Smoke Alarm Requirements for
Residential Property in Maryland
Stricter mandates regarding
smoke detectors
Effective July 1, 2013
Tim Knobloch, (240) 292-1040,
TKnobloch@mris.com
Single-Family (one to two dwelling units)
Sale Requirements as of July 1, 2013:
• Language added to the Seller disclosure form asking
sellers to indicate whether the smoke alarms are over
10 years old and whether they have sealed, tamper
resistant batteries
• This requirement applies to contracts entered into
after July 1, 2013
Single-Family (one to two dwelling units)
New Construction (including renovation) after July 1, 2013
• Number of alarms:
• 1 alarm in each sleeping room
• 1 alarm in each hallway or common area outside of the sleeping rooms
• 1 alarm in a hallway or common area on each level, including basements
but excluding unoccupied attics, garages, and crawl spaces
• If more than two alarms are required in a new residential dwelling, the
alarms shall be configured to sound simultaneously
• The alarms shall operate on alternating current (AC) with a battery
backup or approved secondary power source
• This is the same requirement as the current 2012 International Residential
Code and was already being enforced by building permit offices since
2006
Single-Family (one to two dwelling units)
Existing Properties
• For properties built before July 1, 1975
▫ Number of alarms:
 At least one alarm either battery operated or AC
 After January 1, 2018 (NEW REQUIREMENT)
 At least one alarm on each level of the home (excluding unoccupied
attics, garages)
▫ Battery alarms after 2018 must be sealed, long-life battery
smoke alarms with a silence/hush button feature
Single-Family (one to two dwelling units)
Existing Properties
• For properties built between July 1, 1975 – Jan 1, 1989
▫ Number of alarms:
 At least one AC smoke alarm installed in the sleeping area
 After January 1, 2018 (NEW REQUIREMENT)
 At least one alarm in a sleeping area and one alarm on each level
of the home.
▫ The new additional alarms may be battery-operated as long as they are
sealed, long-life battery smoke alarms with a silence/hush button
feature
▫ No alarm should be older than 10 years
Single-Family (one to two dwelling units)
Existing Properties
• For properties built between January 1, 1989 – July 1,
1990:
▫ Number of alarms:
 At least one alarm outside of each sleeping area and on each
additional story of the home, including the basement but not
unoccupied attics, garages or crawl spaces
 Alarms must be AC and interconnected to alarm
simultaneously
 After January 1, 2018 (NEW REQUIREMENT)
 No change to the number of alarms, but no alarm should be older
than 10 years
Single-Family (one to two dwelling units)
Existing Properties
• For properties built between July 1, 1990 and July 1,
2013:
▫ Same requirement as the previous slide for Jan. 1
1989 – July 1, 1990 properties except that the
alarms must be AC AND have battery back-up
▫ NOTE: some counties required more stringent
rules including alarms in each bedroom for new
construction
Single-Family (one to two dwelling units) after
July 1, 2013 (New Requirement)
• Alarms must be upgraded if:
▫ Existing alarms exceed 10 years from date of manufacture
▫ Existing alarms fail to operate or malfunction
▫ A change in tenancy occurs and the residence has not been previously equipped
with sealed, long-life battery smoke alarms with silence/hush button features
• AC alarms must be upgraded to new AC alarms
• Battery alarms must be upgraded to sealed, long-life battery smoke
alarms with silence/hush button features
• Alarms must be located on each level of the residence excluding
unoccupied attics, garages, or crawl spaces
▫ Any additional alarm required by the new law may be battery operated as long
as it is a sealed, long-life battery with silence/hush button features
Multi-Family Rentals
(more than two dwelling units)
• Alarms must be AC powered
▫ Multi-family units constructed after July 1, 1990 must be AC
powered with battery back-up
• Landlords must provide special alarms for the deaf or hard
of hearing, and may require reimbursement for those alarms
• Landlords are responsible for the installation, repair and
replacement of smoke alarms
• Tenants are responsible for testing the units and notifying
the landlord in writing of the failure or malfunction of the
unit
• No alarms should be older than 10 years unless the alarms
have been sensitivity tested and properly calibrated on an
annual basis per current fire codes
Smoke Alarm Requirements for
Residential Property in Maryland
For questions concerning property
management or leasing services,
please call or email:
Tim Knobloch, (240) 292-1040,
TKnobloch@mris.com

More Related Content

Viewers also liked

Film poster
Film posterFilm poster
Film posterhivron
 
Potencial target market research
Potencial target market researchPotencial target market research
Potencial target market researchhivron
 
Research on teaser trailers
Research on teaser trailersResearch on teaser trailers
Research on teaser trailershivron
 
Storyboard[1]
Storyboard[1]Storyboard[1]
Storyboard[1]hivron
 
Windows 8 and the cloud a match made in heaven
Windows 8 and the cloud a match made in heavenWindows 8 and the cloud a match made in heaven
Windows 8 and the cloud a match made in heavenNoam Sheffer
 
ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้
ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้
ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้Sununtha Putpun
 
การ เรียนรู้เพื่อพัฒนากระบวนการคิด
การ เรียนรู้เพื่อพัฒนากระบวนการคิดการ เรียนรู้เพื่อพัฒนากระบวนการคิด
การ เรียนรู้เพื่อพัฒนากระบวนการคิดSununtha Putpun
 
Integrated marketing - Using LinkedIn as your Hub for marketing
Integrated marketing - Using LinkedIn as your Hub for marketingIntegrated marketing - Using LinkedIn as your Hub for marketing
Integrated marketing - Using LinkedIn as your Hub for marketingRockville Chamber of Commerce
 
Grass roots marketing - marketing for immediate results
Grass roots marketing - marketing for immediate resultsGrass roots marketing - marketing for immediate results
Grass roots marketing - marketing for immediate resultsRockville Chamber of Commerce
 

Viewers also liked (12)

Film poster
Film posterFilm poster
Film poster
 
Potencial target market research
Potencial target market researchPotencial target market research
Potencial target market research
 
Research on teaser trailers
Research on teaser trailersResearch on teaser trailers
Research on teaser trailers
 
Storyboard[1]
Storyboard[1]Storyboard[1]
Storyboard[1]
 
Full Paper
Full PaperFull Paper
Full Paper
 
Windows 8 and the cloud a match made in heaven
Windows 8 and the cloud a match made in heavenWindows 8 and the cloud a match made in heaven
Windows 8 and the cloud a match made in heaven
 
ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้
ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้
ชุดฝึกอบรมการวัดและประเมินผลการเรียนรู้
 
การ เรียนรู้เพื่อพัฒนากระบวนการคิด
การ เรียนรู้เพื่อพัฒนากระบวนการคิดการ เรียนรู้เพื่อพัฒนากระบวนการคิด
การ เรียนรู้เพื่อพัฒนากระบวนการคิด
 
Hubungan etnik
Hubungan etnikHubungan etnik
Hubungan etnik
 
Integrated marketing - Using LinkedIn as your Hub for marketing
Integrated marketing - Using LinkedIn as your Hub for marketingIntegrated marketing - Using LinkedIn as your Hub for marketing
Integrated marketing - Using LinkedIn as your Hub for marketing
 
Terapi bermain
Terapi bermain Terapi bermain
Terapi bermain
 
Grass roots marketing - marketing for immediate results
Grass roots marketing - marketing for immediate resultsGrass roots marketing - marketing for immediate results
Grass roots marketing - marketing for immediate results
 

More from Rockville Chamber of Commerce (8)

Color On The Creek Time To Dance
Color On The Creek Time To DanceColor On The Creek Time To Dance
Color On The Creek Time To Dance
 
NewSchinnerer QRC_2009final
NewSchinnerer QRC_2009finalNewSchinnerer QRC_2009final
NewSchinnerer QRC_2009final
 
Consultants_Postcards2008
Consultants_Postcards2008Consultants_Postcards2008
Consultants_Postcards2008
 
Rockville chamber invite
Rockville chamber inviteRockville chamber invite
Rockville chamber invite
 
Linked in for business2
Linked in for business2Linked in for business2
Linked in for business2
 
Risk Reduction Steps for Landlords
Risk Reduction Steps for LandlordsRisk Reduction Steps for Landlords
Risk Reduction Steps for Landlords
 
Rental statistics june 2013
Rental statistics june 2013Rental statistics june 2013
Rental statistics june 2013
 
Media Overview
Media OverviewMedia Overview
Media Overview
 

Recently uploaded

A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaShree Krishna Exports
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...Aggregage
 
A305_A2_file_Batkhuu progress report.pdf
A305_A2_file_Batkhuu progress report.pdfA305_A2_file_Batkhuu progress report.pdf
A305_A2_file_Batkhuu progress report.pdftbatkhuu1
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 DelhiCall Girls in Delhi
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Roland Driesen
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLSeo
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Delhi Call girls
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...amitlee9823
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayNZSG
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxWorkforce Group
 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insightsseri bangash
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 

Recently uploaded (20)

A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in India
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
A305_A2_file_Batkhuu progress report.pdf
A305_A2_file_Batkhuu progress report.pdfA305_A2_file_Batkhuu progress report.pdf
A305_A2_file_Batkhuu progress report.pdf
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
Forklift Operations: Safety through Cartoons
Forklift Operations: Safety through CartoonsForklift Operations: Safety through Cartoons
Forklift Operations: Safety through Cartoons
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insights
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 

Smoke alarm requirements

  • 1. Smoke Alarm Requirements for Residential Property in Maryland Stricter mandates regarding smoke detectors Effective July 1, 2013 Tim Knobloch, (240) 292-1040, TKnobloch@mris.com
  • 2. Single-Family (one to two dwelling units) Sale Requirements as of July 1, 2013: • Language added to the Seller disclosure form asking sellers to indicate whether the smoke alarms are over 10 years old and whether they have sealed, tamper resistant batteries • This requirement applies to contracts entered into after July 1, 2013
  • 3. Single-Family (one to two dwelling units) New Construction (including renovation) after July 1, 2013 • Number of alarms: • 1 alarm in each sleeping room • 1 alarm in each hallway or common area outside of the sleeping rooms • 1 alarm in a hallway or common area on each level, including basements but excluding unoccupied attics, garages, and crawl spaces • If more than two alarms are required in a new residential dwelling, the alarms shall be configured to sound simultaneously • The alarms shall operate on alternating current (AC) with a battery backup or approved secondary power source • This is the same requirement as the current 2012 International Residential Code and was already being enforced by building permit offices since 2006
  • 4. Single-Family (one to two dwelling units) Existing Properties • For properties built before July 1, 1975 ▫ Number of alarms:  At least one alarm either battery operated or AC  After January 1, 2018 (NEW REQUIREMENT)  At least one alarm on each level of the home (excluding unoccupied attics, garages) ▫ Battery alarms after 2018 must be sealed, long-life battery smoke alarms with a silence/hush button feature
  • 5. Single-Family (one to two dwelling units) Existing Properties • For properties built between July 1, 1975 – Jan 1, 1989 ▫ Number of alarms:  At least one AC smoke alarm installed in the sleeping area  After January 1, 2018 (NEW REQUIREMENT)  At least one alarm in a sleeping area and one alarm on each level of the home. ▫ The new additional alarms may be battery-operated as long as they are sealed, long-life battery smoke alarms with a silence/hush button feature ▫ No alarm should be older than 10 years
  • 6. Single-Family (one to two dwelling units) Existing Properties • For properties built between January 1, 1989 – July 1, 1990: ▫ Number of alarms:  At least one alarm outside of each sleeping area and on each additional story of the home, including the basement but not unoccupied attics, garages or crawl spaces  Alarms must be AC and interconnected to alarm simultaneously  After January 1, 2018 (NEW REQUIREMENT)  No change to the number of alarms, but no alarm should be older than 10 years
  • 7. Single-Family (one to two dwelling units) Existing Properties • For properties built between July 1, 1990 and July 1, 2013: ▫ Same requirement as the previous slide for Jan. 1 1989 – July 1, 1990 properties except that the alarms must be AC AND have battery back-up ▫ NOTE: some counties required more stringent rules including alarms in each bedroom for new construction
  • 8. Single-Family (one to two dwelling units) after July 1, 2013 (New Requirement) • Alarms must be upgraded if: ▫ Existing alarms exceed 10 years from date of manufacture ▫ Existing alarms fail to operate or malfunction ▫ A change in tenancy occurs and the residence has not been previously equipped with sealed, long-life battery smoke alarms with silence/hush button features • AC alarms must be upgraded to new AC alarms • Battery alarms must be upgraded to sealed, long-life battery smoke alarms with silence/hush button features • Alarms must be located on each level of the residence excluding unoccupied attics, garages, or crawl spaces ▫ Any additional alarm required by the new law may be battery operated as long as it is a sealed, long-life battery with silence/hush button features
  • 9. Multi-Family Rentals (more than two dwelling units) • Alarms must be AC powered ▫ Multi-family units constructed after July 1, 1990 must be AC powered with battery back-up • Landlords must provide special alarms for the deaf or hard of hearing, and may require reimbursement for those alarms • Landlords are responsible for the installation, repair and replacement of smoke alarms • Tenants are responsible for testing the units and notifying the landlord in writing of the failure or malfunction of the unit • No alarms should be older than 10 years unless the alarms have been sensitivity tested and properly calibrated on an annual basis per current fire codes
  • 10. Smoke Alarm Requirements for Residential Property in Maryland For questions concerning property management or leasing services, please call or email: Tim Knobloch, (240) 292-1040, TKnobloch@mris.com