Log In
•Upon opening VDC 3D client, User will be prompt to log in
Main floor plan:
•Total device in alarm/warning/unreachable status
•PUE
•Total power consumption
•Estimated yearly consumption
•Estimated yearly cost
•Estimated yearly CO2 emission
•Floor Area – Total usable floor space
•White Area – Total used space
•Grey Area – Area reserved on going projects.
Accessing to Ground floor layout
Accessing to 2nd floor layout
Gnd Floor DCIM Monitoring
•Genset & Battery charger
•RMU A&B
•Transformer 1A, 2A, 3A, 1B, 2B, & 3B
•Switch board - Genset sync board A&B, LV Board A1, A2, B1 & B2, SSB Chiller A & B
•FCU – FCU 1A, 1B, 2A, 2B
•Exhaust Fan – EX-G1, EX-G2, EX-G3, EX-G4, EX-G5 & EX-G6
•Temp & Humidity sensors for facility room
• Active Harmonics Filter
TR1A TR2A TR3A TR1B TR2B TR3B
RMU A RMU B
LVRoomA
LV Room B
GenSyncA
GenSyncB
SSB Chiller B
SSB Chiller A
Genset 1A
Genset 1B
RMU A & B – Expendable to 3 more screen
• On/Off Status - DI
Transformer 1A, 2A, 3A, 1B, 2B & 3B –
Expendable to 3 more screen
• On/off status –DI
• Over temp alarm - DI
LV Board A1 & B1
• 2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 1x ACB output breaker – DI
• 2x change over circuit – DI
• Surge protection – DI

LV Board A2 & B2
• 2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 7x ACB output breaker – DI
• 1x change over circuit – DI
• 2x Surge protection – DI
SSB Chiller A & B
• 1x Incoming DPM – Modbus
• 1x input breakers – DI
• 6x outgoing breaker – DI
• 1x Surge protection – DI

FCU G1A, G1B, G2A, G2B
FCU status from DDC via MODBUS
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status
Fan G1, G2, G3, G4, G5 , G6
Fan Status from DDC via Modbus
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status
Genset Panel A & B
• 2x Output DPM – Modbus
• 2x Output breakers – DI
• 2x Genset breaker – DI
Genset 1A & 1B
Genset status from genset control panel (Power
Wizard 2.1) Via Modbus
• Battery Voltage
• Engine RPM
• Generator average AC RMS current
• Generator average AC RMS frequency
• Generator average line-line AC RMS voltage
• Generator average line-neutral AC RMS voltage
• Generator total apparent power
• Generator total % kVA
• Generator total % kVAr
• Generator total % kW
• Generator total reactive power
• Generator total real power
2nd Floor DCIM Monitoring
• Chiller A/1, A/2, A/3, B/1, B/2, B/3
• CRAC
• Primary & Secondary Pump – PCHWP A/1, A/2, A/3, B1, B2, B3, SCHWP A1, A2, B1, B2
• Switch board – UPS I/P Board A&B, UPS O/P Board A&B, SSB A/C A&B, Chill Water Pump
Control Panel A&B
• UPS – A1, A2, A3, B1, B2, B3
• AHU A&B
• FCU – FCU S30, S31, S32, S33
• Exhaust Fan – FAE-S1, GEF 1, GEF 2, GEF UPS A, GEF UPS B
• Fire Panel, VESDA, WLDS, Temp/Hum Sensor
UPS Input DB A & B
• 1x DPM – Modbus
• 9x Input breakers – DI
• 1x Maintenance bypass breaker – DI
• 1x Surge protection – DI

• Output Power [%], phase 1, 2, 3
• Input Voltage [V], phase 1, 2, 3
• Battery Voltage [V]
• Alarm "Battery Bad“, "On Battery“, "Low
Battery"
• Alarm "Depleted Battery“, "Temperature Bad"
• Alarm "Input Bad“, "Output Bad“, "Overload"
• Alarm "On Bypass“, “Charger Failed“, "Ups
Output Off"
• Alarm "Fan Failure""Fuse Failure""General
Fault"
• Alarm "Awaiting Power"
UPS 1A, 2A, 3A, 1B, 2B, 3B
• UPS status obtained Via Modbus

UPS Output DB A & B
• 13x DPM – Modbus
• 6x Outgoing breakers – DI
• 1x Maintenance bypass breaker – DI
• 1x Surge protection – DI
Notifier IG55 Panel
• Fire alarm - DI
• Smoke alarm – DI
• Fault alarm – DI

VESDA Panel
• Action alarm - DI
• Smoke alarm #1 – DI
• Smoke alarm #2 - DI
• Fault alarm – DI

Water Leak Detection System
• Cable break alarm - Modbus
• Leak alarm – Modbus

Chiller A/1, A/2, A/3, B/1, B/2, B/3
• Chiller status obtained via Modbus
• On/off status, alarm status, start/stop status
• CHWS/CHWR Temp, Water flow status
• Motorized open/closed status, on/off status
• Header pressure, temp, flow rate
• Expansion tank HL level alarm, Trip status
• Control Chiller On/Off
Chilled Water Pump Control Panel
A&B
•7x Incoming DPM – Modbus

PCHWP – A/1, A/2, A/3, B/1, B/2, B/3
• Primary pump status obtained via Modbus
• On/off status, trip status, switch status
• Bypass valve control
• VSD control, feedback

SCHWP – A/1, A/2, B/1, B/2
• Secondary pump status obtained via Modbus
• On/off status, trip status, switch status
• Bypass valve control
• VSD control, feedback

SSB A/C A&B
•2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 17x outgoing breaker – DI
• 2x Surge protection – DI

• Unit (Evaporating Fan) ON
• Cold water temperature sensor failure
• High room temperature
• Low room temperature
• High room humidity
• Low room humidity
• General Alarm
• Maintenance Signaling
• Room temperature
• Room relative humidity
• Supply air temperature
• Cold water temperature
• Control CRAC On/Off (Fan only)
• Monitor ATS for side A or B power – Via DI
CRAC Units – Total 31 units
• CRAC status obtained Via Modbus

• AHU FA/1-On/Off, Trip, Switch Mode, Gas Detection
Status, Start/Stop, Damper Open/close Status, Off-Coil
Air Temperature, Supply Air Humidity Status
• Room Air Temp/Hum
• EF-1-On/Off, Trip, Switch Mode, Damper Open/close
Status
• Under Flr Exh Dam 1&2 - Damper Open/closed Status
• Freash Air Temp/Hum
• Pri/Secondary, HEPA Filter Dirty Alarm
• Chilled Water Valve Ctrl
• Heater Valve Ctrl
AHU A&B
• AHU status obtained Via Modbus

FCU S30, S31, S32, S33
• FCU status obtained Via Modbus
• On/off status – DI
• Trip status – DI
• Dirty filter alarm – DI
• Start/stop status - DI

Fan FAE-S1, GEF UPS A, GEF UPS B, GEF 1, GEF 2
Fan Status via Modbus
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status

DCIM_Linkedin

More Related Content

What's hot

Datasheet-emdriveH300
Datasheet-emdriveH300Datasheet-emdriveH300
Datasheet-emdriveH300
Martin Pec
 

What's hot (19)

Original Power Supply IC TNY290PG TNY290P TNY290 DIP-7 New Power Integration
Original Power Supply IC TNY290PG TNY290P TNY290 DIP-7 New Power IntegrationOriginal Power Supply IC TNY290PG TNY290P TNY290 DIP-7 New Power Integration
Original Power Supply IC TNY290PG TNY290P TNY290 DIP-7 New Power Integration
 
Next gen smodi ms
Next gen smodi msNext gen smodi ms
Next gen smodi ms
 
CENTRALIZED MONITORED COOLING SYSTEM
CENTRALIZED MONITORED COOLING SYSTEMCENTRALIZED MONITORED COOLING SYSTEM
CENTRALIZED MONITORED COOLING SYSTEM
 
F5 b c_g_instruction manual
F5 b c_g_instruction manualF5 b c_g_instruction manual
F5 b c_g_instruction manual
 
Semi hermetic bock compressors
Semi hermetic bock compressorsSemi hermetic bock compressors
Semi hermetic bock compressors
 
TTHERM GEO presentation
TTHERM GEO presentationTTHERM GEO presentation
TTHERM GEO presentation
 
ELECTRICAL SYSTEMS
ELECTRICAL SYSTEMSELECTRICAL SYSTEMS
ELECTRICAL SYSTEMS
 
Datasheet-emdriveH300
Datasheet-emdriveH300Datasheet-emdriveH300
Datasheet-emdriveH300
 
04 adc (pic24, ds pic with dma)
04 adc (pic24, ds pic with dma)04 adc (pic24, ds pic with dma)
04 adc (pic24, ds pic with dma)
 
174085193 pic-prgm-manual
174085193 pic-prgm-manual174085193 pic-prgm-manual
174085193 pic-prgm-manual
 
Analog module omron
Analog module omronAnalog module omron
Analog module omron
 
Rtx 17-23 y-un50_00
Rtx 17-23 y-un50_00Rtx 17-23 y-un50_00
Rtx 17-23 y-un50_00
 
Omron cp1 h
Omron cp1 h Omron cp1 h
Omron cp1 h
 
Understanding SWIFT Step Down DC/DC Converters
Understanding SWIFT Step Down DC/DC ConvertersUnderstanding SWIFT Step Down DC/DC Converters
Understanding SWIFT Step Down DC/DC Converters
 
Basics of ATmega32
Basics of ATmega32Basics of ATmega32
Basics of ATmega32
 
Plc Simulation Examples
Plc Simulation ExamplesPlc Simulation Examples
Plc Simulation Examples
 
Instrumentation & control of typical material handling of FGD Plant
Instrumentation & control of typical material handling of FGD PlantInstrumentation & control of typical material handling of FGD Plant
Instrumentation & control of typical material handling of FGD Plant
 
PLC and SCADA Training
PLC and SCADA TrainingPLC and SCADA Training
PLC and SCADA Training
 
Pushing the Envelope with Machine Automation Controllers (MAC)
Pushing the Envelope with Machine Automation Controllers (MAC)Pushing the Envelope with Machine Automation Controllers (MAC)
Pushing the Envelope with Machine Automation Controllers (MAC)
 

Similar to DCIM_Linkedin

AODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDAAODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDA
Kevin Duke
 
800166837 p0.pptx
800166837 p0.pptx800166837 p0.pptx
800166837 p0.pptx
abdoselem
 
Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS
Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS
Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS
Mohanumar S
 
Plc ( programable logic controllers)
Plc ( programable logic controllers)Plc ( programable logic controllers)
Plc ( programable logic controllers)
masoommehsoud1
 

Similar to DCIM_Linkedin (20)

amplifiers
amplifiersamplifiers
amplifiers
 
Substation monitoring system for maintaining a data log.ppt
Substation monitoring system for maintaining a data log.pptSubstation monitoring system for maintaining a data log.ppt
Substation monitoring system for maintaining a data log.ppt
 
CMOS Logic Circuits
CMOS Logic CircuitsCMOS Logic Circuits
CMOS Logic Circuits
 
Power dissipation cmos
Power dissipation cmosPower dissipation cmos
Power dissipation cmos
 
Cell d dapd product presentation
Cell d dapd product presentationCell d dapd product presentation
Cell d dapd product presentation
 
Eaton ATS Automatic Transfer Switch ATS-PWR
Eaton ATS Automatic Transfer Switch ATS-PWREaton ATS Automatic Transfer Switch ATS-PWR
Eaton ATS Automatic Transfer Switch ATS-PWR
 
Eaton ats automatic transfer switch ats pwr
Eaton ats automatic transfer switch ats pwrEaton ats automatic transfer switch ats pwr
Eaton ats automatic transfer switch ats pwr
 
AODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDAAODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDA
 
ARDUINO BASED GAS LEAKAGE DETECTING ROBOT
ARDUINO BASED GAS LEAKAGE DETECTING ROBOT ARDUINO BASED GAS LEAKAGE DETECTING ROBOT
ARDUINO BASED GAS LEAKAGE DETECTING ROBOT
 
800166837 p0.pptx
800166837 p0.pptx800166837 p0.pptx
800166837 p0.pptx
 
20ME702– MECHATRONICS -UNIT-3.ppt
20ME702– MECHATRONICS -UNIT-3.ppt20ME702– MECHATRONICS -UNIT-3.ppt
20ME702– MECHATRONICS -UNIT-3.ppt
 
Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS
Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS
Unit 3-PROGRAMMABLE PERIPHERAL INTERFACE-ME6702– MECHATRONICS
 
Classic control field and componenets
Classic control field and componenetsClassic control field and componenets
Classic control field and componenets
 
High Efficiency Solutions for process cooling
High Efficiency Solutions for process coolingHigh Efficiency Solutions for process cooling
High Efficiency Solutions for process cooling
 
Plc ( programable logic controllers)
Plc ( programable logic controllers)Plc ( programable logic controllers)
Plc ( programable logic controllers)
 
Servomax
ServomaxServomax
Servomax
 
Dead time pwm
Dead time pwmDead time pwm
Dead time pwm
 
cmos.ppt
cmos.pptcmos.ppt
cmos.ppt
 
PROGRAMMABLE PERIPHERAL INTERFCAE.ppt
PROGRAMMABLE PERIPHERAL INTERFCAE.pptPROGRAMMABLE PERIPHERAL INTERFCAE.ppt
PROGRAMMABLE PERIPHERAL INTERFCAE.ppt
 
VFD Basics.pptx
VFD Basics.pptxVFD Basics.pptx
VFD Basics.pptx
 

DCIM_Linkedin

  • 1. Log In •Upon opening VDC 3D client, User will be prompt to log in
  • 2. Main floor plan: •Total device in alarm/warning/unreachable status •PUE •Total power consumption •Estimated yearly consumption •Estimated yearly cost •Estimated yearly CO2 emission •Floor Area – Total usable floor space •White Area – Total used space •Grey Area – Area reserved on going projects.
  • 3. Accessing to Ground floor layout Accessing to 2nd floor layout
  • 4. Gnd Floor DCIM Monitoring •Genset & Battery charger •RMU A&B •Transformer 1A, 2A, 3A, 1B, 2B, & 3B •Switch board - Genset sync board A&B, LV Board A1, A2, B1 & B2, SSB Chiller A & B •FCU – FCU 1A, 1B, 2A, 2B •Exhaust Fan – EX-G1, EX-G2, EX-G3, EX-G4, EX-G5 & EX-G6 •Temp & Humidity sensors for facility room • Active Harmonics Filter TR1A TR2A TR3A TR1B TR2B TR3B RMU A RMU B LVRoomA LV Room B GenSyncA GenSyncB SSB Chiller B SSB Chiller A Genset 1A Genset 1B
  • 5. RMU A & B – Expendable to 3 more screen • On/Off Status - DI
  • 6. Transformer 1A, 2A, 3A, 1B, 2B & 3B – Expendable to 3 more screen • On/off status –DI • Over temp alarm - DI
  • 7. LV Board A1 & B1 • 2x Incoming DPM – Modbus • 2x ACB input breakers – DI • 1x ACB output breaker – DI • 2x change over circuit – DI • Surge protection – DI
  • 8.  LV Board A2 & B2 • 2x Incoming DPM – Modbus • 2x ACB input breakers – DI • 7x ACB output breaker – DI • 1x change over circuit – DI • 2x Surge protection – DI
  • 9. SSB Chiller A & B • 1x Incoming DPM – Modbus • 1x input breakers – DI • 6x outgoing breaker – DI • 1x Surge protection – DI
  • 10.  FCU G1A, G1B, G2A, G2B FCU status from DDC via MODBUS • On/off status • Trip status • Dirty filter alarm • Start/stop status
  • 11. Fan G1, G2, G3, G4, G5 , G6 Fan Status from DDC via Modbus • On/off status • Trip status • Dirty filter alarm • Start/stop status
  • 12. Genset Panel A & B • 2x Output DPM – Modbus • 2x Output breakers – DI • 2x Genset breaker – DI
  • 13. Genset 1A & 1B Genset status from genset control panel (Power Wizard 2.1) Via Modbus • Battery Voltage • Engine RPM • Generator average AC RMS current • Generator average AC RMS frequency • Generator average line-line AC RMS voltage • Generator average line-neutral AC RMS voltage • Generator total apparent power • Generator total % kVA • Generator total % kVAr • Generator total % kW • Generator total reactive power • Generator total real power
  • 14. 2nd Floor DCIM Monitoring • Chiller A/1, A/2, A/3, B/1, B/2, B/3 • CRAC • Primary & Secondary Pump – PCHWP A/1, A/2, A/3, B1, B2, B3, SCHWP A1, A2, B1, B2 • Switch board – UPS I/P Board A&B, UPS O/P Board A&B, SSB A/C A&B, Chill Water Pump Control Panel A&B • UPS – A1, A2, A3, B1, B2, B3 • AHU A&B • FCU – FCU S30, S31, S32, S33 • Exhaust Fan – FAE-S1, GEF 1, GEF 2, GEF UPS A, GEF UPS B • Fire Panel, VESDA, WLDS, Temp/Hum Sensor
  • 15. UPS Input DB A & B • 1x DPM – Modbus • 9x Input breakers – DI • 1x Maintenance bypass breaker – DI • 1x Surge protection – DI
  • 16.  • Output Power [%], phase 1, 2, 3 • Input Voltage [V], phase 1, 2, 3 • Battery Voltage [V] • Alarm "Battery Bad“, "On Battery“, "Low Battery" • Alarm "Depleted Battery“, "Temperature Bad" • Alarm "Input Bad“, "Output Bad“, "Overload" • Alarm "On Bypass“, “Charger Failed“, "Ups Output Off" • Alarm "Fan Failure""Fuse Failure""General Fault" • Alarm "Awaiting Power" UPS 1A, 2A, 3A, 1B, 2B, 3B • UPS status obtained Via Modbus
  • 17.  UPS Output DB A & B • 13x DPM – Modbus • 6x Outgoing breakers – DI • 1x Maintenance bypass breaker – DI • 1x Surge protection – DI
  • 18. Notifier IG55 Panel • Fire alarm - DI • Smoke alarm – DI • Fault alarm – DI
  • 19.  VESDA Panel • Action alarm - DI • Smoke alarm #1 – DI • Smoke alarm #2 - DI • Fault alarm – DI
  • 20.  Water Leak Detection System • Cable break alarm - Modbus • Leak alarm – Modbus
  • 21.  Chiller A/1, A/2, A/3, B/1, B/2, B/3 • Chiller status obtained via Modbus • On/off status, alarm status, start/stop status • CHWS/CHWR Temp, Water flow status • Motorized open/closed status, on/off status • Header pressure, temp, flow rate • Expansion tank HL level alarm, Trip status • Control Chiller On/Off
  • 22. Chilled Water Pump Control Panel A&B •7x Incoming DPM – Modbus
  • 23.  PCHWP – A/1, A/2, A/3, B/1, B/2, B/3 • Primary pump status obtained via Modbus • On/off status, trip status, switch status • Bypass valve control • VSD control, feedback
  • 24.  SCHWP – A/1, A/2, B/1, B/2 • Secondary pump status obtained via Modbus • On/off status, trip status, switch status • Bypass valve control • VSD control, feedback
  • 25.  SSB A/C A&B •2x Incoming DPM – Modbus • 2x ACB input breakers – DI • 17x outgoing breaker – DI • 2x Surge protection – DI
  • 26.  • Unit (Evaporating Fan) ON • Cold water temperature sensor failure • High room temperature • Low room temperature • High room humidity • Low room humidity • General Alarm • Maintenance Signaling • Room temperature • Room relative humidity • Supply air temperature • Cold water temperature • Control CRAC On/Off (Fan only) • Monitor ATS for side A or B power – Via DI CRAC Units – Total 31 units • CRAC status obtained Via Modbus
  • 27.  • AHU FA/1-On/Off, Trip, Switch Mode, Gas Detection Status, Start/Stop, Damper Open/close Status, Off-Coil Air Temperature, Supply Air Humidity Status • Room Air Temp/Hum • EF-1-On/Off, Trip, Switch Mode, Damper Open/close Status • Under Flr Exh Dam 1&2 - Damper Open/closed Status • Freash Air Temp/Hum • Pri/Secondary, HEPA Filter Dirty Alarm • Chilled Water Valve Ctrl • Heater Valve Ctrl AHU A&B • AHU status obtained Via Modbus
  • 28.  FCU S30, S31, S32, S33 • FCU status obtained Via Modbus • On/off status – DI • Trip status – DI • Dirty filter alarm – DI • Start/stop status - DI
  • 29.  Fan FAE-S1, GEF UPS A, GEF UPS B, GEF 1, GEF 2 Fan Status via Modbus • On/off status • Trip status • Dirty filter alarm • Start/stop status
  • 30.