ТЕОРЕТИЧНА ЕЛЕКТРОТЕХНІКА ELECTRICAL ENGINEERING
2005. Вип. 58. С. 138-146 2005. Is. 58. P. 138-146
_________________________________________________________
© Eleschova Z., Belan A., Gasparovsky D., 2005
УДК 621.311
ROTOR GROUND FAULT PROTECTION OF GENERATOR
WITH STATIC EXCITATION SYSTEM
Z. Eleschova, A. Belan, D. Gasparovsky
Slovak University of Technology in Bratislava, Slovak Republic
This paper deals with the influence of harmonics produced by the static
excitation system of generator on the rotor ground fault protection of synchronous
generator. The report brings measured courses of field voltage and current flow
through insulation system of field winding during generator failure-free operation.
There is analysed potential impact of static excitation system on correct function of
rotor ground protection based on AC injection method.
Key words: rotor, generator, static excitation system.
The synchronous generator is one of the most important and the most complicated
elements of power system. It is main source of electrical energy. It is essential to know
everything about its steady states but mainly about its fault states. Various fault states
can occur during generator operation. We distinguish between internal and external
failures of generators.
The first ground fault of field winding belongs in internal failures of generator
rotor. The single ground fault on the field winding is not hard fault state for synchronous
machine. But there is probability of occurrence of the second ground fault which
presents short circuit with very large currents, dynamic and thermal stress of filed
winding and rotor armature [1].
The Faults on Synchronous Generator Field Winding. Synchronous generator
excitation system is insulated DC electrical system. Rotor of generator, like a rotating
part, has higher probability of single ground fault occurrence than stator. Rotor winding
damage is frequently, mainly on turbogenerators where rotor winding insulation is fairly
stressed effected by centrifugal forces [9].
Ground fault of field winding. The first rotor ground fault causes just a little fault
current, although it stresses the insulation in portions of the winding where the fault is.
The real danger is the second ground fault which can cause significant forces. During
dual ground fault can draw large currents which may cause extensive damage to rotor
winding and armature.
It is important to detect the first ground fault, thereby preventing a serious failure.
The first ground fault is signalizing only. Generator is tripping and damaged winding is
repairing. In this way it can prevent large damages which could be during the second
ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 139
ground fault. Backup protection against the second ground fault is loss of excitation
protection.
Field winding short circuit. Shorted turns in the generator field winding can cause
distorting the field across the air gap. This is due to the unsymmetrical turn current of
magnetomotive force in different parts of the field winding. The accrued much distorted
forces can effect rotor deformation or severe vibrations which can destroy machine
bearings. The machine can be protected before serious damage by vibration detector
which can alarm or trip unit. Shorted winding is often due to rotor ground faults at two
different places.
Open field winding. Field winding open circuit is rare. But rapidly detection of
this fault is required, because it can be accompanied with arcing that can do great
damage to the rotor body. Open field winding can be detected by loss of excitation
protection.
Rotor Ground fault protection. The rotor ground fault protection should protect
whole field circuit of generator in cause of ground fault. In regard to the second ground
fault is non-permissible, the protection which signalize the first ground fault must be
high reliable and shouldn’t incorrect act, because every protection alarm of the rotor first
ground fault is necessary checkup.
The protection, which controls field winding insulation by injection of auxiliary
voltage, is the most frequently used for detecting of rotor ground fault of generator.
According to injected voltage the rotor ground fault protections are based on AC or DC
injection method.
The new rotor ground fault protection uses injected low-frequency squarewave
voltage.
AC injection method. AC injection method is showed in fig. 1. This method is
based on injection of AC auxiliary voltage to field winding through a capacitor. When
any point of field winding is grounded, circuit will be complete and the protection
signalizes the rotor ground fault. This system has no blind point [9].
Fig. 1. Rotor ground fault protection of generator – AC injection method.
Z. Eleschova, A. Belan, D. Gasparovsky140
DC injection method. DC injection method is showed in fig. 2. Protection based
on this method uses DC voltage. The DC output of the rectifier is connected to the
positive side of the field circuit and the second output is grounded. Every point of the
field winding grounded closes circuit through current relay [5].
Fig. 2. Rotor ground fault protection of generator – DC injection method.
Rotor ground fault protection with squarewave auxiliary voltage. Fig. 3 shows
principle of rotor ground fault protection with squarewave auxiliary voltage [1].
Fig. 3. Rotor ground fault protection of generator – low-frequency squarewave
voltage injection.
ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 141
Measuring circuit M is connected to rotor winding through the high resistance
21 and vv RR . The squarewave auxiliary voltage auxU causes an auxiliary current
auxI . The value of auxiliary current is given
,aux
aux
E v M
U
I
R R R
=
+ +
(1)
where
1 2
1 2
.v v
v
v v
R R
R
R R
=
+
(2)
If M vR R<< then measured voltage MU is
aux M
M
E v
U R
U
R R
≈
+
. (3)
For a consideration of measured voltage course and value protection evaluates the
leakage resistance value and state of rotor insulation system.
Flow current through the rotor ground fault protection measurement. The
goal of measurement was to find out and analyse influence of the static excitation
system on correct function of rotor ground fault protection. The measurements were
made on the synchronous machines with static excitation system and rotating exciter too.
The generators were 110 MW, 32 MW and 28 MW. The rotor ground protections of
these machines are based on the AC injection. The measurements were aimed at
determining of harmonic contents in voltages and currents of generator, in voltages and
currents in front of static excitation system, in field voltage, mainly in current flow
through rotor ground fault protection in failure-free state with different value of field
current.
The measurement on 110 MW generator with static excitation system. This
generator had analogue rotor ground protection based on the AC method.
-1000
-500
0
500
1000
0,00 0,02 0,04
t [s]
u[V]
Fig. 4. The voltage in front of the static excitation system.
Z. Eleschova, A. Belan, D. Gasparovsky142
0
100
200
300
400
500
600
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Harmonic Order
U[V]
Fig. 5. The harmonic content of voltage in front of the static excitation system.
-1000
-500
0
500
1000
0,00 0,02 0,04
t [s]
i[A]
Fig. 6. The current in front of the static excitation system.
0
150
300
450
600
750
900
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Harmonic Order
I[A]
Fig. 7. The harmonic content of current in front of the static excitation system.
-200
0
200
400
600
0,00 0,02 0,04
t [s]
uf[V]
Fig. 8. The field voltage.
ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 143
0
20
40
60
80
100
120
140
160
180
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Harmonic Order
Uf[V]
Fig. 9. The harmonic content of field voltage.
400
800
1200
1600
2000
0,00 0,02 0,04
t [s]
if[A]
Fig. 10. The field current.
-400
-200
0
200
400
600
0,00 0,02 0,04
t [s]
i[mA]
Fig. 11. The current flow through rotor ground protection.
0,00
0,05
0,10
0,15
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Harmonic Order
I[A]
Fig. 12. The harmonic content of current flow through rotor ground protection.
Z. Eleschova, A. Belan, D. Gasparovsky144
From the field voltage course (fig. 8) can see that this voltage isn’t DC voltage.
That is way we did harmonic analysis of this voltage. In the field voltage are specific
harmonics (the 6th
, 12th
, 18th
etc.) which are multiples of the number of rectifier impulse
[6].
In histogram of harmonic content of voltage and current in front of the static
excitation system (fig. 5, fig. 7) we can see impact of six-impulse rectifier too. On the
rectifier AC side in the voltage and current are specific harmonics (the 5th
, 7th
, 11th
etc.)
which are given [8]
1n k p= ± , (4)
where p – the number of impulse; n – the harmonic order; k – the natural number.
From measured course of current flow through protection (fig. 11) is to see that
harmonic content is marked. The instantaneous values of this current achieve more than
400 mA. This is more than setting value at the protection (15 mA).
The current flows through the protection contents mainly higher harmonics (it’s
shown in histogram of content harmonic – fig. 12), the magnitude of the fundamental of
the current is cca 9 mA, this is bellow the current nominal value of relay. Till the 6th
harmonic magnitude is larger than 15 mA.
In spite of this the rotor ground protection didn’t act false during measurement
(with fluent field voltage changing). The analogue protection has connected parallel to
current relay two capacitors which eliminate higher harmonics from the current flows
through this relay. It means higher harmonics haven’t negative impact on the protection
function.
The measurement on 28 MW generator with static excitation system. This
generator had the analogue rotor ground protection based on the AC method. In respect
of size of synchronous generator (28 MW) in compare with 110 MW generator (smaller
value of field winding capacitance) the magnitude of current flows through the
protection is markedly smaller. Fundamental harmonic magnitude is cca 5,5 mA and
magnitudes of the other higher harmonics are smaller. In this case the rotor ground
protection shouldn’t act false.
-15
-10
-5
0
5
10
15
0,00 0,02 0,04
t [s]
i[mA]
Fig. 13. The current flow through rotor ground protection.
ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 145
0
2
4
6
1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930
Harmonic Order
I[mA]
Fig. 14. The harmonic content of current flow through rotor ground protection.
The measurement on 32 MW generator with the rotating exciter. This
generator had the digital rotor ground protection based on the AC method. Because this
generator had the rotating exciter – dynamo, the field voltage is really DC and the
injected auxiliary AC voltage of protection isn’t deformed. There wasn’t possible to
measure the current flows through the rotor ground protection because this current had
too small magnitude – non-measurable by the measuring instrument.
The measurements on the generators with the rotor ground protection based on the
AC injection method and with the static excitation system were made at the instance of
generator operator to find out the static excitation system impact on this protection
correct function. Because the rotor ground protection on 110 MW machine signalizes
rotor ground fault in express terms in spite of rotor insulation system was sound.
The measurements on 110 MW generator with the static excitation system and with
the rotor ground protection based on the AC injection show the impact of six-impulse
thyristor rectifier on course and harmonic content of voltage and current in front of the
excitation system, of field voltage, but also of current flows through rotor winding
insulation (and rotor ground protection too) during failure-free and steady state
operation of generator.
From the measurements is result that during steady state of synchronous generator
the rotor ground protection didn’t act false in spite of the instantaneous values and
higher harmonics magnitudes of the current flows through this protection are greater
than setting value on protection. As mentioned above harmonics of current flow through
parallel connected capacitors and don’t through protection current relay.
It means that seemingly “easy solution” – to replace the analogue protection by
digital haven’t enough because in this case the harmonics aren’t causer of the rotor
ground protection incorrect acting.
_____________
1. Anderson P. Power System Protection. New York: IEEE Press, 1999.
2. Arrillaga J., Watson N. Power System Harmonics. John Wiley & Sons, Ltd, West
Sussex, England, 2003.
3. Bašta J., Chládek Mayer I. Teorie elektrických stroju. STNL/ALFA, Praha, 1968.
4. Beláň A., Eleschová Ž., Janíček F., Reváková D. Vplyv statickej budiacej sústavy
generátorov na zemnú rotorovú ochranu GR12. Správa k Zmluve č. 95/130/2002.
KEE FEI STU, Bratislava, 2002.
5. Dohnálek P. Ochrany pro prumysl a energetiku. STNL, Praha, 1991.
Z. Eleschova, A. Belan, D. Gasparovsky146
6. Chladný V. Digital measurement method of local frequency in power system.
Proceeding of International science conference Elektroenergetika 1997, FEI VŠB–
TU Ostrava, 1997.
7. Ungrad H., Winkler W., Wiszniewski A. Protections Techniques in Electrical Energy
Systems. Marcel Dekker, INC. New York, 1995.
8. Vaculíková P., Vaculík E. a kol. Elektromagnetická kompatibilita
elektrotechnických systému. Praha: Grada Publishing, 1998.
9. Janíček F., Chladný V., Beláň A., Eleschová Ž. Digitálne ochrany elektrických
strojov. Košice: FEI TU, 2000.
ЗАХИСТ РОТОРА ГЕНЕРАТОРА ЗІ СТАТИЧНОЮ СИСТЕМОЮ
ЗБУДЖЕННЯ ВІД ЗАМИКАНЬ НА ЗЕМЛЮ
З. Елешова, А. Белан, Д. Гаспаровський
Словацький технологічний університет Братислави, Словацька республіка
Описано вплив гармонік, генерованих статичною системою збудження
генератора, на роботу захисту від замикань на землю синхронного
генератора. Наведено способи вимірювання напруги збудження і струму,
який протікає через систему ізоляції обмотки збудження під час нормальної
роботи генератора. На підставі методу введення змінного струму
проаналізовано потенційний вплив статичної системи збудження на
правильність роботи захисту від замикань на землю.
Ключові слова: ротор, генератор, статична система збудження.
Стаття надійшла до редколегії 20.06.2005
Прийнята до друку 01.09.2005

More Related Content

What's hot

Generator protection system by Nicholas Naing
Generator protection system by Nicholas NaingGenerator protection system by Nicholas Naing
Generator protection system by Nicholas NaingNicholas Naing
 
Alternatorexcitation
AlternatorexcitationAlternatorexcitation
AlternatorexcitationRanjan Naik
 
Protection of alternator
Protection of alternator Protection of alternator
Protection of alternator MILAN MANAVAR
 
To_Siemens_4
To_Siemens_4To_Siemens_4
To_Siemens_4Student
 
Generator rotor earth fault protection
Generator rotor earth fault protectionGenerator rotor earth fault protection
Generator rotor earth fault protectionAditya Parmar
 
Generator Voltage control
Generator Voltage controlGenerator Voltage control
Generator Voltage controljamaju56
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generatorMohammad Abdullah
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Rahul Ruddra
 
Protection Systems for Power generators
Protection Systems for Power generators Protection Systems for Power generators
Protection Systems for Power generators Nicholas Naing
 
Generator protection
Generator protectionGenerator protection
Generator protectionSSVASAVA
 
Functions and performance requirements of excitation systems
Functions and performance requirements of excitation systemsFunctions and performance requirements of excitation systems
Functions and performance requirements of excitation systemsRajshekar Naregal
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2Rahaf Waheep
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centresalehkhan
 
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...Michael George
 
Protection of alternator(encrypted)
Protection of alternator(encrypted)Protection of alternator(encrypted)
Protection of alternator(encrypted)Rohini Haridas
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
Brushless excitation
Brushless excitationBrushless excitation
Brushless excitationsuperbhuppi
 

What's hot (20)

Generator protection system by Nicholas Naing
Generator protection system by Nicholas NaingGenerator protection system by Nicholas Naing
Generator protection system by Nicholas Naing
 
Alternatorexcitation
AlternatorexcitationAlternatorexcitation
Alternatorexcitation
 
synchronous generator excitation
synchronous generator excitationsynchronous generator excitation
synchronous generator excitation
 
Protection of alternator
Protection of alternator Protection of alternator
Protection of alternator
 
To_Siemens_4
To_Siemens_4To_Siemens_4
To_Siemens_4
 
Generator rotor earth fault protection
Generator rotor earth fault protectionGenerator rotor earth fault protection
Generator rotor earth fault protection
 
Generator Voltage control
Generator Voltage controlGenerator Voltage control
Generator Voltage control
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generator
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Protection Systems for Power generators
Protection Systems for Power generators Protection Systems for Power generators
Protection Systems for Power generators
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Functions and performance requirements of excitation systems
Functions and performance requirements of excitation systemsFunctions and performance requirements of excitation systems
Functions and performance requirements of excitation systems
 
Induction Motor Protection System
Induction Motor Protection SystemInduction Motor Protection System
Induction Motor Protection System
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centre
 
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
 
Protection of alternator(encrypted)
Protection of alternator(encrypted)Protection of alternator(encrypted)
Protection of alternator(encrypted)
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
Brushless excitation
Brushless excitationBrushless excitation
Brushless excitation
 

Viewers also liked

Summer Bridge I-2014 Poster Board
Summer Bridge I-2014 Poster BoardSummer Bridge I-2014 Poster Board
Summer Bridge I-2014 Poster BoardHoai nguyen
 
Building Social Networks for Educators
Building Social Networks for EducatorsBuilding Social Networks for Educators
Building Social Networks for Educatorsjahartman
 
APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"
APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"
APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"Sandra Garibotte
 
The Mirror Makers: Sustaining Human Creative Communities With Machines That M...
The Mirror Makers: Sustaining Human Creative Communities With Machines That M...The Mirror Makers: Sustaining Human Creative Communities With Machines That M...
The Mirror Makers: Sustaining Human Creative Communities With Machines That M...Tony Veale
 
“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...
“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...
“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...IOSR Journals
 
Effect of astaxanthin on ethylene glycol induced nephrolithiasis
Effect of astaxanthin on ethylene glycol induced nephrolithiasisEffect of astaxanthin on ethylene glycol induced nephrolithiasis
Effect of astaxanthin on ethylene glycol induced nephrolithiasisIOSR Journals
 
Representantes del pragmatismo lingüístico
Representantes del pragmatismo lingüísticoRepresentantes del pragmatismo lingüístico
Representantes del pragmatismo lingüísticoMazariego Aguilar
 
Från massarbetslöshet till full sysselsättning. Katalys no. 20
Från massarbetslöshet till full sysselsättning. Katalys no. 20Från massarbetslöshet till full sysselsättning. Katalys no. 20
Från massarbetslöshet till full sysselsättning. Katalys no. 20VIRGOkonsult
 
System life cycle c.a.
System life cycle c.a.System life cycle c.a.
System life cycle c.a.yasmeenreem
 
Social networks for educators
Social  networks for educatorsSocial  networks for educators
Social networks for educatorsPBrokenshire
 
Ethnobotanical Euphorbian plants of North Maharashtra Region
Ethnobotanical Euphorbian plants of North Maharashtra RegionEthnobotanical Euphorbian plants of North Maharashtra Region
Ethnobotanical Euphorbian plants of North Maharashtra RegionIOSR Journals
 
Cycling pad 4417
Cycling pad 4417Cycling pad 4417
Cycling pad 4417Hank Hsu
 

Viewers also liked (15)

Summer Bridge I-2014 Poster Board
Summer Bridge I-2014 Poster BoardSummer Bridge I-2014 Poster Board
Summer Bridge I-2014 Poster Board
 
Building Social Networks for Educators
Building Social Networks for EducatorsBuilding Social Networks for Educators
Building Social Networks for Educators
 
Lo nuevo de iOS 8
Lo nuevo de iOS 8Lo nuevo de iOS 8
Lo nuevo de iOS 8
 
APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"
APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"
APOYO A LAS TRAYECTORIAS ESCOLARES: "ACELERACIÓN"
 
The Mirror Makers: Sustaining Human Creative Communities With Machines That M...
The Mirror Makers: Sustaining Human Creative Communities With Machines That M...The Mirror Makers: Sustaining Human Creative Communities With Machines That M...
The Mirror Makers: Sustaining Human Creative Communities With Machines That M...
 
“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...
“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...
“Comparitive Study of Prevalence of Hyperlactatemia in HIV / AIDS Patients re...
 
Effect of astaxanthin on ethylene glycol induced nephrolithiasis
Effect of astaxanthin on ethylene glycol induced nephrolithiasisEffect of astaxanthin on ethylene glycol induced nephrolithiasis
Effect of astaxanthin on ethylene glycol induced nephrolithiasis
 
Representantes del pragmatismo lingüístico
Representantes del pragmatismo lingüísticoRepresentantes del pragmatismo lingüístico
Representantes del pragmatismo lingüístico
 
Från massarbetslöshet till full sysselsättning. Katalys no. 20
Från massarbetslöshet till full sysselsättning. Katalys no. 20Från massarbetslöshet till full sysselsättning. Katalys no. 20
Från massarbetslöshet till full sysselsättning. Katalys no. 20
 
System life cycle c.a.
System life cycle c.a.System life cycle c.a.
System life cycle c.a.
 
Social networks for educators
Social  networks for educatorsSocial  networks for educators
Social networks for educators
 
Ethnobotanical Euphorbian plants of North Maharashtra Region
Ethnobotanical Euphorbian plants of North Maharashtra RegionEthnobotanical Euphorbian plants of North Maharashtra Region
Ethnobotanical Euphorbian plants of North Maharashtra Region
 
resumepost
resumepostresumepost
resumepost
 
CUSTOMER LIST
CUSTOMER LISTCUSTOMER LIST
CUSTOMER LIST
 
Cycling pad 4417
Cycling pad 4417Cycling pad 4417
Cycling pad 4417
 

Similar to Ref connection methods

Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsArjay Automation
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.pptsanipriadi1
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word DocumentBarunava Sikdar
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generatormytechinfo
 
[1339309 x journal of electrical engineering] loss of excitation of synchro...
[1339309 x   journal of electrical engineering] loss of excitation of synchro...[1339309 x   journal of electrical engineering] loss of excitation of synchro...
[1339309 x journal of electrical engineering] loss of excitation of synchro...Abraham Kv
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.pptMAHMOUDMOHAMED431205
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.javid iqbal sodagar
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear johny renoald
 
C0212014018
C0212014018C0212014018
C0212014018theijes
 
Wind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison StudyWind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison StudyCSCJournals
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of GeneratorRahuldey1991
 
9. article azojete vol 11 103 113 dibal
9. article azojete vol 11 103 113 dibal9. article azojete vol 11 103 113 dibal
9. article azojete vol 11 103 113 dibalOyeniyi Samuel
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarBhushan Kumbhalkar
 
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...Wireilla
 
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...ijfls
 

Similar to Ref connection methods (20)

Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault Protections
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
 
protection Training.pptx
protection Training.pptxprotection Training.pptx
protection Training.pptx
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
 
[1339309 x journal of electrical engineering] loss of excitation of synchro...
[1339309 x   journal of electrical engineering] loss of excitation of synchro...[1339309 x   journal of electrical engineering] loss of excitation of synchro...
[1339309 x journal of electrical engineering] loss of excitation of synchro...
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
C0212014018
C0212014018C0212014018
C0212014018
 
Wind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison StudyWind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison Study
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
9. article azojete vol 11 103 113 dibal
9. article azojete vol 11 103 113 dibal9. article azojete vol 11 103 113 dibal
9. article azojete vol 11 103 113 dibal
 
40220140507001
4022014050700140220140507001
40220140507001
 
40220140507001
4022014050700140220140507001
40220140507001
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
 
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
 

Ref connection methods

  • 1. ТЕОРЕТИЧНА ЕЛЕКТРОТЕХНІКА ELECTRICAL ENGINEERING 2005. Вип. 58. С. 138-146 2005. Is. 58. P. 138-146 _________________________________________________________ © Eleschova Z., Belan A., Gasparovsky D., 2005 УДК 621.311 ROTOR GROUND FAULT PROTECTION OF GENERATOR WITH STATIC EXCITATION SYSTEM Z. Eleschova, A. Belan, D. Gasparovsky Slovak University of Technology in Bratislava, Slovak Republic This paper deals with the influence of harmonics produced by the static excitation system of generator on the rotor ground fault protection of synchronous generator. The report brings measured courses of field voltage and current flow through insulation system of field winding during generator failure-free operation. There is analysed potential impact of static excitation system on correct function of rotor ground protection based on AC injection method. Key words: rotor, generator, static excitation system. The synchronous generator is one of the most important and the most complicated elements of power system. It is main source of electrical energy. It is essential to know everything about its steady states but mainly about its fault states. Various fault states can occur during generator operation. We distinguish between internal and external failures of generators. The first ground fault of field winding belongs in internal failures of generator rotor. The single ground fault on the field winding is not hard fault state for synchronous machine. But there is probability of occurrence of the second ground fault which presents short circuit with very large currents, dynamic and thermal stress of filed winding and rotor armature [1]. The Faults on Synchronous Generator Field Winding. Synchronous generator excitation system is insulated DC electrical system. Rotor of generator, like a rotating part, has higher probability of single ground fault occurrence than stator. Rotor winding damage is frequently, mainly on turbogenerators where rotor winding insulation is fairly stressed effected by centrifugal forces [9]. Ground fault of field winding. The first rotor ground fault causes just a little fault current, although it stresses the insulation in portions of the winding where the fault is. The real danger is the second ground fault which can cause significant forces. During dual ground fault can draw large currents which may cause extensive damage to rotor winding and armature. It is important to detect the first ground fault, thereby preventing a serious failure. The first ground fault is signalizing only. Generator is tripping and damaged winding is repairing. In this way it can prevent large damages which could be during the second
  • 2. ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 139 ground fault. Backup protection against the second ground fault is loss of excitation protection. Field winding short circuit. Shorted turns in the generator field winding can cause distorting the field across the air gap. This is due to the unsymmetrical turn current of magnetomotive force in different parts of the field winding. The accrued much distorted forces can effect rotor deformation or severe vibrations which can destroy machine bearings. The machine can be protected before serious damage by vibration detector which can alarm or trip unit. Shorted winding is often due to rotor ground faults at two different places. Open field winding. Field winding open circuit is rare. But rapidly detection of this fault is required, because it can be accompanied with arcing that can do great damage to the rotor body. Open field winding can be detected by loss of excitation protection. Rotor Ground fault protection. The rotor ground fault protection should protect whole field circuit of generator in cause of ground fault. In regard to the second ground fault is non-permissible, the protection which signalize the first ground fault must be high reliable and shouldn’t incorrect act, because every protection alarm of the rotor first ground fault is necessary checkup. The protection, which controls field winding insulation by injection of auxiliary voltage, is the most frequently used for detecting of rotor ground fault of generator. According to injected voltage the rotor ground fault protections are based on AC or DC injection method. The new rotor ground fault protection uses injected low-frequency squarewave voltage. AC injection method. AC injection method is showed in fig. 1. This method is based on injection of AC auxiliary voltage to field winding through a capacitor. When any point of field winding is grounded, circuit will be complete and the protection signalizes the rotor ground fault. This system has no blind point [9]. Fig. 1. Rotor ground fault protection of generator – AC injection method.
  • 3. Z. Eleschova, A. Belan, D. Gasparovsky140 DC injection method. DC injection method is showed in fig. 2. Protection based on this method uses DC voltage. The DC output of the rectifier is connected to the positive side of the field circuit and the second output is grounded. Every point of the field winding grounded closes circuit through current relay [5]. Fig. 2. Rotor ground fault protection of generator – DC injection method. Rotor ground fault protection with squarewave auxiliary voltage. Fig. 3 shows principle of rotor ground fault protection with squarewave auxiliary voltage [1]. Fig. 3. Rotor ground fault protection of generator – low-frequency squarewave voltage injection.
  • 4. ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 141 Measuring circuit M is connected to rotor winding through the high resistance 21 and vv RR . The squarewave auxiliary voltage auxU causes an auxiliary current auxI . The value of auxiliary current is given ,aux aux E v M U I R R R = + + (1) where 1 2 1 2 .v v v v v R R R R R = + (2) If M vR R<< then measured voltage MU is aux M M E v U R U R R ≈ + . (3) For a consideration of measured voltage course and value protection evaluates the leakage resistance value and state of rotor insulation system. Flow current through the rotor ground fault protection measurement. The goal of measurement was to find out and analyse influence of the static excitation system on correct function of rotor ground fault protection. The measurements were made on the synchronous machines with static excitation system and rotating exciter too. The generators were 110 MW, 32 MW and 28 MW. The rotor ground protections of these machines are based on the AC injection. The measurements were aimed at determining of harmonic contents in voltages and currents of generator, in voltages and currents in front of static excitation system, in field voltage, mainly in current flow through rotor ground fault protection in failure-free state with different value of field current. The measurement on 110 MW generator with static excitation system. This generator had analogue rotor ground protection based on the AC method. -1000 -500 0 500 1000 0,00 0,02 0,04 t [s] u[V] Fig. 4. The voltage in front of the static excitation system.
  • 5. Z. Eleschova, A. Belan, D. Gasparovsky142 0 100 200 300 400 500 600 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Harmonic Order U[V] Fig. 5. The harmonic content of voltage in front of the static excitation system. -1000 -500 0 500 1000 0,00 0,02 0,04 t [s] i[A] Fig. 6. The current in front of the static excitation system. 0 150 300 450 600 750 900 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Harmonic Order I[A] Fig. 7. The harmonic content of current in front of the static excitation system. -200 0 200 400 600 0,00 0,02 0,04 t [s] uf[V] Fig. 8. The field voltage.
  • 6. ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 143 0 20 40 60 80 100 120 140 160 180 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Harmonic Order Uf[V] Fig. 9. The harmonic content of field voltage. 400 800 1200 1600 2000 0,00 0,02 0,04 t [s] if[A] Fig. 10. The field current. -400 -200 0 200 400 600 0,00 0,02 0,04 t [s] i[mA] Fig. 11. The current flow through rotor ground protection. 0,00 0,05 0,10 0,15 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Harmonic Order I[A] Fig. 12. The harmonic content of current flow through rotor ground protection.
  • 7. Z. Eleschova, A. Belan, D. Gasparovsky144 From the field voltage course (fig. 8) can see that this voltage isn’t DC voltage. That is way we did harmonic analysis of this voltage. In the field voltage are specific harmonics (the 6th , 12th , 18th etc.) which are multiples of the number of rectifier impulse [6]. In histogram of harmonic content of voltage and current in front of the static excitation system (fig. 5, fig. 7) we can see impact of six-impulse rectifier too. On the rectifier AC side in the voltage and current are specific harmonics (the 5th , 7th , 11th etc.) which are given [8] 1n k p= ± , (4) where p – the number of impulse; n – the harmonic order; k – the natural number. From measured course of current flow through protection (fig. 11) is to see that harmonic content is marked. The instantaneous values of this current achieve more than 400 mA. This is more than setting value at the protection (15 mA). The current flows through the protection contents mainly higher harmonics (it’s shown in histogram of content harmonic – fig. 12), the magnitude of the fundamental of the current is cca 9 mA, this is bellow the current nominal value of relay. Till the 6th harmonic magnitude is larger than 15 mA. In spite of this the rotor ground protection didn’t act false during measurement (with fluent field voltage changing). The analogue protection has connected parallel to current relay two capacitors which eliminate higher harmonics from the current flows through this relay. It means higher harmonics haven’t negative impact on the protection function. The measurement on 28 MW generator with static excitation system. This generator had the analogue rotor ground protection based on the AC method. In respect of size of synchronous generator (28 MW) in compare with 110 MW generator (smaller value of field winding capacitance) the magnitude of current flows through the protection is markedly smaller. Fundamental harmonic magnitude is cca 5,5 mA and magnitudes of the other higher harmonics are smaller. In this case the rotor ground protection shouldn’t act false. -15 -10 -5 0 5 10 15 0,00 0,02 0,04 t [s] i[mA] Fig. 13. The current flow through rotor ground protection.
  • 8. ROTOR GROUND FAULT PROTECTION OF GENERATOR ..... 145 0 2 4 6 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627282930 Harmonic Order I[mA] Fig. 14. The harmonic content of current flow through rotor ground protection. The measurement on 32 MW generator with the rotating exciter. This generator had the digital rotor ground protection based on the AC method. Because this generator had the rotating exciter – dynamo, the field voltage is really DC and the injected auxiliary AC voltage of protection isn’t deformed. There wasn’t possible to measure the current flows through the rotor ground protection because this current had too small magnitude – non-measurable by the measuring instrument. The measurements on the generators with the rotor ground protection based on the AC injection method and with the static excitation system were made at the instance of generator operator to find out the static excitation system impact on this protection correct function. Because the rotor ground protection on 110 MW machine signalizes rotor ground fault in express terms in spite of rotor insulation system was sound. The measurements on 110 MW generator with the static excitation system and with the rotor ground protection based on the AC injection show the impact of six-impulse thyristor rectifier on course and harmonic content of voltage and current in front of the excitation system, of field voltage, but also of current flows through rotor winding insulation (and rotor ground protection too) during failure-free and steady state operation of generator. From the measurements is result that during steady state of synchronous generator the rotor ground protection didn’t act false in spite of the instantaneous values and higher harmonics magnitudes of the current flows through this protection are greater than setting value on protection. As mentioned above harmonics of current flow through parallel connected capacitors and don’t through protection current relay. It means that seemingly “easy solution” – to replace the analogue protection by digital haven’t enough because in this case the harmonics aren’t causer of the rotor ground protection incorrect acting. _____________ 1. Anderson P. Power System Protection. New York: IEEE Press, 1999. 2. Arrillaga J., Watson N. Power System Harmonics. John Wiley & Sons, Ltd, West Sussex, England, 2003. 3. Bašta J., Chládek Mayer I. Teorie elektrických stroju. STNL/ALFA, Praha, 1968. 4. Beláň A., Eleschová Ž., Janíček F., Reváková D. Vplyv statickej budiacej sústavy generátorov na zemnú rotorovú ochranu GR12. Správa k Zmluve č. 95/130/2002. KEE FEI STU, Bratislava, 2002. 5. Dohnálek P. Ochrany pro prumysl a energetiku. STNL, Praha, 1991.
  • 9. Z. Eleschova, A. Belan, D. Gasparovsky146 6. Chladný V. Digital measurement method of local frequency in power system. Proceeding of International science conference Elektroenergetika 1997, FEI VŠB– TU Ostrava, 1997. 7. Ungrad H., Winkler W., Wiszniewski A. Protections Techniques in Electrical Energy Systems. Marcel Dekker, INC. New York, 1995. 8. Vaculíková P., Vaculík E. a kol. Elektromagnetická kompatibilita elektrotechnických systému. Praha: Grada Publishing, 1998. 9. Janíček F., Chladný V., Beláň A., Eleschová Ž. Digitálne ochrany elektrických strojov. Košice: FEI TU, 2000. ЗАХИСТ РОТОРА ГЕНЕРАТОРА ЗІ СТАТИЧНОЮ СИСТЕМОЮ ЗБУДЖЕННЯ ВІД ЗАМИКАНЬ НА ЗЕМЛЮ З. Елешова, А. Белан, Д. Гаспаровський Словацький технологічний університет Братислави, Словацька республіка Описано вплив гармонік, генерованих статичною системою збудження генератора, на роботу захисту від замикань на землю синхронного генератора. Наведено способи вимірювання напруги збудження і струму, який протікає через систему ізоляції обмотки збудження під час нормальної роботи генератора. На підставі методу введення змінного струму проаналізовано потенційний вплив статичної системи збудження на правильність роботи захисту від замикань на землю. Ключові слова: ротор, генератор, статична система збудження. Стаття надійшла до редколегії 20.06.2005 Прийнята до друку 01.09.2005