Three Phase Current – Calculation
Three Phase Power and Current
The power was taken by a circuit (single or three-phase) is measured in watts W (or
kW). The product of the voltage and current is the apparent power and measured in VA
(or kVA). The relationship between kVA and kW is the power factor (Pf):
kW = kVA x pf
which can also be expressed as:
kVA = kW/pf
Single phase system
this is the easiest to deal with. Given the kW and power factor, the kVA can be easily
worked out. The current is simply the kVA divided by the voltage. As an example,
consider a load consuming 23 kW of power at 230 V and a power factor of 0.86:
kVA = kW / power factor = 23/0.86 = 26.7 kVA (26700VA)
Current = VA / voltage = 26700 / 230 = 116 A
Note: you can do these equations in either VA, V, and A or kVA, kV, and KA depending
on the parameters you are dealing with. To convert from VA to kVA just divide by 1000.
Three phase system
The main difference between a three-phase system and a single-phase system is the
voltage. In a three-phase system, we have the line to line voltage (VLL) and the phase
voltage (VLN), related by:
VLL =√3 x VLN
or alternatively as:
VLN = VLL / √3
the easiest way to solve three-phase problems is to convert them to a single-phase
problem. Take a three-phase motor (with three windings, each identical) consuming a
given kW. The kW per winding (single-phase) has to be the total divided by 3. Similarly,
a transformer (with three windings, each identical) supplying a given kVA will have each
winding supplying a third of the total power. To convert a three-phase problem to a
single phase problem take the total kW (or kVA) and divide it by three.
As an example, consider a balanced three phase load consuming 36 kW at a power
factor of 0.86 and line to line voltage of 400 V (VLL) :
note: the line to neutral (phase) voltage VLN = 400/ √3 = 230 V
three phase power is 36 kW, single phase power = 36/3 = 12 kW
now simply follow the above single phase method
kVA = kW / power factor = 12 / 0.86 = 13.9 kVA (13900 VA)
Current = VA / voltage = 13900 / 230 = 60 A
Easy enough. To find the power given current, multiply by the voltage and then the
power factor to convert to W. For a three-phase system multiply by three to get the
total power.
Unbalanced Three Phase Systems
The above deals with balanced three-phase systems. That is the current in each phase is
the same and each phase delivers or consumes the same amount of power. This is
typical of power transmission systems, electrical motors, and similar types of equipment.
Often where single-phase loads are involved, residential and commercial premises, for
example, the system can be unbalanced with each phase have a different current and
delivering or consuming a differing amount of power.
Balanced Voltages
Luckily in practice voltages tend to be fixed or very by only small amounts. In this
situation and with a little thought it is possible to extend the above type of calculation to
unbalanced current three-phase systems. The key to doing this is that the sum of power
in each phase is equal to the total power of the system.
For example, take a 400 V (VLL) three phase system with the following loads: phase 1 = 80
A, phase 2 = 70 A, phase 3 = 82 A
the line to neutral (phase) voltage VLN = 400/√3 = 230 V
phase 1 apparent power = 80 x 230 = 18,400 VA = 18.4 kVA
phase 2 apparent power = 70 x 230 = 16,100 VA = 16.1 kVA
phase 3 apparent power = 82 x 230 = 18,860 VA = 18.86 kVA
Total three phase power = 18.4 + 16.1 + 18.86 = 53.36 kVA
Similarly given the power in each phase you could easily find the phase currents. If you
also know the power factor you can convert between kVA and kW as shown earlier.
Unbalanced Voltages
If the voltages become unbalanced or there are other considerations (i.e. unbalanced
phase shift), then it is necessary to revert to a more traditional network analysis. System
voltages and currents can be found by drawing out the circuit in full detail and using
Kirchhoff’s laws and other network theorems.
How to know the right generator for you
if you have already calculated the total actual load (Total three-phase power), now you
can use the following formulas to choose the right generator for you.
first of all, there are two terms of diesel generators powers, one is the standby power
and the second is the prime power
Prime Power of the generator set
the prime power of the generator set is the 100% capacity of the generator, and this
is where a variable load and unlimited hour usage are applied with an average load
factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload
is permitted for 1hour in every 12-hour operation.
Stand-by Power of the generator set
the stand-by power of the generator set is the 110% capacity of the generator, and this
is where a variable load limited to an annual usage of up to 500 hours is applied, with
300 hours of which may be continuous running. Noting that no overload is permitted.
Conclusion:
so if you are choosing the right generator for your calculated total load, you should
multiply the total load by 1.25 to get the prime power rate. by doing that you are now
running at 80% of the prime power rate.
note: it is a good practice to add extra virtual load to your total load like 10% for future
added equipment. and you should not go below 40% of prime power rates at all.
https://powergenerators-ksa.com/en/three-phase-current-calculation/

More Related Content

Similar to power calculation .docx

ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation
Chandrabhan Sharma
 

Similar to power calculation .docx (20)

Power system calculations
Power system calculationsPower system calculations
Power system calculations
 
H06 elo f
H06 elo fH06 elo f
H06 elo f
 
1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf
 
per_unit_system.pptx
per_unit_system.pptxper_unit_system.pptx
per_unit_system.pptx
 
Lecture 02.pptx
Lecture 02.pptxLecture 02.pptx
Lecture 02.pptx
 
Symmetrical Fault Analysis
Symmetrical Fault AnalysisSymmetrical Fault Analysis
Symmetrical Fault Analysis
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdf
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdf
 
Electrical Troubleshooting
Electrical TroubleshootingElectrical Troubleshooting
Electrical Troubleshooting
 
685 calavia
685 calavia685 calavia
685 calavia
 
Three phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generatorsThree phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generators
 
Assignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemAssignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power system
 
Assignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power systemAssignment 1 170901 interconnected power system
Assignment 1 170901 interconnected power system
 
Per unit system
Per unit systemPer unit system
Per unit system
 
Electromagnetism and phasors for steady state studies
Electromagnetism and phasors for steady state studiesElectromagnetism and phasors for steady state studies
Electromagnetism and phasors for steady state studies
 
ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation
 
Improvement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorImprovement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using Capacitor
 
CHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.pptCHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.ppt
 
ALL DAY EFFICIENCY
ALL DAY EFFICIENCYALL DAY EFFICIENCY
ALL DAY EFFICIENCY
 
Lecture 8
Lecture 8Lecture 8
Lecture 8
 

Recently uploaded

"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
Query optimization and processing for advanced database systems
Query optimization and processing for advanced database systemsQuery optimization and processing for advanced database systems
Query optimization and processing for advanced database systems
meharikiros2
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
hublikarsn
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
 

Recently uploaded (20)

"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
 
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using PipesLinux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptx
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Query optimization and processing for advanced database systems
Query optimization and processing for advanced database systemsQuery optimization and processing for advanced database systems
Query optimization and processing for advanced database systems
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptx
 
Post office management system project ..pdf
Post office management system project ..pdfPost office management system project ..pdf
Post office management system project ..pdf
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Memory Interfacing of 8086 with DMA 8257
Memory Interfacing of 8086 with DMA 8257Memory Interfacing of 8086 with DMA 8257
Memory Interfacing of 8086 with DMA 8257
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth Reinforcement
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 

power calculation .docx

  • 1. Three Phase Current – Calculation Three Phase Power and Current The power was taken by a circuit (single or three-phase) is measured in watts W (or kW). The product of the voltage and current is the apparent power and measured in VA (or kVA). The relationship between kVA and kW is the power factor (Pf): kW = kVA x pf which can also be expressed as: kVA = kW/pf Single phase system this is the easiest to deal with. Given the kW and power factor, the kVA can be easily worked out. The current is simply the kVA divided by the voltage. As an example, consider a load consuming 23 kW of power at 230 V and a power factor of 0.86: kVA = kW / power factor = 23/0.86 = 26.7 kVA (26700VA) Current = VA / voltage = 26700 / 230 = 116 A Note: you can do these equations in either VA, V, and A or kVA, kV, and KA depending on the parameters you are dealing with. To convert from VA to kVA just divide by 1000. Three phase system
  • 2. The main difference between a three-phase system and a single-phase system is the voltage. In a three-phase system, we have the line to line voltage (VLL) and the phase voltage (VLN), related by: VLL =√3 x VLN or alternatively as: VLN = VLL / √3 the easiest way to solve three-phase problems is to convert them to a single-phase problem. Take a three-phase motor (with three windings, each identical) consuming a given kW. The kW per winding (single-phase) has to be the total divided by 3. Similarly, a transformer (with three windings, each identical) supplying a given kVA will have each winding supplying a third of the total power. To convert a three-phase problem to a single phase problem take the total kW (or kVA) and divide it by three. As an example, consider a balanced three phase load consuming 36 kW at a power factor of 0.86 and line to line voltage of 400 V (VLL) : note: the line to neutral (phase) voltage VLN = 400/ √3 = 230 V three phase power is 36 kW, single phase power = 36/3 = 12 kW now simply follow the above single phase method kVA = kW / power factor = 12 / 0.86 = 13.9 kVA (13900 VA) Current = VA / voltage = 13900 / 230 = 60 A Easy enough. To find the power given current, multiply by the voltage and then the power factor to convert to W. For a three-phase system multiply by three to get the total power. Unbalanced Three Phase Systems The above deals with balanced three-phase systems. That is the current in each phase is the same and each phase delivers or consumes the same amount of power. This is typical of power transmission systems, electrical motors, and similar types of equipment. Often where single-phase loads are involved, residential and commercial premises, for example, the system can be unbalanced with each phase have a different current and delivering or consuming a differing amount of power.
  • 3. Balanced Voltages Luckily in practice voltages tend to be fixed or very by only small amounts. In this situation and with a little thought it is possible to extend the above type of calculation to unbalanced current three-phase systems. The key to doing this is that the sum of power in each phase is equal to the total power of the system. For example, take a 400 V (VLL) three phase system with the following loads: phase 1 = 80 A, phase 2 = 70 A, phase 3 = 82 A the line to neutral (phase) voltage VLN = 400/√3 = 230 V phase 1 apparent power = 80 x 230 = 18,400 VA = 18.4 kVA phase 2 apparent power = 70 x 230 = 16,100 VA = 16.1 kVA phase 3 apparent power = 82 x 230 = 18,860 VA = 18.86 kVA Total three phase power = 18.4 + 16.1 + 18.86 = 53.36 kVA Similarly given the power in each phase you could easily find the phase currents. If you also know the power factor you can convert between kVA and kW as shown earlier. Unbalanced Voltages If the voltages become unbalanced or there are other considerations (i.e. unbalanced phase shift), then it is necessary to revert to a more traditional network analysis. System voltages and currents can be found by drawing out the circuit in full detail and using Kirchhoff’s laws and other network theorems. How to know the right generator for you if you have already calculated the total actual load (Total three-phase power), now you can use the following formulas to choose the right generator for you. first of all, there are two terms of diesel generators powers, one is the standby power and the second is the prime power Prime Power of the generator set the prime power of the generator set is the 100% capacity of the generator, and this is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1hour in every 12-hour operation. Stand-by Power of the generator set
  • 4. the stand-by power of the generator set is the 110% capacity of the generator, and this is where a variable load limited to an annual usage of up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted. Conclusion: so if you are choosing the right generator for your calculated total load, you should multiply the total load by 1.25 to get the prime power rate. by doing that you are now running at 80% of the prime power rate. note: it is a good practice to add extra virtual load to your total load like 10% for future added equipment. and you should not go below 40% of prime power rates at all. https://powergenerators-ksa.com/en/three-phase-current-calculation/