Electric Equipment
EMPR “IMP Series”
Intelligent Motor
Protection Relaywww.dienhathe.xyz
www.dienhathe.vn
The EMPR IMP series are optimal solutions for protecting and monitoring
motors in complex industrial fields and provide high safety and productivity.
● Where monitoring panel for the MCC is required
● Where reliability and stable protection are needed
● Semiconductor, chemical, automobile, textile and pharmaceutical plants
● Oil, gas, railway, water supply/drainage, and buildings
● Steel, cement, paper and ship building
Contents
IntelligentMotorProtectionRelay
Features 4
Major Functions 5
System Architecture 6
Ratings and Type 7
Operation and Setting 8
Wiring 12
Characteristic Curve 13
Dimensions 14
List of the Standard Model 16
Annex 18
EMPRIMPSeries IntelligentMotorProtectionRelay
The EMPR is a digital intelligent motor protection relay with an onboard MCU (Microprocessor
Control Unit) and guarantees high reliability with real-time data processing, superb precision
and antisurge functions.
www.dienhathe.xyz
www.dienhathe.vn
Beyond Motor Protection...
The new EMPR IMP series support MODBUS RS-485 communications or
4~20mA analogue output and are the most economic and reliable solution
for MCC monitoring panels
■
The internal CT can be applied to up to 100 A motors
without saturation based on inverse time characteristics.
An escape hole is installed in the CT to make it easy to
penetrate more than two wires.
■
As both zero-phase-sequence current and post-arc
current are detected simultaneously, non-grounded and
directly-grounded systems are reliably protected from
leaks and ground faults.
■
The system can be operated in the definite time, inverse
time, and heat accumulation inverse time modes to
protect motors according to their operation ratings, load
characteristics and external environments.
Wide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control Range
Double Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground Faults
Various Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection Mode
www.dienhathe.xyz
www.dienhathe.vn
4II
IMPFeatures
Total Digital Motor Protection Relay with
the MCU (Microprocessor Control Unit)
Real-time processing and high precision
One-Body Type and Separate Body Type
The display can be attached to the panel front so
that current, operation time and settings can be
checked without fetching the unit. With the display
separated, the motor can be protected.
Applicable to Inverter Circuits
Thankstoitsgoodhighharmonicnoisecharacteristics,
it can be applied to the 2nd stage of inverter control
circuits. The available frequency range is 20~200Hz.
When the relative harmonic factor is over 30%, a
harmonic filter should be installed (However, the
ground fault function should be off).
Wide Current Control Range:
0.125~100A for One Model
With the slide S/W, the current control range can
be decided 0.5~10A or 5~100A. According to the
CT penetration number, even 0.125A current can
be controlled. (Wire penetration hole).
Up to 100A current, it can be used without
an external current transformer for
convenience and economic efficiency.
Various Recovery Functions
Manual, automatic and electric recovery functions
are provided for customer convenience.
Wide Ground Fault Sensitivity Current
Control and Double Protection: 30mA~25A
Both zero-phase-sequence current and post-arc
current are detected simultaneously to provide
customers with convenience and economic
efficiency.
Password
Settings are protected with a password.
Heat Accumulation Inverse Time, Inverse
Time and Definite Time Modes
Accordingtouser’sneeds,themotorcanbeprotected
in the inverse time mode or definite time mode.
Storage of Fault Events
Up to five fault events can be stored for easy fault
history management.
3-Phase Digital Ampere-Meter
3-phase current is displayed every two seconds for
motor monitoring.
Quick Setup
All settings can be decided quickly on the display.
Date
When a fault occurs, its date and time are stored
foreasy checkup.
Total Operating Time Setup
When the total operation time is over, it is displayed
for changing motor bearings or supplying oil.
Communication
RS485 and MODBUS are supported for
communication with various systems.
The model with analogue signals (4~20mA) is
compatible with transducer systems.
MCU
INV
Slide S/W
Return
~100A
30mA 25A
Save
Total
www.dienhathe.xyz
www.dienhathe.vn
II5
EMPRIMPSeries
MajorFunctions
● Overload-49
Motor current is detected and is applied to I2t.
If it reaches the characteristic curve, overload
protection is on.
The overload function can be set to be on
when the current is increased by 600% in
consideration of motor operating time. Since
operation time can be set from 1 second to 60
seconds in 1-second increments, up to 60
classes can be decided for overload
characteristic curves.
In the definite time mode, regardless of motor
heat, current after delaytime is recognized as
excess current and if it lasts over operation
time, a trip occurs.
● Stall/Locked Rotor - 48/51L
Losses caused by motor rotor’s stall, failure or operation delay are prevented. Load current or load torque is over the predefined
value, it is detected to shut down the circuit. Excess current operation triggered by start electric current is on after the delay time
● Under Current - 37
This function detects no-load conditions that take place as the motor shaft is
dislocated or damaged or prevents pump idling. Up to 30~70% of rated current
can be predefined and the system is on within three seconds
● Phase Fail/Phase Unbalance - 47P
When a phase failure occurs in the motor or power, the motor cannot start and the
operating motor will stop due to a torque shortage or be overheated as negative
sequence current keeps flowing in. The IMP is set to be on within 1.5 seconds
when the 3-phase current unbalance is over 70% and be tripped within three
seconds when the unbalance rate is over 10~70%.
* For the single-phase motor, Phase Fail/Phase Unbalance should be off.
● Reverse Phase
This function prevents the motor’s reverse revolution. The phase difference of 3-phase input current is compared and if the
phase sequence is changed, this function is on within 0.1 second. Only with the motor running, the phase reversion is
checked. As this function is not available for the single motor, turn it off for the single motor.
● Ground Fault - 51G
This function is on when leakage current is detected to prevent ground faults and 2nd faults (short circuit and electric shock).
Current sensitivity and operation time can be set differently for each ground systems. Current sensitivity can be set
30mA~25A and operation time 0.05~1.0 second.
Since the IMP supports RS-485/MODBUS, communication networks with various systems can be established.
Also, as analogue current signals (4~20mA) can be used, it is compatible with existing systems with transducers.
(See the system architecture.)
<Inverse Time Characteristics> <Definite Time Characteristics>
Protection
Communication
www.dienhathe.xyz
www.dienhathe.vn
6II
EMPRIMPSeries
SystemArchitecture
GIPAM
GIMAC
PLC
SCADA
MODBUS/RS-485
DCS
4~20mA
www.dienhathe.xyz
www.dienhathe.vn
II7
RatingsandType
Ratings
Protection
Excess Current, Under Current, Instantaneous, Reverse Phase,
Stall, Phase Failure, Unbalance, Constraint, Ground Fault
Connection Penetration
Operation Time
Heat Accumulation Inverse Time /Inverse Time /Definite Time
Characteristics
Rated Current 0.5~10A/5~100A (Selected by Slide S/W)
Display 7-SEGMENT
Power AC/DC 85~245V (50Hz/60Hz)
Recovery Type
Automatic 1~20 minutes
Manual /Electric (ON/OFF Selectable)
Installation Method The display can be installed separately. 35mm DIN rail /nut
Tolerance
Current: ±5%; Time: ±5%
4~20mA Output: ±5%
Time Setup
Start Delay 1~200 sec.
Operation Delay 1~60 sec.
Auxiliary Contact
3-SPST 3A/250VAC Resistance
(Momentary contacts should be purchased separately)
ZCT Input Note) 200mA/100mV (Specific ZCT)
Operation Temperature -10~55℃
Operation Environment Storage Temperature -20~70℃
Relative Humidity 80%RH or less (No condensation)
Insulated Resistance 100Mohm/500VDC
Lightning Impulse Voltage 1.2×50us 6kV Standard Wave
Fast Transient 2kV/1Min
Power Consumption 3W or less
IMP C A420
Ordering Method (Explaining the Model Name)
Communication
NO None
A420 4~20mA Output
M485 MODBUS/RS-485
Items to be Protected
C Current
Note) Available when the zero-phase-sequence current is selected.
One-Body Type
Separate Body Type
www.dienhathe.xyz
www.dienhathe.vn
8II
EMPRIMPSeries
OperationandSetting
1. Test/Reset
1) Check wires.
2) Press the Test/Reset key once. Then“TEST”is displayed and the system is tripped.
3) With the system tripped, press the Test/Reset key to reset the system.
Note) While the motor is running, the Test/Reset key does not work.
2. Setting
1) Press the Test/Reset key once. Then“TEST”is displayed and the system is tripped.
2) Press the Enter key. Then“P-99”is displayed. Use the Up/Down keys to change the password.
3) Press the Enter key to enter A-gr setup mode.
Use the Up/Down keys to select a group and Press the Enter key to enter the selected group.
Press the Test/Reset key to move back to the previous mode.
4) In the A-Grp mode, Press the Enter key. Then“1.CHA”is displayed.
Use the Up/Down keys to select an item and Press the Enter key to enter the selected item.
Press the Test/Reset key to move back to the previous mode.
5) Use the Up/Down keys to set up the value and Press the Enter key to save it.
Note) When the power is supplied first or is resupplied after a power failure, must set up the date in b-gr, 5.S-d. Set up the rated current S/W while the power is off.
3. Quick Setup
1) Press the“Up and Enter”keys at the same time.“UPLD”is displayed and settings are uploaded to the display.
2) Insert the display to the body without settings, and then press the Test key to enter the test mode.
3) Press the“Down and Enter”keys at the same time.“TEST”is displayed and downloading is completed.
4) Press the Test key to return to the normal mode.
Note) Communication settings cannot be uploaded or downloaded.
4. Setting Checkup
1) Press the Enter key.
2) Use the Up/Down keys to select a group and Press the Enter key to enter the selected group.
Press the Test/Reset key to move back to the previous mode.
3) Use the Up/Down keys to select an item and Press the Enter key to enter the selected item.
4) Press the Enter key again to check settings.
5. Failure Event Checkup
1) Press the Up and Down keys at the same time to display“1.O-C”(recent failure events).
Note) When no failure events are stored,“1.non”is displayed.
2) Use the Up/Down keys to select an event and press the Enter key to go to the selected event.
3) The R-phased failure current is displayed. Every time the Down key is pressed, S-phased failure current, Tphased failure current,
overload rate and date are displayed one after the other.
4) Press the Test/Reset key to move back to the previous mode.
5) Press the Up and Down keys at the same time to get out of the failure event checkup mode.
6. Forced Heat Amount Reset
When the system is tripped while it is in the heat accumulation inverse time mode, if you want to turn the system into the cold mode
by resetting the motor’s heat amount, Press the Enter and Test/Rest keys at the same time.
*When a trip occurs due to the heat accumulation excess current, if the motor is started right after it is reset, as the motor is hot, it is highly likely that
the motor is tripped again.
www.dienhathe.xyz
www.dienhathe.vn
II9
Note 1) When the rated current S/W is 100A, the CT ratio is not displayed.
Note 2) Some menus are not displayed if relevant functions are not available.
Group Menu Setting Value Item Default Value
A
1.CHA dEF/th/n-th
Operation Characteristics (Definite Time /
HeatAccumulationInverseTime/InverseTime)
n-th
2.O-t 1~60s Operation Time (sec) 60
3.d-t 1~200s Operation Delay (sec) In chase of dEF
4.r-C 0.5~10A/5~100A Rated Current Max.
5.Ctr 0.25, 0.5, 1~200 CT Ratio (4 times, twice, once) 1
6.Loc OFF, 200~800% Lock Protection (sec) OFF
7.StL OFF, 150~500% Stall Protection (sec) OFF
8.P-F OFF/On Open Phase OFF
9.P-U OFF, 10~70% Unbalance Protection (%) OFF
10.rP OFF/On Reverse Phase OFF
11.UC OFF, 30~90% Low Current Protection (%) OFF
12.gF 0FF, 0.03, 0.05/0.1~3A
Ground Fault Operation Current
(Zero-Phase-Sequence Current) (A)
OFF
13.gn OFF, 20~500% (FLCmin)
Ground Fault Operation Current
(Post-Arc Current) (FLCmin)
OFF
14.gt 0.05, 0.1~1.0s Ground Fault Operation Time (Current) -
15.gd On/OFF Ground Fault Delay During Start ON
16.IC OFF, 500~1000% Instantaneous Protection (%) OFF
17.Io ALt/TriP Instantaneous Warning/Operation TriP
Group Menu Setting Value Item Default Value
B 1.E-r On/OFF Electric Recovery On
2.A-r OFF, 1~20 min Automatic Recovery (Minute) OFF
3.r-t Hour/Minute Operation Time Time Check
4.Srt OFF, 1~8760Hour Operation Time Setup (Hour) -
5.s-d 2009/01.01/00:00 YY/MM/DD/ HH:MM
6.Trt Day/hour:minute Total Operation Time Time Check
A.t-d 0.5~10/5~100A 20mA Output Setup 420 Model
A.Adr 1~247 Communication Address
b.bps 96/192/384 Communication Speed
c.S-P On/OFF SWAP
Note 1) When the power is supplied first or is resupplied after a power failure, must set up the date (5.S-d).
Note 2) Automatic recovery is only possible in case of an excess current trip.
M485 Model
Setting Menu (A Group)
Setting Menu (B Group)
www.dienhathe.xyz
www.dienhathe.vn
10II
EMPRIMPSeries
OperationandSetting
Operation Display
R Phase
S Phase
T Phase
Ground Fault Current
Unbalance Rate Current Unit
Load Rate Unit
Communication Status
Load Rate Display
Reverse Phase Current
Display Description Remark
O-C Excess Current Trip Operate within predefined time.
U-C Low Current Trip Operate within three seconds.
P-F Open Phase Trip Operate within 1.5 seconds when the unbalance rate is over 70%.
P-U Unbalance Trip Operate within three seconds.
Loc Constraint Trip Operate within 0.5 seconds.
StL Stall Trip Operate within three seconds.
r-P Reverse Phase Trip Operate within 0.1 second.
g-F Ground Fault Trip Operate within predefined time.
Sho Instantaneous Trip Operate within 0.05 seconds.
OrH Elapsed Time (No Trip) The operation time is reset when the Reset key is pressed.
C.err
Communication Fault between Body and Display
(Press the ENTER/RESET key to return to the normal mode)
Note 1) This table is written based on the full load current.
Note 2) The CT is selected as a reference for the EMPR’s current setting range.
7. IMP Specifications for Low Voltage 3-Phase Induction Motors (Reference)
Full Load Current IMP Settings
External CT
Motor Output (Less than kW)
for the Motor Current Selection S/W Wire Penetration CT Setup 220V 380V 440V
0.7A or less 4 times 0.25 - 0.1 0.18 0.2
0.7~1.6A 0.5~10A Twice 0.5 - 0.25 0.55 0.6
1.6~8A Once 1 - 1.5 3 3.7
7~100A 5~100A Once 1 - 25 45 55
90~120A Once 30 SCT-150 30 55 55
120A~160A Once 40 SCT-200 45 75 90
160~240A Once 60 SCT-300 55 110 132
240~320A 0.5~10A Once 80 SCT-400 90 160 160
320~400A Once 100 500 : 5 110 200 200
400~480A Once 120 600 : 5 132 250 250
480~640A Once 160 800 : 5 160 320 320
Note) kW, kVar, and V indicate the specification of the voltage models (under development).
www.dienhathe.xyz
www.dienhathe.vn
II11
8. Current Signal (DC 4~20mA) Output
1) The biggest current out of measured 3-phase currents is converted into DC 4mA~20mA and the current measured remotely by
digital meter can be displayed.
2) When there is no current, 4mA is sent. If the current goes beyond the predefined value, 20mA is sent.
Output Current =
16mA
× Load Current + 4mA (Settings are changed in A.t-d of b-gr)
Setting
3) When the system is the 0.5A~10A setting mode, measurement starts from 0.3A. When the system is the 5A~100A setting mode,
measurement starts from 3A. Thus, when the current is under 0.3A (3A), 0A is measured and output is 4mA. (To measure the load
current correctly, an appropriate CT should be used).
Note) The allowable burden is less than 500Ϊ . Considering the receiver resistance (usually 250Ϊ ) and track resistance), the shielding cable should be used.
20mA
13.6mA
16.8mA
20mA
16mA
12mA
8mA
4mA
0A 0.1A 0.2A 0.3A 0.4A 0.5A(0.5A~10A)
0A 1A 2A 3A 4A 5A(5A~100A)
20mA
16mA
12mA
8mA
4mA
20mA
10.4mA
13.6mA
7.2mA
16.8mA
0A 2A 4A 6A 8A 10A(0.5A~10A)
0A 20A 40A 60A 80A 100A(5A~100A)
20mA
10.4mA
13.6mA
7.2mA
16.8mA
20mA
16mA
12mA
8mA
4mA
0A 1A 2A 3A 4A 5A(0.5A~10A)
0A 10A 20A 30A 40A 50A(5A~100A)
< Analogue output when the output is set to be 0.5A(5A) >
< Analogue output when the output is set to be 10A(100A) >
< Analogue output when the output is set to be 5A(50A) >
www.dienhathe.xyz
www.dienhathe.vn
12II
EMPRIMPSeries
OperationandSetting
10A
100A
96 97 98 07 08 Z1 Z2
VT TRX(+) 05 06TRX(-)
ZCTA1 A2 95 96(+) (-)
VR VS VT
Note 1) When the zero-phase-sequence current transformer is used to detect ground faults, connect the ZCT.
Note 2) When the single-phase motor is used, all phases are connected except the S phase, and open-phase, unbalance and ground fault should be set OFF.
Note 1) The 3-phase voltage input terminal and 05-06 output terminal should be connected only for voltage protection models, which will be released in the future.
Note 2) For RS485 connection, the terminal resistance should be 120Ϊ .
Note 3) For 4~20mA current, the maximum burden should be less than 500Ϊ .
Engrave Description Remark
A1(+), A2(-) Input terminal for operation power AC/DC85~245V
95-96 When the power is ON (NC contact output) In case of an instantaneous trip, if 17.lo is ALT, it is NC, and if 17.lo is Trip, it is NO.
97-98 When the power is ON (NC contact output) In case of an instantaneous trip, regardless of 17 .1o setup, it is NC.
07-08 Converted to the NC mode only when an instantaneous trip occurs.
Z1, Z2 Output terminal for the zero-phasesequence current transformer Specific ZCT (for the EMPR)
TRX(+) RS485 terminal (TRX+) Or 4~20mA (+) output
TRX(-) RS485 terminal (TRX-) Or 4~20mA (-) output
10A/100A Max. rated current change S/W 10A : 0.5~10A, 100A : 5~100A
VR/VS/VT 3-phase voltage input terminal
05-06 Output terminal for voltage protection
10A
100A
96 97 98 07 08 Z1 Z2
VT TRX(+) 05 06TRX(-)
ZCTA1 A2 95 96(+) (-)
VR VS VT
ZCT
MC
OL
TRIP
MCCB
AUX
MCCB
RS485
(4~20mA)
OFF
(RESET)
SHT
Y
MC
A1 A2 95 97 07
Z1
TRX (+, -)
OLEMPR
96 98 08 Z2
SR
10A
100A
96 97 98 07 08 Z1 Z2
VT TRX(+) 05 06TRX(-)
ZCTA1 A2 95 96(+) (-)
VR VS VT
With the External CT
Note 1)
Terminal Configuration
www.dienhathe.xyz
www.dienhathe.vn
II13
CharacteristicCurve
<Class5> <Class10>
<Class20> <Class30>
<Class60> <Definite Time Characteristics>
www.dienhathe.xyz
www.dienhathe.vn
14II14II14II14II
EMPRIMPSeries
Externaldimension
Note 1) The cable should be purchased separately (1m/1.5m/2m/3m).
(Unit: mm)
U/2/T1 V/4/T2 W/6/T3
90
68
64
135.5
109.3
53.5
∅17
21
5
7.3
4.2
82
25
One-Body Type
www.dienhathe.xyz
www.dienhathe.vn
II15
(Unit: mm)
U/2/T1 V/4/T2 W/6/T3
90
68
64
109.3
53.5
∅17
21
54.2
82
25
12
121.3
M4
64
90
26 44
5617 17
202222
Separate Body Type
www.dienhathe.xyz
www.dienhathe.vn
16II
EMPRGMPSeries
ListoftheStandardModel
(1) Device: D = Definite Time, I = Inverse Time (2) Attachment: P = Nut, R = Din-Rail. MC= Mag. Contactor Direct Attachment
(3) Open Phase: The 2CT model detects excess current or two phases (4) Constraint: Operate after the predefined time in the define time mode.
(5) Setting: O+D = Operation and Delay times are set as a whole, O/D= Operation and Delay times are set separately, PRG = Program setup,
(6) In the inverse time mode, it can be used without external CTs (7) Model '�' indicates additional terminal platforms are required.
Connection Model Device Characteristic Attachment ExcessCurrent Overcurrent Phasefailure Stall Asymmetry Reversephase GroundFault Setup Output Rated Current
GMP60-TE 2CT D Manual P/R ■ ▲ ▲ O+D 1c 6,30,60A
GMP60-T 2CT D Manual P/R ■ ▲ ▲ O/D 1c 6,30,60A
GMP22-2T 2CT I Manual P/R ■ ▲ ■ O 1a1b 1.5,5,22A
GMP40-2T 2CT I Manual P/R ■ ▲ ■ O 1a1b 20,40A
GMP60-3T(R) 3CT D Manual P/R ■ ■ ▲ ■ ■(R) O/D 1a1b 6,36,60A
GMP60-TA 2CT D Manual,Automatic P/R ■ ▲ ▲ O/R 1c 6,30,60A
GMP60-3TN(R) 3CT D Manual P/R ■ ■ ▲ ■ ■(R) ■ D/G 1a1b 6,60A
GMP60-3TZ(R) 3CT D Manual P/R ■ ■ ▲ ■ ■(R) ■ D/G 1a1b 6,60A
GMP22-3T(R) 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 1.5,5,22A
GMP40-3T(R) 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 20,40A
GMP60-TD 2CT D Manual P/R ■ ▲ ▲ PRG 1a1b 6,60A
GMP60-TDa 2CT D Manual,Automatic P/R ■ ■ ■ *Additionalfunctionsincludingtimeandlowcurrent PRG 1a1b 6,60A
GMP22-2PD 2CT D Manual MC ■ ▲ ▲ O/5 1c 1.5,5,22A
GMP40-2PD 2CT D Manual MC ■ ▲ ▲ O/5 1a1b 20,40A
GMP22-2P 2CT I Manual MC ■ ▲ ■ O 1a1b,1c 1.5,5,22A
GMP40-2P 2CT I Manual MC ■ ▲ ■ O 1a1b 20,40A
GMP22-3P(R) 3CT I Manual MC ■ ■ ■ ■ ■(R) O 1a1b 1.5,5,22A
GMP40-3P(R) 3CT I Manual MC ■ ■ ■ ■ ■(R) O 1a1b 20,40A
GMP22-2PA 2CT I Automatic MC ■ ▲ ■ O 1a1b 1.5,5,22A
GMP40-2PA 2CT I Automatic MC ■ ▲ ■ O 1a1b 20,40A
GMP60-3S(R)� 3CT D Manual P/R ■ ■ ▲ ■ ■(R) O/D 1a1b 6,36,60A
GMP22-3S� 3CT I Manual P/R ■ ■ ■ ■ O 1a1b 1.5,5,22A
GMP40-3S(R)� 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 20,40A
GMP22-2S� 2CT I Manual P/R ■ ▲ ■ O 1a1b 1.5,5,22A
GMP40-2S� 2CT I Manual P/R ■ ▲ ■ O 1a1b 20,40A
GMP80-2S 2CT I Manual P/R ■ ▲ ■ O 1a1b 80A
GMP80-3S(R) 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 80A
GMP80-2SA 2CT I Automatic P/R ■ ▲ ■ O 1a1b 80A
Functions of the Digital Motor Protection Relay (GMP Type)
Ordering Method (Explaining the Model Name)
GMP 22 2 P R a 1.5A 220 Auxiliary
Contact
CT Type
2 2CT
3 3CT
Type
P DirectCoupling(Pin)
S
Terminal
Connection(Screw)
T
Penetration
(Tunnel)
TE Economic
PD
Direct Coupling
(Definite Time)
TD
Current Display
(Definite Time)
TZ
TN
Reverse Phase
-
ReverseProtection
No Protection
R
ReverseProtection
ProtectionAvailable
A
Automatic
Recovery
NominalCurrent CurrentSetupRange(A)
1.5A 0.3~1.5
5A 1~5
22A 4.4~22
20A 4~20
40A 8~40
80A 16~80
06A 0.5~6
30A 3~30
60A 0.5~60 Note)
Operation Current
110/220 AC100~260V
24 AC24V
48 AC48V
110 AC110V
220 AC220V
380 AC380 (440)V
Note) AC24V and AC380 (440)V are
for GMP60T.
Note) For GMP60-TD, GMP60-TDa 6/60A, GMP60-3TZ (R), 3TN (R), 3T (R)
Aux. contactor
1C
1a1b
Note) When the
power is
applied, the
system is in the
contacting
status.
Frame NominalCurrent Type
1.5A
22 5A
22A
40
20A
40A
80 80A TerminalConnection
06A
60 30A Penetration
60A
Classification
- Existing Model
a
OperationTime
Function
관관통통
직직결결
단단자자
GroundFaultProtection
(Zero-Phase-Sequence
CurrentDetection)
GroundFaultProtection
(ResidualCurrent
Detection)
Direct
Coupling,
Terminal
Connection,
Penetration
www.dienhathe.xyz
www.dienhathe.vn
II17
EMPRDMPSeries
Separable
Terminal block
Separable
Display
Nut or Din-Rail
(1) For the separate body model, cables should be purchased separately. For the wiring terminal model, terminals can be bought separately.
(2) '□' indicates 06, 36, and 60 are removed (Rated current).
One/Separate Body
DMP□-T 2a1b DefiniteTime/InverseTime ■ ■ ■ ■
DMP□-Ta 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ ■
One/Separate Body
DMP□-S 2a1b DefiniteTime/InverseTime ■ ■ ■ ■
DMP□-Sa 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ ■
One/Separate Body
DMP□-TZ 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault
DMP□-TZa 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault ■
One/Separate Body
DMP□-SZ 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault
DMP□-SZa 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault ■
One/Separate Body DMP□-TI 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ Instantaneous
One/Separate Body DMP□-SI 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ Instantaneous
Functions the Digital Motor Protection Relay (GMP Type)
Ordering Method (Explaining the Model Name)
DMP 06 S Z a 220 Auxiliary
Contact
Note 1) Even the same
model has different
contact
specifications.
Note 2) When the power is
applied, the system
is in the contacting
status.
Current Control Range
06 0.5~6A
36 3~36A
60 5~60A
Wiring
S
Terminal
(Screw)
T
Penetration
(Tunnel)
OPTION
- Standard Model
Z
Ground Fault
Protection
I
Instantaneous
Short Protection
Classification
- Existing Model
a
Operation Time
Function
Control Voltage
220 AC220V
110 AC110V
Aux. contactor
1a1b
2a
2b
2a1b
Function
Standard
Penetration
Terminal
Penetration
Terminal
Penetration
Terminal
Ground
Fault
Instantaneous
Wiring Display Model Output Operation
Excess Current
Low Current
Constraint
Reverse
Phase
Unbalance
Open Phase
Others
Time
Setup
www.dienhathe.xyz
www.dienhathe.vn
18II
EMPRIMPSeries
CurrentTransformerCT,ZCT-ZeroPhaseSequenceCurrentTransformer
SCT-100 100:5A
SCT-150 150:5A
SCT-200 200:5A
SCT-300 300:5A
SCT-400 400:5A
Grade 1.0
Burden 5VA
Insulation Voltage AC 600V
Deelectric Strength 2kV
Insulation Resistance 10MΪ (DC 500V Megger)
Attachement Panel
Note) Use this product only for EMPR
3CTModel
1CT
3CTs
Dimensions
With GMP60-3T
With DMP
With IMP
Specifications
Current
Transformation
Ratiowww.dienhathe.xyz
www.dienhathe.vn
II19
Annex
● Definite Time : In this mode, if the current goes beyond the predefined value, regardless of the current size, the system is on after
a certain period of time. This is suitable for heaters, circuits and lights which have constant load current.
● Inverse Time : In this mode, if the current goes beyond the predefined value, the system operates in inverse proportion to the
current size. The mode is divided into cold mode and hot mode.
In the cold mode, the motor starts based on normal temperatures (initial starting current). In the hot mode, after
starting is completed, the motor moves from cold to hot mode according to current and operation time. If the motor
is in the hot mode, it operates faster than the cold one.
Ex) When the motor is running with 10 seconds of the operation time, if the current is increased by 600% for 10
seconds, the system is on in the cold mode. However, in the hot mode, when the current is increased by 600, the
system is tripped only for one second.
The motor loss caused by the excess current is in proportion to generated heat (I2t). So, the system in the inverse
time mode is suitable for motor protection. And as the circuit breaker (ACB, MCCB) for the power stage has
inverse time characteristics, the motor protection relay with inverse time characteristics is suitable. Though motor
protection relays with inverse time characteristics are used often because they are easy to set up and handle,
EMPR with inverse time characteristics are suitable for delicate and reliable motor protection.
●● Heat Accumulation Inverse Time : Heat Accumulation Inverse Time: In this mode, though the system has the same
characteristics as the inverse time mode, some time after the motor stops, the system
enters the cold mode.
That is, the system has similar characteristics as the TOR. Only after certain time in the
overload mode, the system can be operated again.
This mode is used when the motor can be damaged because of frequent forward/backward
operation and restarting. If frequent starting and forward/backward operation are required, it
is convenient to operate the system in the inverse time mode as heat is not accumulated
When the system is running in the inverse time mode, the operation current should be recognized precisely by the motor protection relay.
If the current is much bigger than the relay’s rated current, the internal CT is saturated and its size is recognized small, which results in
incorrect inverse time operation.
LG’s motor protection relay can recognize the current which is eight times bigger than the rated current. So, it can operate in the
inverse time mode to protect motors with a rated current of 60A or 100A without external CTs.
1
2
3
Time(s)
Motor’s Heat
Characteristics(cold)
Motor’s Heat
Characteristics(hot)
Definite Time
Motor’s Starting Current
Inverse Time(cold)
Inverse Time(hot)Inverse Time(hot)
Current(%)
<When the Operation Time is 10 Seconds >
No motor deterioration or
Non operation Operation
burning
Hot status: Possible motor
Operation
deterioration or burning
Cold status: No motor
Non operation
Non operation
deterioration or burning
Hot status: Motor burning Operation
Cold status: No motor
Non operation Non operation
deterioration or burning
Inverse Time Definite TimeArea Motor Status
1
2
3
Definite Time, Inverse Time and Heat Accumulation Inverse Time
Comparison of Inverse Time/Definite Time
Inverse Time Characteristics and Excess Current Saturation in the CT
www.dienhathe.xyz
www.dienhathe.vn
www.lsis.biz
ⓒ 2009.10 LS Industrial Systems Co.,Ltd. All rights reserved.
��For your safety, please read user's manual thoroughly before operating.
��Contact the nearest authorized service facility for examination, repair, or adjustment.
��Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
��Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions
�LS Industrial Systems (Middle East) FZE ��Dubai, U.A.E.
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: hwyim@lsis.biz
�Dalian LS Industrial Systems Co., Ltd. ��Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn
�LS Industrial Systems (Wuxi) Co., Ltd. ��Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn
�LS-VINA Industrial Systems Co., Ltd. ��Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com
�LS-VINA Industrial Systems Co., Ltd. ��Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com
�LS Industrial Systems Tokyo Office ��Tokyo, Japan
Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz
�LS Industrial Systems Shanghai Office ��Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn
�LS Industrial Systems Beijing Office ��Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
�LS Industrial Systems Guangzhou Office ��Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz
�LS Industrial Systems Chengdu Office ��Chengdu, China
Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China
Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn
�LS Industrial Systems Qingdao Office ��Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn
�� HEAD OFFICE
LS Tower 1026-6, Hogye-dong, Dongan-gu,
Anyang-si, Gyeonggi-do 431-848, Korea
Tel. (82-2)2034-4887, 4873, 4918, 4148
Fax. (82-2)2034-4648
�� CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea
�� Global Network
Specifications in this catalog are subject to change without notice due to
continuous product development and improvement.
2009. 10 Intelligent Motor Protection Relay (E) 2009. 10/(01) 2009. 10 Printed in Korea STAFF
www.dienhathe.xyz
www.dienhathe.vn

More Related Content

What's hot

Catalog biến tần Frenic Mega Fuji Electric-Beeteco.com
Catalog biến tần Frenic Mega Fuji Electric-Beeteco.comCatalog biến tần Frenic Mega Fuji Electric-Beeteco.com
Catalog biến tần Frenic Mega Fuji Electric-Beeteco.comBeeteco
 
Manual de Danfoss 2800
Manual de Danfoss 2800Manual de Danfoss 2800
Manual de Danfoss 2800Camilo Avelino
 
Arm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorArm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorUday Wankar
 
Catalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.comCatalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.comCTY TNHH HẠO PHƯƠNG
 
Catalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.com
Catalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.comCatalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.com
Catalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.comBeeteco
 
Scada presentation
Scada presentationScada presentation
Scada presentationAmit Kumar
 
Catalog Biến tần Frenic MINI mới nhất 2019
Catalog Biến tần Frenic MINI mới nhất 2019Catalog Biến tần Frenic MINI mới nhất 2019
Catalog Biến tần Frenic MINI mới nhất 2019CTY TNHH HẠO PHƯƠNG
 
Ls catalog thiet bi tu dong imc iii-e_dienhathe.vn
Ls catalog thiet bi tu dong imc iii-e_dienhathe.vnLs catalog thiet bi tu dong imc iii-e_dienhathe.vn
Ls catalog thiet bi tu dong imc iii-e_dienhathe.vnDien Ha The
 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Uday Wankar
 
Catalog Frenic MULTI - www.haophuong.com
Catalog Frenic MULTI - www.haophuong.comCatalog Frenic MULTI - www.haophuong.com
Catalog Frenic MULTI - www.haophuong.comCTY TNHH HẠO PHƯƠNG
 
7SR105 Motor Protection Relay
7SR105 Motor Protection Relay7SR105 Motor Protection Relay
7SR105 Motor Protection Relayashwini reliserv
 
Mitsubishi digital protection relay melpro a series dienhathe.vn
Mitsubishi digital protection relay melpro a series dienhathe.vnMitsubishi digital protection relay melpro a series dienhathe.vn
Mitsubishi digital protection relay melpro a series dienhathe.vnDien Ha The
 

What's hot (16)

Catalog biến tần Frenic Mega Fuji Electric-Beeteco.com
Catalog biến tần Frenic Mega Fuji Electric-Beeteco.comCatalog biến tần Frenic Mega Fuji Electric-Beeteco.com
Catalog biến tần Frenic Mega Fuji Electric-Beeteco.com
 
Manual de Danfoss 2800
Manual de Danfoss 2800Manual de Danfoss 2800
Manual de Danfoss 2800
 
Arm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC MotorArm Processor Based Speed Control Of BLDC Motor
Arm Processor Based Speed Control Of BLDC Motor
 
Catalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.comCatalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.com
 
Frenic5000 vg7s 405c
Frenic5000 vg7s 405cFrenic5000 vg7s 405c
Frenic5000 vg7s 405c
 
Catalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.com
Catalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.comCatalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.com
Catalog Biến tần Frenic5000 vg7s 405c Fuji​-Beeteco.com
 
Ecopowersupplies: Riello sentinel-pro-ups-datasheet
Ecopowersupplies: Riello sentinel-pro-ups-datasheetEcopowersupplies: Riello sentinel-pro-ups-datasheet
Ecopowersupplies: Riello sentinel-pro-ups-datasheet
 
Scada presentation
Scada presentationScada presentation
Scada presentation
 
Zapi sem 2 manual
Zapi sem 2 manualZapi sem 2 manual
Zapi sem 2 manual
 
Catalog Biến tần Frenic MINI mới nhất 2019
Catalog Biến tần Frenic MINI mới nhất 2019Catalog Biến tần Frenic MINI mới nhất 2019
Catalog Biến tần Frenic MINI mới nhất 2019
 
Ls catalog thiet bi tu dong imc iii-e_dienhathe.vn
Ls catalog thiet bi tu dong imc iii-e_dienhathe.vnLs catalog thiet bi tu dong imc iii-e_dienhathe.vn
Ls catalog thiet bi tu dong imc iii-e_dienhathe.vn
 
Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control Arm cortex ( lpc 2148 ) based motor speed control
Arm cortex ( lpc 2148 ) based motor speed control
 
Catalog Frenic MULTI - www.haophuong.com
Catalog Frenic MULTI - www.haophuong.comCatalog Frenic MULTI - www.haophuong.com
Catalog Frenic MULTI - www.haophuong.com
 
7SR105 Motor Protection Relay
7SR105 Motor Protection Relay7SR105 Motor Protection Relay
7SR105 Motor Protection Relay
 
Mitsubishi digital protection relay melpro a series dienhathe.vn
Mitsubishi digital protection relay melpro a series dienhathe.vnMitsubishi digital protection relay melpro a series dienhathe.vn
Mitsubishi digital protection relay melpro a series dienhathe.vn
 
Catalog lift hpc
Catalog lift hpcCatalog lift hpc
Catalog lift hpc
 

Similar to Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910

Ls catalog thiet bi dien g empr-dmpr
Ls catalog thiet bi dien g empr-dmprLs catalog thiet bi dien g empr-dmpr
Ls catalog thiet bi dien g empr-dmprDien Ha The
 
Ls catalog thiet bi tu dong imc iii-e
Ls catalog thiet bi tu dong imc iii-eLs catalog thiet bi tu dong imc iii-e
Ls catalog thiet bi tu dong imc iii-eDien Ha The
 
Catalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.com
Catalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.comCatalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.com
Catalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.comBeeteco
 
Ls catalog thiet bi tu dong i s5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i s5_e_1105_dienhathe.vnLs catalog thiet bi tu dong i s5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i s5_e_1105_dienhathe.vnDien Ha The
 
DIGITAL DC DRIVES & SYSTEMS UPTO 5000 KW
DIGITAL DC DRIVES & SYSTEMS UPTO 5000 KWDIGITAL DC DRIVES & SYSTEMS UPTO 5000 KW
DIGITAL DC DRIVES & SYSTEMS UPTO 5000 KWGemcoControls
 
Ls catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-eLs catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-eDien Ha The
 
Ls catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-eLs catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-eDien Ha The
 
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, DelhiMicrocontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, DelhiIndiaMART InterMESH Limited
 
Catalog Biến tần Frenic 5000g11 Fuji Electric
Catalog Biến tần Frenic 5000g11 Fuji ElectricCatalog Biến tần Frenic 5000g11 Fuji Electric
Catalog Biến tần Frenic 5000g11 Fuji ElectricBeeteco
 
7SK81 Motor Protection Relay
7SK81 Motor Protection Relay7SK81 Motor Protection Relay
7SK81 Motor Protection Relayashwini reliserv
 
7UM62 Generator Protection Relay
7UM62 Generator Protection Relay7UM62 Generator Protection Relay
7UM62 Generator Protection Relayashwini reliserv
 
7UT63 Differential Protection Relay
7UT63 Differential Protection Relay7UT63 Differential Protection Relay
7UT63 Differential Protection Relayashwini reliserv
 
Temp based fan speed control
Temp based fan speed controlTemp based fan speed control
Temp based fan speed controlSai Malleswar
 
7UT612 Transformer Differential Protection relay
7UT612 Transformer Differential Protection relay7UT612 Transformer Differential Protection relay
7UT612 Transformer Differential Protection relayashwini reliserv
 

Similar to Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910 (20)

Ls catalog thiet bi dien g empr-dmpr
Ls catalog thiet bi dien g empr-dmprLs catalog thiet bi dien g empr-dmpr
Ls catalog thiet bi dien g empr-dmpr
 
Ls catalog thiet bi tu dong imc iii-e
Ls catalog thiet bi tu dong imc iii-eLs catalog thiet bi tu dong imc iii-e
Ls catalog thiet bi tu dong imc iii-e
 
Catalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.com
Catalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.comCatalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.com
Catalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.com
 
Ls catalog thiet bi tu dong i s5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i s5_e_1105_dienhathe.vnLs catalog thiet bi tu dong i s5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i s5_e_1105_dienhathe.vn
 
DIGITAL DC DRIVES & SYSTEMS UPTO 5000 KW
DIGITAL DC DRIVES & SYSTEMS UPTO 5000 KWDIGITAL DC DRIVES & SYSTEMS UPTO 5000 KW
DIGITAL DC DRIVES & SYSTEMS UPTO 5000 KW
 
Ls catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-eLs catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-e
 
Ls catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-eLs catalog thiet bi tu dong gipam 2200-e
Ls catalog thiet bi tu dong gipam 2200-e
 
7SJ64 Relay
7SJ64 Relay7SJ64 Relay
7SJ64 Relay
 
InPhase Power Complete Product Catalogue
InPhase Power Complete Product CatalogueInPhase Power Complete Product Catalogue
InPhase Power Complete Product Catalogue
 
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, DelhiMicrocontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
 
Catalog Biến tần Frenic 5000g11 Fuji Electric
Catalog Biến tần Frenic 5000g11 Fuji ElectricCatalog Biến tần Frenic 5000g11 Fuji Electric
Catalog Biến tần Frenic 5000g11 Fuji Electric
 
Riello aros-central-transformer-based-solar-inverters
Riello aros-central-transformer-based-solar-invertersRiello aros-central-transformer-based-solar-inverters
Riello aros-central-transformer-based-solar-inverters
 
7SK81 Motor Protection Relay
7SK81 Motor Protection Relay7SK81 Motor Protection Relay
7SK81 Motor Protection Relay
 
7UM62 Generator Protection Relay
7UM62 Generator Protection Relay7UM62 Generator Protection Relay
7UM62 Generator Protection Relay
 
7UT63 Differential Protection Relay
7UT63 Differential Protection Relay7UT63 Differential Protection Relay
7UT63 Differential Protection Relay
 
Temp based fan speed control
Temp based fan speed controlTemp based fan speed control
Temp based fan speed control
 
S2000Micro_Brochure
S2000Micro_BrochureS2000Micro_Brochure
S2000Micro_Brochure
 
7UT612 Transformer Differential Protection relay
7UT612 Transformer Differential Protection relay7UT612 Transformer Differential Protection relay
7UT612 Transformer Differential Protection relay
 
5000g11s hpc
5000g11s hpc5000g11s hpc
5000g11s hpc
 
siprotec
siprotecsiprotec
siprotec
 

More from Dien Ha The

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Dien Ha The
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comDien Ha The
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookDien Ha The
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseDien Ha The
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Dien Ha The
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalogDien Ha The
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbDien Ha The
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Dien Ha The
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsDien Ha The
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter familyDien Ha The
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesDien Ha The
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesDien Ha The
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuDien Ha The
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesDien Ha The
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Dien Ha The
 

More from Dien Ha The (20)

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.com
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library book
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalog
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcb
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new models
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter family
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din series
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 series
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj series
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
 

Recently uploaded

Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...121011101441
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
An introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxAn introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxPurva Nikam
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 

Recently uploaded (20)

Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
An introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptxAn introduction to Semiconductor and its types.pptx
An introduction to Semiconductor and its types.pptx
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910

  • 1. Electric Equipment EMPR “IMP Series” Intelligent Motor Protection Relaywww.dienhathe.xyz www.dienhathe.vn
  • 2. The EMPR IMP series are optimal solutions for protecting and monitoring motors in complex industrial fields and provide high safety and productivity. ● Where monitoring panel for the MCC is required ● Where reliability and stable protection are needed ● Semiconductor, chemical, automobile, textile and pharmaceutical plants ● Oil, gas, railway, water supply/drainage, and buildings ● Steel, cement, paper and ship building Contents IntelligentMotorProtectionRelay Features 4 Major Functions 5 System Architecture 6 Ratings and Type 7 Operation and Setting 8 Wiring 12 Characteristic Curve 13 Dimensions 14 List of the Standard Model 16 Annex 18 EMPRIMPSeries IntelligentMotorProtectionRelay The EMPR is a digital intelligent motor protection relay with an onboard MCU (Microprocessor Control Unit) and guarantees high reliability with real-time data processing, superb precision and antisurge functions. www.dienhathe.xyz www.dienhathe.vn
  • 3. Beyond Motor Protection... The new EMPR IMP series support MODBUS RS-485 communications or 4~20mA analogue output and are the most economic and reliable solution for MCC monitoring panels ■ The internal CT can be applied to up to 100 A motors without saturation based on inverse time characteristics. An escape hole is installed in the CT to make it easy to penetrate more than two wires. ■ As both zero-phase-sequence current and post-arc current are detected simultaneously, non-grounded and directly-grounded systems are reliably protected from leaks and ground faults. ■ The system can be operated in the definite time, inverse time, and heat accumulation inverse time modes to protect motors according to their operation ratings, load characteristics and external environments. Wide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control RangeWide Current Control Range Double Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground FaultsDouble Protection for Ground Faults Various Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection ModeVarious Protection Mode www.dienhathe.xyz www.dienhathe.vn
  • 4. 4II IMPFeatures Total Digital Motor Protection Relay with the MCU (Microprocessor Control Unit) Real-time processing and high precision One-Body Type and Separate Body Type The display can be attached to the panel front so that current, operation time and settings can be checked without fetching the unit. With the display separated, the motor can be protected. Applicable to Inverter Circuits Thankstoitsgoodhighharmonicnoisecharacteristics, it can be applied to the 2nd stage of inverter control circuits. The available frequency range is 20~200Hz. When the relative harmonic factor is over 30%, a harmonic filter should be installed (However, the ground fault function should be off). Wide Current Control Range: 0.125~100A for One Model With the slide S/W, the current control range can be decided 0.5~10A or 5~100A. According to the CT penetration number, even 0.125A current can be controlled. (Wire penetration hole). Up to 100A current, it can be used without an external current transformer for convenience and economic efficiency. Various Recovery Functions Manual, automatic and electric recovery functions are provided for customer convenience. Wide Ground Fault Sensitivity Current Control and Double Protection: 30mA~25A Both zero-phase-sequence current and post-arc current are detected simultaneously to provide customers with convenience and economic efficiency. Password Settings are protected with a password. Heat Accumulation Inverse Time, Inverse Time and Definite Time Modes Accordingtouser’sneeds,themotorcanbeprotected in the inverse time mode or definite time mode. Storage of Fault Events Up to five fault events can be stored for easy fault history management. 3-Phase Digital Ampere-Meter 3-phase current is displayed every two seconds for motor monitoring. Quick Setup All settings can be decided quickly on the display. Date When a fault occurs, its date and time are stored foreasy checkup. Total Operating Time Setup When the total operation time is over, it is displayed for changing motor bearings or supplying oil. Communication RS485 and MODBUS are supported for communication with various systems. The model with analogue signals (4~20mA) is compatible with transducer systems. MCU INV Slide S/W Return ~100A 30mA 25A Save Total www.dienhathe.xyz www.dienhathe.vn
  • 5. II5 EMPRIMPSeries MajorFunctions ● Overload-49 Motor current is detected and is applied to I2t. If it reaches the characteristic curve, overload protection is on. The overload function can be set to be on when the current is increased by 600% in consideration of motor operating time. Since operation time can be set from 1 second to 60 seconds in 1-second increments, up to 60 classes can be decided for overload characteristic curves. In the definite time mode, regardless of motor heat, current after delaytime is recognized as excess current and if it lasts over operation time, a trip occurs. ● Stall/Locked Rotor - 48/51L Losses caused by motor rotor’s stall, failure or operation delay are prevented. Load current or load torque is over the predefined value, it is detected to shut down the circuit. Excess current operation triggered by start electric current is on after the delay time ● Under Current - 37 This function detects no-load conditions that take place as the motor shaft is dislocated or damaged or prevents pump idling. Up to 30~70% of rated current can be predefined and the system is on within three seconds ● Phase Fail/Phase Unbalance - 47P When a phase failure occurs in the motor or power, the motor cannot start and the operating motor will stop due to a torque shortage or be overheated as negative sequence current keeps flowing in. The IMP is set to be on within 1.5 seconds when the 3-phase current unbalance is over 70% and be tripped within three seconds when the unbalance rate is over 10~70%. * For the single-phase motor, Phase Fail/Phase Unbalance should be off. ● Reverse Phase This function prevents the motor’s reverse revolution. The phase difference of 3-phase input current is compared and if the phase sequence is changed, this function is on within 0.1 second. Only with the motor running, the phase reversion is checked. As this function is not available for the single motor, turn it off for the single motor. ● Ground Fault - 51G This function is on when leakage current is detected to prevent ground faults and 2nd faults (short circuit and electric shock). Current sensitivity and operation time can be set differently for each ground systems. Current sensitivity can be set 30mA~25A and operation time 0.05~1.0 second. Since the IMP supports RS-485/MODBUS, communication networks with various systems can be established. Also, as analogue current signals (4~20mA) can be used, it is compatible with existing systems with transducers. (See the system architecture.) <Inverse Time Characteristics> <Definite Time Characteristics> Protection Communication www.dienhathe.xyz www.dienhathe.vn
  • 7. II7 RatingsandType Ratings Protection Excess Current, Under Current, Instantaneous, Reverse Phase, Stall, Phase Failure, Unbalance, Constraint, Ground Fault Connection Penetration Operation Time Heat Accumulation Inverse Time /Inverse Time /Definite Time Characteristics Rated Current 0.5~10A/5~100A (Selected by Slide S/W) Display 7-SEGMENT Power AC/DC 85~245V (50Hz/60Hz) Recovery Type Automatic 1~20 minutes Manual /Electric (ON/OFF Selectable) Installation Method The display can be installed separately. 35mm DIN rail /nut Tolerance Current: ±5%; Time: ±5% 4~20mA Output: ±5% Time Setup Start Delay 1~200 sec. Operation Delay 1~60 sec. Auxiliary Contact 3-SPST 3A/250VAC Resistance (Momentary contacts should be purchased separately) ZCT Input Note) 200mA/100mV (Specific ZCT) Operation Temperature -10~55℃ Operation Environment Storage Temperature -20~70℃ Relative Humidity 80%RH or less (No condensation) Insulated Resistance 100Mohm/500VDC Lightning Impulse Voltage 1.2×50us 6kV Standard Wave Fast Transient 2kV/1Min Power Consumption 3W or less IMP C A420 Ordering Method (Explaining the Model Name) Communication NO None A420 4~20mA Output M485 MODBUS/RS-485 Items to be Protected C Current Note) Available when the zero-phase-sequence current is selected. One-Body Type Separate Body Type www.dienhathe.xyz www.dienhathe.vn
  • 8. 8II EMPRIMPSeries OperationandSetting 1. Test/Reset 1) Check wires. 2) Press the Test/Reset key once. Then“TEST”is displayed and the system is tripped. 3) With the system tripped, press the Test/Reset key to reset the system. Note) While the motor is running, the Test/Reset key does not work. 2. Setting 1) Press the Test/Reset key once. Then“TEST”is displayed and the system is tripped. 2) Press the Enter key. Then“P-99”is displayed. Use the Up/Down keys to change the password. 3) Press the Enter key to enter A-gr setup mode. Use the Up/Down keys to select a group and Press the Enter key to enter the selected group. Press the Test/Reset key to move back to the previous mode. 4) In the A-Grp mode, Press the Enter key. Then“1.CHA”is displayed. Use the Up/Down keys to select an item and Press the Enter key to enter the selected item. Press the Test/Reset key to move back to the previous mode. 5) Use the Up/Down keys to set up the value and Press the Enter key to save it. Note) When the power is supplied first or is resupplied after a power failure, must set up the date in b-gr, 5.S-d. Set up the rated current S/W while the power is off. 3. Quick Setup 1) Press the“Up and Enter”keys at the same time.“UPLD”is displayed and settings are uploaded to the display. 2) Insert the display to the body without settings, and then press the Test key to enter the test mode. 3) Press the“Down and Enter”keys at the same time.“TEST”is displayed and downloading is completed. 4) Press the Test key to return to the normal mode. Note) Communication settings cannot be uploaded or downloaded. 4. Setting Checkup 1) Press the Enter key. 2) Use the Up/Down keys to select a group and Press the Enter key to enter the selected group. Press the Test/Reset key to move back to the previous mode. 3) Use the Up/Down keys to select an item and Press the Enter key to enter the selected item. 4) Press the Enter key again to check settings. 5. Failure Event Checkup 1) Press the Up and Down keys at the same time to display“1.O-C”(recent failure events). Note) When no failure events are stored,“1.non”is displayed. 2) Use the Up/Down keys to select an event and press the Enter key to go to the selected event. 3) The R-phased failure current is displayed. Every time the Down key is pressed, S-phased failure current, Tphased failure current, overload rate and date are displayed one after the other. 4) Press the Test/Reset key to move back to the previous mode. 5) Press the Up and Down keys at the same time to get out of the failure event checkup mode. 6. Forced Heat Amount Reset When the system is tripped while it is in the heat accumulation inverse time mode, if you want to turn the system into the cold mode by resetting the motor’s heat amount, Press the Enter and Test/Rest keys at the same time. *When a trip occurs due to the heat accumulation excess current, if the motor is started right after it is reset, as the motor is hot, it is highly likely that the motor is tripped again. www.dienhathe.xyz www.dienhathe.vn
  • 9. II9 Note 1) When the rated current S/W is 100A, the CT ratio is not displayed. Note 2) Some menus are not displayed if relevant functions are not available. Group Menu Setting Value Item Default Value A 1.CHA dEF/th/n-th Operation Characteristics (Definite Time / HeatAccumulationInverseTime/InverseTime) n-th 2.O-t 1~60s Operation Time (sec) 60 3.d-t 1~200s Operation Delay (sec) In chase of dEF 4.r-C 0.5~10A/5~100A Rated Current Max. 5.Ctr 0.25, 0.5, 1~200 CT Ratio (4 times, twice, once) 1 6.Loc OFF, 200~800% Lock Protection (sec) OFF 7.StL OFF, 150~500% Stall Protection (sec) OFF 8.P-F OFF/On Open Phase OFF 9.P-U OFF, 10~70% Unbalance Protection (%) OFF 10.rP OFF/On Reverse Phase OFF 11.UC OFF, 30~90% Low Current Protection (%) OFF 12.gF 0FF, 0.03, 0.05/0.1~3A Ground Fault Operation Current (Zero-Phase-Sequence Current) (A) OFF 13.gn OFF, 20~500% (FLCmin) Ground Fault Operation Current (Post-Arc Current) (FLCmin) OFF 14.gt 0.05, 0.1~1.0s Ground Fault Operation Time (Current) - 15.gd On/OFF Ground Fault Delay During Start ON 16.IC OFF, 500~1000% Instantaneous Protection (%) OFF 17.Io ALt/TriP Instantaneous Warning/Operation TriP Group Menu Setting Value Item Default Value B 1.E-r On/OFF Electric Recovery On 2.A-r OFF, 1~20 min Automatic Recovery (Minute) OFF 3.r-t Hour/Minute Operation Time Time Check 4.Srt OFF, 1~8760Hour Operation Time Setup (Hour) - 5.s-d 2009/01.01/00:00 YY/MM/DD/ HH:MM 6.Trt Day/hour:minute Total Operation Time Time Check A.t-d 0.5~10/5~100A 20mA Output Setup 420 Model A.Adr 1~247 Communication Address b.bps 96/192/384 Communication Speed c.S-P On/OFF SWAP Note 1) When the power is supplied first or is resupplied after a power failure, must set up the date (5.S-d). Note 2) Automatic recovery is only possible in case of an excess current trip. M485 Model Setting Menu (A Group) Setting Menu (B Group) www.dienhathe.xyz www.dienhathe.vn
  • 10. 10II EMPRIMPSeries OperationandSetting Operation Display R Phase S Phase T Phase Ground Fault Current Unbalance Rate Current Unit Load Rate Unit Communication Status Load Rate Display Reverse Phase Current Display Description Remark O-C Excess Current Trip Operate within predefined time. U-C Low Current Trip Operate within three seconds. P-F Open Phase Trip Operate within 1.5 seconds when the unbalance rate is over 70%. P-U Unbalance Trip Operate within three seconds. Loc Constraint Trip Operate within 0.5 seconds. StL Stall Trip Operate within three seconds. r-P Reverse Phase Trip Operate within 0.1 second. g-F Ground Fault Trip Operate within predefined time. Sho Instantaneous Trip Operate within 0.05 seconds. OrH Elapsed Time (No Trip) The operation time is reset when the Reset key is pressed. C.err Communication Fault between Body and Display (Press the ENTER/RESET key to return to the normal mode) Note 1) This table is written based on the full load current. Note 2) The CT is selected as a reference for the EMPR’s current setting range. 7. IMP Specifications for Low Voltage 3-Phase Induction Motors (Reference) Full Load Current IMP Settings External CT Motor Output (Less than kW) for the Motor Current Selection S/W Wire Penetration CT Setup 220V 380V 440V 0.7A or less 4 times 0.25 - 0.1 0.18 0.2 0.7~1.6A 0.5~10A Twice 0.5 - 0.25 0.55 0.6 1.6~8A Once 1 - 1.5 3 3.7 7~100A 5~100A Once 1 - 25 45 55 90~120A Once 30 SCT-150 30 55 55 120A~160A Once 40 SCT-200 45 75 90 160~240A Once 60 SCT-300 55 110 132 240~320A 0.5~10A Once 80 SCT-400 90 160 160 320~400A Once 100 500 : 5 110 200 200 400~480A Once 120 600 : 5 132 250 250 480~640A Once 160 800 : 5 160 320 320 Note) kW, kVar, and V indicate the specification of the voltage models (under development). www.dienhathe.xyz www.dienhathe.vn
  • 11. II11 8. Current Signal (DC 4~20mA) Output 1) The biggest current out of measured 3-phase currents is converted into DC 4mA~20mA and the current measured remotely by digital meter can be displayed. 2) When there is no current, 4mA is sent. If the current goes beyond the predefined value, 20mA is sent. Output Current = 16mA × Load Current + 4mA (Settings are changed in A.t-d of b-gr) Setting 3) When the system is the 0.5A~10A setting mode, measurement starts from 0.3A. When the system is the 5A~100A setting mode, measurement starts from 3A. Thus, when the current is under 0.3A (3A), 0A is measured and output is 4mA. (To measure the load current correctly, an appropriate CT should be used). Note) The allowable burden is less than 500Ϊ . Considering the receiver resistance (usually 250Ϊ ) and track resistance), the shielding cable should be used. 20mA 13.6mA 16.8mA 20mA 16mA 12mA 8mA 4mA 0A 0.1A 0.2A 0.3A 0.4A 0.5A(0.5A~10A) 0A 1A 2A 3A 4A 5A(5A~100A) 20mA 16mA 12mA 8mA 4mA 20mA 10.4mA 13.6mA 7.2mA 16.8mA 0A 2A 4A 6A 8A 10A(0.5A~10A) 0A 20A 40A 60A 80A 100A(5A~100A) 20mA 10.4mA 13.6mA 7.2mA 16.8mA 20mA 16mA 12mA 8mA 4mA 0A 1A 2A 3A 4A 5A(0.5A~10A) 0A 10A 20A 30A 40A 50A(5A~100A) < Analogue output when the output is set to be 0.5A(5A) > < Analogue output when the output is set to be 10A(100A) > < Analogue output when the output is set to be 5A(50A) > www.dienhathe.xyz www.dienhathe.vn
  • 12. 12II EMPRIMPSeries OperationandSetting 10A 100A 96 97 98 07 08 Z1 Z2 VT TRX(+) 05 06TRX(-) ZCTA1 A2 95 96(+) (-) VR VS VT Note 1) When the zero-phase-sequence current transformer is used to detect ground faults, connect the ZCT. Note 2) When the single-phase motor is used, all phases are connected except the S phase, and open-phase, unbalance and ground fault should be set OFF. Note 1) The 3-phase voltage input terminal and 05-06 output terminal should be connected only for voltage protection models, which will be released in the future. Note 2) For RS485 connection, the terminal resistance should be 120Ϊ . Note 3) For 4~20mA current, the maximum burden should be less than 500Ϊ . Engrave Description Remark A1(+), A2(-) Input terminal for operation power AC/DC85~245V 95-96 When the power is ON (NC contact output) In case of an instantaneous trip, if 17.lo is ALT, it is NC, and if 17.lo is Trip, it is NO. 97-98 When the power is ON (NC contact output) In case of an instantaneous trip, regardless of 17 .1o setup, it is NC. 07-08 Converted to the NC mode only when an instantaneous trip occurs. Z1, Z2 Output terminal for the zero-phasesequence current transformer Specific ZCT (for the EMPR) TRX(+) RS485 terminal (TRX+) Or 4~20mA (+) output TRX(-) RS485 terminal (TRX-) Or 4~20mA (-) output 10A/100A Max. rated current change S/W 10A : 0.5~10A, 100A : 5~100A VR/VS/VT 3-phase voltage input terminal 05-06 Output terminal for voltage protection 10A 100A 96 97 98 07 08 Z1 Z2 VT TRX(+) 05 06TRX(-) ZCTA1 A2 95 96(+) (-) VR VS VT ZCT MC OL TRIP MCCB AUX MCCB RS485 (4~20mA) OFF (RESET) SHT Y MC A1 A2 95 97 07 Z1 TRX (+, -) OLEMPR 96 98 08 Z2 SR 10A 100A 96 97 98 07 08 Z1 Z2 VT TRX(+) 05 06TRX(-) ZCTA1 A2 95 96(+) (-) VR VS VT With the External CT Note 1) Terminal Configuration www.dienhathe.xyz www.dienhathe.vn
  • 13. II13 CharacteristicCurve <Class5> <Class10> <Class20> <Class30> <Class60> <Definite Time Characteristics> www.dienhathe.xyz www.dienhathe.vn
  • 14. 14II14II14II14II EMPRIMPSeries Externaldimension Note 1) The cable should be purchased separately (1m/1.5m/2m/3m). (Unit: mm) U/2/T1 V/4/T2 W/6/T3 90 68 64 135.5 109.3 53.5 ∅17 21 5 7.3 4.2 82 25 One-Body Type www.dienhathe.xyz www.dienhathe.vn
  • 15. II15 (Unit: mm) U/2/T1 V/4/T2 W/6/T3 90 68 64 109.3 53.5 ∅17 21 54.2 82 25 12 121.3 M4 64 90 26 44 5617 17 202222 Separate Body Type www.dienhathe.xyz www.dienhathe.vn
  • 16. 16II EMPRGMPSeries ListoftheStandardModel (1) Device: D = Definite Time, I = Inverse Time (2) Attachment: P = Nut, R = Din-Rail. MC= Mag. Contactor Direct Attachment (3) Open Phase: The 2CT model detects excess current or two phases (4) Constraint: Operate after the predefined time in the define time mode. (5) Setting: O+D = Operation and Delay times are set as a whole, O/D= Operation and Delay times are set separately, PRG = Program setup, (6) In the inverse time mode, it can be used without external CTs (7) Model '�' indicates additional terminal platforms are required. Connection Model Device Characteristic Attachment ExcessCurrent Overcurrent Phasefailure Stall Asymmetry Reversephase GroundFault Setup Output Rated Current GMP60-TE 2CT D Manual P/R ■ ▲ ▲ O+D 1c 6,30,60A GMP60-T 2CT D Manual P/R ■ ▲ ▲ O/D 1c 6,30,60A GMP22-2T 2CT I Manual P/R ■ ▲ ■ O 1a1b 1.5,5,22A GMP40-2T 2CT I Manual P/R ■ ▲ ■ O 1a1b 20,40A GMP60-3T(R) 3CT D Manual P/R ■ ■ ▲ ■ ■(R) O/D 1a1b 6,36,60A GMP60-TA 2CT D Manual,Automatic P/R ■ ▲ ▲ O/R 1c 6,30,60A GMP60-3TN(R) 3CT D Manual P/R ■ ■ ▲ ■ ■(R) ■ D/G 1a1b 6,60A GMP60-3TZ(R) 3CT D Manual P/R ■ ■ ▲ ■ ■(R) ■ D/G 1a1b 6,60A GMP22-3T(R) 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 1.5,5,22A GMP40-3T(R) 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 20,40A GMP60-TD 2CT D Manual P/R ■ ▲ ▲ PRG 1a1b 6,60A GMP60-TDa 2CT D Manual,Automatic P/R ■ ■ ■ *Additionalfunctionsincludingtimeandlowcurrent PRG 1a1b 6,60A GMP22-2PD 2CT D Manual MC ■ ▲ ▲ O/5 1c 1.5,5,22A GMP40-2PD 2CT D Manual MC ■ ▲ ▲ O/5 1a1b 20,40A GMP22-2P 2CT I Manual MC ■ ▲ ■ O 1a1b,1c 1.5,5,22A GMP40-2P 2CT I Manual MC ■ ▲ ■ O 1a1b 20,40A GMP22-3P(R) 3CT I Manual MC ■ ■ ■ ■ ■(R) O 1a1b 1.5,5,22A GMP40-3P(R) 3CT I Manual MC ■ ■ ■ ■ ■(R) O 1a1b 20,40A GMP22-2PA 2CT I Automatic MC ■ ▲ ■ O 1a1b 1.5,5,22A GMP40-2PA 2CT I Automatic MC ■ ▲ ■ O 1a1b 20,40A GMP60-3S(R)� 3CT D Manual P/R ■ ■ ▲ ■ ■(R) O/D 1a1b 6,36,60A GMP22-3S� 3CT I Manual P/R ■ ■ ■ ■ O 1a1b 1.5,5,22A GMP40-3S(R)� 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 20,40A GMP22-2S� 2CT I Manual P/R ■ ▲ ■ O 1a1b 1.5,5,22A GMP40-2S� 2CT I Manual P/R ■ ▲ ■ O 1a1b 20,40A GMP80-2S 2CT I Manual P/R ■ ▲ ■ O 1a1b 80A GMP80-3S(R) 3CT I Manual P/R ■ ■ ■ ■ ■(R) O 1a1b 80A GMP80-2SA 2CT I Automatic P/R ■ ▲ ■ O 1a1b 80A Functions of the Digital Motor Protection Relay (GMP Type) Ordering Method (Explaining the Model Name) GMP 22 2 P R a 1.5A 220 Auxiliary Contact CT Type 2 2CT 3 3CT Type P DirectCoupling(Pin) S Terminal Connection(Screw) T Penetration (Tunnel) TE Economic PD Direct Coupling (Definite Time) TD Current Display (Definite Time) TZ TN Reverse Phase - ReverseProtection No Protection R ReverseProtection ProtectionAvailable A Automatic Recovery NominalCurrent CurrentSetupRange(A) 1.5A 0.3~1.5 5A 1~5 22A 4.4~22 20A 4~20 40A 8~40 80A 16~80 06A 0.5~6 30A 3~30 60A 0.5~60 Note) Operation Current 110/220 AC100~260V 24 AC24V 48 AC48V 110 AC110V 220 AC220V 380 AC380 (440)V Note) AC24V and AC380 (440)V are for GMP60T. Note) For GMP60-TD, GMP60-TDa 6/60A, GMP60-3TZ (R), 3TN (R), 3T (R) Aux. contactor 1C 1a1b Note) When the power is applied, the system is in the contacting status. Frame NominalCurrent Type 1.5A 22 5A 22A 40 20A 40A 80 80A TerminalConnection 06A 60 30A Penetration 60A Classification - Existing Model a OperationTime Function 관관통통 직직결결 단단자자 GroundFaultProtection (Zero-Phase-Sequence CurrentDetection) GroundFaultProtection (ResidualCurrent Detection) Direct Coupling, Terminal Connection, Penetration www.dienhathe.xyz www.dienhathe.vn
  • 17. II17 EMPRDMPSeries Separable Terminal block Separable Display Nut or Din-Rail (1) For the separate body model, cables should be purchased separately. For the wiring terminal model, terminals can be bought separately. (2) '□' indicates 06, 36, and 60 are removed (Rated current). One/Separate Body DMP□-T 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ DMP□-Ta 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ ■ One/Separate Body DMP□-S 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ DMP□-Sa 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ ■ One/Separate Body DMP□-TZ 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault DMP□-TZa 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault ■ One/Separate Body DMP□-SZ 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault DMP□-SZa 1a1b,2a DefiniteTime/InverseTime ■ ■ ■ ■ Ground Fault ■ One/Separate Body DMP□-TI 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ Instantaneous One/Separate Body DMP□-SI 2a1b DefiniteTime/InverseTime ■ ■ ■ ■ Instantaneous Functions the Digital Motor Protection Relay (GMP Type) Ordering Method (Explaining the Model Name) DMP 06 S Z a 220 Auxiliary Contact Note 1) Even the same model has different contact specifications. Note 2) When the power is applied, the system is in the contacting status. Current Control Range 06 0.5~6A 36 3~36A 60 5~60A Wiring S Terminal (Screw) T Penetration (Tunnel) OPTION - Standard Model Z Ground Fault Protection I Instantaneous Short Protection Classification - Existing Model a Operation Time Function Control Voltage 220 AC220V 110 AC110V Aux. contactor 1a1b 2a 2b 2a1b Function Standard Penetration Terminal Penetration Terminal Penetration Terminal Ground Fault Instantaneous Wiring Display Model Output Operation Excess Current Low Current Constraint Reverse Phase Unbalance Open Phase Others Time Setup www.dienhathe.xyz www.dienhathe.vn
  • 18. 18II EMPRIMPSeries CurrentTransformerCT,ZCT-ZeroPhaseSequenceCurrentTransformer SCT-100 100:5A SCT-150 150:5A SCT-200 200:5A SCT-300 300:5A SCT-400 400:5A Grade 1.0 Burden 5VA Insulation Voltage AC 600V Deelectric Strength 2kV Insulation Resistance 10MΪ (DC 500V Megger) Attachement Panel Note) Use this product only for EMPR 3CTModel 1CT 3CTs Dimensions With GMP60-3T With DMP With IMP Specifications Current Transformation Ratiowww.dienhathe.xyz www.dienhathe.vn
  • 19. II19 Annex ● Definite Time : In this mode, if the current goes beyond the predefined value, regardless of the current size, the system is on after a certain period of time. This is suitable for heaters, circuits and lights which have constant load current. ● Inverse Time : In this mode, if the current goes beyond the predefined value, the system operates in inverse proportion to the current size. The mode is divided into cold mode and hot mode. In the cold mode, the motor starts based on normal temperatures (initial starting current). In the hot mode, after starting is completed, the motor moves from cold to hot mode according to current and operation time. If the motor is in the hot mode, it operates faster than the cold one. Ex) When the motor is running with 10 seconds of the operation time, if the current is increased by 600% for 10 seconds, the system is on in the cold mode. However, in the hot mode, when the current is increased by 600, the system is tripped only for one second. The motor loss caused by the excess current is in proportion to generated heat (I2t). So, the system in the inverse time mode is suitable for motor protection. And as the circuit breaker (ACB, MCCB) for the power stage has inverse time characteristics, the motor protection relay with inverse time characteristics is suitable. Though motor protection relays with inverse time characteristics are used often because they are easy to set up and handle, EMPR with inverse time characteristics are suitable for delicate and reliable motor protection. ●● Heat Accumulation Inverse Time : Heat Accumulation Inverse Time: In this mode, though the system has the same characteristics as the inverse time mode, some time after the motor stops, the system enters the cold mode. That is, the system has similar characteristics as the TOR. Only after certain time in the overload mode, the system can be operated again. This mode is used when the motor can be damaged because of frequent forward/backward operation and restarting. If frequent starting and forward/backward operation are required, it is convenient to operate the system in the inverse time mode as heat is not accumulated When the system is running in the inverse time mode, the operation current should be recognized precisely by the motor protection relay. If the current is much bigger than the relay’s rated current, the internal CT is saturated and its size is recognized small, which results in incorrect inverse time operation. LG’s motor protection relay can recognize the current which is eight times bigger than the rated current. So, it can operate in the inverse time mode to protect motors with a rated current of 60A or 100A without external CTs. 1 2 3 Time(s) Motor’s Heat Characteristics(cold) Motor’s Heat Characteristics(hot) Definite Time Motor’s Starting Current Inverse Time(cold) Inverse Time(hot)Inverse Time(hot) Current(%) <When the Operation Time is 10 Seconds > No motor deterioration or Non operation Operation burning Hot status: Possible motor Operation deterioration or burning Cold status: No motor Non operation Non operation deterioration or burning Hot status: Motor burning Operation Cold status: No motor Non operation Non operation deterioration or burning Inverse Time Definite TimeArea Motor Status 1 2 3 Definite Time, Inverse Time and Heat Accumulation Inverse Time Comparison of Inverse Time/Definite Time Inverse Time Characteristics and Excess Current Saturation in the CT www.dienhathe.xyz www.dienhathe.vn
  • 20. www.lsis.biz ⓒ 2009.10 LS Industrial Systems Co.,Ltd. All rights reserved. ��For your safety, please read user's manual thoroughly before operating. ��Contact the nearest authorized service facility for examination, repair, or adjustment. ��Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself! ��Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions �LS Industrial Systems (Middle East) FZE ��Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: hwyim@lsis.biz �Dalian LS Industrial Systems Co., Ltd. ��Dalian, China Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn �LS Industrial Systems (Wuxi) Co., Ltd. ��Wuxi, China Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn �LS-VINA Industrial Systems Co., Ltd. ��Hanoi, Vietnam Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com �LS-VINA Industrial Systems Co., Ltd. ��Hochiminh , Vietnam Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com �LS Industrial Systems Tokyo Office ��Tokyo, Japan Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz �LS Industrial Systems Shanghai Office ��Shanghai, China Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn �LS Industrial Systems Beijing Office ��Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn �LS Industrial Systems Guangzhou Office ��Guangzhou, China Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz �LS Industrial Systems Chengdu Office ��Chengdu, China Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn �LS Industrial Systems Qingdao Office ��Qingdao, China Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn �� HEAD OFFICE LS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648 �� CHEONG-JU PLANT Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea �� Global Network Specifications in this catalog are subject to change without notice due to continuous product development and improvement. 2009. 10 Intelligent Motor Protection Relay (E) 2009. 10/(01) 2009. 10 Printed in Korea STAFF www.dienhathe.xyz www.dienhathe.vn