This document provides an overview of the monitoring capabilities in the VDC 3D client software for a data center facility. It summarizes the key electrical, mechanical and environmental equipment that can be monitored on the main, ground and second floors, including power distribution units, generators, pumps, chillers, UPS systems, CRAC units, AHUs, fans and sensors. Monitoring points include status, alarms, electrical parameters and environmental data, obtained via protocols like MODBUS, DI and others. Floor plans can also be accessed for layout views.
2. Main floor plan:
•Total device in alarm/warning/unreachable status
•PUE
•Total power consumption
•Estimated yearly consumption
•Estimated yearly cost
•Estimated yearly CO2 emission
•Floor Area – Total usable floor space
•White Area – Total used space
•Grey Area – Area reserved on going projects.
4. Gnd Floor DCIM Monitoring
•Genset & Battery charger
•RMU A&B
•Transformer 1A, 2A, 3A, 1B, 2B, & 3B
•Switch board - Genset sync board A&B, LV Board A1, A2, B1 & B2, SSB Chiller A & B
•FCU – FCU 1A, 1B, 2A, 2B
•Exhaust Fan – EX-G1, EX-G2, EX-G3, EX-G4, EX-G5 & EX-G6
•Temp & Humidity sensors for facility room
• Active Harmonics Filter
TR1A TR2A TR3A TR1B TR2B TR3B
RMU A RMU B
LVRoomA
LV Room B
GenSyncA
GenSyncB
SSB Chiller B
SSB Chiller A
Genset 1A
Genset 1B
5. RMU A & B – Expendable to 3 more screen
• On/Off Status - DI
6. Transformer 1A, 2A, 3A, 1B, 2B & 3B –
Expendable to 3 more screen
• On/off status –DI
• Over temp alarm - DI
7. LV Board A1 & B1
• 2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 1x ACB output breaker – DI
• 2x change over circuit – DI
• Surge protection – DI
8.
LV Board A2 & B2
• 2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 7x ACB output breaker – DI
• 1x change over circuit – DI
• 2x Surge protection – DI
9. SSB Chiller A & B
• 1x Incoming DPM – Modbus
• 1x input breakers – DI
• 6x outgoing breaker – DI
• 1x Surge protection – DI
10.
FCU G1A, G1B, G2A, G2B
FCU status from DDC via MODBUS
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status
11. Fan G1, G2, G3, G4, G5 , G6
Fan Status from DDC via Modbus
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status
12. Genset Panel A & B
• 2x Output DPM – Modbus
• 2x Output breakers – DI
• 2x Genset breaker – DI
13. Genset 1A & 1B
Genset status from genset control panel (Power
Wizard 2.1) Via Modbus
• Battery Voltage
• Engine RPM
• Generator average AC RMS current
• Generator average AC RMS frequency
• Generator average line-line AC RMS voltage
• Generator average line-neutral AC RMS voltage
• Generator total apparent power
• Generator total % kVA
• Generator total % kVAr
• Generator total % kW
• Generator total reactive power
• Generator total real power
23.
PCHWP – A/1, A/2, A/3, B/1, B/2, B/3
• Primary pump status obtained via Modbus
• On/off status, trip status, switch status
• Bypass valve control
• VSD control, feedback
24.
SCHWP – A/1, A/2, B/1, B/2
• Secondary pump status obtained via Modbus
• On/off status, trip status, switch status
• Bypass valve control
• VSD control, feedback
25.
SSB A/C A&B
•2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 17x outgoing breaker – DI
• 2x Surge protection – DI
26.
• Unit (Evaporating Fan) ON
• Cold water temperature sensor failure
• High room temperature
• Low room temperature
• High room humidity
• Low room humidity
• General Alarm
• Maintenance Signaling
• Room temperature
• Room relative humidity
• Supply air temperature
• Cold water temperature
• Control CRAC On/Off (Fan only)
• Monitor ATS for side A or B power – Via DI
CRAC Units – Total 31 units
• CRAC status obtained Via Modbus
27.
• AHU FA/1-On/Off, Trip, Switch Mode, Gas Detection
Status, Start/Stop, Damper Open/close Status, Off-Coil
Air Temperature, Supply Air Humidity Status
• Room Air Temp/Hum
• EF-1-On/Off, Trip, Switch Mode, Damper Open/close
Status
• Under Flr Exh Dam 1&2 - Damper Open/closed Status
• Freash Air Temp/Hum
• Pri/Secondary, HEPA Filter Dirty Alarm
• Chilled Water Valve Ctrl
• Heater Valve Ctrl
AHU A&B
• AHU status obtained Via Modbus
28.
FCU S30, S31, S32, S33
• FCU status obtained Via Modbus
• On/off status – DI
• Trip status – DI
• Dirty filter alarm – DI
• Start/stop status - DI
29.
Fan FAE-S1, GEF UPS A, GEF UPS B, GEF 1, GEF 2
Fan Status via Modbus
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status