4. AMSC STATCOM Business
D-VAR® STATCOM System Applica;ons
Renewables
• Delivery of more power on
exis;ng transmission &
distribu;on assets
• Postpone investments
• Improvement of power
stability, availability, quality
and reliability
• 21 Systems Installed
• Largest System Size:
-96/+240 MVAR
• Enables renewable power
to “act like” power from a
conven;onal source so it
can be smoothly
integrated into the power
grid in compliance with
local grid codes
• 92 Systems Installed
• Largest System Size:
+308/-256MVAR
• Eliminate voltage
disturbances to ensure
high power quality for
semiconductor fabs,
mining opera;ons and
other industrial processes.
• 7 Systems Installed
• Largest System Size:
+/-168 MVAR
Renewables U8li8es Industrials
AMSC Proprietary and Confiden;al 4
5. AMSC’s Gridtec Solu;ons
Smart grid solu;ons from genera;on to end use
• Renewable Energy
Plant Solu;ons
• Power Plant
Generators
• Dynamic Reac;ve
Power Support
• Voltage Regula;on
• AC Power Cables
• HVDC Power Cables
• HTS Fault Current
Limiters
• Dynamic Reac;ve
Power Support
• AC Power Cables
• HTS Fault Current
Limiters
• Substa;on
Interconnec;on
• Power Quality
Solu;ons
• Mine
Interconnec;ons
• Indoor HTS
Power Cables
End Use Distribu;on Transmission Energy Genera;on
• Power Quality
Applica;ons and
Solu;ons
• Transmission
Planning Studies
• Harmonic Analysis
• Voltage Stability
Studies
Engineering
Services
10. • 56 D-VAR Systems sold for wind and solar interconnec8ons
– Connec;ng wind farms employing Vestas, Gamesa, RePower, Mitsubishi and GE
Turbines.
– 26 installa;ons with D-VAR Controller as Master Controller for the complete
plant with Park Controllers.
– Suppor;ng connec;on of more than 5.6GW of wind genera;on to the grid.
• 26 D-VAR Systems sold for U8lity Grid Voltage Support/Power
Quality Applica8ons
– Grid Voltage Support and post-fault voltage recovery
– Semiconductor Fabs and Mining Applica;ons
10 AMSC Proprietary and Confiden;al
D-VAR System Installa;ons – North America
AMSC Provides Local Support and Service from Devens, MA
11. • 39 D-VAR Systems sold for wind and solar interconnec8ons
– Connec;ng wind farms employing Vestas, Gamesa, RePower, Mitsubishi and GE
turbines.
– 17 installa;ons with D-VAR Controller as Master Controller for the complete
plant.
– Suppor;ng connec;on of more than 4.2GW of wind genera;on to the grid.
• 23 D-VAR Systems sold for U8lity Applica8ons and Power Quality
– Grid Voltage Support and post-fault voltage recovery
– Semiconductor Fabs and Mining Applica;ons
– U;lity Applica;on: Long Island Power Authority, +240MVAr/-96MVAr
11 AMSC Proprietary and Confiden;al
D-VAR System Installa;ons – US Summary
AMSC Provides Local Support and Service from Devens, MA
15. D-VAR System’s
Droop Seqng Op;ons
• Independent boost and buck droop
slopes
• Droop slope adjustable from 1% to
10%
• Adjustable reference or target
voltage
• Op;onal dead band and D-VAR
device output limits
• Can switch between voltage and
power factor control
15
D-VAR® System - Voltage Control
Dynamic Control and Regula;on Control
Boos8ng Output Bucking Output
1.00
1.01
1.02
1.03
1.04
0.96
0.97
0.98
0.99
Reference Voltage
= 1.00pu
Voltage (pu)
1x 2x 3x 1x 2x 3x
1.05
0.95
Buck Hard Limit = 1.050pu
Boost Hard Limit = 0.950pu
Fast Buck Turn On
Fast Boost Turn On
Boost Droop = 2%
Deadband
Buck Droop = 2%
Buck Turn On
Boost Turn On
17. • Enhanced ground fault and close-in fault
protec4on handling
• An4-islanding protec4on added
• Improved low voltage inhibit level and
performance
AMSC Proprietary and Confiden;al 17
Protec;on
D-VAR STATCOM System Development
• Enhanced snow heater controls
• Higher capacity snow heaters
• Increased Inverter & Inductor thermal
margins
• Extreme cold weather IGBT opera4ons
Environmental Hardening
- Up to 3x short term overload capability
Opera4ons up to 50°C without de-ra4ng
- Increased steady state nega4ve phase
sequence current injec4on capability.
- Increased system transient handling
capability with advanced DC bus controls
Inverter Improvements
• Advanced interfaces with Power Park
Controllers
• Line drop Compensa4on and Motor Start
Mi4gator
• Auto-clearing and robust handling of
internal faults and system states
• Precise dynamic current injec4on controls
Controls
Making the system more robust, adaptable and in conformance to
global requirements
19. • AMSC Support Capability for Systems Engineering
– Steady-state load flow (power flow) studies
– Dynamic and stability analysis
– Harmonics and resonance scans
– Power transfer capability studies
• Planning Tools (SoNware)
– PTI PSS/E Load flow and Stability
– DIgSILENT load flow, stability, harmonics, short circuit
– PSCAD and RTDS
– GE PSLF Load flow and Stability
• Global Experience
– Studies performed for wind farms, industrial plants and u;li;es
worldwide
AMSC Planning & Engineering Services
19