How to calculate the bus voltages using Power world Simulator with the help of Gauss-Seidel iteration Method. Also calculate the Mismatches and Y-bus. I explained each and every step.
"Good Luck"
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
Power system operation and control lab
1. Lab Experiment No 02
Task
Find the Real power, Reactive Power and State Variable using Gauss -Seidel Method
and save result of first two and Last iteration
Resultof FirstIteration
Figure 1
S13 loss= 0.57 MVar
V1 = 1.025 withangle 0
V2 = 1.0013 withangle -2.78
V3 = 1.03 withangle 0.90
P3 = 300 MW
Q3 = 137 MVar
P1 = 166 MW
Q1 = 92 MVar
P2 = 400 MW
Q2 = 200 MVar
Mismatch of 1st
iteration
4. Y- Bus of Givenpowersystem
ComposedBy Engr. M Rashid Malik