More Related Content
Similar to CHP and WHRU System Sizing Report
Similar to CHP and WHRU System Sizing Report (20)
CHP and WHRU System Sizing Report
- 1. 2G CHP Model Electrical Output (kW) Thermal Output (kW) GPM Qty Total Electrical Output (kW) Total Thermal Output (kW) Total GPM
Patruus 100 100 143 36.2 0 0 0 0
Patruus 160 160 244 61.6 0 0 0 0
Patruus 200 200 280 70.5 0 0 0 0
Agenitor 206 220 262 61.2 0 0 0 0
Agenitor 306 250 297 68.6 0 0 0 0
Patruus 265 265 415 104.6 0 0 0 0
Patruus 280 280 373 94 0 0 0 0
Agenitor 408 330 350 88.4 0 0 0 0
Patruus 400 400 541 136.5 0 0 0 0
Agenitor 312 450 535 134.8 1 450 535 134.8
Avus 600c 600 680 103.32 0 0 0 0
Avus 800c 800 892 125.92 0 0 0 0
Avus 1200c 1200 1196 116.24 0 0 0 0
Avus 1500c 1560 1580 161.44 0 0 0 0
Avus 2000c 2000 1977 193.73 7 14000 13839 1356.11
Totals: 8 14450 14374 1490.91
ElectraTherm WHR Model Temperature (deg F) GPM Electrical Output (kW) Qty Total GPM Total Electrical Output (kW)
SS 6500 240 350 110 4 1400 440
SS 6500 240 325 110 0 0 0
SS 6500 240 300 107 0 0 0
SS 6500 240 275 107 0 0 0
SS 6500 240 250 105 0 0 0
SS 6500 240 225 103 0 0 0
SS 6500 240 200 100 0 0 0
SS 6500 240 175 95 0 0 0
SS 6500 240 150 90 0 0 0
SS 6500 240 125 83 0 0 0
SS 6500 240 100 78 0 0 0
SS 4400 240 200 65 0 0 0
SS 4400 240 175 63 0 0 0
SS 4400 240 150 61 0 0 0
SS 4400 240 125 57 0 0 0
SS 4400 240 100 52 0 0 0
SS 4400 240 75 47 1 75 47
SS 4400 240 50 41 0 0 0
Totals: 5 1475 487
Target kW: 15000
Total kW: 14937
Total Machines: 13
Total GPM being
produced from CHP units: 1490.91
Total GPM being used by
WHRU: 1475
Remaining GPM to put
towards WHRU: 15.91