1. SF6 Gas insulated Switchgear
RMR-24/36 Series
24kV ,. Up to 36kV,……
Technical Manual
ROCKWILL ELECTRIC CO.,LTD
2. C Unit
F Unit
V Unit
++++General
RMR-24/46kV is completely insulated SF6 SAFERIN
(hereinafter short as SF6 Gas insulated Switchgear)
This product is in conformity with the standards the
GB/IEC standard and the design of a high safety
combined switch cabinets.
The system of RMR-24/36kV of combined switch
cabinets can be divided into three kinds of unit cabinet:
++++ 3 position cable connection unit (Cable switch
unit), additional live shows and configuration of surge
arresters and grounding fault component. Code C
++++3 position switch and fuse tripping system and
earthing switch interlock system fuse combined electrical
unit (Fuse combination unit), additional live shows and
configuration of surge arresters and grounding fault
component. Code F
++++3 position switch and vacuum circuit breaker
combined appliances unit (Vacuum circuit breaker unit),
additional current transformer, live shows and
configuration of surge arresters and grounding fault
component. Code V
The combination of the current transformer and the
microcomputer protection to constitute the basic circuit
protection function.
Microcomputer protection using passive protection and
CT electric no need of additional PT power supply
Reference standard:
----IEC62271-200 ----IEC62271-100
----GB3804-2004 ----GB3906-1991
----GB16926-1997 ----GB/T11022-1999
Remark:
Fuse combined electrical follow IEC 60420
VCB unit according to IEC 62271-100/GB1984-2003
3. ++++Service environment
a) Air temperature: ±40℃; Daily average ≤25°C
b)Altitude above sea level: Maximum installation altitude: 4000m
c)Wind: less than 35m/s
d)Earthquake intensity: no more than 8 degrees;
++++ Main technical specifications
No Item Unit Data
1 Rated voltage 24/36
DryPower Frequency withstand
voltage Wet
60/70/80/95
2
Lightning Impulse withstand Voltage
(peak value)
kV
125/150/170/185/200
3 Rated Current A 630/1250/2500
4 Rated short circuit breaking current (peak) kA 20/25(V) 31.5(F)
5 Rated closed-loop breaking current A 630/1250(C)
6 Rated cable charging interrupting current A 50(C)
7 Rated line cable charging interrupting current A 10(C)
Rated off circuit transformer breaking current A 16
8 Rated making current (peak)
9 Rated withstand current (peak)
50(63/80)/2.5(main
switch/grounding)
10 Rated short time withstand current
kA
16/20/25/31.5
11 Rated short time withstand time S 3/4
12 Mechanical life times C/F(2000)V(10,000)
13 Main busbar A 630/1250/2000/2500
++++Each Panel face, dimension & function
Customized Panel View Type & functions W×D×H mm
1C=500×950×1360mm
2C=1000×950×1360mm
3C=1500×950×1360mm
Mainly for switching kiosk or
cable branch box
Extra bushing=140mm
Note: Above unit is for special type using for like solar plant, wind plant cable system.
4. Standard Panel View Unit C Standard Panel View Unit F Standard Panel View Unit V
500×950×1950 500(568)×950×1950 500(568)×950×1950
Note:
1, Unit V type LBS can be changed to be mounted on top for feeder cable outgoing system.
2, Unit V type incomer type with 3 nos VTs configuration width is 568mm.
3, Each unit can be connected with top busbar to be combined as Ring main unit
Standard economic type Ring main unit
Combination complete common gas tank CCF
Dimension 1500×950×1950
5. ++++Busbar system
RMR type GIS switchgear can be used for main station as main switchgear, the main busbar
current up to 2500A, 40kA.. Below is different schema for range of busbar current selection on
RMR type GIS switchgear.
Main busbar 2500A,40kA, Max Busbar 630/1250A ,31.5kA, Max.
Busbar Section Max. up to 2500mm2
Busbar Section Max. up to 600mm2
++++Other expanding configurations for reference
Vacuum circuit breaker unit for incomer using
Fuse combination for transformer protection using
Cable switch unit
Remark: Other accessories like PT, CT, relays can be equipped by special requirement.