Complete Equipment
SIVACON 8PT Low Voltage Switchgear
(Authorized by Siemens)
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 1000A~6300A
Rated current of distribution bus-bar: 1000A~6300A
Rated short-time withstand current of main bus-bar:
100KA
Rated short-time withstand current of distribution
bus-bar: 65KA
Protection grade: IP40
Width: 1200; 1100; 1000; 900; 700mm
Depth: 1000; 800; 600; 400mm
Height: 2200mm
RGCS Low Voltage Extraction Type
Switchgear
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 630A-1600A-2500A-4000A
Rated current of distribution bus-bar: 630A~1000A
Rated short-time withstand current of main bus-bar:
30KA/50KA/80KA
Rated short-time withstand current of distribution
bus-bar: 30KA/50KA
Protection grade: IP30
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
RGCK Low Voltage Switchboard
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 630A-1600A-2500A-4000A
Rated current of distribution bus-bar: 630A~1000A
Rated short-time withstand current of main bus-bar:
30KA/50KA/80KA
Rated short-time withstand current of distribution
bus-bar: 30KA/50KA
Protection grade: IP30
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
RMNS Low Voltage Extraction Type
Switchgear
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 630A-1600A-2500A-4000A
Rated current of distribution bus-bar: 630A-1000A-2500A
Rated short-time withstand current of main bus-bar:
30KA/50KA/80KA
Rated short-time withstand current of distribution
bus-bar: 30KA/50KA
Protection grade: IP30/IP40
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
BloksetD Low Voltage Switchgear
(Authorized by Schneider)
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 630A-1600A-2500A-4000A
Rated current of distribution bus-bar: 630A-1000A
Rated short-time withstand current of main bus-bar:
30KA/50KA/80KA
Rated short-time withstand current of distribution
bus-bar: 30KA/50KA
Protection grade: IP30
Width: 1200; 1100; 1000; 900; 700mm
Depth: 1000; 800; 600mm
Height: 2200mm
MD190 Low Voltage Extraction Type
Switchgear (Authorized by ABB)
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 630A-1600A-2500A-4000A
Rated current of distribution bus-bar: 630A-1000A
Rated short-time withstand current of main bus-bar:
30KA/50KA/80KA
Rated short-time withstand current of distribution
bus-bar: 30KA/50KA
Protection grade: IP42
Width: 760mm
Depth: 950mm
Height: 2185mm
RDGCKZ Low Voltage Switchgear
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 2500A-4000A
Rated current of distribution bus-bar: 1000A
Rated short-time withstand current of main bus-bar:
80KA
Rated short-time withstand current of distribution
bus-bar: 50KA
Protection grade: IP30
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
RSDK1 Low Voltage Extraction Type
Switchgear
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 630A-1600A
Rated current of distribution bus-bar: 800A
Rated short-time withstand current of main bus-bar:
30KA
Rated short-time withstand current of distribution
bus-bar: 30KA
Protection grade: IP30
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
007 www.peopleelectric.com
Complete Equipment
MSN 2.0 (Authorized by ABB)
Rated voltage: 400V
Rated insulation voltage: 660V
Main bus-bar: In5000A/Ipk220KA/Icw100KA
Distribution bus-bar: In1200A/Ipk110KA/Icw50KA
Protection grade: IP30
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
RGGD Low Voltage Switchgear
Rated voltage: 380V
Rated insulation voltage: 380V
Rated current of main bus-bar: 630A-1600A-3150A
Rated current of distribution bus-bar:
630A~1000A-2500A
Rated short-time withstand current of main bus-bar:
30KA/50KA/80KA
Rated short-time withstand current of distribution
bus-bar: 30KA/50KA
Protection grade: IP30
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
RBCJ-1,2,3 Low Voltage Compensator
Compensation type: contactor type, combination switch
type, silicon control type (dynamic compensation)
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current : 507A~87A
Nominal capacity of capacitor: 400kvar~60kvar
Rated short-time withstand current: 15KA
Rated peak withstand current: 30KA
Protection grade: IP30
Width: 1000; 800; 600; 400mm
Depth: 1000; 800; 600mm
Height: 2200mm
RJP-Outdoor Synthetical Distribution
Box
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current: 400A~32A
Single-phase/Three phase synthetical compensation:
145kvar~10kvar
Rated short-time withstand current of main bus-bar: 10KA
Switching control of capacitor: combination switch
Protection grade: IP44 (Outdoors type)
Length 1600mm × width 600mm × height 1200mm
MNS-E Power Cabinet (Authorized by ABB)
Rated voltage: 380V
Rated insulation voltage: 690V
Rated current: 100A~600A
Rated short-time withstand current: 15KA
Protection grade: IP40
Width: 600mm
Depth: 400mm
Height: 1800mm
RXL-21 Power Cabinet
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current: 630A~100A
Rated short-time withstand current: 15KA
Rated peak withstand current:17KA
Protection grade: IP30
Width: 700; 600mm
Depth: 370mm
Height: 1700; 1600mm
RXGL-15 Power Cabinet
Rated voltage: 380V
Rated insulation voltage: 660V
Rated current of main bus-bar: 630A
Breaking capacity of main switch: 30KA
Protection grade: IP40
Width: 700; 600mm
Depth: 370mm
Height: 1700; 1600mm
RXJF Distribution Box
Rated voltage: 220V/380V
Rated insulation voltage: 500V
Rated current: 250A~30A
Rated short-time withstand current: 6KA
Protection grade: IP30
www.peopleelectric.com 008
PZ30 Distribution Box
Rated Voltage: 220V/380V
Rated insulation voltage: 400V
Rated current: 80A~6A
Rated short time current: 6KA
Protection grade: IP30
RXJF-1 Double Power Distribution Box
Rated voltage: 380V
Rated insulation voltage: 660V
Main bus-bar rated current: 630A~100A
Rated ultimate short-circuit breaking capacity (Icu): 65KA
Rated short circuit breaking capacity (Icu): 32.5KA
Rated short-time withstand current: 15KA
Protection grade: IP40
RDWB Combined Type
Low-Voltage Distribution Box
Rated voltage: 380V
Rated insulation voltage: 500V
Main bus-bar rated current: 600A~160A
The main switch breaking capacity: 30KA
Rated short time current: 30KA
Protection grade: IP44
KYN28-12 Metal Armoured Open
Type Switchgear
Rated voltage: 12KV
Rated current: 630A~5000A
Rated short circuit breaking current: 20KA, 25KA,
31.5KA, 40A, 50A
Rated short-circuit making current: 50KA, 63KA,
80KA, 100KA, 125KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP3X
Width: 1000; 800mm
Depth: 1500mm
Height: 2300mm
NXAirS LP Medium Voltage
Switchgear (Authorized by Siemens)
Rated voltage: 12KV
Rated current: 630A, 1250A, 1600A, 2000A, 2500A, 3150A,
4000A
Rated short circuit breaking current: 25KA, 31.5KA, 40KA
Rated short-circuit making current: 63KA, 80KA, 100KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP4X
Width: 800mm
Depth: 1315mm
Height: 2200mm
RGHC-12 Solid Insulation
Ring Main Unit
Rated voltage: 12KV
Rated current: 630A/125A
Rated short circuit breaking current: 20KA/25KA
Rated short-circuit making current: 50KA/63KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP3X
Width: 450mm
Depth: 830mm
Height: 1850mm
XGN15-12 SF6 Ring Main Unit
Rated voltage: 12KV
Rated current: 630A/125A
Rated short circuit breaking current: 20KA/31.5
Rated short-circuit making current: 50KA, 63KA, 80KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP2X
Width: 375; 500mm
Depth: 940mm
Height: 1600; 1850mm
XGN2-12 Cube Type Fixed Switchgear
Rated voltage: 12KV
Rated current: 630A, 1250A, 1600A, 2000A, 2500A, 3150A
Rated short circuit breaking current: 20KA, 25KA, 31.5KA,
40KA
Rated short-circuit making current: 50KA, 63KA, 80KA,
100KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP2X
Width: 1100mm
Depth: 1200mm
Height: 2650mm
009 www.peopleelectric.com
Complete Equipment
HXGN15-12 High-Voltage Metal-Enclosed
Switchgear
Rated voltage: 12KV
Rated current: 630A/1250A
Rated short circuit breaking current: 20KA
Rated short-circuit making current: 50KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP2X
Width: 750; 650mm
Depth: 900mm
Height: 2100mm
Switching Station
Rated voltage: 12KV
Rated current (A): 630A ( Load switch)
1250A (Circuit breaker)
Rated short circuit breaking current (KA):
31.5KA (Circuit breaker)
Rated short-circuit making current (Peak, KA):
50KA(Load switch), 80KA(Circuit breaker)
Rated short-time withstand current (KA/3s):
20KA (Load switch), 31.5KA(Circuit breaker)
Rated peak withstand current (KA):
50KA (Load switch), 80KA(Circuit breaker)
Operating mode: Electric, Manual Operation
TBB-12 High-Voltage Reactive Power
Compensator Cabinet
Rated voltage: 12KV
Rated current: 17.3A
Nominal capacity of capacitor: 300kvar~50kvar
Rated short-time withstand current: 15KA
Rated peak withstand current: 30KA
Protection grade: IP30
Width: 1000; 800mm
Depth: 1500mm
Height: 2300mm
XGN66-12 Switchgear
Rated voltage: 12KV
Rated current: 1250A
Rated short circuit breaking current: 20KA, 25KA,
31.5KA
Rated short-circuit making current: 50KA, 63KA, 80KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP4X
Width: 800mm
Depth: 950mm
Height: 2360mm
KGN-12 Energy Conservation
Intelligentize Switchgear
Rated voltage: 12KV
Rated current: 630A, 1000A, 1250A, 1600A, 2000A
Rated short circuit breaking current: 20KA, 25KA, 31.5KA
Rated short-circuit making current: 50KA, 63KA, 80KA
Rated power-frequency withstand voltage: 42/1min
(Fracture is 48KV)
Rated lightning impulse withstand voltage: 75
(Fracture is 85KV)
Protection grade: IP4X
Width: 800; 650mm
Depth: 1000mm
Height: 2300mm
DFW(R)-12/630-20 Cable Branch Box
Rated voltage: 12KV
Rated current: 630A
thermal stability current (2s): 20KA
Dynamic current (Peak): 50KA
Rated power-frequency withstand voltage: 42
Rated lightning impulse withstand voltage: 75
Protection grade: IP44
KYN61-40.5 Metal Armoured Open
Type Switchgear
Rated voltage: 40.5KV
Rated current: 1250A, 1600A, 2000A, 2500A, 3150A
Rated short circuit breaking current: 20KA, 25KA, 31.5KA
Rated short-circuit making current: 50KA, 63KA, 80KA
Rated power-frequency withstand voltage: 95/1min
(Fracture is 110KV)
Rated lightning impulse withstand voltage: 185
(Fracture is 215KV)
Protection grade: IP3X
Width: 1400; 1200mm
Depth: 2800; 3000mm
Height: 2600; 2400mm
KYN58-40.5 Metal Armoured Open
Type Switchgear
Rated voltage: 40.5KV
Rated current: 1250A, 1600A, 2000A, 2500A, 3150A
Rated short circuit breaking current: 20KA, 25KA, 31.5KA
Rated short-circuit making current: 50KA, 63KA, 80KA
Rated power-frequency withstand voltage: 95/1min
(Fracture is 110KV)
Rated lightning impulse withstand voltage: 185
(Fracture is 215KV)
Protection grade: IP3X
Width: 1400; 1200mm
Depth: 2800; 2600mm
Height: 2600; 2400mm
www.peopleelectric.com 010
XGN17R-40.5 Cube Type Fixed
Switchgear
Rated voltage: 40.5KV
Rated current: 1250A, 1600A, 2000A, 2500A, 3150A
Rated short circuit breaking current: 20KA, 25KA, 31.5KA
Rated short-circuit making current: 50KA, 63KA, 80KA
Rated power-frequency withstand voltage: 95/1min
(Fracture is 110KV)
Rated lightning impulse withstand voltage: 185
(Fracture is 215KV)
Protection grade: IP2X
Width: 1900mm
Depth: 3400mm
Height: 3600mm
DFW(R)-40.5/630-20 Cable Branch Box
Rated voltage: 40.5KV
Rated current: 630A
Thermal stability current (2s): 20KA
Dynamic current (Peak): 50KA
Rated power-frequency withstand voltage: 95
Rated lightning impulse withstand voltage: 185
Protection grade: IP3x
KYN28-24 Metal Armoured Open
Type Switchgear
Rated voltage: 24KV
Rated current: 1250A, 1600A, 2000A, 2500A, 3150A
Rated short circuit breaking current: 20KA, 25KA, 31.5KA
Rated short-circuit making current: 50KA, 63KA, 80KA
Rated power-frequency withstand voltage: 65/1min
(Fracture is 79KV)
Rated lightning impulse withstand voltage: 125
(Fracture is 145KV)
Protection grade: IP3X
Width: 1000mm
Depth: 1760mm
Height: 2420mm
DFW(R)-24/630-20 Cable Branch Box
Rated voltage: 24KV
Rated current: 630A
Thermal stability current (2s): 20KA
Dynamic current (Peak): 50KA
Rated power-frequency withstand voltage: 65/1min
Rated lightning impulse withstand voltage: 125
Protection grade: IP3x
XGN15-24 High-Voltage Metal
Enclosed Switchgear
Rated voltage: 24KV
Rated current: 630A/1250A
Rated short circuit breaking current: 20KA
Rated short-circuit making current: 50KA
Rated power-frequency withstand voltage: 65/1min
(Fracture is 79KV)
Rated lightning impulse withstand voltage: 125
(Fracture is 145KV)
Protection grade: IP3X
Width: 750; 650mm
Depth: 900mm
Height: 2100mm
GZDW Series Direct Current Cabinet
Input power voltage: Three-phase AC voltage 380V
Output DC rated voltage: 24V, 48V, 115V, 230V
Output DC rated current: 30A, 60A, 100A, 400A
Rated capacity of accumulator: 20, 40, 60, 100, 200,
400, 1000Ah
Protection grade: IP20~IP30
Width: 1000; 800mm
Depth: 800; 600mm
Height: 2200mm
GZS2 Series Direct Current Cabinet
Input power voltage: Three-phase AC voltage 380V
Output DC rated voltage: 24V, 48V, 115V, 230V
Output DC rated current: 30A, 60A, 100A, 400A
Rated capacity of accumulator: 20, 40, 60, 100, 200,
400, 1000Ah
Protection grade: IP20~IP30
Width: 1000; 800mm
Depth: 800; 600mm
Height: 2200mm
RMSX Compact Busbar Trunking
System
Rated voltage: 10KV
Rated current: 2500A, 3150A, 4000A
Rated short circuit breaking current: 20KA,
25KA, 31.5KA
Rated short-time withstand current 4s: 80KA
Protection grade: IP54
011 www.peopleelectric.com
Complete Equipment
YBW-12/0.4KV Pre-Assembled
Substation
Rated voltage (High-voltage, low-voltage): 12KV/0.4KV
Rated current (High-voltage, low-voltage): 115.5A/2887A
Ground loop rated short-time withstand current 2s: 20KA
Ground loop rated peak withstand current 3s: 50KA
Rated capacity of transformer: 2000KVA
Protection grade: IP33D
YBW-24/0.4KV Pre-Assembled
Substation
Rated voltage (High-voltage, low-voltage): 24KV/0.4KV
Rated current (High-voltage, low-voltage): 18.2A/909.3A
Ground loop current rated short-time withstand current 2s:
17.4KA
Ground loop current rated peak withstand current 3s:
43.5KA
Rated capacity of transformer: 630KVA
Protection grade: IP23
YBW-40.5/0.69KV Pre-Assembled
Substation
Rated voltage (High-voltage, low-voltage):
40.5KV/0.69KV
Rated current (High-voltage, low-voltage):
26.4A/1338.85A
Ground loop current rated short-time withstand
current 2s: 20KA
Ground loop current rated peak withstand
current 3s: 50KA
Rated capacity of transformer: 1600KVA
Protection grade: IP23D
ZB-M Series Combined Type Transformer
Substation
Rated voltage (High-voltage, low-voltage): 12KV/0.4KV
Rated current (High-voltage, low-voltage): 18.2A/909.3A
Ground loop rated short-time withstand current 2s: 17.4KA
Ground loop rated peak withstand current: 43.5KA
Rated capacity of transformer: 630KVA
Protection grade: IP33D
RPS-1000 Series Computer Integrated
Protection Devices
1. It gathers the functions of protection, measurement,
monitor, human-machine interface, communication as a
whole.
2. It supports the normal RS485 field bus communication.
3. Perfect ability of self-inspection, it will automatic alarm
if discover device fault. Having self-protection ability.
4. International general input power supply module,
compatibility 85~264V AC or DC working power supply.
5. The human-machine interface confirms to the
requirements of human-machine engineering design,
with the backlight graphic LCD, and menu design.
RPS-2000 Series Computer Integrated
Protection Devices
1. It gathers the functions of protection, measurement,
monitor, human-machine interface, communication as a
whole.
2. It supports the normal RS485 field bus communication.
3. Perfect ability of self-inspection, it will automatic alarm
if discover device fault. Having self-protection ability.
4. International general input power supply module,
compatibility 85~264V AC or DC working power supply.
5. The human-machine interface confirms to the
requirements of human-machine engineering design,
with the backlight graphic LCD, and menu design.
RPS-5000 Series Computer Integrated
Protection Devices
1. It gathers the functions of protection, measurement,
monitor, human-machine interface, communication as a
whole.
2. It supports the normal RS485 field bus communication.
3. Perfect ability of self-inspection, it will automatic alarm
if discover device fault. Having self-protection ability.
4. International general input power supply module,
compatibility 85~264V AC or DC working power supply.
5. The human-machine interface confirms to the
requirements of human-machine engineering design,
with the backlight graphic LCD, and menu design.
RPS-5000 Background Monitor Series
www.peopleelectric.com 012

2-Complete Equipment

  • 1.
  • 2.
    SIVACON 8PT LowVoltage Switchgear (Authorized by Siemens) Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 1000A~6300A Rated current of distribution bus-bar: 1000A~6300A Rated short-time withstand current of main bus-bar: 100KA Rated short-time withstand current of distribution bus-bar: 65KA Protection grade: IP40 Width: 1200; 1100; 1000; 900; 700mm Depth: 1000; 800; 600; 400mm Height: 2200mm RGCS Low Voltage Extraction Type Switchgear Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 630A-1600A-2500A-4000A Rated current of distribution bus-bar: 630A~1000A Rated short-time withstand current of main bus-bar: 30KA/50KA/80KA Rated short-time withstand current of distribution bus-bar: 30KA/50KA Protection grade: IP30 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm RGCK Low Voltage Switchboard Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 630A-1600A-2500A-4000A Rated current of distribution bus-bar: 630A~1000A Rated short-time withstand current of main bus-bar: 30KA/50KA/80KA Rated short-time withstand current of distribution bus-bar: 30KA/50KA Protection grade: IP30 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm RMNS Low Voltage Extraction Type Switchgear Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 630A-1600A-2500A-4000A Rated current of distribution bus-bar: 630A-1000A-2500A Rated short-time withstand current of main bus-bar: 30KA/50KA/80KA Rated short-time withstand current of distribution bus-bar: 30KA/50KA Protection grade: IP30/IP40 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm BloksetD Low Voltage Switchgear (Authorized by Schneider) Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 630A-1600A-2500A-4000A Rated current of distribution bus-bar: 630A-1000A Rated short-time withstand current of main bus-bar: 30KA/50KA/80KA Rated short-time withstand current of distribution bus-bar: 30KA/50KA Protection grade: IP30 Width: 1200; 1100; 1000; 900; 700mm Depth: 1000; 800; 600mm Height: 2200mm MD190 Low Voltage Extraction Type Switchgear (Authorized by ABB) Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 630A-1600A-2500A-4000A Rated current of distribution bus-bar: 630A-1000A Rated short-time withstand current of main bus-bar: 30KA/50KA/80KA Rated short-time withstand current of distribution bus-bar: 30KA/50KA Protection grade: IP42 Width: 760mm Depth: 950mm Height: 2185mm RDGCKZ Low Voltage Switchgear Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 2500A-4000A Rated current of distribution bus-bar: 1000A Rated short-time withstand current of main bus-bar: 80KA Rated short-time withstand current of distribution bus-bar: 50KA Protection grade: IP30 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm RSDK1 Low Voltage Extraction Type Switchgear Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 630A-1600A Rated current of distribution bus-bar: 800A Rated short-time withstand current of main bus-bar: 30KA Rated short-time withstand current of distribution bus-bar: 30KA Protection grade: IP30 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm 007 www.peopleelectric.com Complete Equipment
  • 3.
    MSN 2.0 (Authorizedby ABB) Rated voltage: 400V Rated insulation voltage: 660V Main bus-bar: In5000A/Ipk220KA/Icw100KA Distribution bus-bar: In1200A/Ipk110KA/Icw50KA Protection grade: IP30 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm RGGD Low Voltage Switchgear Rated voltage: 380V Rated insulation voltage: 380V Rated current of main bus-bar: 630A-1600A-3150A Rated current of distribution bus-bar: 630A~1000A-2500A Rated short-time withstand current of main bus-bar: 30KA/50KA/80KA Rated short-time withstand current of distribution bus-bar: 30KA/50KA Protection grade: IP30 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm RBCJ-1,2,3 Low Voltage Compensator Compensation type: contactor type, combination switch type, silicon control type (dynamic compensation) Rated voltage: 380V Rated insulation voltage: 660V Rated current : 507A~87A Nominal capacity of capacitor: 400kvar~60kvar Rated short-time withstand current: 15KA Rated peak withstand current: 30KA Protection grade: IP30 Width: 1000; 800; 600; 400mm Depth: 1000; 800; 600mm Height: 2200mm RJP-Outdoor Synthetical Distribution Box Rated voltage: 380V Rated insulation voltage: 660V Rated current: 400A~32A Single-phase/Three phase synthetical compensation: 145kvar~10kvar Rated short-time withstand current of main bus-bar: 10KA Switching control of capacitor: combination switch Protection grade: IP44 (Outdoors type) Length 1600mm × width 600mm × height 1200mm MNS-E Power Cabinet (Authorized by ABB) Rated voltage: 380V Rated insulation voltage: 690V Rated current: 100A~600A Rated short-time withstand current: 15KA Protection grade: IP40 Width: 600mm Depth: 400mm Height: 1800mm RXL-21 Power Cabinet Rated voltage: 380V Rated insulation voltage: 660V Rated current: 630A~100A Rated short-time withstand current: 15KA Rated peak withstand current:17KA Protection grade: IP30 Width: 700; 600mm Depth: 370mm Height: 1700; 1600mm RXGL-15 Power Cabinet Rated voltage: 380V Rated insulation voltage: 660V Rated current of main bus-bar: 630A Breaking capacity of main switch: 30KA Protection grade: IP40 Width: 700; 600mm Depth: 370mm Height: 1700; 1600mm RXJF Distribution Box Rated voltage: 220V/380V Rated insulation voltage: 500V Rated current: 250A~30A Rated short-time withstand current: 6KA Protection grade: IP30 www.peopleelectric.com 008
  • 4.
    PZ30 Distribution Box RatedVoltage: 220V/380V Rated insulation voltage: 400V Rated current: 80A~6A Rated short time current: 6KA Protection grade: IP30 RXJF-1 Double Power Distribution Box Rated voltage: 380V Rated insulation voltage: 660V Main bus-bar rated current: 630A~100A Rated ultimate short-circuit breaking capacity (Icu): 65KA Rated short circuit breaking capacity (Icu): 32.5KA Rated short-time withstand current: 15KA Protection grade: IP40 RDWB Combined Type Low-Voltage Distribution Box Rated voltage: 380V Rated insulation voltage: 500V Main bus-bar rated current: 600A~160A The main switch breaking capacity: 30KA Rated short time current: 30KA Protection grade: IP44 KYN28-12 Metal Armoured Open Type Switchgear Rated voltage: 12KV Rated current: 630A~5000A Rated short circuit breaking current: 20KA, 25KA, 31.5KA, 40A, 50A Rated short-circuit making current: 50KA, 63KA, 80KA, 100KA, 125KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP3X Width: 1000; 800mm Depth: 1500mm Height: 2300mm NXAirS LP Medium Voltage Switchgear (Authorized by Siemens) Rated voltage: 12KV Rated current: 630A, 1250A, 1600A, 2000A, 2500A, 3150A, 4000A Rated short circuit breaking current: 25KA, 31.5KA, 40KA Rated short-circuit making current: 63KA, 80KA, 100KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP4X Width: 800mm Depth: 1315mm Height: 2200mm RGHC-12 Solid Insulation Ring Main Unit Rated voltage: 12KV Rated current: 630A/125A Rated short circuit breaking current: 20KA/25KA Rated short-circuit making current: 50KA/63KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP3X Width: 450mm Depth: 830mm Height: 1850mm XGN15-12 SF6 Ring Main Unit Rated voltage: 12KV Rated current: 630A/125A Rated short circuit breaking current: 20KA/31.5 Rated short-circuit making current: 50KA, 63KA, 80KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP2X Width: 375; 500mm Depth: 940mm Height: 1600; 1850mm XGN2-12 Cube Type Fixed Switchgear Rated voltage: 12KV Rated current: 630A, 1250A, 1600A, 2000A, 2500A, 3150A Rated short circuit breaking current: 20KA, 25KA, 31.5KA, 40KA Rated short-circuit making current: 50KA, 63KA, 80KA, 100KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP2X Width: 1100mm Depth: 1200mm Height: 2650mm 009 www.peopleelectric.com Complete Equipment
  • 5.
    HXGN15-12 High-Voltage Metal-Enclosed Switchgear Ratedvoltage: 12KV Rated current: 630A/1250A Rated short circuit breaking current: 20KA Rated short-circuit making current: 50KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP2X Width: 750; 650mm Depth: 900mm Height: 2100mm Switching Station Rated voltage: 12KV Rated current (A): 630A ( Load switch) 1250A (Circuit breaker) Rated short circuit breaking current (KA): 31.5KA (Circuit breaker) Rated short-circuit making current (Peak, KA): 50KA(Load switch), 80KA(Circuit breaker) Rated short-time withstand current (KA/3s): 20KA (Load switch), 31.5KA(Circuit breaker) Rated peak withstand current (KA): 50KA (Load switch), 80KA(Circuit breaker) Operating mode: Electric, Manual Operation TBB-12 High-Voltage Reactive Power Compensator Cabinet Rated voltage: 12KV Rated current: 17.3A Nominal capacity of capacitor: 300kvar~50kvar Rated short-time withstand current: 15KA Rated peak withstand current: 30KA Protection grade: IP30 Width: 1000; 800mm Depth: 1500mm Height: 2300mm XGN66-12 Switchgear Rated voltage: 12KV Rated current: 1250A Rated short circuit breaking current: 20KA, 25KA, 31.5KA Rated short-circuit making current: 50KA, 63KA, 80KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP4X Width: 800mm Depth: 950mm Height: 2360mm KGN-12 Energy Conservation Intelligentize Switchgear Rated voltage: 12KV Rated current: 630A, 1000A, 1250A, 1600A, 2000A Rated short circuit breaking current: 20KA, 25KA, 31.5KA Rated short-circuit making current: 50KA, 63KA, 80KA Rated power-frequency withstand voltage: 42/1min (Fracture is 48KV) Rated lightning impulse withstand voltage: 75 (Fracture is 85KV) Protection grade: IP4X Width: 800; 650mm Depth: 1000mm Height: 2300mm DFW(R)-12/630-20 Cable Branch Box Rated voltage: 12KV Rated current: 630A thermal stability current (2s): 20KA Dynamic current (Peak): 50KA Rated power-frequency withstand voltage: 42 Rated lightning impulse withstand voltage: 75 Protection grade: IP44 KYN61-40.5 Metal Armoured Open Type Switchgear Rated voltage: 40.5KV Rated current: 1250A, 1600A, 2000A, 2500A, 3150A Rated short circuit breaking current: 20KA, 25KA, 31.5KA Rated short-circuit making current: 50KA, 63KA, 80KA Rated power-frequency withstand voltage: 95/1min (Fracture is 110KV) Rated lightning impulse withstand voltage: 185 (Fracture is 215KV) Protection grade: IP3X Width: 1400; 1200mm Depth: 2800; 3000mm Height: 2600; 2400mm KYN58-40.5 Metal Armoured Open Type Switchgear Rated voltage: 40.5KV Rated current: 1250A, 1600A, 2000A, 2500A, 3150A Rated short circuit breaking current: 20KA, 25KA, 31.5KA Rated short-circuit making current: 50KA, 63KA, 80KA Rated power-frequency withstand voltage: 95/1min (Fracture is 110KV) Rated lightning impulse withstand voltage: 185 (Fracture is 215KV) Protection grade: IP3X Width: 1400; 1200mm Depth: 2800; 2600mm Height: 2600; 2400mm www.peopleelectric.com 010
  • 6.
    XGN17R-40.5 Cube TypeFixed Switchgear Rated voltage: 40.5KV Rated current: 1250A, 1600A, 2000A, 2500A, 3150A Rated short circuit breaking current: 20KA, 25KA, 31.5KA Rated short-circuit making current: 50KA, 63KA, 80KA Rated power-frequency withstand voltage: 95/1min (Fracture is 110KV) Rated lightning impulse withstand voltage: 185 (Fracture is 215KV) Protection grade: IP2X Width: 1900mm Depth: 3400mm Height: 3600mm DFW(R)-40.5/630-20 Cable Branch Box Rated voltage: 40.5KV Rated current: 630A Thermal stability current (2s): 20KA Dynamic current (Peak): 50KA Rated power-frequency withstand voltage: 95 Rated lightning impulse withstand voltage: 185 Protection grade: IP3x KYN28-24 Metal Armoured Open Type Switchgear Rated voltage: 24KV Rated current: 1250A, 1600A, 2000A, 2500A, 3150A Rated short circuit breaking current: 20KA, 25KA, 31.5KA Rated short-circuit making current: 50KA, 63KA, 80KA Rated power-frequency withstand voltage: 65/1min (Fracture is 79KV) Rated lightning impulse withstand voltage: 125 (Fracture is 145KV) Protection grade: IP3X Width: 1000mm Depth: 1760mm Height: 2420mm DFW(R)-24/630-20 Cable Branch Box Rated voltage: 24KV Rated current: 630A Thermal stability current (2s): 20KA Dynamic current (Peak): 50KA Rated power-frequency withstand voltage: 65/1min Rated lightning impulse withstand voltage: 125 Protection grade: IP3x XGN15-24 High-Voltage Metal Enclosed Switchgear Rated voltage: 24KV Rated current: 630A/1250A Rated short circuit breaking current: 20KA Rated short-circuit making current: 50KA Rated power-frequency withstand voltage: 65/1min (Fracture is 79KV) Rated lightning impulse withstand voltage: 125 (Fracture is 145KV) Protection grade: IP3X Width: 750; 650mm Depth: 900mm Height: 2100mm GZDW Series Direct Current Cabinet Input power voltage: Three-phase AC voltage 380V Output DC rated voltage: 24V, 48V, 115V, 230V Output DC rated current: 30A, 60A, 100A, 400A Rated capacity of accumulator: 20, 40, 60, 100, 200, 400, 1000Ah Protection grade: IP20~IP30 Width: 1000; 800mm Depth: 800; 600mm Height: 2200mm GZS2 Series Direct Current Cabinet Input power voltage: Three-phase AC voltage 380V Output DC rated voltage: 24V, 48V, 115V, 230V Output DC rated current: 30A, 60A, 100A, 400A Rated capacity of accumulator: 20, 40, 60, 100, 200, 400, 1000Ah Protection grade: IP20~IP30 Width: 1000; 800mm Depth: 800; 600mm Height: 2200mm RMSX Compact Busbar Trunking System Rated voltage: 10KV Rated current: 2500A, 3150A, 4000A Rated short circuit breaking current: 20KA, 25KA, 31.5KA Rated short-time withstand current 4s: 80KA Protection grade: IP54 011 www.peopleelectric.com Complete Equipment
  • 7.
    YBW-12/0.4KV Pre-Assembled Substation Rated voltage(High-voltage, low-voltage): 12KV/0.4KV Rated current (High-voltage, low-voltage): 115.5A/2887A Ground loop rated short-time withstand current 2s: 20KA Ground loop rated peak withstand current 3s: 50KA Rated capacity of transformer: 2000KVA Protection grade: IP33D YBW-24/0.4KV Pre-Assembled Substation Rated voltage (High-voltage, low-voltage): 24KV/0.4KV Rated current (High-voltage, low-voltage): 18.2A/909.3A Ground loop current rated short-time withstand current 2s: 17.4KA Ground loop current rated peak withstand current 3s: 43.5KA Rated capacity of transformer: 630KVA Protection grade: IP23 YBW-40.5/0.69KV Pre-Assembled Substation Rated voltage (High-voltage, low-voltage): 40.5KV/0.69KV Rated current (High-voltage, low-voltage): 26.4A/1338.85A Ground loop current rated short-time withstand current 2s: 20KA Ground loop current rated peak withstand current 3s: 50KA Rated capacity of transformer: 1600KVA Protection grade: IP23D ZB-M Series Combined Type Transformer Substation Rated voltage (High-voltage, low-voltage): 12KV/0.4KV Rated current (High-voltage, low-voltage): 18.2A/909.3A Ground loop rated short-time withstand current 2s: 17.4KA Ground loop rated peak withstand current: 43.5KA Rated capacity of transformer: 630KVA Protection grade: IP33D RPS-1000 Series Computer Integrated Protection Devices 1. It gathers the functions of protection, measurement, monitor, human-machine interface, communication as a whole. 2. It supports the normal RS485 field bus communication. 3. Perfect ability of self-inspection, it will automatic alarm if discover device fault. Having self-protection ability. 4. International general input power supply module, compatibility 85~264V AC or DC working power supply. 5. The human-machine interface confirms to the requirements of human-machine engineering design, with the backlight graphic LCD, and menu design. RPS-2000 Series Computer Integrated Protection Devices 1. It gathers the functions of protection, measurement, monitor, human-machine interface, communication as a whole. 2. It supports the normal RS485 field bus communication. 3. Perfect ability of self-inspection, it will automatic alarm if discover device fault. Having self-protection ability. 4. International general input power supply module, compatibility 85~264V AC or DC working power supply. 5. The human-machine interface confirms to the requirements of human-machine engineering design, with the backlight graphic LCD, and menu design. RPS-5000 Series Computer Integrated Protection Devices 1. It gathers the functions of protection, measurement, monitor, human-machine interface, communication as a whole. 2. It supports the normal RS485 field bus communication. 3. Perfect ability of self-inspection, it will automatic alarm if discover device fault. Having self-protection ability. 4. International general input power supply module, compatibility 85~264V AC or DC working power supply. 5. The human-machine interface confirms to the requirements of human-machine engineering design, with the backlight graphic LCD, and menu design. RPS-5000 Background Monitor Series www.peopleelectric.com 012