1. The document calculates the stabilizing resistance needed for a 40MVA transformer with a 66kV system voltage and 400:1 CT ratio to have a stability voltage of 18.023V and stabilizing resistor of 106.02 ohms dissipating 3.06W.
2. For a 40MVA transformer with an 11kV system voltage and 2000:1 CT ratio, the calculated stability voltage is 73.4V and stabilizing resistor is 734 ohms dissipating 7.34W.
3. For an earthing transformer with a 0.415kV system voltage and 750:1 CT ratio, the stability voltage is 78.5V and stabilizing resistor is 262 oh