes 2.5 9.9 7.41 134.3
C1142 2 2.5 No 9.8 7.41 119.4
C1162 3 2.5 Yes 2.5 10.3 7.41 174
C1152 3 2.5 No 10.2 7.41 151
C1289 2 4.0 Yes 4.0 12.0 4.61 197.1
C1143 2 4.0 No 11.9 4.61 172.6
C1163 3 4.0 Yes 4.0 12.95 4.61 270
C1153 3 4.0 No 12.85 4.61 234
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 27
Section 5 - BT Security-Tec ™– Coaxial Cables
Application and Construction of Coax Cables for 75 Ohm Video Systems
Applications.
CCTV: Closed Circuit Television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors
SMATV: Satellite Master Antenna Television used to deliver signals to multiple dwelling units (e.g., apartment buildings and
trailer parks).
CATV: Central Antenna Television = Cable television is a system of providing television to consumers via radio frequency signals
transmitted to televisions. Nowadays also used for internet and telephone.
HDTV: High-definition television refers to video having resolution substantially higher than traditional television systems.
Telecom and networking: a number of special cable constructions.
Basic Cable Design.
Coaxial cables are designed to carry radio frequency current of a much higher frequency than the 50 or 60 Hz used in
low voltage cables. And this requires special construction to prevent power losses. If an ordinary wire is used to carry
high frequency currents, the wire acts as an antenna, and the high frequency currents radiate off the wire as radio
waves, causing power losses. To prevent this, in coaxial cable one of the conductors is formed into a tube and encloses
the other conductor. This confines the radio waves from the central conductor to the space inside the tube. To prevent
the outer conductor, or shield, from radiating, it is connected to electrical ground, keeping it at a constant potential.
The dimensions and spacing of the conductors must be uniform throughout the length of the cable. Any abrupt change
in the spacing of the two conductors along the cable tends to reflect radio frequency power back toward the source.
This acts as a bottleneck, reducing the amount of power reaching the destination end of the cable.
Choosing the correct 75 ohm coax cable.
Most coaxial cables for video applications have a nominal impedance of 75 ohms. Their differing electrical and physical
characteristics make it important to select the correct type of cable to suit the application.
Analogue TV
RG59 Acceptable performance on cable runs < 225 metres
RG6
Gives superior performance on cable runs < 225 metres.
Used for cable runs > 225 metres but < 545 metres.
RG11 For cable runs greater than 545 metres.
CCTV
RG59 Acceptable performance on cable runs < 225 metres
RG6
Gives for superior performance on cable runs < 225 metres.
Used for cable runs > 225 metres but < 545 metres.
RG11 For cable runs greater than 545 metres.
This table is for reference only.
BT Cables survey of Part Numbers.
Application Tested Speciality RG-59 RG-6 RG-11
CCTV – PVC sheath 1000 MHz Solid conductor C1028 C1029 C1030
CCTV – HFFR sheath 1000 MHz Solid conductor C1428 C1429 C1430
CCTV 1000 MHz Flexible conductor C1275 C1276 C1277
CATV / SMATV 3000 MHz Dual screen C1025 C1026 C1027
CATV / SMATV 3000 MHz Quad screen C1256 C1257 C1241
HDTV – PVC sheath 4500 MHz Dual Screen 95% C1229 C1279 C1280
HDTV – HFFR sheath 4500 MHz Dual Screen 95% C1378 C1379 C1380
Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms
 
 
 
info.btcables@bt.com 28
Section 5.1 – BT Security-Tec ™– 75 ohm coax cables
CCTV and Video Applications, sweep tested 1to 1000 MHz
CABLE DESCRIPTION
1. Conductor
Solid or Flexible Bare Copper
2. Dielectric
Foamed Polyethylene (FPE)
3. Braid
Bare Copper
4. Sheath Material
Polyvinyl Chloride (PVC) or
Halogen-Free (HFFR)
Standard Put Up Length
305 or 500 metres
Standard References
IEC 61196
(BS) EN 50117
(BS) EN 50290-2
IEC 60332-1 (PVC sheath) or
IEC 60332-3-24 (HFFR cable)
IEC 61034 (only HFFR cable)
IEC 60754-1 & 2 (HFFR cable)
RoHS directives
Physical Characteristics
BT Cables
Part
Number
RG-Type
Conductor
(mm)
Diameter
Dielectric
(mm)
Coverage
braid
(%)
Sheath
Material
Overall
Diameter
(mm)
Weight
(kg/km)
C1028 RG-59 0.81 solid 3.71 95 PVC 6.0 47.12
C1428 RG-59 0.81 solid 3.71 95 HFFR 6.0 48.5
C1275 RG-59 19x0.18TC 3.71 95 PVC 6.0 47.12
C1029 RG-6 1.02 solid 4.60 95 PVC 6.8 55.5
C1429 RG-6 1.02 solid 4.60 95 HFFR 6.8 58.2
C1276 RG-6 19x0.22 4.60 95 PVC 6.8 54.66
C1030 RG-11 1.63 solid 7.11 90 PVC 10.0 115.9
C1480 RG-11 1.63 solid 7.11 90 HFFR 10.0 120
C1277 RG-11 19x0.34 7.11 90 PVC 10.0 115.9
Electrical and Physical Characteristics (at 20°C)
BT Cables
Part
Number
RG-Type
Impedance
(Ω)
Max. DC
Resistance
Conductor
(Ω/km)
Max. DC
Resistance
screen
(Ω/km)
Nominal
Capacitance
(pF/m)
Min.
Return Loss
1 to 1000 MHZ
(dB)
C1028 RG-59 75 ± 3 33.5 10.1 53.5 20
C1428 RG-59 75 ± 3 33.5 10.1 53.5 20
C1275 RG-59 75 ± 3 40 10.1 53.5 20
C1029 RG-6 75 ± 3 21.5 10.8 53.5 20
C1429 RG-6 75 ± 3 21.5 10.8 53.5 20
C1276 RG-6 75 ± 3 30 10.8 53.5 20
C1030 RG-11 75 ± 3 8.8 6.5 52.8 20
C1480 RG-11 75 ± 3 8.8 6.5 52.8 20
C1277 RG-11 75 ± 3 8.8 6.5 52.8 20
Nominal Attenuation in dB/100m
MHz 5 10 50 100 200 300 400 450 550 700 750 870 1000
RG-59 1.9 2.95 6.23 8.53 11.81 15.3 16.41 18.92 21.03 22.97 24.8 26.84 27.89
RG-6 1.78 2.36 4.92 6.56 9.51 12.43 13.78 15.14 17.15 18.37 19.73 20.26 21.96
RG-11 0.99 1.51 2.96 4.27 6.23 8.27 9.51 10.31 11.51 13.45 13.95 14.87 17.06
For more details, please see the respective detailed datasheet(s).
 
 
 
info.btcables@bt.com 29
Section 5.2 – BT Security-Tec ™– 75 ohm coax cables
SMATV - CATV and Video applications, sweep tested1to 3000 MHz
CABLE DESCRIPTION
1. Conductor
Solid Copper Covered Steel
(CCS)
2. Dielectric
Foamed Polyethylene (FPE)
3. Screen 1
Bonded Aluminium/
Polyester foil
100% coverage
4. Braid 1
Aluminium
5. Braid 2 (Quad scrn only)
Aluminium/Polyester foil
100% coverage
6. Screen 2 (Quad scrn only)
Aluminium
7. Sheath
Polyvinyl Chloride (PVC)
Standard Put Up Length
305 or 500 metres
Standard References
IEC 61196
(BS) EN 50117
(BS) EN 50290-2
IEC 60332-1
RoHS directives
Physical Characteristics
BT Cables
Part
Number
RG-Type
Conductor
(mm)
Diameter
Dielectric
(mm)
Type
of
Screen
Coverage
braid
(%)
Sheath
Material
Overall
Diameter
(mm)
Weight
(kg/km)
C1025 RG-59-3 GHz 0.81 3.71 Dual scrn 54 PVC 6.0 32.42
C1256 RG-59-3 GHz 0.81 3.71 Quad scrn 54 + 46 PVC 6.73 39.4
C1026 RG-6-3 GHz 1.02 4.60 Dual scrn 60 PVC 6.8 41.32
C1257 RG-6-3 GHz 1.02 4.60 Quad scrn 60 + 40 PVC 7.52 49.5
C1027 RG-11-3 GHz 1.63 7.11 Dual scrn 61 PVC 10.0 86.6
C1241 RG-11-3 GHz 1.63 7.11 Quad scrn 60 +40 PVC 10.3 90.6
Dual Screen = Screen 1 + Braid 1
Quad Screen = Screen 1 + Braid 1 + Screen 2 + Braid 2
Electrical and Physical Characteristics (at 20°C)
BT Cables
Part
Number
RG-Type Imped.
(Ω)
Max. DC
Resistance
Conductor
(Ω/km)
Max. DC
Resistance
Screen
(Ω/km)
Nominal
Capacitance
(pF/m)
Min. Return Loss
(dB)
< 1000
MHz
< 2000
MHz
< 3000
MHz
C1025 RG-59-3 GHz 75 ± 3 146.5 52 53 20 18 16
C1256 RG-59-3 GHz 75 ± 3 146.5 26 53 20 20 20
C1026 RG-6-3 GHz 75 ± 3 92.2 30 53 20 20 20
C1257 RG-6-3 GHz 75 ± 3 92.2 17 53 20 20 20
C1027 RG-11-3 GHz 75 ± 3 36.5 25 53 20 20 20
C1241 RG-11-3 GHz 75 ± 3 36.5 12 53 20 20 20
Nominal Attenuation in dB/100m
MHz 5 10 50 100 200 400 550 870 1250 1750 2150 2500 3000
RG-59 2.92 3.45 5.40 8.21 12.56 16.01 19.36 24.74 30.62 36.71 40.82 44.72 48.64
RG-6 2.2 2.48 5.15 6.6 9.56 13.12 15.45 19.69 24.25 29.26 32.88 35.88 39.83
RG-11 1.25 2.03 3.75 5.01 6.85 7.05 9.65 12.6 16.66 20.28 22.93 25.12 28.08
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 30
Section 5.3 – BT Security-Tec ™– 75 ohm coax cables
HDTV and HD Video applications, sweep tested1to 4500 MHz
CABLE DESCRIPTION
1. Conductor
Solid Bare Copper
2. Dielectric
Foamed Polyethylene
3. Screen
Bonded Aluminium/
Polyester foil
100% coverage
4. Braid
Tinned Copper
5. Sheath Material
Polyvinyl Chloride (PVC) or
Halogen-free (HFFR)
Colour: Orange
Standard Put Up Length
305 or 500 metres
Standard References
IEC 61196
(BS) EN 50117
(BS) EN 50290-2
IEC 60332-1(PVC sheath) or
IEC 60332-3C ( HFFR cable)
IEC 61034 (HFFR cable)
IEC 60754-1 & 2 (HFFR cable)
RoHS directives
Physical Characteristics
BT Cables
Part
Number
RG-Type
Conductor
(mm)
Diameter
Dielectric
(mm)
Coverage
braid
(%)
Sheath
Material
Overall
Diameter
(mm)
Weight
(kg/km)
C1229 RG-59-4.5 GHz 0.81 3.71 95 PVC 6.0 46.72
c1378 RG-59-4.5 GHz 0.81 3.71 95 HFFR 6.0 48.2
C1279 RG-6-4.5 GHz 1.02 4.60 95 PVC 6.8 56.2
c1379 RG-6-4.5 GHz 1.02 4.60 95 HFFR 6.8 59
C1280 RG-11-4.5 GHz 1.63 7.11 95 PVC 10.0 114.5
C1380 RG-11-4.5 GHz 1.63 7.11 95 HFFR 10.0 117
Electrical and Physical Characteristics (at 20°C)
BT Cables
Part
Number
RG-Type Imp.
(Ω)
Max. DC
Resistance
Conductor
(Ω/km)
Max. DC
Resistance
Screen
(Ω/km)
Nom.
Cap.
(pF/m)
Min. Return Loss
(dB)
<1000
MHz
< 2000
MHz
< 3000
MHz
< 4500
MHz
C1229 RG-59-4.5 GHz 75 ± 3 33.5 12.5 53 23 22 16 15
c1378 RG-59-4.5 GHz 75 ± 3 33.5 12.5 53 23 22 16 15
C1279 RG-6-4.5 GHz 75 ± 3 21.5 10.6 53 23 22 16 15
c1379 RG-6-4.5 GHz 75 ± 3 21.5 10.6 53 23 22 16 15
C1280 RG-11-4.5 GHz 75 ± 3 8.8 6.6 53 23 22 16 15
C1380 RG-11-4.5 GHz 75 ± 3 8.8 6.6 53 23 22 16 15
Nominal Attenuation in dB/100m
MHz 1 5 10 50 100 300 550 750 1000 2000 3000 4500
RG-59 0.98 2.07 2.95 6.23 7.55 13.68 18.83 22.23 25.96 38.24 46.13 56.50
RG-6 0.79 1.71 2.33 4.57 6.40 11.96 15.76 18.05 21.36 31.44 39.76 50.46
RG-11 0.53 1.12 1.51 2.96 4.20 7.49 10.41 12.38 14.57 21.84 27.93 35.98
For more details, please see the respective detailed datasheet(s).
 
 
 
info.btcables@bt.com 31
Section 6 – BT Data-Tec™ - Category LAN Cables
Application and Construction of Category Cables
for Local Area Networks and Structured Wiring Systems
1. Application
Horizontal or Building Wiring for one of the following categories of twisted pair cabling systems
Category
Max. data
rate
Usual application
Standard(s)
TIA/EIA ISO/IEC EN
Cat 1 1 Mbps Analogue voice
De facto, never a standard
Cat 2 4 Mbps Token ring of IBM
Cat 3 16 Mbps Voice, 10MbE(thernet) TIA/EIA 568-B
Cat 4 20 Mbps 16 Mbps Token Ring Was only a standard briefly
Cat 5 100 MHz 10/100/1000 MbE
155 Mbps ATM,
4/16 Mbps Token Ring
Replaced by 5e
Cat 5e 100 MHz
TIA/EIA 568-C.2
ISO/IEC 11806, 2nd
edition
IEC 61156
EN 50173-1
EN 50288
Cat 6 250 MHz
as Cat5e plus 10Gb
Ethernet over ≤ 55 m.
Cat 6a 500 MHz
As Cat 6 plus 10Gb
Ethernet over 100 m.
Cat 7 600 MHz
As Cat 6a plus supporting
100GbE
ISO/IEC 11801:
2002,
category 7 / class F
Cat 7a 1000 MHz
CATV (862 MHz),
40GBASE-T over 50 m.
100GbE over 15 m.
Cat 7a is not
recognised in
TIA/EIA-569
ISO/IEC 11801,
amendment 1
(2008) and
amendment 2
(2010).
2. Basic Cable Construction of the standard cables (not being patch cables)
Wire = Conductor with Insulation
Insulation: will be good strippable, suitable for insulation displacement and coloured. The colours are not interchangeable.
Pair = two twisted – colour coded – wires.
Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire.
Braiding (if applicable): tinned copper wires.
Ripcord: to ease removal of the sheath.
Sheath: PVC or Halogen-Free (HFFR).
Cat 3 Cat 5e Cat 6 Cat 6a Cat 7 Cat 7a
Type UUTP UUTP FUTP UUTP FUTP UUTP
UFTP &
FUTP
S-FTP S-FTP
Conductor Solid BC Solid BC Solid BC Solid BC Solid BC Solid BC
Insulation Polyolefin PE PE Skin-foam-skin PE
Cable core 6 to 200 pairs 4 pairs 4 Individually screened pairs
Core wrapping Yes No
Drain wire No No Yes No Yes No Central drain wire
Overall screen No No Foil No Foil Braiding
Sheath PVC PVC or HFFR HFFR
 
 
 
info.btcables@bt.com 32
Section 6 – BT Data-Tec™ - Category LAN Cables
3. Basic Cable Construction of the standard patch cables
Cat 5e Cat 6
Type UUTP FUTP UUTP FUTP
Conductor Flexible BC
Insulation PE PE
Cable core 4 pairs 4 pairs
Core wrapping no yes no yes
Drain wire (TC) no yes no yes
Overall Screen no foil no foil
Rip cord yes
Sheath PVC or HFFR
4. General Characteristics
Cat 3 Cat 5e Cat 6 Cat 6a Cat 7
Max. DCR conductor Ω/100m 9.6 9.38 9.38 7.7 7.7
Impedance Ω 100 100 100 100 100
Standard Colour scheme of Cat 5e – 6 – 6a and 7:
Pair number Pair 1 Pair 2 Pair 3 Pair 4
a-wire Blue Orange Green Brown
b-wire
White
with blue stripe
White
with orange stripe
White
with green stripe
White
with brown stripe
Operating temperature range: -20 to +80 °C and Rated Voltage: 300 Vrms.
5. Cable Range of BT Cables:
2 pairs 6 pairs 12 pairs 25 pairs 50 pairs 100 pairs 150 pairs 200 pairs
Cat3 - PVC C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269
Category Cat 5e Cat 5e Cat 5e Cat 5e Cat 5e Cat 5e
Type UTP UTP-UL listed UTP FTP FTP-UL listed FTP
Sheath PVC PVC HFFR PVC PVC HFFR
BT P/N C1035 C1285 C1235 C1036 C1286 C1236
Category Cat 6 Cat 6 Cat 6 Cat 6 Cat 6 Cat 6
Type UUTP UUTP-UL listed UUTP FUTP FUTP-UL listed FUTP
Sheath PVC PVC HFFR PVC PVC HFFR
BT P/N C1037 C1287 C1227 C1038 C1288 C1238
Category Cat 6a Cat 6a Cat 7 Cat 7a
Type U-UTP U-FTP S-FTP S-FTP
Sheath PVC HFFR HFFR HFFR
BT P/N C1200 C1053 C1039 C1201
Category Cat 5e Cat 5e Cat 5e Cat 5e Cat 6 Cat 6 Cat 6 Cat 6
Type UTP-Patch UTP-Patch FTP-Patch FTP-Patch UTP-Patch UTP-Patch FTP-Patch FTP-Patch
Sheath PVC HFFR PVC HFFR PVC HFFR PVC HFFR
BT P/N C1500 C1510 C1520 C1530 C1540 C1550 C1560 C1570
Non-standard cable constructions, colours, details and/or additional information are available on request.
For more details, please see the respective detailed datasheet(s).
Please note that technical specifications are subject to change without notice.
 
 
 
info.btcables@bt.com 33
Section 6.1 – BT Data-Tec™ - Category LAN Cables
Cat 5e and 6 UTP and FTP cables
Cat 5e cables
Cat 5e Variants
BT Cables
Part Number
Type Sheath
Overall Diameter
(mm)
Weight
(kg/km)
C1035 UUTP PVC 5.0 30
C1285 UUTP-UL PVC 5.0 30
C1235 UUTP HFFR 5.0 29
C1036 FUTP PVC 6.3 42
C1286 FUTP-UL PVC 6.3 42
C1236 FUTP HFFR 6.3 42
Main Transmission Characteristics of Cat 5e cables
Frequency
(MHz)
Min. Return
Loss
(dB/100m)
Maximum
Attenuation
(dB/100m)
Minimum
NEXT
(dB)
Maximum
Time Delay
(ns/100m)
Minimum
PSNEXT
(dB)
Minimum
ELFEXT
(dB)
Minimum
PSELFEXT
(dB)
1 20.0 2.0 65.3 570.00 62.3 64.0 61.0
4 23.0 4.1 56.3 552.00 53.3 52.0 49.0
8 24.5 5.8 51.8 546.73 48.8 45.9 42.9
10 25.0 6.5 50.3 545.38 47.3 44.0 41.0
16 25.0 8.2 47.2 543.00 44.4 39.9 36.9
20 25.0 9.3 45.8 542.05 42.8 38.0 35.0
25 24.3 10.4 44.3 541.20 41.3 35.8 33.0
31.25 23.6 11.7 42.9 540.44 39.9 34.1 31.1
62.5 21.5 17.0 38.4 538.55 35.4 28.1 25.1
100 20.1 22.0 35.3 537.60 32.3 24.0 21.0
Cat 6 cables
Cat 6 Variant
BT Cables
Part Number
Type Sheath
Overall Diameter
(mm)
Weight
(kg/km)
C1037 UUTP PVC 6.2 42
C1287 UUTP-UL PVC 6.2 42
C1237 UUTP HFFR 6.2 42
C1038 FUTP PVC 7.4 56
C1288 FUTP-UL PVC 7.4 56
C1238 FUTP HFFR 7.4 54.1
Main Transmission Characteristics of Cat 6 cables
Frequency
(MHz)
Return
Loss
(dB/100m)
Maximum
Attenuation
(dB/100m)
Minimum
NEXT
(dB)
Maximum
Time Delay
(ns/100m)
Minimum
PSNEXT
(dB)
Minimum
ELFEXT
(dB)
Minimum
PSELFEXT
(dB)
1 20.0 2.0 74.3 570.00 72.3 67.8 64.8
4 23.0 3.8 65.3 552.00 63.3 55.8 52.8
8 24.5 5.3 60.8 546.73 58.8 49.7 46.7
10 25.0 6.0 59.3 545.38 57.3 47.8 44.8
16 25.0 7.6 56.2 543.00 54.2 43.7 40.7
20 25.0 8.5 54.8 542.05 52.8 41.8 38.8
25 24.3 9.5 53.3 541.20 51.3 39.8 36.8
31.25 23.6 10.7 51.9 540.44 49.9 37.9 34.9
62.5 21.5 15.4 47.4 538.55 45.4 31.9 28.9
100 20.1 19.8 44.3 537.80 42.3 27.8 24.8
200 18.0 29.0 39.8 536.54 37.8 21.8 18.8
250 17.3 32.8 38.3 536.27 36.3 19.8 16.8
For more details, please see the respective detailed datasheet(s).
 
 
 
info.btcables@bt.com 34
Section 6.2 – BT Data-Tec™ - Category LAN Cables
Cat 6a U-FTP and Cat 7 S-FTP cables
Cat 6a U-FTP cables
Cat 6a Variants
BT Cables
Part Number
Type Sheath
Overall Diameter
(mm)
Weight
(kg/km)
C1200 U-UTP PVC 8.3 61.2
C1053 U-FTP HFFR 7.2 49.9
Main Transmission Characteristics of Cat 6a U-FTP cables
Freq.
(MHz)
Return Loss
(dB/100m)
Attenuation
(dB/100m)
NEXT
(dB/100m)
PSNEXT
(dB/100m)
ELFEXT
(dB/100m)
Impedance
(Ohm))
1 20.0 3.7 74.3 72.3 55.9 100 ± 15
10 25.0 5.8 59.3 57.3 47.8 100 ± 15
31.25 23.6 10.4 51.9 49.9 37.9 100 ± 15
100 20.1 19.0 44.3 42.3 27.8 100 ± 15
300 17.3 34.2 37.1 35.1 18.1 100 ± 25
500 17.3 45.2 33.8 31.8 14.0 100 ± 15
Cat 7 cables
Cat 7 Variants
BT Cables
Part Number
Type Sheath
Overall Diameter
(mm)
Weight
(kg/km)
C1039 S-FTP HFFR 7.8 67.5
Main Transmission Characteristics of Cat 7 S-FTP cables
Frequency
(MHz)
Return Loss
(dB/100m)
Attenuation
(dB/100m)
NEXT
(dB)
PSNEXT
(dB)
ELFEXT
(dB)
Impedance
(Ohm)
1 20.0 2.5 78 75 78.0 100 ± 15
10 25.0 6.5 78 75 56.5 100 ± 15
20 25.0 8.9 78 75 56.5 100 ± 15
62.5 21.5 14.9 75.5 72.5 56.8 100 ± 15
300 14.5 35.2 65.2 62.2 25.0 100 ± 25
600 12.5 50.1 60.7 57.7 16.0 100 ± 25
Cat 7a cables
Cat 7a Variants
BT Cables
Part Number
Type Sheath
Overall Diameter
(mm)
Weight
(kg/km)
C1201 S-FTP HFFR 8.5 71.1
Main Transmission Characteristics of Cat 7a S-FTP cables
Frequency
(MHz)
Return Loss
(dB/100m)
Attenuation
(dB/100m)
NEXT
(dB)
PSNEXT
(dB)
ACR
(dB)
Impedance
(Ohm)
4 23.0 4.0 80.0 77.0 78.0 100 ± 15
10 25.0 5.8 80.0 77.0 74.3 100 ± 15
20 25.0 8.2 80.0 77.0 71.0 100 ± 15
62.5 21.5 14.6 80.0 77.0 60.6 100 ± 15
300 17.3 32.7 71.2 68.2 38.6 100 ± 25
600 17.3 47.1 66.7 63.7 19.6 100 ± 25
900 17.3 54.9 64.9 61.9 9.93 100 ± 25
1000 16.0 61.9 63.4 60.4 1.47 100 ± 25
For more details, please see the respective detailed datasheet(s).
 
 
 
info.btcables@bt.com 35
Section 6.3 – BT Data-Tec™ - Category LAN Cables
Cat 5e and Cat 6 UTP and FTP PATCH Cables
Cat 5e and Cat6 Patch cables
Cat 5e Variants
BT Cables
Part Number
Type Sheath
Overall Diameter
(mm)
Weight
(kg/km)
C1500 UUTP PVC 5.2 30.7
C1510 UUTP HFFR 5.2 31.4
C1520 FUTP PVC 5.1 31.2
C1530 FUTP HFFR 5.1 31.1
Main Transmission Characteristics of Cat 5e Patch cables
Cat 5e - Patch UTP / FTP UTP FTP UTP / FTP UTP / FTP UTP / FTP UTP / FTP
Frequency
(MHz)
Return
Loss
(dB/100m)
Maximum
Attenuation
(dB/100m)
Minimum
NEXT
(dB)
Minimum
PSNEXT
(dB)
Minimum
ELFEXT
(dB)
Minimum
PSELFEXT
(dB)
1 20.0 2.4 3.1 65.3 62.3 63.8 60.8
4 23.0 4.9 6.1 56.3 53.3 51.8 48.8
8 24.5 6.9 8.6 51.8 48.8 45.7 42.7
10 25.0 7.8 9.7 50.3 47.3 43.8 40.8
16 25.0 9.9 12.4 47.2 44.2 39.7 36.7
20 25.0 11.1 13.9 45.8 42.8 37.8 34.8
25 24.2 12.5 15.6 44.3 41.3 35.8 32.8
31.25 23.3 14.1 17.6 42.9 39.9 33.9 30.9
62.5 20.7 20.4 25.5 38.4 35.4 27.9 24.9
100 19.0 26.4 33.0 35.3 32.3 23.8 20.8
Cat 6 Patch cables
Cat 6 Variants
BT Cables
Part number
Type Sheath
Overall Diameter
(mm)
Weight
(kg/km)
C1540 UUTP PVC 5.9 31.6
C1550 UUTP HFFR 5.9 32.4
C1560 FUTP PVC 6.2 34.6
C1570 FUTP HFFR 6.2 35.8
Main Transmission Characteristics of Cat 6 Patch cables
Cat 6 - Patch UTP / FTP UTP FTP UTP / FTP UTP / FTP UTP / FTP UTP / FTP
Frequency
(MHz)
Return
Loss
(dB/100m)
Maximum
Attenuation
(dB/100m)
Minimum
NEXT
(dB)
Minimum
PSNEXT
(dB)
Minimum
ELFEXT
(dB)
Minimum
PSELFEXT
(dB)
1 20.0 2.4 3.1 74.3 72.3 67.8 64.8
4 23.0 4.6 6.1 65.3 63.3 56.0 53.0
10 25.0 7.2 8.6 59.3 57.3 48.0 45.0
16 25.0 9.1 12.4 56.2 54.2 43.9 40.9
20 25.0 10.2 13.9 54.8 52.8 42.0 39.0
31.25 23.3 12.9 17.6 51.9 49.9 38.1 35.1
62.5 20.7 18.6 25.5 47.4 45.4 32.1 29.1
100 19.0 23.9 33.0 44.3 42.3 28.0 25.0
200 16.4 35.0 48.6 39.8 37.8 22.0 19.0
250 15.5 39.4 55.3 38.3 36.3 20.0 17.0
For more details, please see the respective detailed datasheet(s).
 
 
 
info.btcables@bt.com 36
Section 6.4 – BT Data-Tec™ - Category LAN Cables
Cat 3 multi pair Cables
Cat 3 cables
Cat 3 cables
BT Cables
Part
Number
No. of
pairs
Nom. Diameter
Conductor
(mm)
Nom.
Diameter
Insulation
(mm)
Nom. Overall
Diameter
(mm)
Weight
(kg/km)
C1031 2 0.5 0.9 3.6 16
C1266 6 0.5 0.9 5.5 39
C1267 12 0.5 0.9 7.4 73
C1032 25 0.5 0.9 11.8 154
C1033 50 0.5 0.9 15.5 280
C1034 100 0.5 0.9 21.6 530
C1268 150 0.5 0.9 26.8 800
C1269 200 0.5 0.9 29.4 1040
Electrical Characteristics Cat 3 cables at 20°
Frequency Max. Attenuation Max. NEXT Min. Return Loss Impedance
MHz (dB/100m) (dB) (dB) (Ohm)
1 2.6 41.3 12.0 100 ± 15
4 5.6 32.3 12.0 100 ± 15
8 8.5 27.8 12.0 100 ± 15
10 9.7 26.3 12.0 100 ± 15
16 13.1 23.3 10.0 100 ± 15
Cable Make-Up Cat 3 cables
BT Cables Part Number C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269
No of pairs 2 6 12 25 50 100 150 200
Number of pairs per unit 25 10 25 25 25
Number of units in the centre 1 5 4 1 1
Number of units in the 1e layer 5 7
Pair Colour Code Cat 3 cables
Pair
No.
Pair Colours in
2 – 6 -12 or 25 pairs
cables
Pair
No.
Pair Colours in
Unit of 12 or 25 pairs
Pair
No.
Pair Colours in
Unit of 25 pairs
1 White / Blue 11 Black / Blue 21 Purple / Blue
2 White / Orange 12 Black / Orange 22 Purple / Orange
3 White / Green 13 Black / Green 23 Purple / Green
4 White / Brown 14 Black / Brown 24 Purple / Brown
5 White / Grey 15 Black / Grey 25 Purple / Grey
6 Red / Blue 16 Yellow / Blue
7 Red / Orange 17 Yellow / Orange
8 Red / Green 18 Yellow / Green
9 Red / Brown 19 Yellow / Brown
10 Red / Grey 20 Yellow / Grey
For more details, please see the respective detailed datasheet(s).
 
 
 
info.btcables@bt.com 37
Section 7 – BT Industrial-Tec™ - DEF Standard Cables
DEF Standard 51-12 Parts 4 & 5
1. Application
Originally developed for military use, these flexible multi-conductor cables are now widely used within the industry. They are
designed for high density wiring between and within instruments and electronic equipment and/or components and especially
used in process control systems, computers, data processors, sound systems and of course in military equipment.
2. Main Standard
DEF standard 61-12, part 4 and 5.
2. Basic Construction of the cables
Wire = Conductor with Insulation.
Conductor: flexible = stranded tinned copper wires.
Size mm2
0.055 0.22 0.5
configuration mm 7 x 0.1 7 x 0.2 16 x 0.20
Max. DC Resistance Ω/km 345 86.2 37.7
Max. recommended current Amps 0.25 1 2.5
Rated Voltage Vrms 250 440 440
Insulation: PVC (Polyvinyl Chloride). Good strippable and coloured insulation. The colours are not interchangeable.
Cable core: two or more wires, stranded.
Colour scheme:
Core
No.
Color
Core
No.
Color
Core
No.
Color
Core
No.
Color
1 Red 11 Turquoise 21 BLUE/Black 31 WHITE/Brown
2 Blue 12 Grey 22 ORANGE/Blue 32 BROWN/Black
3 Green 13 RED/Blue 23 GREEN/Blue 33 GREY/Brown
4 Yellow 14 GREEN/Red 24 GREY/Blue 34 YELLOW/Violet
5 White 15 YELLOW/Red 25 YELLOW/Green 35 VIOLET/Black
6 Black 16 WHITE/Red 26 WHITE/Green 36 WHITE/Violet
7 Brown 17 RED/Black 27 GREEN/Black
50
Special scheme,
on request available8 Violet 18 RED/Brown 28 ORANGE/Green
9 Orange 19 YELLOW/Blue 29 GREY/Green
10 Pink 20 WHITE/Blue 30 YELLOW/Brown
Drain wire (only in combination with a screen): twisted (= flexible) tinned copper wires.
Screen (if applicable): Braiding of tinned copper wires, coverage 91%.
Sheath: grey PVC.
Flame Retardancy: IEC 60332-1 (Vertical Wire test).
Operating temperature range: -20 to +70 °C.
Non-standard cable constructions, colours, details and/or additional information are available on request.
For more details, please see the respective detailed datasheet(s).
Please note that technical specifications are subject to change without notice.
 
 
 
info.btcables@bt.com 38
Section 7 – BT Industrial-Tec™ - DEF Standard Cables
CABLE DESCRIPTION
1. Conductor
Stranded
Tinned Copper
2. Insulation
PVC
3. Cable core)
Two or more
wires stranded
4. Screen (if required)
Tinned Copper
91% Coverage
5. Ripcord
6. Sheath Material
Flame-Retardant
Polyvinyl Chloride (PVC)
Standard colour: grey
Standard Put Up Length
305 metres
Standard References
DEF standard 61-12, part 4 & 5
IEC 60332-1
RoHS directives
Conductor 7 x 0.1 mm = 0.055 mm²
No of
wires
BT Cables
Part Number
Screen
Diameter
(mm)
BT Cables
Part Number
Screen
Diameter
(mm)
2 C1164 Yes 3.2 C1360 No 2.3
3 C1165 Yes 3.6 C1361 No 2.4
4 C1362 No 2.6
6 C1166 Yes 4.2 C1144 No 3.1
9 C1145 No 3.7
15 C1146 No 4.2
25 C1168 Yes 6.3 C1147 No 5.5
36 C1169 Yes 6.9 C1148 No 6.1
50 C1365 Yes 8.0 C1364 No 7.2
Conductor 7 x 0.2 mm = 0.22 mm²
No of
wires
BT Cables
Part Number
Screen
Diameter
(mm)
BT Cables
Part Number
Screen
Diameter
(mm)
2 C1366 No 3.4
3 C1367 No 3.6
4 C1471 Yes 4.4 C1368 No 3.9
6 C1472 Yes 5.6 C1369 No 4.6
8 C1473 Yes 6.1 C1154 No 5.6
12 C1474 Yes 6.9 C1155 No 6.1
20 C1475 Yes 8.6 C1156 No 7.8
36 C1476 Yes 10.8 C1157 No 9.8
Conductor 16 x 0.2 mm = 0.5 mm²
No of
wires
BT Cables
Part Number
Screen
Diameter
(mm)
BT Cables
Part Number
Screen
Diameter
(mm)
2 C1158 No 5.5
3 C1370 No 5.8
4 C1177 Yes 7.3 C1371 No 6.3
6 C1178 Yes 8.3 C1372 No 7.3
12 C1375 Yes 10.5 C1373 No 9.5
18 C1180 Yes 12.0 C1374 No 11.0
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 39
Section 8 – BT Industrial-Tec™ - Industrial Cables
Application and Construction
1. Application
These cables are generally used to transmit analogue or digital signals in industrial process plants where chemical and mechanical
protections are needed (chemical and petrochemical industries). The unarmoured versions (Type 1) are generally use for indoor
installation.
2. Main Standard
BS(PAS) 5308 – Part 2 – Type 1 & 2.
2. Basic Construction of the cables
Wire = Conductor with Insulation.
Conductor: flexible = stranded tinned copper wires.
Pair: two twisted wires.
Conductor Size mm2
0.5 0.75 1.5
configuration mm 16 x 0.2 24 x 0.2 7 x 0.53
Max. DC Resistance at 20°C Ω/km 39.7 26.5 12.3
Max. conductor temperature °C 65 65 65
Min. operating temperature °C -20 -20 -20
Max. recommended current Amps 6 8 12
Max. mutual capacitance at 1 kHz pF/m 250 250 250
Max. L/R ratio μH/Ω 25 25 40
Rated Voltage Vrms 300 / 500 300 / 500 300 / 500
Insulation: PVC (Polyvinyl Chloride) in accordance with BS 7655. Good strippable and coloured insulation. The colours are not
interchangeable.
Cable core: two or more pairs, stranded.
Colour scheme:
Pair No. 1 2 3 4 5 6 7 8 9 10
a-wire White White White White White Red Red Red Red Red
b-wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey
Pair No. 11 12 13 14 15 16 17 18 19 20
a-wire Black Black Black Black Black Yellow Yellow Yellow Yellow Yellow
b-wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey
Drain wire (only in combination with an individual or collective screen): stranded tinned copper wires.
Individual Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%.
Collective Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%.
Bedding (if applicable): Flame Retardant PVC.
Armour (if applicable): galvanised steel wires.
Sheath: Flame Retardant PVC.
Flame Retardancy: IEC 60332-1 (Vertical Wire test).
Non-standard cable constructions, colours, details and/or additional information are available on request.
For more details, please see the respective detailed datasheet(s).
Please note that technical specifications are subject to change without notice.
 
 
 
info.btcables@bt.com 40
Section 8 – BT Industrial-Tec™ - Industrial Cables
BS(PAS) 5308 - Part 2 – Type 1 – Collectively Screened Cables
Conductor 0.5 mm² (16 x 0.2 mm)
No of
pairs
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km)
1 C1081 No 7.0 50 C1096 Yes 11.4 240
2 C1082 No 7.9 72 C1092 Yes 12.3 290
5 C1083 No 13.1 170 C1093 Yes 17.9 510
10 C1084 No 17.2 290 C1094 Yes 22.9 880
20 C1085 No 22.3 500 C1095 Yes 29.1 1500
Conductor 0.75 mm² (24 x 0.2 mm)
No of
pairs
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km)
1 C1086 No 7.3 60 C1101 Yes 11.7 270
2 C1087 No 8.3 100 C1102 Yes 12.9 310
5 C1088 No 14.3 210 C1103 Yes 19.8 710
10 C1089 No 18.7 350 C1104 Yes 25.3 1200
20 C1090 No 24.5 750 C1105 Yes 31.3 1700
Conductor 1.5 mm² (7 x 0.53 mm)
No of
pairs
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km)
1 C1091 No 8.3 90 C1106 Yes 12.9 300
2 C1092 No 9.7 140 C1107 Yes 14.3 390
5 C1093 No 16.4 330 C1108 Yes 22.1 870
10 C1094 No 20.6 580 C1109 Yes 28.4 1500
20 C1095 No 28.5 1100 C1110 Yes 35.7 2400
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 41
Section 8 – BT Industrial-Tec™ - Industrial Cables
BS(PAS) 5308 - Part 2 – Type 1 – Individually & Collectively Screened Cables
Conductor 0.5 mm² (16 x 0.2 mm)
No of
pairs
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km)
2 C1111 No 12.0 100 C1123 Yes 16.8 450
5 C1112 No 15.2 250 C1124 Yes 20.9 750
10 C1113 No 21.1 480 C1125 Yes 27.9 1300
20 C1114 No 27.3 780 C1126 Yes 34.4 1900
Conductor 0.75 mm² (24 x 0.2 mm)
No of
pairs
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km)
2 C1115 No 12.8 190 C1127 Yes 17.6 490
5 C1116 No 16.3 270 C1128 Yes 22.0 801
10 C1117 No 22.7 550 C1129 Yes 29.5 1800
20 C1118 No 29.8 960 C1130 Yes 37.8 2200
Conductor 0.75 mm² (24 x 0.2 mm)
No of
pairs
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km
BT Cables
Part
Number
Armour Diameter
(mm)
Weight
(kg/km)
2 C1119 No 14.7 250 C1131 Yes 20.4 660
5 C1120 No 18.8 460 C1132 Yes 25.4 1000
10 C1121 No 26.5 760 C1133 Yes 33.5 1700
20 C1122 No 34.4 1350 C1134 Yes 42.6 2800
For more details, please see the respective detailed datasheet(s) 
 
 
 
info.btcables@bt.com 42
Section 9 - BT Industrial-Tec™ -– Control Cables
Application and Construction
1. Application
These cables are commonly used as interconnecting cables to control, measure and regulate processor aided production within
the industry and also as flexible power control cables suitable for robotic and automated equipment.
2. Main Standard
VDE 0250/VDE 0255
2. Basic Construction of the cables
Wire = Conductor with Insulation.
Conductor: flexible = stranded tinned copper wires.
Conductor Size mm2
0.75 1.0 1.5 2.5 4 6
Conductor material bare copper
configuration mm 24x0.2 32x0.2 30x0.24 50x0.24 56x0.29 84x0.29
Max. DC Resistance at 20°C Ω/km 27 20.2 14 8.4 4.95 3.3
Insulation: Flame Retardant PVC (Polyvinyl Chloride). Insulation Resistance > 500 MΩ/km. Good strippable insulation.
Conductor Size mm2
0.75 1.0 1.5 2.5 4 6
Radial thickness insulation mm 0.5 0.5 0.4 0.5 0.8 0.7
Cable core: three or more wires stranded. In case of 5 wires with a central filler.
Colour scheme:
Green/yellow - black with printed numbers.
Collective Screen (CY series): braiding of tinned copper wires with a coverage of 70%.
Bedding (SY series): Flame Retardant PVC.
Armour (SY series): galvanised steel wires.
Sheath: Flame Retardant PVC.
Flame Retardancy: IEC 60332-1 (Vertical Wire test).
Operating temperature range: -20 to +70 °C.
Rated Voltage: 300 V.
Cable Types:
YY series: three or more stranded cores, surrounded by a PVC sheath.
CY series: as YY series plus a collective screen between cable core and PVC sheath.
SY series: as YY series plus a Steel Wire Armouring between cable core and transparent PVC sheath.
Non-standard cable constructions, colours, details and/or additional information are available on request.
For more details, please see the respective detailed datasheet(s).
Please note that technical specifications are subject to change without notice.
 
 
 
info.btcables@bt.com 43
Section 9 - BT Industrial-Tec™ -– Control Cables
YY Series: Cable core of stranded cores surrounded by a PVC sheath
No of
wires
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
3 C1631 0.75 / 24x0.2 5.6 C1632 1.0 / 32X0.2 6.2
4 C1635 0.75 / 24x0.2 6.6 C1636 1.0 / 32X0.2 7.1
12 C1645 0.75 / 24x0.2 10.4
18 C1648 0.75 / 24x0.2 12.4
No of
wires
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
3 C1633 1.5 / 30X0.24 6.5 C1634 2.5 / 50X0.24 6.5
4 C1637 1.5 / 30X0.24 7.6 C1638 2.5 / 50X0.24 9.1
5 C1639 1.5 / 30X0.24 8.4 C1640 2.5 / 50X0.24 10.3
7 C1641 1.5 / 30X0.24 9.5 C1642 2.5 / 50X0.24 11.8
8 C1643 1.5 / 30X0.24 10.4 C1644 2.5 / 50X0.24 12.6
12 C1646 1.5 / 30X0.24 12.4 C1647 2.5 / 50X0.24 14.9
18 C1649 1.5 / 30X0.24 14.5 C1650 2.5 / 50X0.24 14.5
CY Series: Cable core of stranded cores surrounded by a braiding of tinned copper wires plus a PVC sheath
No of
wires
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
3 C 1620 0.75 / 24x0.2 6.0 C1621 1.0 / 32X0.2 6.4
4 C1624 0.75 / 24x0.2 6.7 C1625 1.0 / 32X0.2 7.0
No of
wires
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
3 C1622 1.5 / 30X0.24 6.8 C1623 2.5 / 50X0.24 8.0
4 C1626 1.5 / 30X0.24 7.6 C1627 2.5 / 50X0.24 9.0
5 C1628 1.5 / 30X0.24 8.2 C1629 2.5 / 50X0.24 9.8
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 44
Section 9 - BT Industrial-Tec™ -– Control Cables
SY Series: Cable core of stranded cores surrounded by a bedding, a Steel Wire Armouring plus a PVC
sheath
No of
wires
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
3 C1655 0.75 / 24x0.2 7.8 C1658 2.5 / 50X0.24
4 C1662 2.5 / 50X0.24
No of
wires
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
2 C1651 1.0 / 32X0.2 8.2 C1652 1.5 / 30X0.24 9.4
3 C1656 1.0 / 32X0.2 8.2 C1657 1.5 / 30X0.24 9.4
4 C1660 1.0 / 32X0.2 8.2 C1661 1.5 / 30X0.24 9.4
5 C1665 1.0 / 32X0.2 10.6 C1666 1.5 / 30X0.24 11.2
6 C1668 1.5 / 30X0.24 12.3
7 C1669 1.0 / 32X0.2 11.7 C1670 1.5 / 30X0.24 12.4
12 C1671 1.0 / 32X0.2 13.8 C1672 1.5 / 30X0.24 14.3
18 C1673 1.0 / 32X0.2 15.8 C1674 1.5 / 30X0.24 16.8
25 C1675 1.0 / 32X0.2 19.7
No of
wires
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
BT Cables
Part Number
Conductor
(mm² / mm)
Diameter
(mm)
3 C1659 4.0 / 56x0.29 13.4
4 C1663 4.0 / 56x0.29 13.4 C1664 6.0 / 84X0.29 16.0
For more details, please see the respective detailed datasheet(s)
 
 
 
info.btcables@bt.com 45
GENERAL TECHNICAL INFORMATION
American Wire Gauge (AWM) Conductors (of bare or tinned copper)
Flexible Conductors AWG 24 22 20 18 16 14 12
Number of strands 7 7 7 7 19 19 19
Gauge single strand AWG 32 30 28 26 29 27 25
Diameter single strand mm 0.2 0.25 0.32 0.40 0.28 0.36 0.45
Solid Conductors AWG 24 22 20 18 16 14 12
Diameter mm 0.51 0.64 0.81 1.02 1.29 1.63 2.05
All Conductors AWG 24 22 20 18 16 14 12
Cross section mm² 0.20 0.32 0.52 0.82 1.37 2.08 3.31
Max. DC resistance Ω/km 88 57.4 32.16 22.7 15.47 9.36 5.61
Max. Recommended current 2 or
3 core cable
Amps 2.7 2.8 3.75 5 6.25 8 12
Max. Recommended current 4 or
5 core cable
Amps 2.2 2.25 3 4 5 6.4 9.6
Max. Recommended current 6 to
19 core cable
Amps 1.9 1.95 2.6 3.5 4.35 5.6 8.4
Max. Recommended current 20
to 36 core cable
Amps 1.35 1.4 1.65 2.5 3.12 4 6
Metric Conductors (of bare copper according to IEC 60228)
Conductor mm² 0.75 1.0 1.5 2.5 4.0
Max. Recommended
current 2 or 3 core cable
Amps ≤ 5 ≤ 5.70 ≤ 6.25 ≤ 8 ≤ 12
Flexible Conductors, class 2 mm² 0.055 0.22 0.50 0.75 1.0 1.5 2.5 4.0 6.0
Number of strands 7 7 7 7 7 7 7 7 7
Diameter single strand mm 0.1 0.2 0.53
Max. DC resistance Ω/km 345 86.2 36.0 24.5 18.1 12.1 7.41 4.61 3.08
Flexible Conductors, class 5 mm² 0.055 0.22 0.50 0.75 1.0 1.5 2.5 4.0 6.0
Number of strands 16 24 32 30 50 56 84
Diameter single strand mm 0.2 0.2 0.2 0.24 0.24 0.29 0.29
Max. DC resistance Ω/km 39.0 26.0 19.5 13.3 7.98 4.95 3.30
Max. Recommended current 2 or
3 core cable
Amps 2.7 2.8 3.75 5 6.25 8 12
Max. Recommended current 4 or
5 core cable
Amps 2.2 2.25 3 4 5 6.4 9.6
Max. Recommended current 6 to
19 core cable
Amps 1.9 1.95 2.6 3.5 4.35 5.6 8.4
Max. Recommended current 20
to 36 core cable
Amps 1.35 1.4 1.65 2.5 3.12 4 6
All conductors in BT Cables are in accordance with above tables unless otherwise stated in the respective section of this
publication or datasheets.
 
 
 
info.btcables@bt.com 46
Pairs: all pairs consist of two twisted wires with a lay-length < 40 D.
Cable Cores: all cable cores consist of stranded wires or pairs
Foil screens for multi-core and multi-pair cables, screens or shields mostly consist of an aluminium foil laminated to polyester, broadly
known as Alpet. These foils are helically (as a spiral) applied with sufficient overlap to guarantee 115 % or more coverage. . For the
flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend.
A drain wire or continuity wire, contacting the aluminium side of the foil, is used for the termination of the screen and also to ground
electrostatic discharges.
In case the screen of a coaxial cable where the screen may be a foil, this foil will be applied longitudinally and will also be bonded to the
dielectric around the conductor.
Braided screens consist of 16 or 24 groups of strands. One set of 8 or 12 strands is woven clockwise and the other set of 8 or 12 strands
anti-clockwise. Strands can consist of tinned or bare copper or aluminium wires.
Braided screens provide good screening efficiency and flexibility. Higher coverage provides better screening.
Sheaths: grey PVC, purple HFFR or black for PE, all in accordance with BS EN 50290-2.
Sheath PVC
PVC
Alarm cables
HFFR PE
Physical properties BS EN 50290-2-22 UL444 BS EN 50290-2 BS EN 50290-2
Retardancy Flame Fire Fire Not applicable
Retardancy acc. to IEC 60332-1 UL1666 IEC 60332-3C Not applicable
Low Smoke Not applicable Not applicable IEC 61034 Not applicable
Halogen-free (non acid, non toxic) Not applicable Not applicable IEC 60754 Not applicable
RoHS compliant YES YES YES YES
Installation ** INDOOR INDOOR INDOOR OUTDOOR
** on request cables with a sheath for in- & outdoor = universal use available.
RoHS Limits for Hazardous Substances
Substance Max. Concentration
Unless so marked, all BT Cables do not contain restricted or hazardous substances
and are compliant with the European Regulations or Directives for RoHS
(Restriction of Hazardous Substances), REACH (Regulation Registration,
Evaluation, Authorisation and Restriction of Chemical substances), WEEE (Waste
Electrical and Electronic Equipment ), ELV (End of Life Vehicles) and BFR
(Brominated Flame Retardants).
Lead (Pb) 0.03%
Mercury (Hg) 0.10%
Cadmium (Cd) 0.01%
Chromium 6 0.1%
PBB 0.1%
PBDE 0.1%
RS Protocol
RS-232 RS-422 RS-485
Differential no yes yes
Max. number of drivers
Max. number of receivers
1
1
1
10
1
32
Modes of operation full duplex half duplex half duplex
Network topology point-to-point multidrop multidrop
Max. distance acc. to standard 15 m 1200 m 1200 m
Max. speed at 12 m.
Max. speed at 1200 m.
20 kbs
1 kbs
10 Mbs
100 kbs
35 Mbs
100 kbs
Cables used
6 to 25 conductors.
No impedance specified
mainly 24AWG conductors.
Two pairs or more.
100 ohm
mainly 24AWG conductors.
One pair or more.
120 ohm
BT Cables main part numbers see section 1.3 section 1.2 section 1.1
 
 
 
info.btcables@bt.com 47
Nominal Attenuation in dB/100m for RG Coaxial Cables
MHz 1 5 10 50 100 300 550 750 1000 2000 3000 4500
RG-59 0.98 2.07 2.95 6.23 7.55 13.68 18.83 22.23 25.96 38.24 46.13 56.50
RG-6 0.79 1.71 2.33 4.57 6.40 11.96 15.76 18.05 21.36 31.44 39.76 50.46
RG-11 0.53 1.12 1.51 2.96 4.20 7.49 10.41 12.38 14.57 21.84 27.93 35.98
COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS
Europe USA
Focus on SAFETY = SAVING LIVES Focus Focus on REDUCING INSURANCE CLAIMS
Low Voltage Directive Directives National Electrical Code
220 Volt, 50 Hz Power supply system 120 Volt, 60 Hz
More radial thickness of insulation Cable basics More copper in conductors
IEC-EN and National Standards Standards UL standards
Cable specs. in mm, N, etc. Units Cable specs. in inches, lbs, etc.
70 °C (is equal to 80 °C in USA) Temperature Ratings 80 °C (Is equal to 70 °C in Europe)
300 / 500 Vrms
Voltage Ratings
300 Vrms
450 / 750 Vrms 600 Vrms
IEC 60332-1
Retardancy levels
UL1581 – VW-1
IEC 60332-3-24 (former 3C) UL1685
RoHS compliant
Environmental
requirements
A number of states banned Hg and PBDE
CE Marking
The CE marking certifies that a product has met EU
consumer safety, health or environmental
requirements. By affixing the CE marking to a
product, the manufacturer – on his sole responsibility
– declares that it meets EU safety, health and
environmental requirements or, if stipulated in the
directive(s), it had to be examined by a notified
conformity assessment body.
Quality assurance
UL Approval / Listing
UL does not approve products. Rather it evaluates
products for compliance to specific requirements, and
permits acceptable products to carry a UL certification
mark, as long as they remain compliant with the
standards.
Products under its listing service are said to be “UL
Listed,” identified by the distinctive UL mark.
CONVERSIONS
Europe USA
1 mm = 0.03937 inches 1 inch = 25,4 mm
1 m = 3.2808 feet (305 m = 1000 feet) 1 feet = 0.3048 m
1 m = 1.0936 feet 1 yard = 0.9144m
1 km = 0.6214 miles 1 mile = 1.6093 km
1 kg/km = 0.6719 lbs/1000 ft 1 lbs/1000 ft = 1.488 kg/km
1 ohm/km = 0.3048 ohm/1000 ft 1 ohm/1000 ft = 3.2808 ohm/km
1 N = 0.2248 lbs force 1 lbs force = 0.2248 N
-40 °C = -40 °F -40 °F = -40 °C
-30 °C = -22 °F -22 °F = -30 °C
0 °C = 32 °F 32 °F = 0 °C
60 °C = 90 °F 90 °F = -60 °C
75 °C = 167 °F 167 °F = -75 °C
90 °C = 194 °F 194 °F = -90 °C
 
 
 
info.btcables@bt.com 48
Area Conversions
From To Multiply by To Multiply by To Multiply by
Circular mils Square inches 0.0000007854 Square mils 0.7854 mm² 0.0005067
Square
inches
Circular mils 1,273.240 Square mils 1,000,000.00 mm² 645.16
mm² Square inches 0.00155 Square mils 1550.01 Circular mils 1,973.53
Square feet Square meters 0.0929
Common Wire Conversions
AWG 24 22 20 19/18 18 18/17
Cir. mils 404 640 987 1029 1481 1620 1974
mm² 0.205 0.324 0.5 0.521 0.75 0.821 1.0
AWG 16 15/16 14 14/13 12 11
Cir. mils 2580 2961 4110 4935 6530 7896 8230
mm² 1.371 1.5 2.082 2.5 3.309 4.0 4.170
Force, Mass and Weight Conversion
From To Multiply by From To Multiply by
Pounds Kilograms 0.4535 Kilograms Pounds 2.205
Pound per 1000 ft
Kilogram per
kilometre
1.488
Kilogram per
kilometre
Pound per 1000 ft 0.6719
Pound-force Newton 4.4482 Newton Pound-force 0.2248
 
 
 
info.btcables@bt.com 49
BT CATALOGUE
BT CATALOGUE
BT CATALOGUE
BT CATALOGUE

More Related Content

Similar to BT CATALOGUE

B3_Communications_Brochure
B3_Communications_BrochureB3_Communications_Brochure
B3_Communications_BrochureDonna M Sheridan
 
Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...
Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...
Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...
Thorne & Derrick International
 
Wavecom Fiber Lab Catalog
Wavecom Fiber Lab CatalogWavecom Fiber Lab Catalog
Wavecom Fiber Lab CatalogMounir Farag
 
3106 11012 os2clct
3106 11012 os2clct3106 11012 os2clct
3106 11012 os2clct
sunny786921
 
Crabtree White EWA Catalogue
Crabtree White EWA CatalogueCrabtree White EWA Catalogue
Crabtree White EWA Catalogue
Mark Cheatle
 
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable TerminationsNexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Thorne & Derrick International
 
2013 datwyler training 2 product overview - info tech middle east
2013 datwyler training 2   product overview - info tech middle east2013 datwyler training 2   product overview - info tech middle east
2013 datwyler training 2 product overview - info tech middle east
Ali Shoaee
 
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HVNexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Thorne & Derrick International
 
Nexans Euromold Interface A 200 Series Screened Cable Connectors
Nexans Euromold Interface A 200 Series Screened Cable Connectors Nexans Euromold Interface A 200 Series Screened Cable Connectors
Nexans Euromold Interface A 200 Series Screened Cable Connectors
Thorne & Derrick International
 
Nexans Euromold MV Separable Connectors & Bushings - Interface A
Nexans Euromold MV Separable Connectors & Bushings - Interface ANexans Euromold MV Separable Connectors & Bushings - Interface A
Nexans Euromold MV Separable Connectors & Bushings - Interface A
Thorne & Derrick International
 
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C BushingEuromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Thorne & Derrick International
 
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface CNexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Thorne & Derrick International
 
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
Thorne & Derrick International
 
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HVNexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Thorne & Derrick International
 
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Thorne & Derrick International
 
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAILAbb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
AKBAR TRADING
 
Fanout assemblies catalogue
Fanout assemblies catalogueFanout assemblies catalogue
Fanout assemblies catalogue
Fatih BATAL
 
Dienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344dDienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dien Ha The
 
Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...
Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...
Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...
Thorne & Derrick International
 
Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...
Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...
Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...
Thorne & Derrick International
 

Similar to BT CATALOGUE (20)

B3_Communications_Brochure
B3_Communications_BrochureB3_Communications_Brochure
B3_Communications_Brochure
 
Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...
Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...
Nexans Euromold 158LR Screened Separable Connectors 200 Series up to 250A 24k...
 
Wavecom Fiber Lab Catalog
Wavecom Fiber Lab CatalogWavecom Fiber Lab Catalog
Wavecom Fiber Lab Catalog
 
3106 11012 os2clct
3106 11012 os2clct3106 11012 os2clct
3106 11012 os2clct
 
Crabtree White EWA Catalogue
Crabtree White EWA CatalogueCrabtree White EWA Catalogue
Crabtree White EWA Catalogue
 
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable TerminationsNexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
 
2013 datwyler training 2 product overview - info tech middle east
2013 datwyler training 2   product overview - info tech middle east2013 datwyler training 2   product overview - info tech middle east
2013 datwyler training 2 product overview - info tech middle east
 
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HVNexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
 
Nexans Euromold Interface A 200 Series Screened Cable Connectors
Nexans Euromold Interface A 200 Series Screened Cable Connectors Nexans Euromold Interface A 200 Series Screened Cable Connectors
Nexans Euromold Interface A 200 Series Screened Cable Connectors
 
Nexans Euromold MV Separable Connectors & Bushings - Interface A
Nexans Euromold MV Separable Connectors & Bushings - Interface ANexans Euromold MV Separable Connectors & Bushings - Interface A
Nexans Euromold MV Separable Connectors & Bushings - Interface A
 
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C BushingEuromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
 
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface CNexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
 
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
 
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HVNexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
 
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
 
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAILAbb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAIL
 
Fanout assemblies catalogue
Fanout assemblies catalogueFanout assemblies catalogue
Fanout assemblies catalogue
 
Dienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344dDienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344d
 
Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...
Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...
Nexans Euromold Connectors 400 Series Interface C Symmetrical Cable Connector...
 
Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...
Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...
Nexans Euromold Connectors - 400LB Elbow, 400TB & 440TB Tee Connectors (Inter...
 

BT CATALOGUE

  • 2. CONTENTS CABLE FINDER BT CABLES – BELDEN EQUIVALENTS SECTION 1 BT BMS-TECTM - Paired Cables SECTION 2 BT BMS-TECTM - Multi-Conductor Cables SECTION 3 BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables SECTION 4 BT FIREPRO-TEC™ – Fire Resistant Cables SECTION 5 BT Security-Tec ™– Coaxial Cables SECTION 6 BT Data-Tec™ - Category LAN Cables SECTION 7 BT Industrial-Tec™ - DEF Standard Cables SECTION 8 BT Industrial-Tec™ - Industrial Cables SECTION 9 BT Industrial-Tec™ – Control Cables GENERALTECHNICAL INFORMATION COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS CONVERSIONS GLOSSARY BT CABLES PART NUMBER INDEX       info.btcables@bt.com 2
  • 3. Cable Finder BT BMS-TECTM - Paired Cables Application Cond.- Size ↓ No. of pairs → 1 2 3 4 5 6 7 8 § Page Screen Sheath RS-485 24 AWG Foil+ braid PVC C1189 C1190 C1191 C1192 1.1 24 AWG HFFR C1318 C1319 C1320 C1321 1.1 22 AWG PVC C1080 C1295 C1296 C1297 1.1 22AWG HFFR C1401 C1402 C1403 C1404 1.1 RS-422 24 AWG every pair a foil PVC C1382 C1383 C1384 C1386 1.2 G.P. Bus 22 AWG PVC C1196 C1197 C1298 C1299 C1214 1.6 22 AWG HFFR C1281 C1282 C1314 1.6 RS-232 24 AWG Foil PVC C1181 C1182 C1183 C1184 C1185 C1186 C1187 C1188 1.3 Lon Works 0.64 mm no scrn HFFR C1346 C1347 1.5 0.64 mm every pair a foil HFFR C1348 C1349 1.5 KNX 0.8 mm Foil PVC C1219 C1217 1.4 0.8 mm HFFR C1220 C1218 1.4 Security & Alarm 18 AWG Foil HFFR C1171 C1172 C1173 C1174 C1175 C1176 1.8 Foil + Braid HFFR C1418 C1419 C1420 C1421 C1422 C1423 1.8 BMS 0.6 mm² Foil PVC C1381 1.9 Application No. of pairs ↓ AWG conductor size → 22 20 18 16 14 12 Section Page Screen ↓ Sheath ↓ G.P Bus 1 Yes PVC C1199 C1195 C1193 C1213 C1224 C1313 1.7 1 Yes HFFR C1310 C1308 C1272 C1270 C1305 C1303 1.7 1 No PVC C1301 C1300 C1203 C1198 C1222 C1302 1.7 1 No HFFR C1311 C1309 C1271 C1307 C1306 C1304 1.7 BT BMS-TECTM - Multi-Conductor Cables Cond. Size AWG↓ No. of conductors → 2 3 4 6 8 Section Page Sheath ↓ Screen 22 PVC Yes C1226 C1228 C1230 C1264 C1232 2.1 No C1227 C1278 C1231 C1265 C1233 2.1 HFFR Yes C1741 C1743 C1745 C1747 C1749 2.2 No C1742 C1744 C1746 C1748 C1750 2.2 20 PVC Yes C1019 C1021 C1023 C1260 C1262 2.1 No C1020 C1022 C1024 C1261 C1263 2.1 HFFR Yes C1731 C1733 C1735 C1737 C1739 2.2 No C1732 C1734 C1736 C1738 C1740 2.2 18 PVC Yes C1013 C1015 C1017 C1211 C1258 2.1 No C1014 C1016 C1018 C1212 C1259 2.1 HFFR Yes C1721 C1723 C1725 C1727 C1729 2.2 No C1722 C1724 C1726 C1728 C1730 2.2 UV-HFFR Yes C1351 C1352 C1353 C1354 C1355 2.3 16 PVC Yes C1007 C1009 C1011 C1252 C1254 2.1 No C1008 C1010 C1012 C1253 C1255 2.1 HFFR Yes C1711 C1713 C1715 C1717 C1719 2.2 No C1712 C1714 C1716 C1718 C1720 2.2 UV-HFFR Yes C1391 C1392 C1393 C1394 C1395 2.3 14 PVC Yes C1001 C1003 C1005 C1248 C1250 2.1 No C1002 C1004 C1006 C1249 C1251 2.1 HFFR Yes C1701 C1703 C1705 C1707 C1709 2.2 No C1702 C1704 C1706 C1708 C1710 2.2 12 PVC Yes C1322 C1324 C1326 C1330 C1332 2.1 No C1323 C1325 C1327 C1331 C1333 2.1 HFFR Yes C1334 C1336 C1338 C1342 C1344 2.2 No C1335 C1337 C1339 C1343 C1345 2.2 No. of conductors Conductor size → 22 AWG 20 AWG 18 AWG Section Page Sheath ↓ Screen 3 PVC Yes C1215 C1245 C1225 ? Multi-Conductor Power Limited Tray Cables (PLTC) are available on request       info.btcables@bt.com 3
  • 4. BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables Application No. of pairs ↓ Cond. size → AWG 18 AWG 16 AWG 14 AWG 12 Section Page Screen ↓ Sheath ↓ Fire Alarm 1 Yes PVC C1040 C1041 C1042 C1043 3 1 No PVC C1135 C1136 C1137 C1138 3 BT FIREPRO-TEC™ – Fire Resistant Cables Application No. of cores ↓ Cond. size → 0.75 mm 2 1.0 mm 2 1.5 mm 2 2.5 mm 2 4.0 mm 2 Section Page Screen ↓ Sheath ↓ Circuit integrity 1 No HFFR C1760 C1761 4 2 Yes HFFR C1284 C1283 C1044 C1045 C1289 4 2 No HFFR C1139 C1140 C1141 C1142 C1143 4 3 Yes HFFR C1159 C1160 C1161 C1162 C1163 4 3 No HFFR C1149 C1150 1151 C1152 C1153 4 BT Security-Tec ™– Coaxial Cables Application Inner Conductor Screen Sheath RG-59 RG-6 RG-11 Section Page CCTV Solid BC Braid BC PVC C1028 C1029 C1030 5.1 Solid BC Braid BC HFFR C1428 C1429 C1430 5.1 Flex BC Braid BC PVC C1275 C1276 C1277 5.1 SMATV CATV CCS Foil+Alu Braid PVC C1025 C1026 C1027 5.2 CCS Quad screen PVC C1256 C1257 C1241 5.2 HDTV Solid BC Foil+TC Braid PVC C1229 C1279 C1280 5.3 Solid BC Foil+TC Braid HFFR C1378 C1379 C1380 5.3 50 Ohm Coaxial cables are available on request BT Data-Tec™ - Category LAN Cables Cat. type Sheath 2 pairs 6 prs 12 prs 25 prs 50 prs 100 prs 150 prs 200 prs section Page Cat 3 PVC C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269 6.4 Cat. types Sheath UTP UTP-UL FTP FTP-UL U-FTP S-FTP Section Page Cat 5e PVC C1035 C1285 C1036 C1286 6.1 HFFR C1235 C1236 6.1 Cat 5e- patch PVC C1500 C1520 6.3 HFFR C1510 C1530 6.3 Cat 6 PVC C1037 C1287 C1038 C1288 6.1 HFFR C1237 C1238 6.1 Cat 6-patch PVC C1540 C1560 6.3 HFFR C1550 C1570 6.3 Cat 6a PVC C1055 C1056 C1057 6.2 HFFR C1200 C1052 C1053 6.2 Cat 7 HFFR C1039 6.2 Cat 7a HFFR C1201 6.2       info.btcables@bt.com 4
  • 5. BT Industrial-Tec™ - DEF Standard Cables Conductor 7 x 0.1 mm = 0.055 mm² No. of cores 2 3 4 6 9 15 25 36 50 section Page Screened C1164 C1165 C1166 C1168 C1169 C1365 7 Unscreened C1360 C1361 C1362 C1144 C1145 C1146 C1147 C1148 C1364 7 Conductor 7 x 0.2mm = 0.22 mm² No. of cores 2 3 4 6 8 12 20 36 section Page Screened C1171 C1172 C1173 C1174 C1175 C1176 7 Unscreened C1366 C1367 C1368 C1369 C1154 C1155 C1156 C1157 7 Conductor 16 x 0.2mm = 0.5 mm² No. of cores 2 3 4 6 12 18 section Page Screened C1177 C1178 C1375 C1180 7 Unscreened C1158 C1370 C1371 C1372 C1373 C1374 7 BT Industrial-Tec™ - Industrial Cables BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Unarmoured cables No. of pairs 1 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1081 C1082 C1083 C1084 C1085 8 Conductor 0.75 mm² (24x0.2 mm) C1086 C1087 C1088 C1089 C1090 8 Conductor 1.5 mm² (7x0.53 mm) C1091 C1092 C1093 C1094 C1095 8 BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Armoured cables No. of pairs 1 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1096 C1097 C1098 C1099 C1100 8 Conductor 0.75 mm² (24x0.2 mm) C1101 C1102 C1103 C1104 C1105 8 Conductor 1.5 mm² (7x0.53 mm) C1106 C1107 C1108 C1109 C1110 8 BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Unarmoured cables No. of pairs 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1111 C1112 C1113 C1114 8 Conductor 0.75 mm² (24x0.2 mm) C1115 C1116 C1117 C1118 8 Conductor 1.5 mm² (7x0.53 mm) C1119 C1120 C1121 C1122 8 BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Armoured cable No. of pairs 2 5 10 20 section Page Conductor 0.5 mm² (16x0.2 mm) C1123 C1124 C1125 C1126 8 Conductor 0.75 mm² (24x0.2 mm) C1127 C1128 C1129 C1130 8 Conductor 1.5 mm² (7x0.53 mm) C1131 C1132 C1133 C1134 8       info.btcables@bt.com 5
  • 6. BT Industrial-Tec™ - Control Cables YY Series (N stranded cores surrounded by a PVC sheath) No. of cores 3 4 5 7 8 12 18 section Page Conductor 0.75 mm² (24x0.2 mm) C1631 C1635 C1645 C1648 9 Conductor 1.0 mm² (32x0.2 mm) C1632 C1636 9 Conductor 1.5 mm² (30x0.24 mm) C1633 C1637 C1639 C1641 C1643 C1646 C649 9 Conductor 2.5 mm² (50x0.24 mm) C1634 C1638 C1640 C1642 C1644 C1647 C1650 9 CY Series (N stranded cores surrounded by a braiding plus a PVC sheath) No. of cores 3 4 5 section Page Conductor 0.75 mm² (24x0.2 mm) C1620 C1624 9 Conductor 1.0 mm² (32x0.2 mm) C1621 C1625 9 Conductor 1.5 mm² (30x0.24 mm) C1622 C1626 C1628 9 Conductor 2.5 mm² (50x0.24 mm) C1623 C1627 C1629 9 SY Series (N stranded cores surrounded by Steel Wire Armouring plus a PVC sheath) No. of cores 2 3 4 5 7 12 18 25 section Page Conductor 0.75 mm² (24x0.2 mm) C1655 9 Conductor 1.0 mm² (32x0.2 mm) C1651 C1656 C1660 C1665 C1669 C1671 C1673 C1675 9 No. of cores 2 3 4 5 6 7 12 18 Conductor 1.5 mm² (30x0.24 mm) C1652 C1657 C1661 C1666 C1668 C1670 C1672 C1674 9 Conductor 2.5 mm² (50x0.24 mm) C1658 C1662 9 Conductor 4.0 mm² (56x0.29 mm) C1659 C1663 9 Conductor 6.0 mm² (84x0.29 mm) C1664 9       info.btcables@bt.com 6
  • 7. BT Cables - Belden equivalents Belden P/N BT Cables P/N Conductor Size No. of Conductors No. of Pairs Individually shielded pairs Collective shield Jacket BT Cables Brand and Additional Data 1030A C1223 16(7*24) AWG 1 Yes PVC 300V PL Tray Cable 1043A C1078 16 (7*24) AWG 16 Yes Yes PVC 600V Tray Cable 1044A C1077 16 (7*24) AWG 20 Yes Yes PVC 600V Tray Cable 1064A C1076 18 (7*26) AWG 4 Yes Yes PVC 600V Tray Cable 1067A C1074 18 (7*26) AWG 16 Yes Yes PVC 600V Tray Cable 1467A C1075 18 (7*26) AWG 8 Yes Yes PVC 300V PL Tray Cable 1505A C1229 20 AWG 1 Yes PVC RG-59 Coaxial Cable (BC) 1523A C1027 14 AWG 1 Yes PVC RG11 Coaxial Cable (CCS) 1583A C1035 24 AWG 4 CAT 5E UTP Cable 1617A C1241 14 AWG 1 Yes PVC RG-11 Quad Shield Coaxial Cable (CCS) 1633E C1036 24 AWG 4 yes PVC CAT 5E FTP Cable 1694A C1279 18 AWG 1 Yes PVC RG-6 Coaxial Cable (BC) 1885ENH C1039 23 AWG 4 Yes Yes PVC CAT 7 ISTP Cable 3079E C1315 22 (7*30) AWG 1 Yes PVC Profibus DP 3105A C1080 22 (7*30) AWG 2 Yes PVC RS-485 Computer Cable 3107A C1295 22 (7*30) AWG 2 Yes PVC RS-485 Low Cap Computer Cable 3108A C1296 22 (7*30) AWG 3 Yes PVC RS-485 Computer Cable 3109A C1297 22 (7*30) AWG 4 Yes PVC RS-485 Computer Cable 4000FE C1334 12 (19*25) AWG 2 Yes HFFR BMS-HFFR cables 4000UE C1335 12 (19*25) AWG 2 HFFR BMS-HFFR cables 4001UE C1337 12 (19*25) AWG 3 HFFR BMS-HFFR cables 4100FE C1701 14 (19*27) AWG 2 Yes HFFR BMS-HFFR cables 4100UE C1702 14 (19*27) AWG 3 HFFR BMS-HFFR cables 4101UE C1704 14 (19*27) AWG 3 HFFR BMS-HFFR cables 4102UE C1706 14 (19*27) AWG 4 HFFR BMS-HFFR cables 4200FE C1711 16 (19*29) AWG 2 Yes HFFR BMS-HFFR cables 4200UE C1712 16 (19*29) AWG 2 HFFR BMS-HFFR cables 4201FE C1713 16 (19*29) AWG 3 Yes HFFR BMS-HFFR cables 4201UE C1714 16 (19*29) AWG 3 HFFR BMS-HFFR cables 4202FE C1715 16 (19*29) AWG 4 Yes HFFR BMS-HFFR cables 4202UE C1716 16 (19*29) AWG 4 HFFR BMS-HFFR cables 4300FE C1721 18 (7*26) AWG 2 Yes HFFR BMS-HFFR cables 4300UE C1722 18 (7*26) AWG 2 HFFR BMS-HFFR cables 4301FE C1723 18 (7*26) AWG 3 Yes HFFR BMS-HFFR cables 4301UE C1724 18 (7*26) AWG 3 HFFR BMS-HFFR cables 4302FE C1725 18 (7*26) AWG 4 Yes HFFR BMS-HFFR cables 4302UE C1726 18 (7*26) AWG 4 HFFR BMS-HFFR cables 4304FE C1727 18 (7*26) AWG 6 Yes HFFR BMS-HFFR cables 4304UE C1728 18 (7*26) AWG 6 HFFR BMS-HFFR cables 4306FE C1729 18 (7*26) AWG 8 Yes HFFR BMS-HFFR cables 4306UE C1730 18 (7*26) AWG 8 HFFR BMS-HFFR cables 4400FE C1731 20 (7*28) AWG 2 Yes HFFR BMS-HFFR cables 4400UE C1732 20 (7*28) AWG 2 HFFR BMS-HFFR cables 4401FE C1733 20 (7*28) AWG 3 Yes HFFR BMS-HFFR cables 4402FE C1735 20 (7*28) AWG 4 Yes HFFR BMS-HFFR cables 4402UE C1736 20 (7*28) AWG 4 HFFR BMS-HFFR cables 4500FE C1741 22 (7*30) AWG 2 Yes HFFR BMS-HFFR cables 4500UE C1742 22 (7*30) AWG 2 HFFR BMS-HFFR cables 4501FE C1743 22 (7*30) AWG 3 Yes HFFR BMS-HFFR cables 4501UE C1744 22 (7*30) AWG 3 HFFR BMS-HFFR cables 4502FE C1745 22 (7*30) AWG 4 Yes HFFR BMS-HFFR cables 4502UE C1746 22 (7*30) AWG 4 HFFR BMS-HFFR cables 4504FE C1747 22 (7*30) AWG 6 Yes HFFR BMS-HFFR cables 4504UE C1748 22 (7*30) AWG 6 HFFR BMS-HFFR cables 4506FE C1749 22 (7*30) AWG 8 Yes HFFR BMS-HFFR cables 4506UE C1750 22 (7*30) AWG 8 HFFR BMS-HFFR cables 5100FE C1001 14 (19*27) AWG 2 Yes PVC BMS-PVC cables 5100UE C1002 14 (19*27) AWG 2 PVC BMS-PVC cables 5101FE C1003 14 (19*27) AWG 3 Yes PVC BMS-PVC cables 5101UE C1004 14 (19*27) AWG 3 PVC BMS-PVC cables 5102FE C1005 14 (19*27) AWG 4 Yes PVC BMS-PVC cables 5102UE C1006 14 (19*27) AWG 4 PVC BMS-PVC cables 5200FE C1007 16 (19*29) AWG 2 Yes PVC BMS-PVC cables 5200UE C1008 16 (19*29) AWG 2 PVC BMS-PVC cables 5201FE C1009 16 (19*29) AWG 3 Yes PVC BMS-PVC cables 5201UE C1010 16 (19*29) AWG 3 PVC BMS-PVC cables 5202FE C1011 16 (19*29) AWG 4 Yes PVC BMS-PVC cables 5202UE C1012 16 (19*29) AWG 4 PVC BMS-PVC cables 5300FE C1013 18 (7*26) AWG 2 Yes PVC BMS-PVC cables 5300UE C1014 18 (7*26) AWG 2 PVC BMS-PVC cables 5301FE C1015 18 (7*26) AWG 3 Yes PVC BMS-PVC cables 5301UE C1016 18 (7*26) AWG 3 PVC BMS-PVC cables 5302FE C1017 18 (7*26) AWG 4 Yes PVC BMS-PVC cables 5302UE C1018 18 (7*26) AWG 4 PVC BMS-PVC cables 5305FE C1239 18 (7*26) AWG 7 PVC BMS-PVC cables 5400FE C1019 20 (7*28) AWG 2 Yes PVC BMS-PVC cables 5400UE C1020 20 (7*28) AWG 2 PVC BMS-PVC cables 5401FE C1021 20 (7*28) AWG 3 Yes PVC BMS-PVC cables 5401UE C1022 20 (7*28) AWG 3 PVC BMS-PVC cables 5402FE C1023 20 (7*28) AWG 4 Yes PVC BMS-PVC cables 5402UE C1024 20 (7*28) AWG 4 PVC BMS-PVC cables 7731A C1280 14 AWG 1 Yes PVC RG-11 Coaxial Cable (BC) 7860E C1038 23 AWG 4 Yes CAT6 FTP Cable 7965E C1037 23 AWG 4 CAT 6 UTP Cable 8205 C1300 20 (7*28) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable 8205NH C1415 20 (7*28) AWG 1 HFFR High Conductivity Speaker and BMS-PVC-TC Cable 8259 C1046 20 (10*33) AWG 1 Yes PVC RG-58 Coaxial Cable 8442 C1301 22 (7*30) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable 8442NH C1416 22 (7*30) AWG 1 HFFR BMS-HFFR cables 8471 C1198 16 (19*29) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable 8471NH C1307 16 (19*29) AWG 1 HFFR BMS-HFFR cables 8473 C1222 14 (19*27) AWG 2 PVC High Conductivity Speaker and BMS-PVC-TC Cable 8473NH C1306 14 (19*27) AWG 2 HFFR BMS-HFFR cables       info.btcables@bt.com 7
  • 8. BT Cables - Belden equivalents Belden P/N BT Cables P/N Conductor Size No. of Conductors No. of Pairs Individually shielded pairs Collective shield Jacket BT Cables Brand and Additional Data 8477 C1302 12 (19*25) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable 8477NH C1417 12 (19*25) AWG 1 HFFR BMS-HFFR cables 8718NH C1303 12 (19*25) AWG 1 Yes HFFR BMS-HFFR cables 8719 C1213 16 (19*29) AWG 2 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable 8719NH C1270 16 (19*29) AWG 2 HFFR BMS-HFFR cables 8720 C1224 14 (19*27) AWG 2 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable 8720NH C1305 14 (19*27) AWG 2 Yes HFFR BMS-HFFR cables 8723 C1196 22 (7*30) AWG 2 Yes PVC Individually Shielded TP BMS-PVC-TC Cable 8723NH C1281 22 (7*30) AWG 2 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable 8723PE C1316 22 (7*30) AWG 2 Yes PE Individually Shielded TP BMS-PE-TC Cable 8760 C1193 18 (7*26) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable 8760NH C1272 18 (7*26) AWG 1 Yes HFFR BMS-HFFR cables 8761 C1199 22 (7*30) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable 8761NH C1310 22 (7*30) AWG 1 Yes HFFR BMS-HFFR cables 8762 C1195 20 (7*28) AWG 1 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable 8762NH C1308 20 (7*28) AWG 1 Yes HFFR BMS-HFFR cables 8770 C1225 18 (7*26) AWG 3 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable 8772 C1245 20 (7*28) AWG 3 Yes PVC High Conductivity Speaker and BMS-PVC-TC Cable 8777 C1197 22 (7*30) AWG 3 Yes PVC Individually Shielded TP BMS-PVC-TC Cable 8777NH C1282 22 (7*30) AWG 3 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable 8777PE C1317 22 (7*30) AWG 3 Yes PE Individually Shielded TP BMS-PE-TC Cable 8778 C1214 22 (7*30) AWG 6 Yes PVC Individually Shielded TP BMS-PVC-TC Cable 8778NH C1314 22 (7*30) AWG 6 Yes HFFR Individually Shielded TP BMS-HFFR-TC Cable 9100 C1025 20 AWG 1 Yes PVC RG-59 Coaxial Cable (CCS) 9116 C1026 18 AWG 1 Yes PVC RG-6 Coaxial Cable (CCS) 9259 C1275 20 (19*33) 1 Yes PVC RG-59 Coaxial CCTV cable 9463F C1079 20 (42*36) AWG 1 Yes PVC Twinax - Blue Hose cable 9501 C1181 24 (7*32) AWG 1 Yes PVC RS-232 Computer Cable 9501NH C1441 24 (7*32) AWG 1 Yes HFFR RS-232 Computer Cable 9501PE C1451 24 (7*32) AWG 1 Yes PE RS-232 Computer Cable 9502 C1182 24 (7*32) AWG 2 Yes PVC RS-232 Computer Cable 9502NH C1442 24 (7*32) AWG 2 Yes HFFR RS-232 Computer Cable 9502PE C1452 24 (7*32) AWG 2 Yes PE RS-232 Computer Cable 9503 C1183 24 (7*32) AWG 3 Yes PVC RS-232 Computer Cable 9503NH C1443 24 (7*32) AWG 3 Yes HFFR RS-232 Computer Cable 9503PE C1453 24 (7*32) AWG 3 Yes PE RS-232 Computer Cable 9504 C1184 24 (7*32) AWG 4 Yes PVC RS-232 Computer Cable 9504NH C1444 24 (7*32) AWG 4 Yes HFFR RS-232 Computer Cable 9504PE C1454 24 (7*32) AWG 4 Yes PE RS-232 Computer Cable 9505 C1185 24 (7*32) AWG 5 Yes PVC RS-232 Computer Cable 9505NH C1445 24 (7*32) AWG 5 Yes HFFR RS-232 Computer Cable 9505PE C1455 24 (7*32) AWG 5 Yes PE RS-232 Computer Cable 9506 C1186 24 (7*32) AWG 6 Yes PVC RS-232 Computer Cable 9506NH C1446 24 (7*32) AWG 6 Yes HFFR RS-232 Computer Cable 9506PE C1456 24 (7*32) AWG 6 Yes PE RS-232 Computer Cable 9507 C1187 24 (7*32) AWG 7 Yes PVC RS-232 Computer Cable 9507NH C1447 24 (7*32) AWG 7 Yes HFFR RS-232 Computer Cable 9507PE C1457 24 (7*32) AWG 7 Yes PE RS-232 Computer Cable 9508 C1188 24 (7*32) AWG 8 Yes PVC RS-232 Computer Cable 9508NH C1448 24 (7*32) AWG 8 Yes HFFR RS-232 Computer Cable 9508PE C1458 24 (7*32) AWG 8 Yes PE RS-232 Computer Cable 9510NH C1206 24 (7*32) AWG 10 Yes PVC RS-232 Computer Cable 9510NH C1449 24 (7*32) AWG 10 Yes HFFR RS-232 Computer Cable 9536 NH C1358 24 (7*32) AWG 6 Yes HFFR RS-232 Computer Cable 9536 C1398 24 (7*32) AWG 6 Yes PVC RS-232 Computer Cable 9538 C1399 24 (7*32) AWG 8 Yes PVC RS-232 Computer Cable 9538NH C1359 24 (7*32) AWG 8 Yes HFFR RS-232 Computer Cable 9540 C1400 24 (7*32) AWG 10 Yes PVC RS-232 Computer Cable 9571 C1135 18 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9572 C1136 16 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9574 C1040 18 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9575 C1041 16 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9580 C1137 14 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9581 C1042 14 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9582 C1138 12 AWG 1 PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9583 C1043 12 AWG 2 Yes PVC Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed 9728 C1384 24 (7*32) AWG 4 Yes PVC Low Cap Computer Cable 9729 C1382 24 (7*32) AWG 2 Yes PVC Low Cap Computer Cable 9730 C1383 24 (7*32) AWG 1 Yes PVC Low Cap Computer Cable 9740 C1203 18 (7*26) AWG 1 PVC High Conductivity Speaker and BMS-PVC-TC Cable 9740NH C1271 18 (7*26) AWG 1 HFFR BMS-HFFR cables 9773 C1298 22 (7*30) AWG 4 Yes PVC Individually Shielded TP BMS-PVC-TC Cable 9774 C1299 22 (7*30) AWG 5 Yes PVC Individually Shielded TP BMS-PVC-TC Cable 9841 C1189 24 (7*32) AWG 1 PVC RS-485 Low Cap Computer Cable 9841NH C1318 24 (7*32) AWG 1 HFFR RS-485 Low Cap Computer Cable 9841PE C1409 24 (7*32) AWG 1 PE RS-485 Low Cap Computer Cable 9842 C1190 24 (7*32) AWG 2 PVC RS-485 Low Cap Computer Cable 9842NH C1319 24 (7*32) AWG 2 HFFR RS-485 Low Cap Computer Cable 9843 C1191 24 (7*32) AWG 3 PVC RS-485 Low Cap Computer Cable 9843NH C1320 24 (7*32) AWG 3 HFFR RS-485 Low Cap Computer Cable 9844 C1192 24 (7*32) AWG 4 PVC RS-485 Low Cap Computer Cable 9844NH C1321 24 (7*32) AWG 4 HFFR RS-485 Low Cap Computer Cable 9913 C1047 10 AWG 1 Yes PVC RG-8 Series Coaxial Cable 1227A1 C1031 24 AWG 2 PVC CAT 3 UTP Cable 1232A1 C1032 24 AWG 25 PVC CAT 3 UTP Cable 43051 C1208 0.4 mm 8 Yes PVC 8 Pair/0.4 Braided Telecoms Cable 43113 C1207 26 AWG 1 Yes HFFR TELCO 75 Ohm Coaxial Cable 513945 C1030 14 AWG 1 Yes PVC RG-11 Coaxial Cable (BC) 533945 C1029 18 AWG 1 Yes PVC RG6 Series Coaxial Cable (BC) 543945 C1028 20 AWG 1 Yes PVC RG-59 Coaxial Cable (BC) 9842NH C1319 24 (7*32) AWG 2 Yes HFFR 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 9842PE C1410 24 (7*32) AWG 2 Yes PE 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 9843NH C1320 24 (7*32) AWG 3 Yes HFFR 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket       info.btcables@bt.com 8
  • 9. BT Cables - Belden equivalents Belden P/N BT Cables P/N Conductor Size No. of Conductors No. of Pairs Individually shielded pairs Collective shield Jacket BT Cables Brand and Additional Data 9843PE C1411 24 (7*32) AWG 3 Yes PE 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 9844NH C1321 24 (7*32) AWG 4 Yes HFFR 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 9844PE C1412 24 (7*32) AWG 4 Yes PE 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket MRG2130 C1048 2.25 (7*0.75) mm 1 Yes PVC RG213 Series Coaxial cable MRG214 C1049 2.25 (7*0.75) mm 1 Yes PVC RG214 Series Coaxial Cable YE00819 C1219 0.8 1 Yes PVC KNX (was EIB) CABLE YE00820 C1217 0.8 2 Yes PVC KNX (was EIB) CABLE YE00905 C1220 0.8 1 Yes HFFR KNX (was EIB) CABLE YE00906 C1218 0.8 2 Yes HFFR KNX (was EIB) CABLE       info.btcables@bt.com 9
  • 10. Section 1 - BT BMS-TECTM - Paired Cables PVC, PE or HFFR sheathed cables for BUS and Interface Systems 1. Application RS-232, RS-422, RS-485, KNX (EIB or Instabus), LonWorks, ModBus, M-Bus, CAN-bus, BACnet, BMS (Building Management Systems) or general interface systems. 2. Basic Construction of the cables Wire = conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: may be solid = one single rod or flexible = twisted bare or tinned copper strands, ranging from 12 to 24AWG. Conductor (AWG) Configuration (AWG) Configuration (mm) DC Resistance (Ohm/km) 24 7 x 32 7 x 0.20 ≤ 88 22 7 x 30 7 x 0.25 ≤ 57.4 20 7 x 28 7 x 0.32 ≤ 32.16 18 7 x 26 7 x 0.40 ≤ 22.7 16 19 x 29 19 x 0.28 ≤ 15.47 14 19 x 27 19 x 0.36 ≤ 9.36 12 19 x 25 19 x 0.45 ≤ 5.61 Insulation: Polyethylene (PE) or Foam PE (FPE) for PVC (Polyvinyl Chloride) or Halogen-Free (HFFR) sheathed cables. And Halogen-Free (HFFR) for HFFR sheathed cables. All insulations are in accordance with BS EN 50290-2, good strippable and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Cable core: two or more (individually screened) pairs stranded. Good twisting (lay-length < 30 ~ 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Braiding (if applicable): tinned copper wires. Sheath: grey PVC , black PE or purple HFFR, all in accordance with BS EN 50290-2. Cable Configuration Cable Retardancy Low Smoke Halogen-free (non acid, non toxic) RoHS compliantInsulation Sheath PE, FPE or PVC PVC according to IEC 60332-1 No No Yes PE, FPE or PVC PE No No Only with (F)PE insulation Yes PE, FPE or HFFR HFFR according to IEC 60332-3-24 according to IEC 61034-1-2 according to IEC 60754-1 & 2 Yes Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms       info.btcables@bt.com 10
  • 11. RS-232: Hand shake interface used for low data rates. Computer to printer or to modem or to another device. RS-422: Balanced digital circuit. Medium speed data exchange. Long line modems and Daisy chain configuration. RS-485: Balanced digital circuit. Medium speed fieldbus interfaces. RS-232 RS-422 RS-485 Differential no yes yes Max. number of drivers Max. number of receivers 1 1 1 10 1 32 Modes of operation full duplex half duplex half duplex Network topology point-to-point multidrop multidrop Max. distance acc. to standard 15 m 1200 m 1200 m Max. speed at 12 m. Max. speed at 1200 m. 20 kbs 1 kbs 10 Mbs 100 kbs 35 Mbs 100 kbs Cables used Conductor size mainly 24 AWG mainly 24 AWG mainly 24 AWG Number of conductors 6 to 25 2 pairs or more 1 pair or more Impedance not defined 100 Ohm 120 Ohm BT Cables main part numbers see section 1.3 section 1.2 section 1.1 KNX is a standardised (EN 50090, ISO/IEC 14543), OSI-based network communications protocol for intelligent buildings. KNX is the successor to, and convergence of, three previous standards: the European Home Systems Protocol (EHS), BatiBUS, and the European Installation Bus (EIB or Instabus). BT Cables main part numbers for KNX cables: C1217 (quad – PVC) – C1218 (quad – HFFR) – C1219 (1 pair – PVC) – C1220 (1 pair – HFFR). LonWorks is a networking platform specifically created to address the needs of control applications. The platform is built on a protocol created by Echelon Corporation for networking devices over media such as twisted pair, power lines, fibre optics, and RF. It is used for the automation of various functions within buildings such as lighting and HVAC. BT Cables main part numbers for LonWorks: C1198 (PVC) - C1203 (PVC) – C1307 (HFFR) – C1271 (HFFR) – C1346 (HFFR) – C1347 (HFFR) – C1348 (HFFR) and C1349 (HFFR). Modbus is a serial communications protocol published by Modicon in 1979 for use with its programmable logic controllers (PLCs). Simple and robust, it has since become one of the de facto standard communications protocols in the industry. BT Cables main part numbers for Modbus: C1197 (PVC) - C1193 (PVC) – C1282 (HFFR) – C1272 (HFFR). M-Bus (Meter-Bus) is a European standard (EN 13757-2 physical and link layer, EN 13757-3 application layer) for the remote reading of gas or electricity meters. M-Bus is also usable for other types of consumption meters. BT Cables main part number for M-bus: C1020 – C1193. Controller–area network (CAN or CAN-bus) is a vehicle bus standard designed specifically for automotive applications but now also used in other areas such as industrial automation and medical equipment. CAN bus utilize TIA/EIA-485 cables. BT Cables main part numbers for CAN-bus: C1080 - C1189 – C1190 – C1191 – C1192 – C1295 – C1296 – C1297 and HFFR cables C1318 – C1319 – C1320 – C1321. BACnet is a communications protocol for building automation and control networks. It is was designed to allow communication of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems and their associated equipment. BACnet over IP can utilize Cat 6. BT Cables main part numbers for BACnet: C1228 (PVC) – C1189 (PVC) – C1190 (PVC) - C1318 (HFFR) and C1319 (HFFR).       info.btcables@bt.com 11
  • 12. Section 1.1 Paired Cables for TIA/EIA-485 = RS-485 applications 22 and 24AWG conductors – PE or FPE insulation – Dual Screen - PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 2. Insulation Polyethylene (PE) or Foam PE (FPE) 3. Pair Impedance 120 Ω 4. Tinned Copper Drain Wire 24 AWG(7 x 32) 5. Screen Aluminium/Polyester 6. Braiding Tinned Copper wires 7. Sheath Material Grey PVC or Purple HFFR Standard Put Up Length 305 or 500 meters Standard References TIA/EIA-485 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives Cables with 24 AWG conductors – PE insulation - PVC sheath BTCL Part Number No of pairs Conductor (AWG) Max. DC Resistance Conductor (Ω/km) Coverage braiding (%) Sheath Overall Diameter (mm) Capacitance (pF/m) Weight (kg/km) C1189 1 24 (7 x 32) 88 90 PVC 5.9 41 49 C1190 2 24 (7 x 32) 88 90 PVC 8.5 41 80.5 C1191 3 24 (7 x 32) 88 90 PVC 9.0 41 92.6 C1192 4 24 (7 x 32) 88 90 PVC 9.9 41 114.4 C1318 1 24 (7 x 32) 88 90 HFFR 5.9 41 49 C1319 2 24 (7 x 32) 88 90 HFFR 8.5 42 80.5 C1320 3 24 (7 x 32) 88 90 HFFR 9.0 42 92.6 C1321 4 24 (7 x 32) 88 90 HFFR 9.9 42 114.4 Cables with 22 AWG conductors – Foam PE insulation - Halogen-free (HFFR) sheath BTCL Part Number No of pairs Conductor (AWG) Max. DC Resistance Conductor (Ω/km) Coverage braiding (%) Sheath Overall Diameter (mm) Capacitance (pF/m) Weight (kg/km) C1080 1 22 (7 x 30) 57.4 65 PVC 6.1 36 63.7 C1295 2 22 (7 x 30) 57.4 65 PVC 9.1 37 75.6 C1296 3 22 (7 x 30) 57.4 65 PVC 10.5 38 97 C1297 4 22 (7 x 30) 57.4 65 PVC 11.4 38 119.1 C1401 1 22 (7 x 30) 57.4 65 HFFR 6.1 36 63.7 C1402 2 22 (7 x 30) 57.4 65 HFFR 9.1 37 75.6 C1403 3 22 (7 x 30) 57.4 65 HFFR 10.5 38 97 C1404 4 22 (7 x 30) 57.4 65 HFFR 11.4 38 119.1 Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Wire a (insulation colour / colour of stripe) White / blue White / orange White / green White / brown Wire b (insulation colour / colour of stripe) Blue / white Orange / white Green / white Brown /white For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 12
  • 13. Section 1.2 Cables with 2 to 6 pairs for RS-422 applications 24AWG conductors – FPE insulation – every pair screened - PVC sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 2. Insulation Foam Polyethylene (FPE) 3. Pair Two twisted wires 4. Drain Wire Flexible Tinned Copper 24 AWG (7 x 32) 5. Screen Aluminium/Polyester Wrapped around each Pair 6. Cable core 2 or more individually screened pairs stranded 7. Sheath Material Grey PVC Standard Put Up Length 305 or 500 metres Standard References ANSI/TIA/EIA-422-B (BS) EN 50290-2 IEC 60332-1 RoHS directives Cables with 24 AWG conductors – PE insulation – PVC sheath BTCL Part Number No. of Pairs Conductor and Drain Wire (AWG) Max. DC Resistance Conductor (Ω/km) Overall Diameter (mm) Capacitance (pF/m) Impedance (Ohm) Weight (kg/km) C1382 2 24 (7 x 32) 88 6.7 41 100 41.8 C1383 3 24 (7 x 32) 88 8.4 41 100 59.4 C1384 4 24 (7 x 32) 88 9.2 41 100 75.5 C1386 6 24 (7 x 32) 88 10.6 41 100 104.8 Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6 C1382 to C1386 Black/Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 13
  • 14. Section 1.3 Cables with 2 to 8 pairs for RS-232 applications 24AWG conductors – PVC insulation – overall screen – PVC, PE or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 24AWG(7x32) 2. Insulation PVC or HFFR 3. Pair Two twisted wires 4. Cable core 2 or more pairs stranded 5. Tinned Copper Drain Wire 24 AWG(7 x 32) 6. Screen Aluminium/Polyester 7. Sheath Material Grey PVC Purple HFFR Black PE Standard Put Up Length 305 or 500 metres Standard References ANSI/TIA/EIA-232-F (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) RoHS directives BTCL Part Number No. of Pairs Insulation Sheath Conductor and Drain Wire Max. DCR Conductor (Ω/km) Overall Diameter Capacitance Weight C1181 1 PVC PVC 24 (7 x 32) 88 4.0 135 18 C1182 2 PVC PVC 24 (7 x 30) 88 5.6 76 28 C1183 3 PVC PVC 24 (7 x 30) 88 5.9 76 39 C1184 4 PVC PVC 24 (7 x 30) 88 6.7 80 48 C1185 5 PVC PVC 24 (7 x 30) 88 7.3 80 57 C1186 6 PVC PVC 24 (7 x 30) 88 7.4 80 65 C1187 7 PVC PVC 24 (7 x 30) 88 7.5 80 68 C1188 8 PVC PVC 24 (7 x 30) 88 8.3 80 76 BTCL Part Number No. of Pairs Insulation Sheath Conductor and Drain Wire Max. DCR Conductor (Ω/km) Overall Diameter Capacitance Weight C1441 1 HFFR HFFR 24 (7 x 32) 88 4.0 95 18 C1442 2 HFFR HFFR 24 (7 x 30) 88 5.6 55 28 C1443 3 HFFR HFFR 24 (7 x 30) 88 5.9 55 39 C1444 4 HFFR HFFR 24 (7 x 30) 88 6.7 60 48 C1445 5 HFFR HFFR 24 (7 x 30) 88 7.3 60 57 C1446 6 HFFR HFFR 24 (7 x 30) 88 7.4 60 65 C1447 7 HFFR HFFR 24 (7 x 30) 88 7.5 60 73 C1448 8 HFFR HFFR 24 (7 x 30) 88 8.3 60 85 C1449 10 HFFR HFFR 24 (7 x 30) 88 9.2 60 95 BTCL Part Number No. of Pairs Insulation Sheath Conductor and Drain Wire Max. DCR Conductor (Ω/km) Overall Diameter Capacitance Weight C1451 1 PVC PE 24 (7 x 32) 88 4.0 135 14.5 C1452 2 PVC PE 24 (7 x 30) 88 5.6 76 24.5 C1453 3 PVC PE 24 (7 x 30) 88 5.9 76 31 C1454 4 PVC PE 24 (7 x 30) 88 6.7 80 39 C1455 5 PVC PE 24 (7 x 30) 88 7.3 80 47 C1456 6 PVC PE 24 (7 x 30) 88 7.4 80 55 C1457 7 PVC PE 24 (7 x 30) 88 7.5 80 59 C1458 8 PVC PE 24 (7 x 30) 88 8.3 80 67 Colour scheme of the pairs Pair number Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6 Pair 7 Pair 8 Pair 10 Wire a Black Black Black Black Black Black Black Red Red Wire b Red White Green Blue Yellow Brown Orange White Blue For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 14
  • 15. Section 1.4 Cables for KNX (was EIB or Instabus) applications 0.8 mm conductors – PE insulation – overall screen - PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Solid Bare Copper 0.8 mm = 0.5 mm2 2. Insulation Polyethylene (PE) Black-Red- White-Green 3. Cable Core Quad or Pair 4. Polyester tape 5. Drain Wire 0.4 mm Tinned Copper 6. Screen Aluminium/Polyester 7 Sheath Material Green PVC or Green HFFR Standard Put Up Length 305 or 500 metres Standard References EN 50090 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives BTCL Part Number No. of wires Lay-Up Sheath Material Diameter Insulation (mm) Overall Diameter (mm) Max. DC Resistance Conductor (Ω/km) Capacitance (pF/m) Weight (kg/km) C1217 1 x 4 quad PVC 1.45 6.1 37 ≤ 100 51 C1218 1 x 4 quad HFFR 1.45 6.1 37 ≤ 100 53 C1219 1 x 2 pair PVC 1.45 5.5 37 ≤ 100 37 C1220 1 x 2 pair HFFR 1.45 5.5 37 ≤ 100 39 BTCL Part Number Wire a Wire b Wire c Wire d C1217 Black White Red Green C1218 Black White Red Green C1219 Black White C1220 Black White For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 15
  • 16. Section 1.5 Cables for LonWorks applications 0.64 mm conductors – PE or FPE insulation Individually screened pairs or unscreened pairs - HFFR sheath CABLE DESCRIPTION 1. Conductor Solid Bare Copper 0.64 mm = 0.32 mm² 2. Insulation Polyethylene (PE) or Foam Polyethylene (FPE) 3. Pairs with no screen two twisted wires 4. Individually screened pair two twisted wires plus drain wire wrapped with an Aluminium/Polyester foil 5. Cable core one pair or two pairs stranded 6 Sheath Material Purple HFFR Standard Put Up Length 305 or 500 metres Standard References EN 50090 (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives BTCL Part Number No. of pairs Insulation Material Indiv. screened pairs Overall Diameter (mm) Max. DC Resistance Conductor (Ω/km) Capacitance (pF/m) Weight (kg/km) C1346 1 Solid PE No 3.5 61 46 17.1 C1347 2 Solid PE No 5.2 61 46 27.7 C1348 1 Foam PE Yes 4.6 61 46 24.2 C1349 2 Foam PE Yes 7.6 61 46 56.1 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 16
  • 17. Section 1.6 Cables for General Interface applications 2 to 6 pairs – 22AWG conductors – PE or HFFR insulation Individually screened pairs – PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 22AWG(7 x 30) 2. Insulation Polyethylene (PE) or Halogen-free (HFFR) 3. Pair Two twisted wires 4. Tinned Copper Drain Wire 24 AWG(7 x 32) 5. Screen Aluminium/Polyester foil wrapped around each pair 6. Cable core 2 or more individually screened pairs stranded 7. Sheath Material Grey PVC or Purple HFFR Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives BTCL Part Number No. of pairs Insulation Material Sheath Material Overall Diameter (mm) Max. DC Resistance Conductor (Ω/km) Capacitance (pF/m) Weight (kg/km) C1196 2 PE PVC 6.0 57.4 90 36.1 C1281 2 HFFR HFFR 6.5 57.4 150 50.8 C1197 3 PE PVC 6.5 57.4 98 49.1 C1282 3 HFFR HFFR 7.5 57.4 155 67.4 C1298 4 PE PVC 7.0 57.4 98 62 C1299 5 PE PVC 7.7 57.4 99 74.2 C1214 6 PE PVC 8.9 57.4 99 87.2 C1314 6 HFFR HFFR 9.5 57.4 155 115.6 Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6 C1196 and C1281 Black/ Red Green/White C1197 and C1282 Black/ Red Black/White Black/Green C1298 Black/ Red Black/White Black/Green Black/Blue C1299 Black/ Red Black/White Black/Green Black/Blue Black/Yellow C1214 and C1314 Black/ Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 17
  • 18. Section 1.7 Cables for General Interface applications One pair – 22 to 12AWG conductors – PE insulation Collective (overall) screen – PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 2. Insulation PVC or Polyethylene (PE) or Halogen-free (HFFR) 3. Pair Two wires twisted 4. T.C. Drain Wire (only with screen) 24 AWG(7 x 32) 5. Screen (if applicable) Aluminium/Polyester 6. Sheath Material Grey PVC or Purple HFFR Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives DC Resistance 12 to 22 AWG conductors Conductor AWG 22 20 18 16 14 12 No. of strands x gauge AWG 7 x 30 7 x 28 7 x 26 19 x 29 19 x 27 19 x 25 No. of strands x mm Mm 7 x 0.25 7 x 0.32 7 x 0.40 19 x 0.28 19 x 0.36 19 x 0.45 Max. DC resistance conductor Ω/km 57.4 35.75 22.7 15.47 9.36 5.61 One pair cables with PE insulation and PVC sheath Screened Unscreened BTCL Part Number Cond. (AWG) Overall Diameter (mm) Capacity (pF/m) Weight (kg/km) BTCL Part Number Cond. (AWG) Overall Diameter (mm) Capacity (pF/m) Weight (kg/km) C1199 22 4.4 75 25 C1301 22 4.0 70 19.5 C1195 20 5.0 75 36.4 C1300 20 4.3 80 23 C1193 18 5.6 75 43.2 C1203 18 5.1 85 38.6 C1213 16 7.9 60 75.7 C1198 16 6.9 90 63.3 C1224 14 9.0 76 104.9 C1222 14 8.6 108 91.8 C1313 12 10.2 77 124.7 C1302 12 9.8 115 115 One pair cables with HFFR insulation and HFFR sheath Screened Unscreened BTCL Part Number Cond. (AWG) Overall Diameter (mm) Capacity (pF/m) Weight (kg/km) BTCL Part Number Cond. (AWG) Overall Diameter (mm) Capacity (pF/m) Weight (kg/km) C1310 22 4.8 140 27.1 C1311 22 4.7 48 24.7 C1308 20 5.3 158 37.2 C1309 20 5,2 52 34.7 C1272 18 6.0 165 48.4 C1271 18 5.9 65 45.9 C1270 16 7.8 150 74.3 C1307 16 7.7 48 71.8 C1305 14 8.8 180 97.9 C1306 14 8.7 55 95.3 C1303 12 9.8 195 132.6 C1304 12 9.7 57 128.2 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 18
  • 19. Section 1.8 Cables for Security & Alarm applications 1 to 6 pairs – 18AWG conductors – polyolefin insulation foil or foil + braid overall screen –HFFR sheath CABLE DESCRIPTION Design 1. Conductor Flexible Bare Copper 2. Insulation Polyolefin 3. Pair Two twisted wires 4. Cable core N pairs stranded 5. Drain Wire Flexible Tinned Copper 24 AWG (7 x 32) 6. Overall Screen 1 Aluminium/Polyester foil 7. Overall Screen 2 braid coverage 8. Sheath Material Purple Halogen-free (HFFR) Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-3-24 IEC 61034 IEC 60754-1 & 2 RoHS directives Cables with 18AWG conductors – Polyolefin insulation – Collective Screen and HFFR sheath BTCL Part Number No. of Pairs Conductor (AWG) Screen Max. DC Resistance Conductor (Ω/km) Overall Diameter (mm) Capacitance (pF/m) Weight (kg/km) C1171 1 18 (7 x 26) foil 22.7 5.1 115 4.1 C1172 2 18 (7 x 26) foil 22.7 7.7 115 7.41 C1173 3 18 (7 x 26) foil 22.7 8.1 115 9.64 C1174 4 18 (7 x 26) foil 22.7 8.9 115 12.37 C1175 5 18 (7 x 26) foil 22.7 9.9 115 14.92 C1176 6 18 (7 x 26) foil 22.7 10.2 115 17.11 BTCL Part Number No. of Pairs Conductor (AWG) Screen Max. DC Resistance Conductor (Ω/km) Overall Diameter (mm) Capacitance (pF/m) Weight (kg/km) C1418 1 18 (7 x 26) foil + braid 22.7 5.8 115 4.7 C1419 2 18 (7 x 26) foil + braid 22.7 8.4 115 10.5 C1420 3 18 (7 x 26) foil + braid 22.7 8.8 115 11.6 C1421 4 18 (7 x 26) foil + braid 22.7 9.6 115 13.7 C1422 5 18 (7 x 26) foil + braid 22.7 10.5 115 16.5 C1423 6 18 (7 x 26) foil + braid 22.7 10.9 115 18.6 Colour scheme Pair 1 Pair 2 Pair 3 Pair 4 Pair 5 Pair 6 C1171 to C1176 Black/Red Black/White Black/Green Black/Blue Black/Yellow Black/Brown For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 19
  • 20. Section 1.9 Cable for Building Management Systems 1 pair – 0.6 mm² conductors – polyolefin insulation Collective overall screen –PVC sheath CABLE DESCRIPTION 1. Conductor Flexible Bare Copper 7 x 0.35 mm = 0.6 mm² 2. Insulation Polyolefin Core 1: Black Core 2: Red 3. Pairs two twisted wires 4. Tinned Copper Drain Wirer 7 x 0.20 mm 5. Screen Aluminium/Polyester foil 6 Sheath Material Grey PVC Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 RoHS directives BTCL Part Number No. of pairs Overall Diameter (mm) Max. DC Resistance Conductor (Ω/km) Capacitance (pF/m) Weight (kg/km) C1381 1 3.9 61 110 14.6 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 20
  • 21. Section 2 - BT BMS-TECTM - Multi-Conductor Cables Application and Construction 1. Application All PVC and HFFR sheathed multi-conductor cables are suitable for Building Management Systems (BMS), Sound, Audio, Security, Safety, Control and Instrumentation. 2. Basic Construction of the cables Wire = Conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: flexible = twisted bare or tinned copper strands, ranging from 12 to 22AWG. Conductor (AWG) configuration (AWG) configuration (mm) DC Resistance (Ohm/km) 24 7 x 32 7 x 0.2 ≤ 88 22 7 x 30 7 x 0.25 ≤ 57.4 20 7 x 28 7 x 0.32 ≤ 32.16 18 7 x 26 7 x 0.40 ≤ 22.7 16 19 x 29 19 x 0.28 ≤ 15.47 14 19 x 27 19 x 0.36 ≤ 9.36 12 19 x 25 19 x 0.45 ≤ 5.61 Insulation: Polypropylene (PP) for PVC (Polyvinyl Chloride) sheathed cables and Halogen-Free (HFFR) for HFFR sheathed cables. Both insulations are in accordance with BS EN 50290-2. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme of wires with 12 or 14 AWG conductors: black-white-red-green-brown-blue-orange-yellow-purlpe-grey-pink- tan. Colour scheme of wires with ≥ 16AWG conductors: black-red-white-green-brown-blue-orange-yellow-purlpe-grey-pink-tan. Cable core: two or more wires, twisted. Good twisting (lay-length < 30 – 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: grey PVC or purple HFFR or black UV-resistant HFFR, all in accordance with BS EN 50290-2. Cable configurations Cables with PVC sheath Halogen-Free cables Insulation PP acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2 Sheath PVC acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2 Retardancy Flame Retardant Fire Retardant Retardant acc. to IEC 60332-1 / UL1581 IEC 60332-3-24 / UL 1685 Low Smoke emission acc. to Not applicable IEC 61034 Halogen-free acc. to Not applicable IEC 60754 RoHS compliant Yes yes Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms. Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.       info.btcables@bt.com 21
  • 22. Section 2.1 – Multi-Conductor Cables PVC sheathed cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRPTION Design 1. Conductor Stranded Bare Copper 2. Insulation Polypropylene (PP) 3 Cable Core Two or more wires stranded 4 Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper 5 Screen (if applicable) Aluminium/Polyester > 100% Coverage 6. Sheath Material Grey PVC Standard Put Up Length 305 and 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 RoHS directives No of wires Cond. (AWG) BT Cables Part Number Scrn Diam. (mm) Weight (kg/km) BT Cables Part Number Scrn Diam. (mm) Weight (kg/km) 2 22 C1226 Yes 3.3 16.5 C1227 No 3.3 14.6 3 22 C1228 Yes 3.5 21.4 C1278 No 3.5 19.7 4 22 C1230 Yes 3.8 26 C1231 No 3.8 23.9 6 22 C1264 Yes 4.5 35.7 C1265 No 4.5 33.6 8 22 C1232 Yes 4.9 45.1 C1233 No 4.9 43 2 20 C1019 Yes 3.5 22 C1020 No 3.4 19.7 3 20 C1021 Yes 3.7 28.5 C1022 No 3.6 26.2 4 20 C1023 Yes 4.1 35.4 C1024 No 4.0 33.1 6 20 C1260 Yes 5.0 49.9 C1261 No 4.9 47.9 8 20 C1262 Yes 5.4 62.9 C1263 No 5.3 60.6 2 18 C1013 Yes 4.0 29.6 C1014 No 3.9 27.3 3 18 C1015 Yes 4.2 39.2 C1016 No 4.1 36.9 4 18 C1017 Yes 4.6 49.4 C1018 No 4.55 47.2 6 18 C1211 Yes 5.75 70.9 C1212 No 5.7 68.2 8 18 C1258 Yes 6.0 89.5 C1259 No 5.9 87 2 16 C1007 Yes 4.6 37.3 C1008 No 4.5 35 3 16 C1009 Yes 4.9 50 C1010 No 4.75 47.7 4 16 C1011 Yes 5.3 63.5 C1012 No 5.25 61.1 6 16 C1252 Yes 6.8 91.6 C1253 No 6.7 89 8 16 C1254 Yes 7.6 120.8 C1255 No 7.5 118.1 2 14 C1001 Yes 6.0 57 C1002 No 5.75 53.3 3 14 C1003 Yes 6.5 77.9 C1004 No 6.35 72.5 4 14 C1005 Yes 6.9 102.5 C1006 No 6.75 97.1 6 14 C1248 Yes 8.6 151 C1249 No 8.4 148.2 8 14 C1250 Yes 9.8 197.3 C1251 No 9.7 194.5 2 12 C1322 Yes 6.9 85.7 C1323 No 6.7 79.8 3 12 C1324 Yes 7.4 118.1 C1325 No 7.2 112.1 4 12 C1326 Yes 8.2 151.1 C1327 No 8.0 145.3 6 12 C1330 Yes 9.8 215.5 C1331 No 9.6 209.7 8 12 C1332 Yes 10.7 279.5 C1333 No 10.5 273.7 Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s       info.btcables@bt.com 22
  • 23. Section 2.2 – Multi-Conductor Cables Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION Design 1. Conductor Stranded Bare Copper 2. Insulation HFFR 3. Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper 4. Screen (if applicable) Aluminium/Polyester > 100% Coverage 5. Ripcord 6. Sheath Material Purple Halogen-Free (HFFR) Standard Put Up Length 305 metres Standard References (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives No of wires Cond. (AWG) BT Cables Part Number Scrn Diam. (mm) Weight (kg/km) BT Cables Part Number Scrn Diam. (mm) Weight (kg/km) 2 22 C1741 Yes 3.9 22.4 C1742 No 3.9 20.5 3 22 C1743 Yes 4.1 27.6 C1744 No 4.1 26.0 4 22 C1745 Yes 4.4 33.7 C1746 No 4.4 31.7 6 22 C1747 Yes 5.2 45.8 C1748 No 5.2 43.9 8 22 C1749 Yes 5.6 56.4 C1750 No 5.6 54.4 2 20 C1731 Yes 4.7 32.6 C1732 No 4.6 30.1 3 20 C1733 Yes 4.9 40.2 C1734 No 4.8 37.7 4 20 C1735 Yes 5.3 48.7 C1736 No 5.2 46.2 6 20 C1737 Yes 6.2 66.2 C1738 No 6.1 63.7 8 20 C1739 Yes 6.7 81.9 C1740 No 6.6 79.4 2 18 C1721 Yes 5.1 41.0 C1722 No 5.0 38.5 3 18 C1723 Yes 5.4 52.3 C1724 No 5.3 49.8 4 18 C1725 Yes 5.8 64.1 C1726 No 5.7 61.6 6 18 C1727 Yes 6.8 88.6 C1728 No 6.7 86.1 8 18 C1729 Yes 7.3 110.8 C1730 No 7.2 108.2 2 16 C1711 Yes 5.4 49.3 C1712 No 5.4 46.8 3 16 C1713 Yes 5.7 63.8 C1714 No 5.7 61.3 4 16 C1715 Yes 6.2 79.3 C1716 No 6.2 78.2 6 16 C1717 Yes 7.3 108.2 C1718 No 7.3 107.0 8 16 C1719 Yes 7.9 137.0 C1720 No 7.9 135.9 2 14 C1701 Yes 6.5 67.7 C1702 No 6.4 65.2 3 14 C1703 Yes 6.9 92.8 C1704 No 6.8 89.1 4 14 C1705 Yes 7.5 115.4 C1706 No 7.4 112.9 6 14 C1707 Yes 8.9 163.7 C1708 No 8.8 162.8 8 14 C1709 Yes 9.6 210.8 C1710 No 9.5 208.3 2 12 C1334 Yes 7.7 102.2 C1335 No 7.5 97.0 3 12 C1336 Yes 8.1 135.0 C1337 No 7.9 129.7 4 12 C1338 Yes 8.9 170.9 C1339 No 8.7 165.7 6 12 C1342 Yes 10.6 243.3 C1343 No 10.4 237.1 8 12 C1344 Yes 11.6 314.6 C1345 No 11.4 306.2 Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s       info.btcables@bt.com 23
  • 24. Section 2.3 – Multi-Conductor Cables UV-Resistant Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION Design 1. Conductor Stranded Bare Copper 2. Insulation HFFR 3. Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper 4. Screen (if applicable) Aluminium/Polyester > 100% Coverage 5. Ripcord 6. Sheath Material Black UV-resistant Halogen-Free (HFFR) Standard Put Up Length 305 metres Standard References (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives No of wires Cond. (AWG) BT Cables Part Number Screen Diameter (mm) Weight (kg/km) 2 18 C1351 Yes 5.1 41.0 3 18 C1352 Yes 5.4 52.3 4 18 C1353 Yes 5.8 64.1 6 18 C1354 Yes 6.8 88.6 8 18 C1355 Yes 7.3 110.8 10 18 C1356 Yes 8.4 135.7 20 18 C1357 Yes 10.7 249.6 No of wires Cond. (AWG) BT Cables Part Number Screen Diameter (mm) Weight (kg/km) 2 16 C1391 Yes 5.5 49.3 3 16 C1392 Yes 5.8 63.8 4 16 C1393 Yes 6.3 79.3 6 16 C1394 Yes 7.4 108.2 8 16 C1395 Yes 8.0 137.0 10 16 C1396 Yes 9.5 173.1 20 16 C1397 Yes 12.1 316.6 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 24
  • 25. Section 3 - BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables Bare Copper 12 to 18AWG, one pair, PVC insulation and Sheath, Screened and Unscreened ©UL Certification: type FPLR rated 105°C - ©UL listed APPLICATION Fire Detection and Alarm Systems Fire Retardancy: UL 1666 Operating temperature range: -40 to +105 °C and Rated Voltage: 300 Vrms CABLE DESCRIPTION 1. Conductor Solid Bare Copper 2. Insulation PVC acc. to UL444 Black and Red 3. Pair Two wires twisted 4. TC Drain Wire (only under screen) 22 AWG (7 x 30) 5. Screen (if applicable) Aluminium/Polyester > 100% Coverage 6. Sheath Material Red PVC acc. to UL444 Standard Put Up Length 305 metres Standard References UL1424 UL444 UL1666 RoHS directives BT Cables Part Number No. of Pairs Conductor ( AWG) Screen Overall Diameter (mm) Max. DC Resistance Conductor (Ω/km) Capacitance (pF/m) Weight (kg/km) C1040 1 18 Yes 5.9 22.7 160 19.2 C1135 1 18 No 5.8 22.7 60 16.0 C1041 1 16 Yes 6.1 15.47 189 28.5 C1136 1 16 No 6.0 15.47 71 25.0 C1042 1 14 Yes 7.8 9.36 160 43.0 C1137 1 14 No 7.7 9.36 69 40.0 C1043 1 12 Yes 8.7 5.61 216 66.0 C1138 1 12 No 8.6 5.61 65 63.0 Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice. POWER-LIMITED CIRCUIT CABLE NO. 000001 1000 FEET F ORM 3       info.btcables@bt.com 25
  • 26. Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables Bare and Flexible Copper Conductors 0.75 to 4.0 mm2 , Silicon insulation and Halogen-free Sheath, Screened and Unscreened 1. Application All Fire Resistant cables are suitable for Security, Safety, Control and Instrumentation with special requirements for circuit integrity in case of a fire. 2. Fire Resistance confirming with BS6387 CWZ: Fire Resistant to BS 6387, Cat. C: exposed to fire at 950°C for 3 hours Fire Resistant to BS 6387, Cat. W: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with water for 15 minutes Fire Resistant to BS 6387, Cat. Z: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with mechanical shock for 15 minutes 3. Fire Retardancy confirming with IEC 60332-3-24 (was 3C) 4. Basic Construction of the cables Wire = Conductor with Insulation Conductor: solid bare copper wires, ranging from 0.75 to 2.5 mm² and the 4.0 mm² conductor consists of stranded bare copper wires = flexible Cross Section (mm²) Diameter (mm) DC Resistance (Ohm/km) Recommended Current (Amp) 0.75 1 x 1.0 ≤ 24.5 ≤ 12 1.0 1 x 1.13 ≤ 18.1 ≤ 18 1.5 1 x 1.4 ≤ 12.1 ≤ 21 2.5 1 x 1.8 ≤ 7.41 ≤ 30 4.0 7 x 0.85 = 2.55 ≤ 4.61 ≤ 40 Insulation: Silicon Rubber blends acc. to BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme: 2 cores: brown – blue, 3 cores: brown – black – grey, 4 and more cores: brown – blue – black – grey – others black numbered. Cable core: two or more cores, twisted. Good twisting is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): solid bare copper. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: red HFFR in accordance with BS EN 50290-2 Operating temperature range: -20 to +90 °C. Rated Voltage: 300/500 Vrms Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.       info.btcables@bt.com 26
  • 27. Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables CABLE DESCRIPTION 1. Conductor Solid or Flexible Bare Copper 2. Insulation Silicon Rubber blend 3. Cable core Two or three wires Twisted 4. BC Drain Wire (only under screen) 5. Screen (if applicable) Aluminium/Polyester > 100% Coverage 6. Sheath Material Red HFFR Standard Put Up Length 305 and 500 metres Standard References BS 6387 CWZ BS 7655 IEC 60332-3C IEC 60754-1 & 2 RoHS directives BT Cables Part Number No. of wires Conductor (mm²) Screen Drain Wire (mm²) Overall Diameter (mm) Max. DC Resistance Conductor (Ω/km) Weight (kg/km) C1284 2 0.75 Yes 0.75 7.5 24.5 67.0 C1139 2 0.75 No 7.4 24.5 61.7 C1159 3 0.75 Yes 0.75 7.9 24.5 83 C1149 3 0.75 No 7.8 24.5 75 C1283 2 1.0 Yes 1.0 7.8 18.1 73.4 C1140 2 1.0 No 7.7 18.1 65.5 C1160 3 1.0 Yes 1.0 8.1 18.1 93 C1150 3 1.0 No 8.0 18.1 83 C1044 2 1.5 Yes 1.5 8.7 12.1 98.1 C1141 2 1.5 No 8.6 12.1 87.6 C1161 3 1.5 Yes 1.5 8.95 12.1 123 C1151 3 1.5 No 8.85 12.1 108 C1045 2 2.5 Yes 2.5 9.9 7.41 134.3 C1142 2 2.5 No 9.8 7.41 119.4 C1162 3 2.5 Yes 2.5 10.3 7.41 174 C1152 3 2.5 No 10.2 7.41 151 C1289 2 4.0 Yes 4.0 12.0 4.61 197.1 C1143 2 4.0 No 11.9 4.61 172.6 C1163 3 4.0 Yes 4.0 12.95 4.61 270 C1153 3 4.0 No 12.85 4.61 234 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 27
  • 28. Section 5 - BT Security-Tec ™– Coaxial Cables Application and Construction of Coax Cables for 75 Ohm Video Systems Applications. CCTV: Closed Circuit Television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors SMATV: Satellite Master Antenna Television used to deliver signals to multiple dwelling units (e.g., apartment buildings and trailer parks). CATV: Central Antenna Television = Cable television is a system of providing television to consumers via radio frequency signals transmitted to televisions. Nowadays also used for internet and telephone. HDTV: High-definition television refers to video having resolution substantially higher than traditional television systems. Telecom and networking: a number of special cable constructions. Basic Cable Design. Coaxial cables are designed to carry radio frequency current of a much higher frequency than the 50 or 60 Hz used in low voltage cables. And this requires special construction to prevent power losses. If an ordinary wire is used to carry high frequency currents, the wire acts as an antenna, and the high frequency currents radiate off the wire as radio waves, causing power losses. To prevent this, in coaxial cable one of the conductors is formed into a tube and encloses the other conductor. This confines the radio waves from the central conductor to the space inside the tube. To prevent the outer conductor, or shield, from radiating, it is connected to electrical ground, keeping it at a constant potential. The dimensions and spacing of the conductors must be uniform throughout the length of the cable. Any abrupt change in the spacing of the two conductors along the cable tends to reflect radio frequency power back toward the source. This acts as a bottleneck, reducing the amount of power reaching the destination end of the cable. Choosing the correct 75 ohm coax cable. Most coaxial cables for video applications have a nominal impedance of 75 ohms. Their differing electrical and physical characteristics make it important to select the correct type of cable to suit the application. Analogue TV RG59 Acceptable performance on cable runs < 225 metres RG6 Gives superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres. RG11 For cable runs greater than 545 metres. CCTV RG59 Acceptable performance on cable runs < 225 metres RG6 Gives for superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres. RG11 For cable runs greater than 545 metres. This table is for reference only. BT Cables survey of Part Numbers. Application Tested Speciality RG-59 RG-6 RG-11 CCTV – PVC sheath 1000 MHz Solid conductor C1028 C1029 C1030 CCTV – HFFR sheath 1000 MHz Solid conductor C1428 C1429 C1430 CCTV 1000 MHz Flexible conductor C1275 C1276 C1277 CATV / SMATV 3000 MHz Dual screen C1025 C1026 C1027 CATV / SMATV 3000 MHz Quad screen C1256 C1257 C1241 HDTV – PVC sheath 4500 MHz Dual Screen 95% C1229 C1279 C1280 HDTV – HFFR sheath 4500 MHz Dual Screen 95% C1378 C1379 C1380 Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms       info.btcables@bt.com 28
  • 29. Section 5.1 – BT Security-Tec ™– 75 ohm coax cables CCTV and Video Applications, sweep tested 1to 1000 MHz CABLE DESCRIPTION 1. Conductor Solid or Flexible Bare Copper 2. Dielectric Foamed Polyethylene (FPE) 3. Braid Bare Copper 4. Sheath Material Polyvinyl Chloride (PVC) or Halogen-Free (HFFR) Standard Put Up Length 305 or 500 metres Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (HFFR cable) IEC 61034 (only HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives Physical Characteristics BT Cables Part Number RG-Type Conductor (mm) Diameter Dielectric (mm) Coverage braid (%) Sheath Material Overall Diameter (mm) Weight (kg/km) C1028 RG-59 0.81 solid 3.71 95 PVC 6.0 47.12 C1428 RG-59 0.81 solid 3.71 95 HFFR 6.0 48.5 C1275 RG-59 19x0.18TC 3.71 95 PVC 6.0 47.12 C1029 RG-6 1.02 solid 4.60 95 PVC 6.8 55.5 C1429 RG-6 1.02 solid 4.60 95 HFFR 6.8 58.2 C1276 RG-6 19x0.22 4.60 95 PVC 6.8 54.66 C1030 RG-11 1.63 solid 7.11 90 PVC 10.0 115.9 C1480 RG-11 1.63 solid 7.11 90 HFFR 10.0 120 C1277 RG-11 19x0.34 7.11 90 PVC 10.0 115.9 Electrical and Physical Characteristics (at 20°C) BT Cables Part Number RG-Type Impedance (Ω) Max. DC Resistance Conductor (Ω/km) Max. DC Resistance screen (Ω/km) Nominal Capacitance (pF/m) Min. Return Loss 1 to 1000 MHZ (dB) C1028 RG-59 75 ± 3 33.5 10.1 53.5 20 C1428 RG-59 75 ± 3 33.5 10.1 53.5 20 C1275 RG-59 75 ± 3 40 10.1 53.5 20 C1029 RG-6 75 ± 3 21.5 10.8 53.5 20 C1429 RG-6 75 ± 3 21.5 10.8 53.5 20 C1276 RG-6 75 ± 3 30 10.8 53.5 20 C1030 RG-11 75 ± 3 8.8 6.5 52.8 20 C1480 RG-11 75 ± 3 8.8 6.5 52.8 20 C1277 RG-11 75 ± 3 8.8 6.5 52.8 20 Nominal Attenuation in dB/100m MHz 5 10 50 100 200 300 400 450 550 700 750 870 1000 RG-59 1.9 2.95 6.23 8.53 11.81 15.3 16.41 18.92 21.03 22.97 24.8 26.84 27.89 RG-6 1.78 2.36 4.92 6.56 9.51 12.43 13.78 15.14 17.15 18.37 19.73 20.26 21.96 RG-11 0.99 1.51 2.96 4.27 6.23 8.27 9.51 10.31 11.51 13.45 13.95 14.87 17.06 For more details, please see the respective detailed datasheet(s).       info.btcables@bt.com 29
  • 30. Section 5.2 – BT Security-Tec ™– 75 ohm coax cables SMATV - CATV and Video applications, sweep tested1to 3000 MHz CABLE DESCRIPTION 1. Conductor Solid Copper Covered Steel (CCS) 2. Dielectric Foamed Polyethylene (FPE) 3. Screen 1 Bonded Aluminium/ Polyester foil 100% coverage 4. Braid 1 Aluminium 5. Braid 2 (Quad scrn only) Aluminium/Polyester foil 100% coverage 6. Screen 2 (Quad scrn only) Aluminium 7. Sheath Polyvinyl Chloride (PVC) Standard Put Up Length 305 or 500 metres Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 RoHS directives Physical Characteristics BT Cables Part Number RG-Type Conductor (mm) Diameter Dielectric (mm) Type of Screen Coverage braid (%) Sheath Material Overall Diameter (mm) Weight (kg/km) C1025 RG-59-3 GHz 0.81 3.71 Dual scrn 54 PVC 6.0 32.42 C1256 RG-59-3 GHz 0.81 3.71 Quad scrn 54 + 46 PVC 6.73 39.4 C1026 RG-6-3 GHz 1.02 4.60 Dual scrn 60 PVC 6.8 41.32 C1257 RG-6-3 GHz 1.02 4.60 Quad scrn 60 + 40 PVC 7.52 49.5 C1027 RG-11-3 GHz 1.63 7.11 Dual scrn 61 PVC 10.0 86.6 C1241 RG-11-3 GHz 1.63 7.11 Quad scrn 60 +40 PVC 10.3 90.6 Dual Screen = Screen 1 + Braid 1 Quad Screen = Screen 1 + Braid 1 + Screen 2 + Braid 2 Electrical and Physical Characteristics (at 20°C) BT Cables Part Number RG-Type Imped. (Ω) Max. DC Resistance Conductor (Ω/km) Max. DC Resistance Screen (Ω/km) Nominal Capacitance (pF/m) Min. Return Loss (dB) < 1000 MHz < 2000 MHz < 3000 MHz C1025 RG-59-3 GHz 75 ± 3 146.5 52 53 20 18 16 C1256 RG-59-3 GHz 75 ± 3 146.5 26 53 20 20 20 C1026 RG-6-3 GHz 75 ± 3 92.2 30 53 20 20 20 C1257 RG-6-3 GHz 75 ± 3 92.2 17 53 20 20 20 C1027 RG-11-3 GHz 75 ± 3 36.5 25 53 20 20 20 C1241 RG-11-3 GHz 75 ± 3 36.5 12 53 20 20 20 Nominal Attenuation in dB/100m MHz 5 10 50 100 200 400 550 870 1250 1750 2150 2500 3000 RG-59 2.92 3.45 5.40 8.21 12.56 16.01 19.36 24.74 30.62 36.71 40.82 44.72 48.64 RG-6 2.2 2.48 5.15 6.6 9.56 13.12 15.45 19.69 24.25 29.26 32.88 35.88 39.83 RG-11 1.25 2.03 3.75 5.01 6.85 7.05 9.65 12.6 16.66 20.28 22.93 25.12 28.08 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 30
  • 31. Section 5.3 – BT Security-Tec ™– 75 ohm coax cables HDTV and HD Video applications, sweep tested1to 4500 MHz CABLE DESCRIPTION 1. Conductor Solid Bare Copper 2. Dielectric Foamed Polyethylene 3. Screen Bonded Aluminium/ Polyester foil 100% coverage 4. Braid Tinned Copper 5. Sheath Material Polyvinyl Chloride (PVC) or Halogen-free (HFFR) Colour: Orange Standard Put Up Length 305 or 500 metres Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1(PVC sheath) or IEC 60332-3C ( HFFR cable) IEC 61034 (HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives Physical Characteristics BT Cables Part Number RG-Type Conductor (mm) Diameter Dielectric (mm) Coverage braid (%) Sheath Material Overall Diameter (mm) Weight (kg/km) C1229 RG-59-4.5 GHz 0.81 3.71 95 PVC 6.0 46.72 c1378 RG-59-4.5 GHz 0.81 3.71 95 HFFR 6.0 48.2 C1279 RG-6-4.5 GHz 1.02 4.60 95 PVC 6.8 56.2 c1379 RG-6-4.5 GHz 1.02 4.60 95 HFFR 6.8 59 C1280 RG-11-4.5 GHz 1.63 7.11 95 PVC 10.0 114.5 C1380 RG-11-4.5 GHz 1.63 7.11 95 HFFR 10.0 117 Electrical and Physical Characteristics (at 20°C) BT Cables Part Number RG-Type Imp. (Ω) Max. DC Resistance Conductor (Ω/km) Max. DC Resistance Screen (Ω/km) Nom. Cap. (pF/m) Min. Return Loss (dB) <1000 MHz < 2000 MHz < 3000 MHz < 4500 MHz C1229 RG-59-4.5 GHz 75 ± 3 33.5 12.5 53 23 22 16 15 c1378 RG-59-4.5 GHz 75 ± 3 33.5 12.5 53 23 22 16 15 C1279 RG-6-4.5 GHz 75 ± 3 21.5 10.6 53 23 22 16 15 c1379 RG-6-4.5 GHz 75 ± 3 21.5 10.6 53 23 22 16 15 C1280 RG-11-4.5 GHz 75 ± 3 8.8 6.6 53 23 22 16 15 C1380 RG-11-4.5 GHz 75 ± 3 8.8 6.6 53 23 22 16 15 Nominal Attenuation in dB/100m MHz 1 5 10 50 100 300 550 750 1000 2000 3000 4500 RG-59 0.98 2.07 2.95 6.23 7.55 13.68 18.83 22.23 25.96 38.24 46.13 56.50 RG-6 0.79 1.71 2.33 4.57 6.40 11.96 15.76 18.05 21.36 31.44 39.76 50.46 RG-11 0.53 1.12 1.51 2.96 4.20 7.49 10.41 12.38 14.57 21.84 27.93 35.98 For more details, please see the respective detailed datasheet(s).       info.btcables@bt.com 31
  • 32. Section 6 – BT Data-Tec™ - Category LAN Cables Application and Construction of Category Cables for Local Area Networks and Structured Wiring Systems 1. Application Horizontal or Building Wiring for one of the following categories of twisted pair cabling systems Category Max. data rate Usual application Standard(s) TIA/EIA ISO/IEC EN Cat 1 1 Mbps Analogue voice De facto, never a standard Cat 2 4 Mbps Token ring of IBM Cat 3 16 Mbps Voice, 10MbE(thernet) TIA/EIA 568-B Cat 4 20 Mbps 16 Mbps Token Ring Was only a standard briefly Cat 5 100 MHz 10/100/1000 MbE 155 Mbps ATM, 4/16 Mbps Token Ring Replaced by 5e Cat 5e 100 MHz TIA/EIA 568-C.2 ISO/IEC 11806, 2nd edition IEC 61156 EN 50173-1 EN 50288 Cat 6 250 MHz as Cat5e plus 10Gb Ethernet over ≤ 55 m. Cat 6a 500 MHz As Cat 6 plus 10Gb Ethernet over 100 m. Cat 7 600 MHz As Cat 6a plus supporting 100GbE ISO/IEC 11801: 2002, category 7 / class F Cat 7a 1000 MHz CATV (862 MHz), 40GBASE-T over 50 m. 100GbE over 15 m. Cat 7a is not recognised in TIA/EIA-569 ISO/IEC 11801, amendment 1 (2008) and amendment 2 (2010). 2. Basic Cable Construction of the standard cables (not being patch cables) Wire = Conductor with Insulation Insulation: will be good strippable, suitable for insulation displacement and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Braiding (if applicable): tinned copper wires. Ripcord: to ease removal of the sheath. Sheath: PVC or Halogen-Free (HFFR). Cat 3 Cat 5e Cat 6 Cat 6a Cat 7 Cat 7a Type UUTP UUTP FUTP UUTP FUTP UUTP UFTP & FUTP S-FTP S-FTP Conductor Solid BC Solid BC Solid BC Solid BC Solid BC Solid BC Insulation Polyolefin PE PE Skin-foam-skin PE Cable core 6 to 200 pairs 4 pairs 4 Individually screened pairs Core wrapping Yes No Drain wire No No Yes No Yes No Central drain wire Overall screen No No Foil No Foil Braiding Sheath PVC PVC or HFFR HFFR       info.btcables@bt.com 32
  • 33. Section 6 – BT Data-Tec™ - Category LAN Cables 3. Basic Cable Construction of the standard patch cables Cat 5e Cat 6 Type UUTP FUTP UUTP FUTP Conductor Flexible BC Insulation PE PE Cable core 4 pairs 4 pairs Core wrapping no yes no yes Drain wire (TC) no yes no yes Overall Screen no foil no foil Rip cord yes Sheath PVC or HFFR 4. General Characteristics Cat 3 Cat 5e Cat 6 Cat 6a Cat 7 Max. DCR conductor Ω/100m 9.6 9.38 9.38 7.7 7.7 Impedance Ω 100 100 100 100 100 Standard Colour scheme of Cat 5e – 6 – 6a and 7: Pair number Pair 1 Pair 2 Pair 3 Pair 4 a-wire Blue Orange Green Brown b-wire White with blue stripe White with orange stripe White with green stripe White with brown stripe Operating temperature range: -20 to +80 °C and Rated Voltage: 300 Vrms. 5. Cable Range of BT Cables: 2 pairs 6 pairs 12 pairs 25 pairs 50 pairs 100 pairs 150 pairs 200 pairs Cat3 - PVC C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269 Category Cat 5e Cat 5e Cat 5e Cat 5e Cat 5e Cat 5e Type UTP UTP-UL listed UTP FTP FTP-UL listed FTP Sheath PVC PVC HFFR PVC PVC HFFR BT P/N C1035 C1285 C1235 C1036 C1286 C1236 Category Cat 6 Cat 6 Cat 6 Cat 6 Cat 6 Cat 6 Type UUTP UUTP-UL listed UUTP FUTP FUTP-UL listed FUTP Sheath PVC PVC HFFR PVC PVC HFFR BT P/N C1037 C1287 C1227 C1038 C1288 C1238 Category Cat 6a Cat 6a Cat 7 Cat 7a Type U-UTP U-FTP S-FTP S-FTP Sheath PVC HFFR HFFR HFFR BT P/N C1200 C1053 C1039 C1201 Category Cat 5e Cat 5e Cat 5e Cat 5e Cat 6 Cat 6 Cat 6 Cat 6 Type UTP-Patch UTP-Patch FTP-Patch FTP-Patch UTP-Patch UTP-Patch FTP-Patch FTP-Patch Sheath PVC HFFR PVC HFFR PVC HFFR PVC HFFR BT P/N C1500 C1510 C1520 C1530 C1540 C1550 C1560 C1570 Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.       info.btcables@bt.com 33
  • 34. Section 6.1 – BT Data-Tec™ - Category LAN Cables Cat 5e and 6 UTP and FTP cables Cat 5e cables Cat 5e Variants BT Cables Part Number Type Sheath Overall Diameter (mm) Weight (kg/km) C1035 UUTP PVC 5.0 30 C1285 UUTP-UL PVC 5.0 30 C1235 UUTP HFFR 5.0 29 C1036 FUTP PVC 6.3 42 C1286 FUTP-UL PVC 6.3 42 C1236 FUTP HFFR 6.3 42 Main Transmission Characteristics of Cat 5e cables Frequency (MHz) Min. Return Loss (dB/100m) Maximum Attenuation (dB/100m) Minimum NEXT (dB) Maximum Time Delay (ns/100m) Minimum PSNEXT (dB) Minimum ELFEXT (dB) Minimum PSELFEXT (dB) 1 20.0 2.0 65.3 570.00 62.3 64.0 61.0 4 23.0 4.1 56.3 552.00 53.3 52.0 49.0 8 24.5 5.8 51.8 546.73 48.8 45.9 42.9 10 25.0 6.5 50.3 545.38 47.3 44.0 41.0 16 25.0 8.2 47.2 543.00 44.4 39.9 36.9 20 25.0 9.3 45.8 542.05 42.8 38.0 35.0 25 24.3 10.4 44.3 541.20 41.3 35.8 33.0 31.25 23.6 11.7 42.9 540.44 39.9 34.1 31.1 62.5 21.5 17.0 38.4 538.55 35.4 28.1 25.1 100 20.1 22.0 35.3 537.60 32.3 24.0 21.0 Cat 6 cables Cat 6 Variant BT Cables Part Number Type Sheath Overall Diameter (mm) Weight (kg/km) C1037 UUTP PVC 6.2 42 C1287 UUTP-UL PVC 6.2 42 C1237 UUTP HFFR 6.2 42 C1038 FUTP PVC 7.4 56 C1288 FUTP-UL PVC 7.4 56 C1238 FUTP HFFR 7.4 54.1 Main Transmission Characteristics of Cat 6 cables Frequency (MHz) Return Loss (dB/100m) Maximum Attenuation (dB/100m) Minimum NEXT (dB) Maximum Time Delay (ns/100m) Minimum PSNEXT (dB) Minimum ELFEXT (dB) Minimum PSELFEXT (dB) 1 20.0 2.0 74.3 570.00 72.3 67.8 64.8 4 23.0 3.8 65.3 552.00 63.3 55.8 52.8 8 24.5 5.3 60.8 546.73 58.8 49.7 46.7 10 25.0 6.0 59.3 545.38 57.3 47.8 44.8 16 25.0 7.6 56.2 543.00 54.2 43.7 40.7 20 25.0 8.5 54.8 542.05 52.8 41.8 38.8 25 24.3 9.5 53.3 541.20 51.3 39.8 36.8 31.25 23.6 10.7 51.9 540.44 49.9 37.9 34.9 62.5 21.5 15.4 47.4 538.55 45.4 31.9 28.9 100 20.1 19.8 44.3 537.80 42.3 27.8 24.8 200 18.0 29.0 39.8 536.54 37.8 21.8 18.8 250 17.3 32.8 38.3 536.27 36.3 19.8 16.8 For more details, please see the respective detailed datasheet(s).       info.btcables@bt.com 34
  • 35. Section 6.2 – BT Data-Tec™ - Category LAN Cables Cat 6a U-FTP and Cat 7 S-FTP cables Cat 6a U-FTP cables Cat 6a Variants BT Cables Part Number Type Sheath Overall Diameter (mm) Weight (kg/km) C1200 U-UTP PVC 8.3 61.2 C1053 U-FTP HFFR 7.2 49.9 Main Transmission Characteristics of Cat 6a U-FTP cables Freq. (MHz) Return Loss (dB/100m) Attenuation (dB/100m) NEXT (dB/100m) PSNEXT (dB/100m) ELFEXT (dB/100m) Impedance (Ohm)) 1 20.0 3.7 74.3 72.3 55.9 100 ± 15 10 25.0 5.8 59.3 57.3 47.8 100 ± 15 31.25 23.6 10.4 51.9 49.9 37.9 100 ± 15 100 20.1 19.0 44.3 42.3 27.8 100 ± 15 300 17.3 34.2 37.1 35.1 18.1 100 ± 25 500 17.3 45.2 33.8 31.8 14.0 100 ± 15 Cat 7 cables Cat 7 Variants BT Cables Part Number Type Sheath Overall Diameter (mm) Weight (kg/km) C1039 S-FTP HFFR 7.8 67.5 Main Transmission Characteristics of Cat 7 S-FTP cables Frequency (MHz) Return Loss (dB/100m) Attenuation (dB/100m) NEXT (dB) PSNEXT (dB) ELFEXT (dB) Impedance (Ohm) 1 20.0 2.5 78 75 78.0 100 ± 15 10 25.0 6.5 78 75 56.5 100 ± 15 20 25.0 8.9 78 75 56.5 100 ± 15 62.5 21.5 14.9 75.5 72.5 56.8 100 ± 15 300 14.5 35.2 65.2 62.2 25.0 100 ± 25 600 12.5 50.1 60.7 57.7 16.0 100 ± 25 Cat 7a cables Cat 7a Variants BT Cables Part Number Type Sheath Overall Diameter (mm) Weight (kg/km) C1201 S-FTP HFFR 8.5 71.1 Main Transmission Characteristics of Cat 7a S-FTP cables Frequency (MHz) Return Loss (dB/100m) Attenuation (dB/100m) NEXT (dB) PSNEXT (dB) ACR (dB) Impedance (Ohm) 4 23.0 4.0 80.0 77.0 78.0 100 ± 15 10 25.0 5.8 80.0 77.0 74.3 100 ± 15 20 25.0 8.2 80.0 77.0 71.0 100 ± 15 62.5 21.5 14.6 80.0 77.0 60.6 100 ± 15 300 17.3 32.7 71.2 68.2 38.6 100 ± 25 600 17.3 47.1 66.7 63.7 19.6 100 ± 25 900 17.3 54.9 64.9 61.9 9.93 100 ± 25 1000 16.0 61.9 63.4 60.4 1.47 100 ± 25 For more details, please see the respective detailed datasheet(s).       info.btcables@bt.com 35
  • 36. Section 6.3 – BT Data-Tec™ - Category LAN Cables Cat 5e and Cat 6 UTP and FTP PATCH Cables Cat 5e and Cat6 Patch cables Cat 5e Variants BT Cables Part Number Type Sheath Overall Diameter (mm) Weight (kg/km) C1500 UUTP PVC 5.2 30.7 C1510 UUTP HFFR 5.2 31.4 C1520 FUTP PVC 5.1 31.2 C1530 FUTP HFFR 5.1 31.1 Main Transmission Characteristics of Cat 5e Patch cables Cat 5e - Patch UTP / FTP UTP FTP UTP / FTP UTP / FTP UTP / FTP UTP / FTP Frequency (MHz) Return Loss (dB/100m) Maximum Attenuation (dB/100m) Minimum NEXT (dB) Minimum PSNEXT (dB) Minimum ELFEXT (dB) Minimum PSELFEXT (dB) 1 20.0 2.4 3.1 65.3 62.3 63.8 60.8 4 23.0 4.9 6.1 56.3 53.3 51.8 48.8 8 24.5 6.9 8.6 51.8 48.8 45.7 42.7 10 25.0 7.8 9.7 50.3 47.3 43.8 40.8 16 25.0 9.9 12.4 47.2 44.2 39.7 36.7 20 25.0 11.1 13.9 45.8 42.8 37.8 34.8 25 24.2 12.5 15.6 44.3 41.3 35.8 32.8 31.25 23.3 14.1 17.6 42.9 39.9 33.9 30.9 62.5 20.7 20.4 25.5 38.4 35.4 27.9 24.9 100 19.0 26.4 33.0 35.3 32.3 23.8 20.8 Cat 6 Patch cables Cat 6 Variants BT Cables Part number Type Sheath Overall Diameter (mm) Weight (kg/km) C1540 UUTP PVC 5.9 31.6 C1550 UUTP HFFR 5.9 32.4 C1560 FUTP PVC 6.2 34.6 C1570 FUTP HFFR 6.2 35.8 Main Transmission Characteristics of Cat 6 Patch cables Cat 6 - Patch UTP / FTP UTP FTP UTP / FTP UTP / FTP UTP / FTP UTP / FTP Frequency (MHz) Return Loss (dB/100m) Maximum Attenuation (dB/100m) Minimum NEXT (dB) Minimum PSNEXT (dB) Minimum ELFEXT (dB) Minimum PSELFEXT (dB) 1 20.0 2.4 3.1 74.3 72.3 67.8 64.8 4 23.0 4.6 6.1 65.3 63.3 56.0 53.0 10 25.0 7.2 8.6 59.3 57.3 48.0 45.0 16 25.0 9.1 12.4 56.2 54.2 43.9 40.9 20 25.0 10.2 13.9 54.8 52.8 42.0 39.0 31.25 23.3 12.9 17.6 51.9 49.9 38.1 35.1 62.5 20.7 18.6 25.5 47.4 45.4 32.1 29.1 100 19.0 23.9 33.0 44.3 42.3 28.0 25.0 200 16.4 35.0 48.6 39.8 37.8 22.0 19.0 250 15.5 39.4 55.3 38.3 36.3 20.0 17.0 For more details, please see the respective detailed datasheet(s).       info.btcables@bt.com 36
  • 37. Section 6.4 – BT Data-Tec™ - Category LAN Cables Cat 3 multi pair Cables Cat 3 cables Cat 3 cables BT Cables Part Number No. of pairs Nom. Diameter Conductor (mm) Nom. Diameter Insulation (mm) Nom. Overall Diameter (mm) Weight (kg/km) C1031 2 0.5 0.9 3.6 16 C1266 6 0.5 0.9 5.5 39 C1267 12 0.5 0.9 7.4 73 C1032 25 0.5 0.9 11.8 154 C1033 50 0.5 0.9 15.5 280 C1034 100 0.5 0.9 21.6 530 C1268 150 0.5 0.9 26.8 800 C1269 200 0.5 0.9 29.4 1040 Electrical Characteristics Cat 3 cables at 20° Frequency Max. Attenuation Max. NEXT Min. Return Loss Impedance MHz (dB/100m) (dB) (dB) (Ohm) 1 2.6 41.3 12.0 100 ± 15 4 5.6 32.3 12.0 100 ± 15 8 8.5 27.8 12.0 100 ± 15 10 9.7 26.3 12.0 100 ± 15 16 13.1 23.3 10.0 100 ± 15 Cable Make-Up Cat 3 cables BT Cables Part Number C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269 No of pairs 2 6 12 25 50 100 150 200 Number of pairs per unit 25 10 25 25 25 Number of units in the centre 1 5 4 1 1 Number of units in the 1e layer 5 7 Pair Colour Code Cat 3 cables Pair No. Pair Colours in 2 – 6 -12 or 25 pairs cables Pair No. Pair Colours in Unit of 12 or 25 pairs Pair No. Pair Colours in Unit of 25 pairs 1 White / Blue 11 Black / Blue 21 Purple / Blue 2 White / Orange 12 Black / Orange 22 Purple / Orange 3 White / Green 13 Black / Green 23 Purple / Green 4 White / Brown 14 Black / Brown 24 Purple / Brown 5 White / Grey 15 Black / Grey 25 Purple / Grey 6 Red / Blue 16 Yellow / Blue 7 Red / Orange 17 Yellow / Orange 8 Red / Green 18 Yellow / Green 9 Red / Brown 19 Yellow / Brown 10 Red / Grey 20 Yellow / Grey For more details, please see the respective detailed datasheet(s).       info.btcables@bt.com 37
  • 38. Section 7 – BT Industrial-Tec™ - DEF Standard Cables DEF Standard 51-12 Parts 4 & 5 1. Application Originally developed for military use, these flexible multi-conductor cables are now widely used within the industry. They are designed for high density wiring between and within instruments and electronic equipment and/or components and especially used in process control systems, computers, data processors, sound systems and of course in military equipment. 2. Main Standard DEF standard 61-12, part 4 and 5. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Size mm2 0.055 0.22 0.5 configuration mm 7 x 0.1 7 x 0.2 16 x 0.20 Max. DC Resistance Ω/km 345 86.2 37.7 Max. recommended current Amps 0.25 1 2.5 Rated Voltage Vrms 250 440 440 Insulation: PVC (Polyvinyl Chloride). Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more wires, stranded. Colour scheme: Core No. Color Core No. Color Core No. Color Core No. Color 1 Red 11 Turquoise 21 BLUE/Black 31 WHITE/Brown 2 Blue 12 Grey 22 ORANGE/Blue 32 BROWN/Black 3 Green 13 RED/Blue 23 GREEN/Blue 33 GREY/Brown 4 Yellow 14 GREEN/Red 24 GREY/Blue 34 YELLOW/Violet 5 White 15 YELLOW/Red 25 YELLOW/Green 35 VIOLET/Black 6 Black 16 WHITE/Red 26 WHITE/Green 36 WHITE/Violet 7 Brown 17 RED/Black 27 GREEN/Black 50 Special scheme, on request available8 Violet 18 RED/Brown 28 ORANGE/Green 9 Orange 19 YELLOW/Blue 29 GREY/Green 10 Pink 20 WHITE/Blue 30 YELLOW/Brown Drain wire (only in combination with a screen): twisted (= flexible) tinned copper wires. Screen (if applicable): Braiding of tinned copper wires, coverage 91%. Sheath: grey PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C. Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.       info.btcables@bt.com 38
  • 39. Section 7 – BT Industrial-Tec™ - DEF Standard Cables CABLE DESCRIPTION 1. Conductor Stranded Tinned Copper 2. Insulation PVC 3. Cable core) Two or more wires stranded 4. Screen (if required) Tinned Copper 91% Coverage 5. Ripcord 6. Sheath Material Flame-Retardant Polyvinyl Chloride (PVC) Standard colour: grey Standard Put Up Length 305 metres Standard References DEF standard 61-12, part 4 & 5 IEC 60332-1 RoHS directives Conductor 7 x 0.1 mm = 0.055 mm² No of wires BT Cables Part Number Screen Diameter (mm) BT Cables Part Number Screen Diameter (mm) 2 C1164 Yes 3.2 C1360 No 2.3 3 C1165 Yes 3.6 C1361 No 2.4 4 C1362 No 2.6 6 C1166 Yes 4.2 C1144 No 3.1 9 C1145 No 3.7 15 C1146 No 4.2 25 C1168 Yes 6.3 C1147 No 5.5 36 C1169 Yes 6.9 C1148 No 6.1 50 C1365 Yes 8.0 C1364 No 7.2 Conductor 7 x 0.2 mm = 0.22 mm² No of wires BT Cables Part Number Screen Diameter (mm) BT Cables Part Number Screen Diameter (mm) 2 C1366 No 3.4 3 C1367 No 3.6 4 C1471 Yes 4.4 C1368 No 3.9 6 C1472 Yes 5.6 C1369 No 4.6 8 C1473 Yes 6.1 C1154 No 5.6 12 C1474 Yes 6.9 C1155 No 6.1 20 C1475 Yes 8.6 C1156 No 7.8 36 C1476 Yes 10.8 C1157 No 9.8 Conductor 16 x 0.2 mm = 0.5 mm² No of wires BT Cables Part Number Screen Diameter (mm) BT Cables Part Number Screen Diameter (mm) 2 C1158 No 5.5 3 C1370 No 5.8 4 C1177 Yes 7.3 C1371 No 6.3 6 C1178 Yes 8.3 C1372 No 7.3 12 C1375 Yes 10.5 C1373 No 9.5 18 C1180 Yes 12.0 C1374 No 11.0 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 39
  • 40. Section 8 – BT Industrial-Tec™ - Industrial Cables Application and Construction 1. Application These cables are generally used to transmit analogue or digital signals in industrial process plants where chemical and mechanical protections are needed (chemical and petrochemical industries). The unarmoured versions (Type 1) are generally use for indoor installation. 2. Main Standard BS(PAS) 5308 – Part 2 – Type 1 & 2. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Pair: two twisted wires. Conductor Size mm2 0.5 0.75 1.5 configuration mm 16 x 0.2 24 x 0.2 7 x 0.53 Max. DC Resistance at 20°C Ω/km 39.7 26.5 12.3 Max. conductor temperature °C 65 65 65 Min. operating temperature °C -20 -20 -20 Max. recommended current Amps 6 8 12 Max. mutual capacitance at 1 kHz pF/m 250 250 250 Max. L/R ratio μH/Ω 25 25 40 Rated Voltage Vrms 300 / 500 300 / 500 300 / 500 Insulation: PVC (Polyvinyl Chloride) in accordance with BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more pairs, stranded. Colour scheme: Pair No. 1 2 3 4 5 6 7 8 9 10 a-wire White White White White White Red Red Red Red Red b-wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey Pair No. 11 12 13 14 15 16 17 18 19 20 a-wire Black Black Black Black Black Yellow Yellow Yellow Yellow Yellow b-wire Blue Orange Green Brown Grey Blue Orange Green Brown Grey Drain wire (only in combination with an individual or collective screen): stranded tinned copper wires. Individual Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Collective Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Bedding (if applicable): Flame Retardant PVC. Armour (if applicable): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.       info.btcables@bt.com 40
  • 41. Section 8 – BT Industrial-Tec™ - Industrial Cables BS(PAS) 5308 - Part 2 – Type 1 – Collectively Screened Cables Conductor 0.5 mm² (16 x 0.2 mm) No of pairs BT Cables Part Number Armour Diameter (mm) Weight (kg/km BT Cables Part Number Armour Diameter (mm) Weight (kg/km) 1 C1081 No 7.0 50 C1096 Yes 11.4 240 2 C1082 No 7.9 72 C1092 Yes 12.3 290 5 C1083 No 13.1 170 C1093 Yes 17.9 510 10 C1084 No 17.2 290 C1094 Yes 22.9 880 20 C1085 No 22.3 500 C1095 Yes 29.1 1500 Conductor 0.75 mm² (24 x 0.2 mm) No of pairs BT Cables Part Number Armour Diameter (mm) Weight (kg/km BT Cables Part Number Armour Diameter (mm) Weight (kg/km) 1 C1086 No 7.3 60 C1101 Yes 11.7 270 2 C1087 No 8.3 100 C1102 Yes 12.9 310 5 C1088 No 14.3 210 C1103 Yes 19.8 710 10 C1089 No 18.7 350 C1104 Yes 25.3 1200 20 C1090 No 24.5 750 C1105 Yes 31.3 1700 Conductor 1.5 mm² (7 x 0.53 mm) No of pairs BT Cables Part Number Armour Diameter (mm) Weight (kg/km BT Cables Part Number Armour Diameter (mm) Weight (kg/km) 1 C1091 No 8.3 90 C1106 Yes 12.9 300 2 C1092 No 9.7 140 C1107 Yes 14.3 390 5 C1093 No 16.4 330 C1108 Yes 22.1 870 10 C1094 No 20.6 580 C1109 Yes 28.4 1500 20 C1095 No 28.5 1100 C1110 Yes 35.7 2400 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 41
  • 42. Section 8 – BT Industrial-Tec™ - Industrial Cables BS(PAS) 5308 - Part 2 – Type 1 – Individually & Collectively Screened Cables Conductor 0.5 mm² (16 x 0.2 mm) No of pairs BT Cables Part Number Armour Diameter (mm) Weight (kg/km BT Cables Part Number Armour Diameter (mm) Weight (kg/km) 2 C1111 No 12.0 100 C1123 Yes 16.8 450 5 C1112 No 15.2 250 C1124 Yes 20.9 750 10 C1113 No 21.1 480 C1125 Yes 27.9 1300 20 C1114 No 27.3 780 C1126 Yes 34.4 1900 Conductor 0.75 mm² (24 x 0.2 mm) No of pairs BT Cables Part Number Armour Diameter (mm) Weight (kg/km BT Cables Part Number Armour Diameter (mm) Weight (kg/km) 2 C1115 No 12.8 190 C1127 Yes 17.6 490 5 C1116 No 16.3 270 C1128 Yes 22.0 801 10 C1117 No 22.7 550 C1129 Yes 29.5 1800 20 C1118 No 29.8 960 C1130 Yes 37.8 2200 Conductor 0.75 mm² (24 x 0.2 mm) No of pairs BT Cables Part Number Armour Diameter (mm) Weight (kg/km BT Cables Part Number Armour Diameter (mm) Weight (kg/km) 2 C1119 No 14.7 250 C1131 Yes 20.4 660 5 C1120 No 18.8 460 C1132 Yes 25.4 1000 10 C1121 No 26.5 760 C1133 Yes 33.5 1700 20 C1122 No 34.4 1350 C1134 Yes 42.6 2800 For more details, please see the respective detailed datasheet(s)        info.btcables@bt.com 42
  • 43. Section 9 - BT Industrial-Tec™ -– Control Cables Application and Construction 1. Application These cables are commonly used as interconnecting cables to control, measure and regulate processor aided production within the industry and also as flexible power control cables suitable for robotic and automated equipment. 2. Main Standard VDE 0250/VDE 0255 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Conductor Size mm2 0.75 1.0 1.5 2.5 4 6 Conductor material bare copper configuration mm 24x0.2 32x0.2 30x0.24 50x0.24 56x0.29 84x0.29 Max. DC Resistance at 20°C Ω/km 27 20.2 14 8.4 4.95 3.3 Insulation: Flame Retardant PVC (Polyvinyl Chloride). Insulation Resistance > 500 MΩ/km. Good strippable insulation. Conductor Size mm2 0.75 1.0 1.5 2.5 4 6 Radial thickness insulation mm 0.5 0.5 0.4 0.5 0.8 0.7 Cable core: three or more wires stranded. In case of 5 wires with a central filler. Colour scheme: Green/yellow - black with printed numbers. Collective Screen (CY series): braiding of tinned copper wires with a coverage of 70%. Bedding (SY series): Flame Retardant PVC. Armour (SY series): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C. Rated Voltage: 300 V. Cable Types: YY series: three or more stranded cores, surrounded by a PVC sheath. CY series: as YY series plus a collective screen between cable core and PVC sheath. SY series: as YY series plus a Steel Wire Armouring between cable core and transparent PVC sheath. Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.       info.btcables@bt.com 43
  • 44. Section 9 - BT Industrial-Tec™ -– Control Cables YY Series: Cable core of stranded cores surrounded by a PVC sheath No of wires BT Cables Part Number Conductor (mm² / mm) Diameter (mm) BT Cables Part Number Conductor (mm² / mm) Diameter (mm) 3 C1631 0.75 / 24x0.2 5.6 C1632 1.0 / 32X0.2 6.2 4 C1635 0.75 / 24x0.2 6.6 C1636 1.0 / 32X0.2 7.1 12 C1645 0.75 / 24x0.2 10.4 18 C1648 0.75 / 24x0.2 12.4 No of wires BT Cables Part Number Conductor (mm² / mm) Diameter (mm) BT Cables Part Number Conductor (mm² / mm) Diameter (mm) 3 C1633 1.5 / 30X0.24 6.5 C1634 2.5 / 50X0.24 6.5 4 C1637 1.5 / 30X0.24 7.6 C1638 2.5 / 50X0.24 9.1 5 C1639 1.5 / 30X0.24 8.4 C1640 2.5 / 50X0.24 10.3 7 C1641 1.5 / 30X0.24 9.5 C1642 2.5 / 50X0.24 11.8 8 C1643 1.5 / 30X0.24 10.4 C1644 2.5 / 50X0.24 12.6 12 C1646 1.5 / 30X0.24 12.4 C1647 2.5 / 50X0.24 14.9 18 C1649 1.5 / 30X0.24 14.5 C1650 2.5 / 50X0.24 14.5 CY Series: Cable core of stranded cores surrounded by a braiding of tinned copper wires plus a PVC sheath No of wires BT Cables Part Number Conductor (mm² / mm) Diameter (mm) BT Cables Part Number Conductor (mm² / mm) Diameter (mm) 3 C 1620 0.75 / 24x0.2 6.0 C1621 1.0 / 32X0.2 6.4 4 C1624 0.75 / 24x0.2 6.7 C1625 1.0 / 32X0.2 7.0 No of wires BT Cables Part Number Conductor (mm² / mm) Diameter (mm) BT Cables Part Number Conductor (mm² / mm) Diameter (mm) 3 C1622 1.5 / 30X0.24 6.8 C1623 2.5 / 50X0.24 8.0 4 C1626 1.5 / 30X0.24 7.6 C1627 2.5 / 50X0.24 9.0 5 C1628 1.5 / 30X0.24 8.2 C1629 2.5 / 50X0.24 9.8 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 44
  • 45. Section 9 - BT Industrial-Tec™ -– Control Cables SY Series: Cable core of stranded cores surrounded by a bedding, a Steel Wire Armouring plus a PVC sheath No of wires BT Cables Part Number Conductor (mm² / mm) Diameter (mm) BT Cables Part Number Conductor (mm² / mm) Diameter (mm) 3 C1655 0.75 / 24x0.2 7.8 C1658 2.5 / 50X0.24 4 C1662 2.5 / 50X0.24 No of wires BT Cables Part Number Conductor (mm² / mm) Diameter (mm) BT Cables Part Number Conductor (mm² / mm) Diameter (mm) 2 C1651 1.0 / 32X0.2 8.2 C1652 1.5 / 30X0.24 9.4 3 C1656 1.0 / 32X0.2 8.2 C1657 1.5 / 30X0.24 9.4 4 C1660 1.0 / 32X0.2 8.2 C1661 1.5 / 30X0.24 9.4 5 C1665 1.0 / 32X0.2 10.6 C1666 1.5 / 30X0.24 11.2 6 C1668 1.5 / 30X0.24 12.3 7 C1669 1.0 / 32X0.2 11.7 C1670 1.5 / 30X0.24 12.4 12 C1671 1.0 / 32X0.2 13.8 C1672 1.5 / 30X0.24 14.3 18 C1673 1.0 / 32X0.2 15.8 C1674 1.5 / 30X0.24 16.8 25 C1675 1.0 / 32X0.2 19.7 No of wires BT Cables Part Number Conductor (mm² / mm) Diameter (mm) BT Cables Part Number Conductor (mm² / mm) Diameter (mm) 3 C1659 4.0 / 56x0.29 13.4 4 C1663 4.0 / 56x0.29 13.4 C1664 6.0 / 84X0.29 16.0 For more details, please see the respective detailed datasheet(s)       info.btcables@bt.com 45
  • 46. GENERAL TECHNICAL INFORMATION American Wire Gauge (AWM) Conductors (of bare or tinned copper) Flexible Conductors AWG 24 22 20 18 16 14 12 Number of strands 7 7 7 7 19 19 19 Gauge single strand AWG 32 30 28 26 29 27 25 Diameter single strand mm 0.2 0.25 0.32 0.40 0.28 0.36 0.45 Solid Conductors AWG 24 22 20 18 16 14 12 Diameter mm 0.51 0.64 0.81 1.02 1.29 1.63 2.05 All Conductors AWG 24 22 20 18 16 14 12 Cross section mm² 0.20 0.32 0.52 0.82 1.37 2.08 3.31 Max. DC resistance Ω/km 88 57.4 32.16 22.7 15.47 9.36 5.61 Max. Recommended current 2 or 3 core cable Amps 2.7 2.8 3.75 5 6.25 8 12 Max. Recommended current 4 or 5 core cable Amps 2.2 2.25 3 4 5 6.4 9.6 Max. Recommended current 6 to 19 core cable Amps 1.9 1.95 2.6 3.5 4.35 5.6 8.4 Max. Recommended current 20 to 36 core cable Amps 1.35 1.4 1.65 2.5 3.12 4 6 Metric Conductors (of bare copper according to IEC 60228) Conductor mm² 0.75 1.0 1.5 2.5 4.0 Max. Recommended current 2 or 3 core cable Amps ≤ 5 ≤ 5.70 ≤ 6.25 ≤ 8 ≤ 12 Flexible Conductors, class 2 mm² 0.055 0.22 0.50 0.75 1.0 1.5 2.5 4.0 6.0 Number of strands 7 7 7 7 7 7 7 7 7 Diameter single strand mm 0.1 0.2 0.53 Max. DC resistance Ω/km 345 86.2 36.0 24.5 18.1 12.1 7.41 4.61 3.08 Flexible Conductors, class 5 mm² 0.055 0.22 0.50 0.75 1.0 1.5 2.5 4.0 6.0 Number of strands 16 24 32 30 50 56 84 Diameter single strand mm 0.2 0.2 0.2 0.24 0.24 0.29 0.29 Max. DC resistance Ω/km 39.0 26.0 19.5 13.3 7.98 4.95 3.30 Max. Recommended current 2 or 3 core cable Amps 2.7 2.8 3.75 5 6.25 8 12 Max. Recommended current 4 or 5 core cable Amps 2.2 2.25 3 4 5 6.4 9.6 Max. Recommended current 6 to 19 core cable Amps 1.9 1.95 2.6 3.5 4.35 5.6 8.4 Max. Recommended current 20 to 36 core cable Amps 1.35 1.4 1.65 2.5 3.12 4 6 All conductors in BT Cables are in accordance with above tables unless otherwise stated in the respective section of this publication or datasheets.       info.btcables@bt.com 46
  • 47. Pairs: all pairs consist of two twisted wires with a lay-length < 40 D. Cable Cores: all cable cores consist of stranded wires or pairs Foil screens for multi-core and multi-pair cables, screens or shields mostly consist of an aluminium foil laminated to polyester, broadly known as Alpet. These foils are helically (as a spiral) applied with sufficient overlap to guarantee 115 % or more coverage. . For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. A drain wire or continuity wire, contacting the aluminium side of the foil, is used for the termination of the screen and also to ground electrostatic discharges. In case the screen of a coaxial cable where the screen may be a foil, this foil will be applied longitudinally and will also be bonded to the dielectric around the conductor. Braided screens consist of 16 or 24 groups of strands. One set of 8 or 12 strands is woven clockwise and the other set of 8 or 12 strands anti-clockwise. Strands can consist of tinned or bare copper or aluminium wires. Braided screens provide good screening efficiency and flexibility. Higher coverage provides better screening. Sheaths: grey PVC, purple HFFR or black for PE, all in accordance with BS EN 50290-2. Sheath PVC PVC Alarm cables HFFR PE Physical properties BS EN 50290-2-22 UL444 BS EN 50290-2 BS EN 50290-2 Retardancy Flame Fire Fire Not applicable Retardancy acc. to IEC 60332-1 UL1666 IEC 60332-3C Not applicable Low Smoke Not applicable Not applicable IEC 61034 Not applicable Halogen-free (non acid, non toxic) Not applicable Not applicable IEC 60754 Not applicable RoHS compliant YES YES YES YES Installation ** INDOOR INDOOR INDOOR OUTDOOR ** on request cables with a sheath for in- & outdoor = universal use available. RoHS Limits for Hazardous Substances Substance Max. Concentration Unless so marked, all BT Cables do not contain restricted or hazardous substances and are compliant with the European Regulations or Directives for RoHS (Restriction of Hazardous Substances), REACH (Regulation Registration, Evaluation, Authorisation and Restriction of Chemical substances), WEEE (Waste Electrical and Electronic Equipment ), ELV (End of Life Vehicles) and BFR (Brominated Flame Retardants). Lead (Pb) 0.03% Mercury (Hg) 0.10% Cadmium (Cd) 0.01% Chromium 6 0.1% PBB 0.1% PBDE 0.1% RS Protocol RS-232 RS-422 RS-485 Differential no yes yes Max. number of drivers Max. number of receivers 1 1 1 10 1 32 Modes of operation full duplex half duplex half duplex Network topology point-to-point multidrop multidrop Max. distance acc. to standard 15 m 1200 m 1200 m Max. speed at 12 m. Max. speed at 1200 m. 20 kbs 1 kbs 10 Mbs 100 kbs 35 Mbs 100 kbs Cables used 6 to 25 conductors. No impedance specified mainly 24AWG conductors. Two pairs or more. 100 ohm mainly 24AWG conductors. One pair or more. 120 ohm BT Cables main part numbers see section 1.3 section 1.2 section 1.1       info.btcables@bt.com 47
  • 48. Nominal Attenuation in dB/100m for RG Coaxial Cables MHz 1 5 10 50 100 300 550 750 1000 2000 3000 4500 RG-59 0.98 2.07 2.95 6.23 7.55 13.68 18.83 22.23 25.96 38.24 46.13 56.50 RG-6 0.79 1.71 2.33 4.57 6.40 11.96 15.76 18.05 21.36 31.44 39.76 50.46 RG-11 0.53 1.12 1.51 2.96 4.20 7.49 10.41 12.38 14.57 21.84 27.93 35.98 COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS Europe USA Focus on SAFETY = SAVING LIVES Focus Focus on REDUCING INSURANCE CLAIMS Low Voltage Directive Directives National Electrical Code 220 Volt, 50 Hz Power supply system 120 Volt, 60 Hz More radial thickness of insulation Cable basics More copper in conductors IEC-EN and National Standards Standards UL standards Cable specs. in mm, N, etc. Units Cable specs. in inches, lbs, etc. 70 °C (is equal to 80 °C in USA) Temperature Ratings 80 °C (Is equal to 70 °C in Europe) 300 / 500 Vrms Voltage Ratings 300 Vrms 450 / 750 Vrms 600 Vrms IEC 60332-1 Retardancy levels UL1581 – VW-1 IEC 60332-3-24 (former 3C) UL1685 RoHS compliant Environmental requirements A number of states banned Hg and PBDE CE Marking The CE marking certifies that a product has met EU consumer safety, health or environmental requirements. By affixing the CE marking to a product, the manufacturer – on his sole responsibility – declares that it meets EU safety, health and environmental requirements or, if stipulated in the directive(s), it had to be examined by a notified conformity assessment body. Quality assurance UL Approval / Listing UL does not approve products. Rather it evaluates products for compliance to specific requirements, and permits acceptable products to carry a UL certification mark, as long as they remain compliant with the standards. Products under its listing service are said to be “UL Listed,” identified by the distinctive UL mark. CONVERSIONS Europe USA 1 mm = 0.03937 inches 1 inch = 25,4 mm 1 m = 3.2808 feet (305 m = 1000 feet) 1 feet = 0.3048 m 1 m = 1.0936 feet 1 yard = 0.9144m 1 km = 0.6214 miles 1 mile = 1.6093 km 1 kg/km = 0.6719 lbs/1000 ft 1 lbs/1000 ft = 1.488 kg/km 1 ohm/km = 0.3048 ohm/1000 ft 1 ohm/1000 ft = 3.2808 ohm/km 1 N = 0.2248 lbs force 1 lbs force = 0.2248 N -40 °C = -40 °F -40 °F = -40 °C -30 °C = -22 °F -22 °F = -30 °C 0 °C = 32 °F 32 °F = 0 °C 60 °C = 90 °F 90 °F = -60 °C 75 °C = 167 °F 167 °F = -75 °C 90 °C = 194 °F 194 °F = -90 °C       info.btcables@bt.com 48
  • 49. Area Conversions From To Multiply by To Multiply by To Multiply by Circular mils Square inches 0.0000007854 Square mils 0.7854 mm² 0.0005067 Square inches Circular mils 1,273.240 Square mils 1,000,000.00 mm² 645.16 mm² Square inches 0.00155 Square mils 1550.01 Circular mils 1,973.53 Square feet Square meters 0.0929 Common Wire Conversions AWG 24 22 20 19/18 18 18/17 Cir. mils 404 640 987 1029 1481 1620 1974 mm² 0.205 0.324 0.5 0.521 0.75 0.821 1.0 AWG 16 15/16 14 14/13 12 11 Cir. mils 2580 2961 4110 4935 6530 7896 8230 mm² 1.371 1.5 2.082 2.5 3.309 4.0 4.170 Force, Mass and Weight Conversion From To Multiply by From To Multiply by Pounds Kilograms 0.4535 Kilograms Pounds 2.205 Pound per 1000 ft Kilogram per kilometre 1.488 Kilogram per kilometre Pound per 1000 ft 0.6719 Pound-force Newton 4.4482 Newton Pound-force 0.2248       info.btcables@bt.com 49