Design criteria for dynamic performance of a suspended
structure for competition grade tennis courts
Mark Sheldon a,⇑
, Benjamin Delaney b
a
Aurecon, Australia
b
Major Projects Victoria, Australia
a r t i c l e i n f o
Article history:
Available online 1 April 2014
Keyword:
Tennis court dynamic performance
vibration
a b s t r a c t
The redevelopment of the Melbourne Park Tennis Centre incorporates something not pre-
viously seen at the home of a ‘‘Grand Slam’’ tournament – courts on the roof of a carpark
building. To determine an appropriate structural design criterion for the suspended slabs, a
study was undertaken on how vibrations induced by the players and external sources
would be perceived. Following testing on existing courts and undertaking real time studies
on forces exerted by tennis players, a series of criteria for acceptable vibrations in the
structure was developed. The structure has now been successfully used during the 2013
and 2014 Australian Open tournaments.
Ó 2014 The Authors. Published by Elsevier Ltd. This is an open access article under the CC
BY-NC-SA license (http://creativecommons.org/licenses/by-nc-sa/3.0/).
Introduction
The Eastern Plaza and National Tennis Centre are part of the Melbourne Park Redevelopment project which is being man-
aged by Major Projects Victoria for Sport and Recreation Victoria, the Melbourne and Olympic Parks and Tennis Australia. The
recently completed Eastern Plaza project incorporates world-class tennis courts on the roof of the new carpark building. The
new tennis courts are both indoor and outdoor, with the indoor courts covered by a metal and glass-clad architectural
envelop as shown in the image above. Constructing international standard courts on top of a building is something not pre-
viously seen at the home of a ‘‘Grand Slam’’ tournament. This presented the design team with a new challenge – to determine
an appropriate structural design criterion for the suspended slabs. The ‘‘stiffness’’ of the structure needed to be considered, in
particular how vibrations induced by the players and external sources would be perceived. Following testing on existing
courts and undertaking real time studies on forces exerted by tennis players, a design criteria for acceptable vibrations
was developed for the suspended structure supporting the tennis courts.
This paper is not a ‘‘cook book’’ on how to design international standard competition courts on a suspended structure, as
each case will vary. However it does provide guidance on the main parameters that should be considered, and describes the
design approach that was successfully applied at the Melbourne Park venue.
Background
Most tennis courts suitable for international competition are located at ground level, on stable loadbearing layers
supported by the ground. The structural design methodology for these courts is reasonably well understood within the
http://dx.doi.org/10.1016/j.csse.2014.03.001
2214-3998/Ó 2014 The Authors. Published by Elsevier Ltd.
This is an open access article under the CC BY-NC-SA license (http://creativecommons.org/licenses/by-nc-sa/3.0/).
⇑ Corresponding author. Tel.: +61 411575422.
E-mail address: mark.sheldon@aurecongroup.com (M. Sheldon).
Case Studies in Structural Engineering 1 (2014) 13–19
Contents lists available at ScienceDirect
Case Studies in Structural Engineering
journal homepage: www.elsevier.com/locate/csse
structural engineering fraternity. However site constraints within the Melbourne Park complex dictated that for the new
Eastern Plaza extension, opened just prior to the 2013 Australian Open, eight inside warm up courts and six outside courts
needed to be located over the 1000 car carpark building. The Eastern Plaza extension also includes a player’s gymnasium, a
running track, and associated facilities which the design team identified could induce vibrations in the structure.
A study of major tennis venues around the world did not identify any design precedents for suspended ‘‘international
standard’’ courts, so a design approach needed to be developed. The main concern was structure-borne vibrations, i.e.
whether the movement of players or other external sources would cause unacceptable levels of vibration.
Structure-borne vibrations can be initiated from a number of sources. The simplest form of initiator is a single strike. Once
struck, the structure will oscillate at its fundamental frequency or natural frequency. The length of time over which it will
oscillate and the rate at which energy dissipates is a function of the inherent damping of the structure, which is influenced by
the fixtures, services and furnishings attached to the structure, and the original form of the structure.
At the other end of the spectrum is the case where a cyclical load induces what could be considered a regular series of
strikes on the structure. The effect of this type of loading is very dependent on the frequency of this cyclical load. If the load
frequency does not match the natural frequency of the structure, then the resultant vibrations may not be significant. How-
ever when the load frequency matches the structure’s natural frequency (or an integer multiple of the natural frequency),
then significant vibrations can be induced.
In reality a tennis slab structure would be subjected to a wide range of forces, from single strikes generated by players
jumping; a series of rhythmic strikes from players running; forces randomly generated from the movement of weights in
the gymnasium; transient forces from cars moving around in the carpark or trains passing Melbourne Park on the nearby
rail lines; and continuous forces from machinery in plantrooms. Each of these cases needed to be investigated.
Whilst the study of structure-borne vibrations can become quite technical, it was the desire of the client group (in par-
ticular Major Projects Victoria and Tennis Australia) that a quantifiable design approach be developed, so that this may be
able to be used on similar future projects.
General principles of dynamics
Under the influence of an applied load, or series of loads, a series of vibrations will be induced in the structure. One of the
simplest forms of an oscillating element is a guitar string. Once plucked, it will vibrate back and forth at its ‘‘natural fre-
quency’’. At the moment just before it is released it has its maximum displacement and zero acceleration. Once released
it will quickly return to its ‘‘at-rest’’ position, at which time its velocity would have accelerated to its maximum and its dis-
placement will be zero. Momentum will drive the string beyond the at-rest position but it will decelerate until the moment it
reaches its maximum negative displacement, at which time its acceleration will again be zero. As the string will be affected
by friction from the air around it, and there will be some stretch in the string itself, there is an amount of ‘‘damping’’ in this
system. The string will continue oscillating for some time, although the damping will ensure that in every cycle the displace-
ment is slightly less than the previous, such that it will eventually cease. A structure however, is significantly more complex
than a guitar string. It will generally consist of slabs, beams, columns and foundations, all of which can influence the fre-
quency of the structure. Instead of having one natural frequency, as is the case of the guitar string, a structure can have a
number of resonant frequencies (frequencies at which parts of the structure will resonate).
The main design parameter associated with an investigation into structure-borne vibration is usually the resultant accel-
eration. A person standing on the vibrating structure will feel this vibration. What they are actually sensing is the cycles of
accelerations and decelerations. Remember that whilst sitting in a car travelling at a constant velocity we do not generally
sense the motion. It is the accelerating force and the braking force (deceleration) that we feel. Interestingly, some people are
more sensitive to the oscillating motion than others, and some people are more tolerant of this motion than others (and this
may even change depending on the player’s temperament).
Whilst the behaviour of the oscillation of a floor system can be quite complex, in simple terms under an applied striking
force the following will occur:
 The structure will vibrate at its ‘‘natural frequency’’ or one of its resonant frequencies
 The length of time over which it will oscillate is a function of the magnitude of the force and the damping in the building
 People will sense the acceleration of the slab caused by the vibration
There are various ways to measure and report accelerations, the relevance of which is dependent upon the type of floor
and the predominant forcing loads. In this instance, it was determined that the as the forcing load during play was a single
strike, the most important structural response parameter is the peak acceleration induced in the structure.
A significant body of research has been undertaken over many years studying the perceptions of vibrations, particularly in
North America based on work by Thomas Murray and David Allen. Much of this work has been published over a 30+ year
period, and has formed the basis of the National Buildings Code of Canada’s design criteria [1] and the American Institute
of Steel Construction’s Design Guide No. 11 [2]. These studies have identified that humans are most susceptible to vibrations
in the range of 4–8 Hz. This means we are less concerned with vibrations that occur less than 4 times per second or more
than 8 times per second. It was also identified that people are more tolerant of vibrations in structures such as footbridges
14 M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19
and shopping centres (where they only have limited exposure to the vibration) but are less tolerant of vibrations in an office
environment and even less tolerant in their home. The following chart (Fig. 1) is well known within the engineering frater-
nity as the basis for acceptable vibrations in different building types, based on the works of Murray and Allen.
A significant observation from these curves is that, above approximately 8 Hz, the allowable accelerations can increase.
This is due in part to the fact that people are less susceptible to higher frequency vibrations, but also recognizes that as the
frequency increases, the displacement associated with the oscillation will be less (for a similar applied force).
In addition to the works by Murray and Allen, other structure-borne vibration studies have been undertaken in Australia
and internationally over many years on buildings such as hospital wards, operating theatres and the like. These have been
referenced in the development of the criteria for the Eastern Plaza tennis courts.
Another critical factor in the development of the criteria for the tennis courts is the fact that a person using their own
body weight to cause the load (by jumping, lunging, running etc) is generally not able to sense the resultant vibrations in
a normal structure. This observation was central to the decision on where the accelerations should be measured in the struc-
ture, and is discussed in more detail below.
As is the norm for structures, the accelerations in the design curves above are expressed as a percentage of the acceler-
ation due to gravity (g = 9.8 m/s2
).
Load testing
At the pre-tender stage of the Eastern Plaza project Major Projects Victoria and Tennis Australia recognised that this was
an unusual project requiring additional inputs, so Tennis Australia commissioned testing to examine the dynamic perfor-
mance of selected existing tennis courts. One court tested was the existing Margaret Court Arena, which has been used
for many years during previous Australian Open Grand Slam tournaments, and consists of a post-tensioned slab-on-grade.
The second test was on a tennis court located on a carpark building associated with a major hotel development. In addition,
to accumulate more data for comparison a third series of tests were undertaken on a tennis court located on a suspended
slab at a tennis facility in Auckland New Zealand during the final design stage. Measurements of accelerations and frequen-
cies were taken at each of the facilities during a tennis match. As was expected, the dynamic response measured from these
three tennis courts differed greatly. It was determined that for the Melbourne Park facility, the new suspended courts needed
to be stiffer than the two suspended courts tested.
In addition, Major Projects Victoria and Tennis Australia also commissioned some actual impact load tests, undertaken at
the Victoria Institute of Sport (VIS) Sports Science Department. A competition player was put through a series of typical ten-
nis manoeuvres over a load cell. The actual forces exerted on to the floor from these manoeuvres were measured against
time. Selected graphical outputs of these tests follow. The testing showed that under a ‘‘jump smash’’ action, the force
exerted on the floor was equivalent to approximately 12.5 times the player’s weight, but only for a short period of time.
Under actions such as running and changing directions, the Gross Reaction Force (GRF) is approximately 2 times body
weight, but occurs over a longer time and is obviously likely to occur much more frequently during a match. Under a serve
Fig. 1. Acceleration Design Curves based on the works of Murray and Allen. (Adapted from American Institute of Steel Construction Design Guide No. 11,
AISC 1997.)
M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19 15
motion, the maximum GRF was approximately 2.5 times the body weight, increasing to approximately 3.2 times under a
volley motion (Figs. 2 and 3).
The results of the Volley tests were of particular interest, as this represents an activity that would occur relatively fre-
quently during a match, and produces a GRF plot with a peak similar to a ‘‘Heel Drop’’. A Heel Drop test is a universally
accepted (albeit crude) test to study vibrations in structures. It is performed by a person of approximately 80 kg standing
on their toes with their heels approximately 50 mm above the surface, dropping their heels to the surface whilst keeping
their legs stiff. It was identified that a Heel Drop test could be used to simulate the Volley design case, and could be repro-
duced with reasonable consistently.
Development of a criteria
To design a structure with ‘‘imperceptible’’ accelerations under all load conditions was virtually impossible and, at best,
extremely cost-prohibitive. It was accepted that a design criteria had to be developed. Rather than try to adopt a single cri-
terion for the design of the structure, it was decided that a rational approach coupling the probability of a load occurrence
with an appropriate allowable acceleration was more logical. The Jump Smash action was identified as the most severe of the
design cases, however this activity is expected to occur less frequently than serving, volleying and significantly less than run-
ning/changing directions. In addition to these forces caused by the players, we also needed to consider structure-borne
vibrations caused by vehicles in the carpark, trains and trams passing the facilities, activities in the gymnasium, and machin-
ery in the plantrooms of the facility.
Given that the professional players normally play on ‘‘on grade’’ courts that experience minimal accelerations under
impacts, it was deemed necessary that a tight criteria for the suspended slabs was necessary. The starting point was to con-
sider a criterion for the most common forms of activity – running and changing directions during a match. Australian Stan-
dard AS2670.1 – 2001 [3], which is based on ISO 2631-1:1997, indicates that approximately 25% of alert fit persons cannot
detect a vertical vibration with a peak magnitude of 0.2%g. Similarly, the Department of Environment and Conservation
NSW’s ‘‘Assessing Vibration: A Technical Guideline’’ [4] provides a maximum recommended acceleration from a vertical con-
tinuous vibration source in a hospital operating theatre which equates to a peak acceleration of approximately 0.14%g. Anec-
dotal evidence from the design team on the National Tennis Centre was that a figure of 0.2%g had recently been used as the
design criterion for a large Australian hospital. It was therefore decided that the criterion where the peak accelerations is
limited to less than 0.2%g (for structures in the range of 4–8 Hz) would be appropriate, as it was deemed that even the most
temperamental tennis player would agree that if a surface was stiff enough to for a doctor to operate, it would be acceptable
for a tennis match. Following the precedent of the curves as shown above, the allowable acceleration could increase if a stif-
fer structure (with a higher natural frequency) was provided.
The ‘‘background’’ vibrations from external sources (vehicles, trains, trams, activities in the gym, mechanical plant etc.)
was the second criterion to be determined. As this vibration could be expected to occur for extended periods of time, an
acceleration limit less than the running/changing direction criterion was deemed appropriate. Following an assessment of
what could be realistically and economically achieved in design, an acceleration curve at 80% of the running/changing direc-
tion criteria was adopted. This is nearing the level at which many people would consider is imperceptible.
The next criterion to be considered was for the serve action and volley action. As this activity would occur less frequently
than the running and changing direction, a higher acceleration was considered acceptable. A peak acceleration of 0.5%g was
Fig. 2. Gross reaction force diagram for change in direction.
16 M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19
adopted, increasing in line with the curves shown above for frequencies greater than 8 Hz. This is similar to what would be
deemed acceptable in an office or residential environment, as shown in Fig. 1. A convenient aspect of this criterion is that the
Gross Reaction Force generated from the players is similar in magnitude and duration to a heel drop test, which is relatively
easy to replicate by technicians.
Under the jump smash action a more lenient criteria was necessary, as a cost-prohibitive structure would otherwise be
necessary. Through consultation with Marshall Day Acoustics, it was agreed that as the duration of the significant force was
extremely short, an allowable acceleration of 2%g (increasing for structures above 8 Hz) would be acceptable. The resultant
design curves are presented in Fig. 4 below.
Location of acceleration measurements
The location of the acceleration measurements on the structure is another important feature of the adopted design cri-
teria. For the bottom-most curve, (the background vibrations), these accelerations should not be exceeded anywhere on the
slab. For the remainder of the criteria, however, two different practical factors were considered. As noted previously, it is
Fig. 3. Gross reaction force diagram for volley.
Fig. 4. Adopted design criteria.
M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19 17
known that the person performing the forcing action does not feel the resulting accelerations. In a tennis match environment
it is therefore typically the umpire or a doubles partner that is likely to be located within about 4 m of that player.
It was also known that the structure, to have requisite stiffness to accommodate the design criteria, would likely have
columns and/or beams on a grid of around 8–10 m. By undertaking a preliminary 3D Finite Element Analysis (FEA) and
studying the modeshapes of the resonant frequencies of the likely structural system, it was known that maximum and min-
imum accelerations are likely to occur at multiples of grids and half-grids of the structure. The selected criteria was therefore
to place the forcing load at the most severe location on the structure as determined by the FEA analyses. Accelerations were
then checked at a maximum of 5 m centres in all directions (but coinciding with the grids and half-grids of the structure).
Due to the length of a tennis court (and the fact that the players may be both located beyond the baseline) it was considered
necessary to continue the measurements for a distance of approximately 25–30 m.
Pre-construction dynamic analysis
Significant analysis of the structure is required prior to construction, to determine the dimensions of structure to be con-
structed to meet the design criteria. A full 3D finite element analysis (FEA) with time history capability is necessary to model
the characteristics of the load (from the GRF plots) and the response of the structure at multiple locations. To model the
structure’s response, an accurate assessment of the effective Moment of Inertia of the structural elements is essential. All
flexural concrete members form fine cracks in the tensile zones which reduce its stiffness at these locations and increase
deflections. These micro-cracks result in a varying effective Moment of Inertia across the structure, which needs to be accu-
rately modelled before a realistic FEA can be undertaken. Similarly, under dynamic loads it is appropriate to use a higher
Young’s Modulus for the structural elements than what would normally be used for a static analysis.
The design of the floor structure was undertaken by the structural consultant for the builder, however to test the accuracy
of their model, Aurecon produced our own Strand 7 FEA model. This reflected the edge conditions between the movement
joints in the structure and the properties of the supporting columns below. Based on the layout of the courts and the struc-
tural grids, it was identified that the maximum accelerations in the applicable portions of the building could be generated in
the structure by locating the forcing load in the bay as shown in Fig. 5. The structure was then designed and detailed based
on this pre-construction dynamic analysis.
From the FEA analysis, a design will evolve to satisfy the vibration criteria. The resultant structure is likely to be consid-
erably stiffer than a ‘‘normal’’ slab that would otherwise be required for an office or retail development based on the same
column grid.
The net result of the complexity of the dynamics issue is that a structure of this type could easily take the designer at least
ten times the effort to design, and will cost at least double the cost to construct, when compared to a normal slab of similar
spans. Further allowances should then be made for testing post-construction.
Post construction testing
Once the structure had been completed, a series of tests were undertaken to measure the accelerations produced at the
critical point located in Fig. 5. Tests were done whilst a player ran, changed direction, served, volleyed and hit jump smashes,
Fig. 5. Screen shot of the Aurecon Strand 7 model displacement under dynamic load (Load exerted at ‘‘P’’. Magenta lines represent supports below). (For
interpretation of the references to colour in this figure legend, the reader is referred to the web version of this article.)
18 M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19
with accelerometers at intervals up to 28 m away from the strike point. Tests were also performed using dropped loads,
which were considered to more accurately reproduce the specified design GRF’s in a repeatable manner. In addition, Heel
Drop tests were undertaken to simulate the volley action. The results of the measured resonant frequencies of the structure
were found to be lower than predicted, although the resulting accelerations were still found to be within the criteria set for
the project, as shown in Fig. 4.
As the Eastern Plaza was opened prior to the end of 2012, it was used for the first time during the 2013 Australian Open,
and again during the recent 2014 Australian Open. Feedback from the players and Tennis Australia was that the facility has
performed well and met their expectations.
Summary
The redevelopment of the Melbourne Park Tennis Centre incorporates courts on the roof of the new carpark building. Con-
structing international standard courts on top of a building is something not previously seen at the home of a ‘‘Grand Slam’’
tournament. This presented the design team with the challenge of how to determine an appropriate structural design crite-
rion for the response of the structure to vibrations induced by the players and external sources.
Tests on existing courts were undertaken, as well as real time studies on forces exerted by tennis players. Based on a
rational approach, relating how often an event may occur to an appropriate acceleration limit, a series of design curves
was developed for acceptable vibrations in the suspended structure supporting the tennis courts. A criteria for the locations
on the slab where the measurements should be taken was also determined.
This report provides guidance on the main parameters that should be considered, and the design approach that was
applied for the dynamic performance of the suspended tennis courts at the Melbourne Park venue. The structure was suc-
cessfully used during the 2013 and 2014 Australian Open tournaments.
Acknowledgments
The authors wish to acknowledge the contributions made during the development of the design criteria by Tennis Aus-
tralia, Melbourne  Olympic Parks, Watson Moss Growcott, and Marshall Day Acoustics. We also acknowledge the inputs of
Watpac Construction and the project structural engineer Winward Structures.
References
[1] National Research Council Canada. User’s Guide – NBC 2005, Structural Commentaries (Part 4 of Division B).
[2] Murray, Allen, Unger. Floor vibrations due to human activity, american institute of steel construction steel design guide 11; 1997.
[3] Standards Australia. AS2670.1 – 2001, Evaluation of human exposure to whole-body vibration, Part 1: General Requirements.
[4] Department of Environment and Conservation NSW (Aust). Assessing Vibration: a technical guideline; 2006.
M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19 19

More Related Content

Similar to Structural Dynamics in Tennis Courts

Free Vibrational Analysis of Cracked RC Beam- A Review
Free Vibrational Analysis of Cracked RC Beam- A ReviewFree Vibrational Analysis of Cracked RC Beam- A Review
Free Vibrational Analysis of Cracked RC Beam- A ReviewIRJET Journal
 
Effect of Overload on Fatigue Crack Growth Behavior of Air Frame Structure
Effect of Overload on Fatigue Crack Growth Behavior of Air Frame StructureEffect of Overload on Fatigue Crack Growth Behavior of Air Frame Structure
Effect of Overload on Fatigue Crack Growth Behavior of Air Frame StructureShishir Shetty
 
Wind Induced Vibrations on Cable Stayed Bridges
Wind Induced Vibrations on Cable Stayed BridgesWind Induced Vibrations on Cable Stayed Bridges
Wind Induced Vibrations on Cable Stayed BridgesIRJET Journal
 
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...Cemal Ardil
 
Study Report - Column Vibration
Study Report - Column Vibration Study Report - Column Vibration
Study Report - Column Vibration Anup kumar Singh
 
Optimized skid design for compressor packages
Optimized skid design for compressor packagesOptimized skid design for compressor packages
Optimized skid design for compressor packagesdieselpub
 
تقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docx
تقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docxتقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docx
تقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docxAdnan Lazem
 
Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)
Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)
Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)Ferit Fazliu
 
Analysis of Beam-Column Joint subjected to Seismic Lateral Loading – A Review
Analysis of Beam-Column Joint subjected to Seismic Lateral Loading – A ReviewAnalysis of Beam-Column Joint subjected to Seismic Lateral Loading – A Review
Analysis of Beam-Column Joint subjected to Seismic Lateral Loading – A ReviewIRJET Journal
 
Analzying Lift Over A Rotating Cylinder
Analzying Lift Over A Rotating CylinderAnalzying Lift Over A Rotating Cylinder
Analzying Lift Over A Rotating CylinderNicholas Cordero
 
Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...
Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...
Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...Mukul Yambal
 
Wind analysis of structure by SHYAMSUNDAR BOSU,INDIA
Wind analysis of structure by SHYAMSUNDAR BOSU,INDIAWind analysis of structure by SHYAMSUNDAR BOSU,INDIA
Wind analysis of structure by SHYAMSUNDAR BOSU,INDIASHYAMSUNDARBOSU
 
Orientation Effects of Stress Concentrators on the Material Deformation Beha...
Orientation Effects of Stress Concentrators on the Material  Deformation Beha...Orientation Effects of Stress Concentrators on the Material  Deformation Beha...
Orientation Effects of Stress Concentrators on the Material Deformation Beha...IJMER
 
Free Vibrational Analysis of Cracked and Un-cracked Cantilever Beam
Free Vibrational Analysis of Cracked and Un-cracked Cantilever BeamFree Vibrational Analysis of Cracked and Un-cracked Cantilever Beam
Free Vibrational Analysis of Cracked and Un-cracked Cantilever BeamIRJET Journal
 
Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...
Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...
Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...IRJET Journal
 
04) drift requirements-searer_and_freeman.pdf
04) drift requirements-searer_and_freeman.pdf04) drift requirements-searer_and_freeman.pdf
04) drift requirements-searer_and_freeman.pdfmyself008
 

Similar to Structural Dynamics in Tennis Courts (20)

Free Vibrational Analysis of Cracked RC Beam- A Review
Free Vibrational Analysis of Cracked RC Beam- A ReviewFree Vibrational Analysis of Cracked RC Beam- A Review
Free Vibrational Analysis of Cracked RC Beam- A Review
 
Effect of Overload on Fatigue Crack Growth Behavior of Air Frame Structure
Effect of Overload on Fatigue Crack Growth Behavior of Air Frame StructureEffect of Overload on Fatigue Crack Growth Behavior of Air Frame Structure
Effect of Overload on Fatigue Crack Growth Behavior of Air Frame Structure
 
Wind Induced Vibrations on Cable Stayed Bridges
Wind Induced Vibrations on Cable Stayed BridgesWind Induced Vibrations on Cable Stayed Bridges
Wind Induced Vibrations on Cable Stayed Bridges
 
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
Development of-new-control-techniques-for-vibration-isolation-of-structures-u...
 
Study Report - Column Vibration
Study Report - Column Vibration Study Report - Column Vibration
Study Report - Column Vibration
 
Optimized skid design for compressor packages
Optimized skid design for compressor packagesOptimized skid design for compressor packages
Optimized skid design for compressor packages
 
تقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docx
تقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docxتقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docx
تقرير فني -تدعيم المبنى مع الرسوم ضد الزلازل.docx
 
Mechanical & drilling
Mechanical & drilling Mechanical & drilling
Mechanical & drilling
 
FinalReport
FinalReportFinalReport
FinalReport
 
Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)
Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)
Evaluation of dynamic_behavior_of_waffle_slab_to_g (1)
 
Analysis of Beam-Column Joint subjected to Seismic Lateral Loading – A Review
Analysis of Beam-Column Joint subjected to Seismic Lateral Loading – A ReviewAnalysis of Beam-Column Joint subjected to Seismic Lateral Loading – A Review
Analysis of Beam-Column Joint subjected to Seismic Lateral Loading – A Review
 
Analzying Lift Over A Rotating Cylinder
Analzying Lift Over A Rotating CylinderAnalzying Lift Over A Rotating Cylinder
Analzying Lift Over A Rotating Cylinder
 
Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...
Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...
Seismic Performance Enhancement of a 20-Storey Steel Moment Resisting Frame u...
 
Wind analysis of structure by SHYAMSUNDAR BOSU,INDIA
Wind analysis of structure by SHYAMSUNDAR BOSU,INDIAWind analysis of structure by SHYAMSUNDAR BOSU,INDIA
Wind analysis of structure by SHYAMSUNDAR BOSU,INDIA
 
Orientation Effects of Stress Concentrators on the Material Deformation Beha...
Orientation Effects of Stress Concentrators on the Material  Deformation Beha...Orientation Effects of Stress Concentrators on the Material  Deformation Beha...
Orientation Effects of Stress Concentrators on the Material Deformation Beha...
 
Free Vibrational Analysis of Cracked and Un-cracked Cantilever Beam
Free Vibrational Analysis of Cracked and Un-cracked Cantilever BeamFree Vibrational Analysis of Cracked and Un-cracked Cantilever Beam
Free Vibrational Analysis of Cracked and Un-cracked Cantilever Beam
 
research paper draft 2
research paper draft 2research paper draft 2
research paper draft 2
 
Steel structures failure
Steel structures failureSteel structures failure
Steel structures failure
 
Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...
Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...
Comparative Study of Post Tensioned and RCC Flat Slab in Multi-Storey Commerc...
 
04) drift requirements-searer_and_freeman.pdf
04) drift requirements-searer_and_freeman.pdf04) drift requirements-searer_and_freeman.pdf
04) drift requirements-searer_and_freeman.pdf
 

More from Mark Sheldon

Presentation to Interior Designers
Presentation to Interior DesignersPresentation to Interior Designers
Presentation to Interior DesignersMark Sheldon
 
Steel Compliance from the Consulting Engineer's Perspective
Steel Compliance from the Consulting Engineer's PerspectiveSteel Compliance from the Consulting Engineer's Perspective
Steel Compliance from the Consulting Engineer's PerspectiveMark Sheldon
 
Onesteel MCourt Arena_0314
Onesteel MCourt Arena_0314Onesteel MCourt Arena_0314
Onesteel MCourt Arena_0314Mark Sheldon
 
Civil Engineers Aust - Margaret Court Arena April 2014
Civil Engineers Aust - Margaret Court Arena April 2014Civil Engineers Aust - Margaret Court Arena April 2014
Civil Engineers Aust - Margaret Court Arena April 2014Mark Sheldon
 
TEDA ACSE magazine Sept 05
TEDA ACSE magazine Sept 05TEDA ACSE magazine Sept 05
TEDA ACSE magazine Sept 05Mark Sheldon
 
MCG Concrete 2005 050725
MCG Concrete 2005 050725MCG Concrete 2005 050725
MCG Concrete 2005 050725Mark Sheldon
 

More from Mark Sheldon (10)

Presentation to Interior Designers
Presentation to Interior DesignersPresentation to Interior Designers
Presentation to Interior Designers
 
Steel Compliance from the Consulting Engineer's Perspective
Steel Compliance from the Consulting Engineer's PerspectiveSteel Compliance from the Consulting Engineer's Perspective
Steel Compliance from the Consulting Engineer's Perspective
 
Onesteel MCourt Arena_0314
Onesteel MCourt Arena_0314Onesteel MCourt Arena_0314
Onesteel MCourt Arena_0314
 
Civil Engineers Aust - Margaret Court Arena April 2014
Civil Engineers Aust - Margaret Court Arena April 2014Civil Engineers Aust - Margaret Court Arena April 2014
Civil Engineers Aust - Margaret Court Arena April 2014
 
TEDA ACSE magazine Sept 05
TEDA ACSE magazine Sept 05TEDA ACSE magazine Sept 05
TEDA ACSE magazine Sept 05
 
SEI 2002
SEI 2002SEI 2002
SEI 2002
 
MCG Concrete 2005 050725
MCG Concrete 2005 050725MCG Concrete 2005 050725
MCG Concrete 2005 050725
 
IABSE 2002
IABSE 2002IABSE 2002
IABSE 2002
 
CEI 2000
CEI 2000CEI 2000
CEI 2000
 
AISC 1999
AISC 1999AISC 1999
AISC 1999
 

Recently uploaded

Resultados del Campeonato mundial de Marcha por equipos Antalya 2024
Resultados del Campeonato mundial de Marcha por equipos Antalya 2024Resultados del Campeonato mundial de Marcha por equipos Antalya 2024
Resultados del Campeonato mundial de Marcha por equipos Antalya 2024Judith Chuquipul
 
办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样
办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样
办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样7pn7zv3i
 
Interpreting the Secrets of Milan Night Chart
Interpreting the Secrets of Milan Night ChartInterpreting the Secrets of Milan Night Chart
Interpreting the Secrets of Milan Night ChartChart Kalyan
 
Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...
Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...
Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...Eticketing.co
 
Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...
Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...
Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...Eticketing.co
 
CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service 🧣
CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service  🧣CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service  🧣
CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service 🧣anilsa9823
 
( Sports training) All topic (MCQs).pptx
( Sports training) All topic (MCQs).pptx( Sports training) All topic (MCQs).pptx
( Sports training) All topic (MCQs).pptxParshotamGupta1
 
Stunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCR
Stunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCRStunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCR
Stunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCRDelhi Call girls
 
ppt on Myself, Occupation and my Interest
ppt on Myself, Occupation and my Interestppt on Myself, Occupation and my Interest
ppt on Myself, Occupation and my InterestNagaissenValaydum
 
08448380779 Call Girls In Lajpat Nagar Women Seeking Men
08448380779 Call Girls In Lajpat Nagar Women Seeking Men08448380779 Call Girls In Lajpat Nagar Women Seeking Men
08448380779 Call Girls In Lajpat Nagar Women Seeking MenDelhi Call girls
 
Dubai Call Girls Bikni O528786472 Call Girls Dubai Ebony
Dubai Call Girls Bikni O528786472 Call Girls Dubai EbonyDubai Call Girls Bikni O528786472 Call Girls Dubai Ebony
Dubai Call Girls Bikni O528786472 Call Girls Dubai Ebonyhf8803863
 
Chennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts service
Chennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts serviceChennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts service
Chennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts servicevipmodelshub1
 
Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...
Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...
Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...Eticketing.co
 
VIP Kolkata Call Girl Liluah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Liluah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Liluah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Liluah 👉 8250192130 Available With Roomdivyansh0kumar0
 
Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝
Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝
Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝soniya singh
 
Presentation: The symbols of the Olympic Games
Presentation: The symbols of the Olympic  GamesPresentation: The symbols of the Olympic  Games
Presentation: The symbols of the Olympic Gamesluciavilafernandez
 
CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service 🦺
CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service  🦺CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service  🦺
CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service 🦺anilsa9823
 
Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...
Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...
Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...Neil Horowitz
 

Recently uploaded (20)

Resultados del Campeonato mundial de Marcha por equipos Antalya 2024
Resultados del Campeonato mundial de Marcha por equipos Antalya 2024Resultados del Campeonato mundial de Marcha por equipos Antalya 2024
Resultados del Campeonato mundial de Marcha por equipos Antalya 2024
 
FULL ENJOY Call Girls In Savitri Nagar (Delhi) Call Us 9953056974
FULL ENJOY Call Girls In  Savitri Nagar (Delhi) Call Us 9953056974FULL ENJOY Call Girls In  Savitri Nagar (Delhi) Call Us 9953056974
FULL ENJOY Call Girls In Savitri Nagar (Delhi) Call Us 9953056974
 
办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样
办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样
办理学位证(KCL文凭证书)伦敦国王学院毕业证成绩单原版一模一样
 
Interpreting the Secrets of Milan Night Chart
Interpreting the Secrets of Milan Night ChartInterpreting the Secrets of Milan Night Chart
Interpreting the Secrets of Milan Night Chart
 
Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...
Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...
Serbia vs England Vanja Milinkovic-Savic's Stellar Performance in Euro 2024 P...
 
Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...
Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...
Italy vs Albania Tickets: Italy's Quest for Euro Cup Germany History, Defendi...
 
Call Girls Service Noida Extension @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
Call Girls Service Noida Extension @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...Call Girls Service Noida Extension @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...
Call Girls Service Noida Extension @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
 
CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service 🧣
CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service  🧣CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service  🧣
CALL ON ➥8923113531 🔝Call Girls Telibagh Lucknow best Night Fun service 🧣
 
( Sports training) All topic (MCQs).pptx
( Sports training) All topic (MCQs).pptx( Sports training) All topic (MCQs).pptx
( Sports training) All topic (MCQs).pptx
 
Stunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCR
Stunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCRStunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCR
Stunning ➥8448380779▻ Call Girls In Delhi Cantt Delhi NCR
 
ppt on Myself, Occupation and my Interest
ppt on Myself, Occupation and my Interestppt on Myself, Occupation and my Interest
ppt on Myself, Occupation and my Interest
 
08448380779 Call Girls In Lajpat Nagar Women Seeking Men
08448380779 Call Girls In Lajpat Nagar Women Seeking Men08448380779 Call Girls In Lajpat Nagar Women Seeking Men
08448380779 Call Girls In Lajpat Nagar Women Seeking Men
 
Dubai Call Girls Bikni O528786472 Call Girls Dubai Ebony
Dubai Call Girls Bikni O528786472 Call Girls Dubai EbonyDubai Call Girls Bikni O528786472 Call Girls Dubai Ebony
Dubai Call Girls Bikni O528786472 Call Girls Dubai Ebony
 
Chennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts service
Chennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts serviceChennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts service
Chennai Call Girls Anna Nagar Phone 🍆 8250192130 👅 celebrity escorts service
 
Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...
Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...
Croatia vs Albania Clash of Euro Cup 2024 Squad Preparations and Euro Cup Dre...
 
VIP Kolkata Call Girl Liluah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Liluah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Liluah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Liluah 👉 8250192130 Available With Room
 
Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝
Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝
Call Girls in Dhaula Kuan 💯Call Us 🔝8264348440🔝
 
Presentation: The symbols of the Olympic Games
Presentation: The symbols of the Olympic  GamesPresentation: The symbols of the Olympic  Games
Presentation: The symbols of the Olympic Games
 
CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service 🦺
CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service  🦺CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service  🦺
CALL ON ➥8923113531 🔝Call Girls Saharaganj Lucknow best Female service 🦺
 
Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...
Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...
Atlanta Dream Exec Dan Gadd on Driving Fan Engagement and Growth, Serving the...
 

Structural Dynamics in Tennis Courts

  • 1. Design criteria for dynamic performance of a suspended structure for competition grade tennis courts Mark Sheldon a,⇑ , Benjamin Delaney b a Aurecon, Australia b Major Projects Victoria, Australia a r t i c l e i n f o Article history: Available online 1 April 2014 Keyword: Tennis court dynamic performance vibration a b s t r a c t The redevelopment of the Melbourne Park Tennis Centre incorporates something not pre- viously seen at the home of a ‘‘Grand Slam’’ tournament – courts on the roof of a carpark building. To determine an appropriate structural design criterion for the suspended slabs, a study was undertaken on how vibrations induced by the players and external sources would be perceived. Following testing on existing courts and undertaking real time studies on forces exerted by tennis players, a series of criteria for acceptable vibrations in the structure was developed. The structure has now been successfully used during the 2013 and 2014 Australian Open tournaments. Ó 2014 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-SA license (http://creativecommons.org/licenses/by-nc-sa/3.0/). Introduction The Eastern Plaza and National Tennis Centre are part of the Melbourne Park Redevelopment project which is being man- aged by Major Projects Victoria for Sport and Recreation Victoria, the Melbourne and Olympic Parks and Tennis Australia. The recently completed Eastern Plaza project incorporates world-class tennis courts on the roof of the new carpark building. The new tennis courts are both indoor and outdoor, with the indoor courts covered by a metal and glass-clad architectural envelop as shown in the image above. Constructing international standard courts on top of a building is something not pre- viously seen at the home of a ‘‘Grand Slam’’ tournament. This presented the design team with a new challenge – to determine an appropriate structural design criterion for the suspended slabs. The ‘‘stiffness’’ of the structure needed to be considered, in particular how vibrations induced by the players and external sources would be perceived. Following testing on existing courts and undertaking real time studies on forces exerted by tennis players, a design criteria for acceptable vibrations was developed for the suspended structure supporting the tennis courts. This paper is not a ‘‘cook book’’ on how to design international standard competition courts on a suspended structure, as each case will vary. However it does provide guidance on the main parameters that should be considered, and describes the design approach that was successfully applied at the Melbourne Park venue. Background Most tennis courts suitable for international competition are located at ground level, on stable loadbearing layers supported by the ground. The structural design methodology for these courts is reasonably well understood within the http://dx.doi.org/10.1016/j.csse.2014.03.001 2214-3998/Ó 2014 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-SA license (http://creativecommons.org/licenses/by-nc-sa/3.0/). ⇑ Corresponding author. Tel.: +61 411575422. E-mail address: mark.sheldon@aurecongroup.com (M. Sheldon). Case Studies in Structural Engineering 1 (2014) 13–19 Contents lists available at ScienceDirect Case Studies in Structural Engineering journal homepage: www.elsevier.com/locate/csse
  • 2. structural engineering fraternity. However site constraints within the Melbourne Park complex dictated that for the new Eastern Plaza extension, opened just prior to the 2013 Australian Open, eight inside warm up courts and six outside courts needed to be located over the 1000 car carpark building. The Eastern Plaza extension also includes a player’s gymnasium, a running track, and associated facilities which the design team identified could induce vibrations in the structure. A study of major tennis venues around the world did not identify any design precedents for suspended ‘‘international standard’’ courts, so a design approach needed to be developed. The main concern was structure-borne vibrations, i.e. whether the movement of players or other external sources would cause unacceptable levels of vibration. Structure-borne vibrations can be initiated from a number of sources. The simplest form of initiator is a single strike. Once struck, the structure will oscillate at its fundamental frequency or natural frequency. The length of time over which it will oscillate and the rate at which energy dissipates is a function of the inherent damping of the structure, which is influenced by the fixtures, services and furnishings attached to the structure, and the original form of the structure. At the other end of the spectrum is the case where a cyclical load induces what could be considered a regular series of strikes on the structure. The effect of this type of loading is very dependent on the frequency of this cyclical load. If the load frequency does not match the natural frequency of the structure, then the resultant vibrations may not be significant. How- ever when the load frequency matches the structure’s natural frequency (or an integer multiple of the natural frequency), then significant vibrations can be induced. In reality a tennis slab structure would be subjected to a wide range of forces, from single strikes generated by players jumping; a series of rhythmic strikes from players running; forces randomly generated from the movement of weights in the gymnasium; transient forces from cars moving around in the carpark or trains passing Melbourne Park on the nearby rail lines; and continuous forces from machinery in plantrooms. Each of these cases needed to be investigated. Whilst the study of structure-borne vibrations can become quite technical, it was the desire of the client group (in par- ticular Major Projects Victoria and Tennis Australia) that a quantifiable design approach be developed, so that this may be able to be used on similar future projects. General principles of dynamics Under the influence of an applied load, or series of loads, a series of vibrations will be induced in the structure. One of the simplest forms of an oscillating element is a guitar string. Once plucked, it will vibrate back and forth at its ‘‘natural fre- quency’’. At the moment just before it is released it has its maximum displacement and zero acceleration. Once released it will quickly return to its ‘‘at-rest’’ position, at which time its velocity would have accelerated to its maximum and its dis- placement will be zero. Momentum will drive the string beyond the at-rest position but it will decelerate until the moment it reaches its maximum negative displacement, at which time its acceleration will again be zero. As the string will be affected by friction from the air around it, and there will be some stretch in the string itself, there is an amount of ‘‘damping’’ in this system. The string will continue oscillating for some time, although the damping will ensure that in every cycle the displace- ment is slightly less than the previous, such that it will eventually cease. A structure however, is significantly more complex than a guitar string. It will generally consist of slabs, beams, columns and foundations, all of which can influence the fre- quency of the structure. Instead of having one natural frequency, as is the case of the guitar string, a structure can have a number of resonant frequencies (frequencies at which parts of the structure will resonate). The main design parameter associated with an investigation into structure-borne vibration is usually the resultant accel- eration. A person standing on the vibrating structure will feel this vibration. What they are actually sensing is the cycles of accelerations and decelerations. Remember that whilst sitting in a car travelling at a constant velocity we do not generally sense the motion. It is the accelerating force and the braking force (deceleration) that we feel. Interestingly, some people are more sensitive to the oscillating motion than others, and some people are more tolerant of this motion than others (and this may even change depending on the player’s temperament). Whilst the behaviour of the oscillation of a floor system can be quite complex, in simple terms under an applied striking force the following will occur: The structure will vibrate at its ‘‘natural frequency’’ or one of its resonant frequencies The length of time over which it will oscillate is a function of the magnitude of the force and the damping in the building People will sense the acceleration of the slab caused by the vibration There are various ways to measure and report accelerations, the relevance of which is dependent upon the type of floor and the predominant forcing loads. In this instance, it was determined that the as the forcing load during play was a single strike, the most important structural response parameter is the peak acceleration induced in the structure. A significant body of research has been undertaken over many years studying the perceptions of vibrations, particularly in North America based on work by Thomas Murray and David Allen. Much of this work has been published over a 30+ year period, and has formed the basis of the National Buildings Code of Canada’s design criteria [1] and the American Institute of Steel Construction’s Design Guide No. 11 [2]. These studies have identified that humans are most susceptible to vibrations in the range of 4–8 Hz. This means we are less concerned with vibrations that occur less than 4 times per second or more than 8 times per second. It was also identified that people are more tolerant of vibrations in structures such as footbridges 14 M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19
  • 3. and shopping centres (where they only have limited exposure to the vibration) but are less tolerant of vibrations in an office environment and even less tolerant in their home. The following chart (Fig. 1) is well known within the engineering frater- nity as the basis for acceptable vibrations in different building types, based on the works of Murray and Allen. A significant observation from these curves is that, above approximately 8 Hz, the allowable accelerations can increase. This is due in part to the fact that people are less susceptible to higher frequency vibrations, but also recognizes that as the frequency increases, the displacement associated with the oscillation will be less (for a similar applied force). In addition to the works by Murray and Allen, other structure-borne vibration studies have been undertaken in Australia and internationally over many years on buildings such as hospital wards, operating theatres and the like. These have been referenced in the development of the criteria for the Eastern Plaza tennis courts. Another critical factor in the development of the criteria for the tennis courts is the fact that a person using their own body weight to cause the load (by jumping, lunging, running etc) is generally not able to sense the resultant vibrations in a normal structure. This observation was central to the decision on where the accelerations should be measured in the struc- ture, and is discussed in more detail below. As is the norm for structures, the accelerations in the design curves above are expressed as a percentage of the acceler- ation due to gravity (g = 9.8 m/s2 ). Load testing At the pre-tender stage of the Eastern Plaza project Major Projects Victoria and Tennis Australia recognised that this was an unusual project requiring additional inputs, so Tennis Australia commissioned testing to examine the dynamic perfor- mance of selected existing tennis courts. One court tested was the existing Margaret Court Arena, which has been used for many years during previous Australian Open Grand Slam tournaments, and consists of a post-tensioned slab-on-grade. The second test was on a tennis court located on a carpark building associated with a major hotel development. In addition, to accumulate more data for comparison a third series of tests were undertaken on a tennis court located on a suspended slab at a tennis facility in Auckland New Zealand during the final design stage. Measurements of accelerations and frequen- cies were taken at each of the facilities during a tennis match. As was expected, the dynamic response measured from these three tennis courts differed greatly. It was determined that for the Melbourne Park facility, the new suspended courts needed to be stiffer than the two suspended courts tested. In addition, Major Projects Victoria and Tennis Australia also commissioned some actual impact load tests, undertaken at the Victoria Institute of Sport (VIS) Sports Science Department. A competition player was put through a series of typical ten- nis manoeuvres over a load cell. The actual forces exerted on to the floor from these manoeuvres were measured against time. Selected graphical outputs of these tests follow. The testing showed that under a ‘‘jump smash’’ action, the force exerted on the floor was equivalent to approximately 12.5 times the player’s weight, but only for a short period of time. Under actions such as running and changing directions, the Gross Reaction Force (GRF) is approximately 2 times body weight, but occurs over a longer time and is obviously likely to occur much more frequently during a match. Under a serve Fig. 1. Acceleration Design Curves based on the works of Murray and Allen. (Adapted from American Institute of Steel Construction Design Guide No. 11, AISC 1997.) M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19 15
  • 4. motion, the maximum GRF was approximately 2.5 times the body weight, increasing to approximately 3.2 times under a volley motion (Figs. 2 and 3). The results of the Volley tests were of particular interest, as this represents an activity that would occur relatively fre- quently during a match, and produces a GRF plot with a peak similar to a ‘‘Heel Drop’’. A Heel Drop test is a universally accepted (albeit crude) test to study vibrations in structures. It is performed by a person of approximately 80 kg standing on their toes with their heels approximately 50 mm above the surface, dropping their heels to the surface whilst keeping their legs stiff. It was identified that a Heel Drop test could be used to simulate the Volley design case, and could be repro- duced with reasonable consistently. Development of a criteria To design a structure with ‘‘imperceptible’’ accelerations under all load conditions was virtually impossible and, at best, extremely cost-prohibitive. It was accepted that a design criteria had to be developed. Rather than try to adopt a single cri- terion for the design of the structure, it was decided that a rational approach coupling the probability of a load occurrence with an appropriate allowable acceleration was more logical. The Jump Smash action was identified as the most severe of the design cases, however this activity is expected to occur less frequently than serving, volleying and significantly less than run- ning/changing directions. In addition to these forces caused by the players, we also needed to consider structure-borne vibrations caused by vehicles in the carpark, trains and trams passing the facilities, activities in the gymnasium, and machin- ery in the plantrooms of the facility. Given that the professional players normally play on ‘‘on grade’’ courts that experience minimal accelerations under impacts, it was deemed necessary that a tight criteria for the suspended slabs was necessary. The starting point was to con- sider a criterion for the most common forms of activity – running and changing directions during a match. Australian Stan- dard AS2670.1 – 2001 [3], which is based on ISO 2631-1:1997, indicates that approximately 25% of alert fit persons cannot detect a vertical vibration with a peak magnitude of 0.2%g. Similarly, the Department of Environment and Conservation NSW’s ‘‘Assessing Vibration: A Technical Guideline’’ [4] provides a maximum recommended acceleration from a vertical con- tinuous vibration source in a hospital operating theatre which equates to a peak acceleration of approximately 0.14%g. Anec- dotal evidence from the design team on the National Tennis Centre was that a figure of 0.2%g had recently been used as the design criterion for a large Australian hospital. It was therefore decided that the criterion where the peak accelerations is limited to less than 0.2%g (for structures in the range of 4–8 Hz) would be appropriate, as it was deemed that even the most temperamental tennis player would agree that if a surface was stiff enough to for a doctor to operate, it would be acceptable for a tennis match. Following the precedent of the curves as shown above, the allowable acceleration could increase if a stif- fer structure (with a higher natural frequency) was provided. The ‘‘background’’ vibrations from external sources (vehicles, trains, trams, activities in the gym, mechanical plant etc.) was the second criterion to be determined. As this vibration could be expected to occur for extended periods of time, an acceleration limit less than the running/changing direction criterion was deemed appropriate. Following an assessment of what could be realistically and economically achieved in design, an acceleration curve at 80% of the running/changing direc- tion criteria was adopted. This is nearing the level at which many people would consider is imperceptible. The next criterion to be considered was for the serve action and volley action. As this activity would occur less frequently than the running and changing direction, a higher acceleration was considered acceptable. A peak acceleration of 0.5%g was Fig. 2. Gross reaction force diagram for change in direction. 16 M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19
  • 5. adopted, increasing in line with the curves shown above for frequencies greater than 8 Hz. This is similar to what would be deemed acceptable in an office or residential environment, as shown in Fig. 1. A convenient aspect of this criterion is that the Gross Reaction Force generated from the players is similar in magnitude and duration to a heel drop test, which is relatively easy to replicate by technicians. Under the jump smash action a more lenient criteria was necessary, as a cost-prohibitive structure would otherwise be necessary. Through consultation with Marshall Day Acoustics, it was agreed that as the duration of the significant force was extremely short, an allowable acceleration of 2%g (increasing for structures above 8 Hz) would be acceptable. The resultant design curves are presented in Fig. 4 below. Location of acceleration measurements The location of the acceleration measurements on the structure is another important feature of the adopted design cri- teria. For the bottom-most curve, (the background vibrations), these accelerations should not be exceeded anywhere on the slab. For the remainder of the criteria, however, two different practical factors were considered. As noted previously, it is Fig. 3. Gross reaction force diagram for volley. Fig. 4. Adopted design criteria. M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19 17
  • 6. known that the person performing the forcing action does not feel the resulting accelerations. In a tennis match environment it is therefore typically the umpire or a doubles partner that is likely to be located within about 4 m of that player. It was also known that the structure, to have requisite stiffness to accommodate the design criteria, would likely have columns and/or beams on a grid of around 8–10 m. By undertaking a preliminary 3D Finite Element Analysis (FEA) and studying the modeshapes of the resonant frequencies of the likely structural system, it was known that maximum and min- imum accelerations are likely to occur at multiples of grids and half-grids of the structure. The selected criteria was therefore to place the forcing load at the most severe location on the structure as determined by the FEA analyses. Accelerations were then checked at a maximum of 5 m centres in all directions (but coinciding with the grids and half-grids of the structure). Due to the length of a tennis court (and the fact that the players may be both located beyond the baseline) it was considered necessary to continue the measurements for a distance of approximately 25–30 m. Pre-construction dynamic analysis Significant analysis of the structure is required prior to construction, to determine the dimensions of structure to be con- structed to meet the design criteria. A full 3D finite element analysis (FEA) with time history capability is necessary to model the characteristics of the load (from the GRF plots) and the response of the structure at multiple locations. To model the structure’s response, an accurate assessment of the effective Moment of Inertia of the structural elements is essential. All flexural concrete members form fine cracks in the tensile zones which reduce its stiffness at these locations and increase deflections. These micro-cracks result in a varying effective Moment of Inertia across the structure, which needs to be accu- rately modelled before a realistic FEA can be undertaken. Similarly, under dynamic loads it is appropriate to use a higher Young’s Modulus for the structural elements than what would normally be used for a static analysis. The design of the floor structure was undertaken by the structural consultant for the builder, however to test the accuracy of their model, Aurecon produced our own Strand 7 FEA model. This reflected the edge conditions between the movement joints in the structure and the properties of the supporting columns below. Based on the layout of the courts and the struc- tural grids, it was identified that the maximum accelerations in the applicable portions of the building could be generated in the structure by locating the forcing load in the bay as shown in Fig. 5. The structure was then designed and detailed based on this pre-construction dynamic analysis. From the FEA analysis, a design will evolve to satisfy the vibration criteria. The resultant structure is likely to be consid- erably stiffer than a ‘‘normal’’ slab that would otherwise be required for an office or retail development based on the same column grid. The net result of the complexity of the dynamics issue is that a structure of this type could easily take the designer at least ten times the effort to design, and will cost at least double the cost to construct, when compared to a normal slab of similar spans. Further allowances should then be made for testing post-construction. Post construction testing Once the structure had been completed, a series of tests were undertaken to measure the accelerations produced at the critical point located in Fig. 5. Tests were done whilst a player ran, changed direction, served, volleyed and hit jump smashes, Fig. 5. Screen shot of the Aurecon Strand 7 model displacement under dynamic load (Load exerted at ‘‘P’’. Magenta lines represent supports below). (For interpretation of the references to colour in this figure legend, the reader is referred to the web version of this article.) 18 M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19
  • 7. with accelerometers at intervals up to 28 m away from the strike point. Tests were also performed using dropped loads, which were considered to more accurately reproduce the specified design GRF’s in a repeatable manner. In addition, Heel Drop tests were undertaken to simulate the volley action. The results of the measured resonant frequencies of the structure were found to be lower than predicted, although the resulting accelerations were still found to be within the criteria set for the project, as shown in Fig. 4. As the Eastern Plaza was opened prior to the end of 2012, it was used for the first time during the 2013 Australian Open, and again during the recent 2014 Australian Open. Feedback from the players and Tennis Australia was that the facility has performed well and met their expectations. Summary The redevelopment of the Melbourne Park Tennis Centre incorporates courts on the roof of the new carpark building. Con- structing international standard courts on top of a building is something not previously seen at the home of a ‘‘Grand Slam’’ tournament. This presented the design team with the challenge of how to determine an appropriate structural design crite- rion for the response of the structure to vibrations induced by the players and external sources. Tests on existing courts were undertaken, as well as real time studies on forces exerted by tennis players. Based on a rational approach, relating how often an event may occur to an appropriate acceleration limit, a series of design curves was developed for acceptable vibrations in the suspended structure supporting the tennis courts. A criteria for the locations on the slab where the measurements should be taken was also determined. This report provides guidance on the main parameters that should be considered, and the design approach that was applied for the dynamic performance of the suspended tennis courts at the Melbourne Park venue. The structure was suc- cessfully used during the 2013 and 2014 Australian Open tournaments. Acknowledgments The authors wish to acknowledge the contributions made during the development of the design criteria by Tennis Aus- tralia, Melbourne Olympic Parks, Watson Moss Growcott, and Marshall Day Acoustics. We also acknowledge the inputs of Watpac Construction and the project structural engineer Winward Structures. References [1] National Research Council Canada. User’s Guide – NBC 2005, Structural Commentaries (Part 4 of Division B). [2] Murray, Allen, Unger. Floor vibrations due to human activity, american institute of steel construction steel design guide 11; 1997. [3] Standards Australia. AS2670.1 – 2001, Evaluation of human exposure to whole-body vibration, Part 1: General Requirements. [4] Department of Environment and Conservation NSW (Aust). Assessing Vibration: a technical guideline; 2006. M. Sheldon, B. Delaney / Case Studies in Structural Engineering 1 (2014) 13–19 19