EN English UME-0304-200115
WPM 1.04 Installation and Operating Instructions
Energy Driven Switch
II
Revision History
Rev.
Doc.
Date Revisor Page Description
1 20/01/2015 RC All Initial Draft
1
Device Description
Version C Version S
Line Phase connection terminal
Null Neutral connection terminal
Controlled Line No and Lo Lines controlled by internal relay
Ls External switch connection
Push Button Service button: 1 click to add the device to the Z-Wave network, 3 clicks to
remove it, 6 clicks to reset to factory settings
Power Supply Transformer Connection terminals for external Current Transformer
Technical Specifications
Power Supply 230 VAC±10% 50/60 Hz
Maximum Load on Relay 3000 VA – 250VAC – 12.5 A
Work Temperature -10 +40 °C
Radio Protocol Z-Wave 868,4 MHz
Radio Range
Up to 100 m outdoor
Up to 40 m indoor
Dimensions (HxWxD) 37x37x17 mm
Consumption
< 260 mW in standby
< 480 mW with working load
Electrical IP Rating IP 20
Actuator element Relay
Conformity CE, RoHS
Push Button
Current
transformer
Controlled Line
Line
Null
L
N
No
Lo
Energy Driven Switch
Version C
2
1
WiDom
Push Button
Line
Controlled Line
Null
Line Signal
L
N Lo
No L
Ls
Energy Driven Switch
Version S
WiDom
2
Meter Specifications
Parameters Voltage RMS, Current RMS, Active Power, Power Factor, Energy
Meter Range
Voltage RMS: 250 V
Current RMS:
 45 A – vers. C
 12 A – vers. S
Active Power:
 ± 11250 W – vers. C
 ± 3000 W – vers. S
Power Factor: ±1.00
Energy: 2.000.000 kWh
Resolution
Voltage RMS: 0.1 V
Current RMS: 0.01 A
Active Power: 0.01 W
Power Factor: 0.01
Energy: 0.001 kWh
Maximum Error
(within the dynamic range)
Voltage (dynamic range 20:1): ±0.95%
Current (dynamic range 1000:1):
 ±0.6% - vers. S
 ±2.9% - vers. C
Active Power (dynamic range 4000:1):
 ±1.6% - vers. S
 PF=1: ±4% - vers. C
 PF=0.8: ±5.5% - vers. C
3
Introduction
WiDom Energy Driven Switch is a device designed to monitor all parameters, usage, faults and overloads
of your electrical system. Unlike an ordinary energy meter, WiDom Energy Driven Switch can be installed to
monitor an entire electricity network or a section of the latter.
 Active Energy-saving management
Automatically connects and disconnects a specific load if the established threshold limit is exceeded, or
supplies the required power, momentarily excluding non-priority loads.
 Management and prevention of electrical faults
Identifies malfunctions based on irregular consumptions and to the maximum time of activity.
 Electrical overload management
Notifies or disconnects non-priority loads in the eventuality of system overloads.
External switch1
: External button or switch
Events: Actions performed on the external switch: click and hold.
Click: If the external switch is a button (when pressed it automatically returns to the initial position), a
click corresponds to pushing and releasing the button. If the external switch is a regular switch (when
pressed it does not return to the initial position), a single click corresponds to a single flip of the switch.
1 Valid only for version S.
4
Installation
INFO: WiDom Energy Driven Switch is designed for installation in flush mounting boxes, close to the
loads to be controlled, at the point of entry of the electric network sections to be monitored.
WARNING: WiDom Energy Driven Switch must be installed by electricians qualified to operate on
electrical systems in compliance with safety requirements set out by current regulations.
DANGER: WiDom Energy Driven Switch must be connected to 230V AC voltage mains supplies; please
ensure that the general switch is in the OFF position prior to carrying out any operation.
DANGER: Any operation requiring the use of service button (B) must only be carried out during the
installation phase and must be considered as a service procedure to be performed by qualified
personnel. This operation must be carried out by adopting all necessary precautions to operate on areas with
a single level of isolation.
WARNING: Do not connect loads exceeding the maximum power load permitted by the relay contacts.
WARNING: All connections must be performed according to the electrical diagrams provided.
WARNING: WiDom Energy Driven Switch must be installed in norm-compliant systems suitably
protected from overloads and short circuits.
WiDom Driven Switch Activation
1) Ensure that the main power switch is set in the OFF position
2) Connect the device following the diagrams provided
3) Shut the electrical box containing the device
4) Turn the main power switch back on
5) Include the device into the Z-Wave network
5
Electrical Connections
The device must be supplied by phase and neutral. Connections must be made according to one of the
diagrams below.
In devices requiring a current transformer, the latter must be connected by attaching the black wire to
terminal 1 and the white wire to terminal 2. The current transformer must be clamped on the phase wire
leading to the load and adjusted to have the arrow pointing towards the load to be monitored.
Local load control
In this mode the load is controlled directly by the internal relay. The opening and closing of the relay contacts
are synchronized to take place, respectively, when a zero current or voltage is reached.
Versione C
LINE IN
L
N
L
N
No
Lo
Energy Driven Switch
Version C
2
1
WiDom
LINE OUT/LOAD
Versione S
Push Button
L
N
LINE IN
L
N
L
N Lo
No L
Ls
Energy Driven Switch
Version S
WiDom
LINE OUT/LOAD
6
Remote load control
In this mode the device has no locally connected load, and the measures of current and power are based on
all devices connected to the “LINE OUT” section of the system. The devices connected to the “LINE OUT” can
be controlled individually based on the configured energy events.
Versione C
L
N
LINE IN
LINE OUT/LOAD
L
N
L
N
No
Lo
Energy Driven Switch
Version C
2
1
WiDom
Versione S
L
N
LINE IN
L
N
L
N Lo
No L
Ls
Energy Driven Switch
Version S
WiDom
LINE OUT/LOAD
7
Load control by external contactor
This mode, available only for version C and the use of an external contactor, allows the management of loads
up to 45A. The device supports two types of external contactors:
 Normally open (in the absence of signal from the relay the “LINE OUT” is disconnected)
 Normally close (in the absence of signal from the relay the “LINE OUT” is connected)
The load control mode and type of external contactor can be set up with parameter No. 63.
Versione C
L
N
LINE IN
L
N
L
N
No
Lo
Energy Driven Switch
Version C
2
1
WiDom
LINE OUT/LOAD
8
Reset to factory settings
The device can be reset to the original factory settings by means of one of the following methods:
Method 1: Remove the device from the Z-Wave network;
Method 2: Six consecutive clicks on (B) button or on the external switch within 1 minute from system start-up;
Method 3: Set the parameter 61 to 0 – FACTORY RESET (see Configuration Parameters).
INFO: Please use methods 2 and 3 only in the event that the primary controller is missing or otherwise
inoperable.
INFO: If the device is reset when included in a network, the latter will notify its removal (Device Reset
Locally Notification). Conversely, if WiDom Energy Driven Switch receives a notification of removal of
another device from the network, this device will be removed from its associations.
Including the device into an existing Z-Wave network
WiDom Energy Driven Switch can be included into any Z-Wave network and operate with Z-Wave devices
from any other manufacturer. WiDom Energy Driven Switch, used as a constantly powered node, will act as
a signal repeater to increase the network reliability.
The device supports both the Network Wide Inclusion (which offers the opportunity of inclusion into a network
even if the device is not directly connected to the controller) and the Normal Inclusion mechanisms.
If the device is not included into a Z-Wave network, a single click on the (B) button or on the external switch
will launch the process of traditional inclusion. If the device inclusion procedure does not start within 2 seconds,
the Network Wide Inclusion network will be launched lasting a variable amount of time between 15-30 seconds.
INFO: Through the inclusion procedure, activated with a single click on the external switch2, the system
determines the type of external switch (see parameter No. 62).
Excluding the device from a Z-Wave network
Only a controller can remove a device from the network. WiDom Energy Driven Switch is compatible with all
Z-Wave certified controllers. After the exclusion procedure has been activated by the controller, the device can
be removed, putting it in Exclusion Mode by three consecutive clicks on the (B) button or on the external switch,
when available.
Associations
WiDom Energy Driven Switch can control other devices such as relays or dimmers. WiDom Energy Driven
Switch supports three association groups, each of which supports the association of up to 8 devices:
Group ID Group Name Profile Commands received Description
1 LifeLine Group General:
LifeLine
Basic Report, Device
Reset Locally
Notification, Meter
Report, Multilevel
Sensor: Power Report
Devices to receive
notifications on: status
changes; energy and
power levels; device local
reset
2 Up Power Level
Group
Sensor:
Power
Basic Set Devices controlled by the
Up Power event
3 Down Power Level
Group
Sensor:
Power
Basic Set Devices controlled by the
Down Power event
2 Applicable only to version S.
9
TIP: WiDom Energy Driven Switch can control up to 8 devices for every group. In order to prevent the
network from slowing down it is advisable to limit the associated devices to no more than 5 per group.
Controlling the device with external switch
When available, the external switch carries out the same function as the (B) button.
Controlling the device through Z-Wave network
All Z-Wave controllers can control the device by using the Basic Set command.
The behaviour of the device based on its status and the commands received from the network can also be
configured.
Switch ALL ON/OFF
By default, WiDom Energy Driven Switch accepts Switch All ON/OFF commands.
Overcurrent Protection
The device can be configured to react (opening/closing the integrated relay) to current overloads lasting over
a configurable amount of time. See parameters 30 to 32.
Zero Crossing
Relay open/close switchings always take place when a zero of current or voltage occurs. In this way, electrical
stress on the relay contacts is minimized, thus affording a longer duration.
10
Active Energy management
Energy Driven Switch is capable of implementing an active energy saving policy by managing electric loads in
order to maximize the self-consumption during the greater production period of our wind power or photovoltaic
plant, optimizing the net metering and the energy saving.
An upper and lower power threshold can be configured which, when exceeded, activates or deactivates the
two groups of loads connected to the two thresholds.
Predefined loads can be disconnected when the power consumed exceeds a specific threshold for longer than
a certain amount of time, or specific loads can be activated when the level of energy produced and not
consumed exceeds a second threshold.
WiDom Energy Driven Switch allows you to detect irregular consumption in order to prevent or identify faults
by means of specific alarms.
The product can also be used to set levels of total energy produced above which the user can be notified. This
mode allows you, for instance, to manage programmed maintenance interventions based on the actual usage
of the systems. For further details about these configurations, please refer to parameters 30 to 50.
Electric parameters reading
In addition to Power and Energy, the device also provides data for Voltage RMS, Current RMS and Power
Factor. These values, together with power and energy measurements, can be obtained through the certified
controllers that support the Meter Command Class version 3. These parameters can also be read by means
of parameters 51 to 55.
Firmware Update
The system supports over-the-air firmware updates that do not require the device to be removed from its
location. The firmware update can be activated from all certified controllers supporting version 2 of the
Firmware Update function. The firmware update procedure must be enabled on the device with four
consecutive clicks. The activation lasts 10 seconds, after which the firmware update procedure will need to be
re-enabled if it has not been activated in the first instance.
WARNING: The system will be rebooted at the end of the firmware update procedure. If a load is
connected to the relay output, it will be disconnected and reconnected, depending on the settings
configured for system rebooting. It is advisable to carry out the firmware update procedure only when
necessary and following careful planning of the intervention.
11
Configurations
Device Status
Controlling the relay by means of a single click on the external switch or on the integrated button.
Parameter No. 1: Device Status (1 byte)
Configuration Initial Status Final Status
1 – TOGGLE
(Default Value)
ON OFF
OFF ON
2 – ON
ON If the initial status is OFF the system switches to ON;
conversely, it maintains its status (ON).
OFF
3 – OFF
ON If the initial status is ON the system switches to OFF;
conversely, it maintains its status (OFF).
OFF
4 – IGNORE
ON
The device maintains the initial status
OFF
Controlling the device through Z-Wave network
The final status achieved by the device when it receives a Basic Set command through the Z-Wave network.
Parameter No. 20 (0x14): Device status upon receipt of a Basic Set command (1 byte)
Configuration Command received Final Status
1 – AS RECEIVED
(Default Value)
ON ON
OFF OFF
2 – IGNORE IF ON
ON Maintains the initial status
OFF OFF
3 – IGNORE IF OFF
ON ON
OFF Maintains the initial status
4 – IGNORE
ON
Maintains the initial status
OFF
12
Overcurrent detector
The overcurrent detector determines when the current level remains over a threshold level (OverCurrent Level)
for longer than a certain amount of time (OverCurrent Time). When this happens, an Overcurrent Event occurs
and it can be associated, for instance, to opening of the relay contacts.
Parameter No. 30 (0x1E): Overcurrent level (2 byte) – Sets the current level above which the time spent
above that level is measured.
Version C: From 0 to 45003 hundredths of Amperes – Default Value: 4500 Hundredths of Amperes
Version S: From 0 to 1250 hundredths of Amperes – Default Value: 1250 Hundredths of Amperes
Parameter No. 31 (0x1F): Overcurrent time (2 byte) – Sets the time beyond which, in the case of overcurrent
at a level higher than that established in parameter 30, an OverCurrent event occurs.
From 0 to 10800 Seconds (3 Hours) – Default Value: 10 Seconds
Parameter No. 32 (0x20): Next State (1 byte) – Defines the next state of the device if an overcurrent event
has occurred.
Configuration Next Status
0 – IGNORE
(Default Value)
The device maintains the initial status.
1 – ON
If the initial status is OFF the system switches to ON; conversely, it maintains
its status (ON).
2 – OFF
If the initial status is ON the system switches to OFF: conversely, it maintains
its status (OFF).
3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON.
3 Values above 1250 can only be managed with version C using the configuration “LOAD CONTROLLED BY
EXTERNAL CONTACTOR”.
OverCurrent
Level
OverCurrent Time
Current
OverCurrent
Event
OverCurrent Event
Previous State
OverCurrent
State Next State
OverCurrent Time
13
Energy Management
Parameter No. 33 (0x21): Meter Reset (4 byte)
Provides total operating time from last meter reset. When set to 0 it resets the cumulated values of energy
and total operating time.
Configuration Final Status
0 – RESET METER Meter parameters, including total operating time, will be reset
Greater than 0 – IGNORE
(Default value)
The meter will not be reset
Parameter No. 34 (0x22): Energy flow (1 byte)
Determines whether energy events are related to energy consumed or energy produced.
Configuration Final Status
1 – Consumed
(Default value)
Events will be active for Consumed energy flows to which the positive sign will be
attributed
2 – Produced
Events will be active for Produced energy flows to which the negative sign will be
attributed
Upper Limit Power Threshold Detector
The upper limit power threshold detector determines when instantaneous power remains above the threshold
point (UP Power Level) beyond a specified duration (UP Power Time). When this happens, a UP Power Event
occurs.
The occurrence of a UP Power event can be configured in order to determine the Next State both of the device
and of the devices associated to the UP Power Group.
Parameter No. 35 (0x23): UP Power Level (2 byte) – Sets the level of instantaneous power in Watts
beyond which time of permanence above this level is calculated.
Version C: From 0 to 112504 – Default value: 11250
Version S: From 0 to 3000 – Default value: 3000
Parameter No. 36 (0x24): UP Power Time (2 byte) – Sets the time in seconds beyond which, if
instantaneous power remains at levels exceeding threshold defined by parameter 35, a UP Power event
occurs.
From 0 to 10800 seconds (3 Hours) – Default value: 10 Seconds
4 Values above 3000 may only be managed with the version C using the configuration of “LOAD
CONTROLLED BY EXTERNAL CONTACTOR”.
UP Power
Level
Power
UP Power
Event
UP Power
Associated
UP Power Time
UP Power Time
Previous State
UP Power
State
Next State
Up Power Event
Previous State Next State
14
Parameter No. 37 (0x25): UP Power State (1 byte) – Defines the next status of the device in the case of a
UP Power event occurring.
Configuration Next Status
0 – IGNORE
(Default Value)
The device maintains the initial status.
1 – ON
If the initial status is OFF the system switches to ON; conversely, it maintains
its status (ON).
2 – OFF
If the initial status is ON the system switches to OFF: conversely, it maintains
its status (OFF).
3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON.
Parameter No. 38 (0x26): UP Power Associated (1 byte) – Defines the status of associated devices in the
presence of a UP Power event.
From: 1 to 99 for dimming purpose – 0 (OFF) and -1(ON) for switching ON/OFF.
Default: 0 – OFF
15
Lower Limit Power Threshold Detector
The lower limit power threshold detector determines when instantaneous power remains below the threshold
point (DOWN Power Limit) beyond a specified duration (DOWN Power Time). When this happens, a DOWN
Power Event occurs.
The occurrence of a DOWN Power event can be configured in order to determine the next state both of the
device and of the devices associated to the DOWN Power Group.
Parameter No. 39 (0x27): DOWN Power Level (2 byte) – Sets the level of instantaneous power beyond
which the time of permanence below this level is calculated.
From 0 to 11250 Watt – Default value: 0 W
Parameter No. 40 (0x28): DOWN Power Time (2 byte) – Sets the time beyond which, if instantaneous
power remains at levels below threshold defined by parameter 39, a DOWN Power event occurs.
From 0 to 10800 Seconds (3 Hours) – Default value: 10 Seconds
Parameter No. 41 (0x29): DOWN Power State (1 byte) – Defines the next state of the device in the case of
a DOWN Power event occurring.
Configuration Next Status
0 – IGNORE
(Default Value)
The device maintains the initial status.
1 – ON
If the initial status is OFF the system switches to ON; conversely, it maintains
its status (ON).
2 – OFF
If the initial status is ON the system switches to OFF: conversely, it maintains
its status (OFF).
3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON.
Parameter No. 42 (0x2A): DOWN Power Associated (1 byte) – Defines the status of associated devices in
the presence of a DOWN Power event.
From: 1 to 99 for dimming purpose – 0 (OFF) and -1(ON) for switching ON/OFF.
Default: 0 – OFF
DOWN Power
Level
Power
DOWN Power
Event
DOWN Power
Associated
Power
DOWN Power Time
DOWN Power Time
Previous State
DOWN Power
State
Next State
Down Power Event
Previous State Next State
16
Detection of exceeded Energy Limits
The detection of exceeded energy limits determines when total accumulated energy exceeds a specific
threshold (Limit Energy). When this happens, a Limit Energy Event occurs.
The occurrence of a Limit Energy event can be configured in order to determine the Next State of the device.
Parameter No. 43 (0x2B): Energy Level (4 byte) – Sets the energy level that once exceeded an Energy
Limit event occurs.
From 0 to 2.000.000 KWh – Default value: 2.000.000 KWh
Parameter No. 44 (0x2C): Energy Limit State (1 byte) – Defines the next state of the device in the case of
an Energy Limit event occurring.
Configuration Next Status
0 – IGNORE
(Default Value)
The device maintains the initial status.
1 – ON
If the initial status is OFF the system switches to ON; conversely, it maintains
its status (ON).
2 – OFF
If the initial status is ON the system switches to OFF: conversely, it maintains
its status (OFF).
3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON.
Limit Energy
Level
Energy
Limit Energy
Event Limit Energy Event
Previous State
Device Status Next State
17
Automatic meter notifications
The system can send automatic notifications listing the values obtained for Power, Energy, Voltage, Current
and Power Factor. These reports may be sent following a specific event (over current, voltage out of limit, etc.);
subsequent to a variation of one of the parameters beyond a given threshold; following an excessively long
time since the sending of the previous report. The table below summarizes all instances covered by automatic
notifications.
Event Reports sent Configuration parameters
affected
Percentage variation of
instantaneous power
3 Instantaneous Power Reports at a
minimum interval of 3 seconds
1 Voltage Report
1 Current Report
1 Power Factor Report
45
Exceeding of Upper/Lower
Power limit
1 instantaneous Power Report
1 instantaneous Power Report for each
remotely controlled device at a minimum
interval of 3 seconds apart
Automatic
Exceeding of overcurrent
limits
A series of current reports throughout the
duration of the event at a minimum interval
of 9 seconds
Automatic
Voltage out of permitted
limits
A series of current reports throughout the
duration of the event at a minimum interval
of 12 seconds
48, 49
Maximum time from the last
instantaneous power report
1 Instantaneous Power Report at a
minimum interval of 3 seconds
1 Voltage Report
1 Current Report
1 Power Factor Report
46
Variation of total energy 1 Total Energy Report 47
The maximum frequency for all reports, including those relating to change of state of the device, never exceeds
1 report every 3 seconds calculated over a 30-second period.
Parameter No. 45 (0x2D): Variation Instantaneous Power (1 byte) – Defines the percentage variation of
instantaneous power determining the sending of the report.
From: 1 (1%) to 100 (100%) Default value: 10 – 10%
Parameter No. 46 (0x2E): Report Time Frequency (1 byte) – Defines the maximum time in minutes since
the previous report beyond which an Instantaneous Power Report will still be sent.
From: 1 to 100 minutes. Default value: 10 minutes
18
Parameter No. 47 (0x2F): Variation Total Energy (1 byte) – Defines the increase of total energy required
to generate a report listing the level of total energy to the devices associated to the Energy Notification
Group.
Configuration Energy variation generating the issuing of a report
0 – IGNORE No report provided
1 1 thousandth of KWh
2 1 hundredth of KWh
3
(Default value)
1 tenth of KWh
4 1 KWh
Parameter No. 48 (0x30): Nominal Voltage (2 byte) – Defines the nominal voltage value in tenths of volts.
Together with parameter No. 49 this is used by the automatic notification system to send reports on
variations of voltage.
Default value: 2300
From: 1100 to 2500
Parameter No. 49 (0x31): Fall in maximum voltage (1 byte) – Defines, as a percentage, the nominal value
for permitted fall in maximum voltage.
From: 1 (1%) to 100 (100%) Default value: 10 – 10%
Parameter No. 50 (0x32): Electric parameters subjected to automatic notification (1 byte) – Defines
which electric parameters, other than power, will be subjected to automatic notification.
The value to be set for this parameter must be calculated as the sum of values associated to the individual
electric parameter indicated in the table.
Scale Value
Power 0
Energy 2
Voltage 4
Current 8
Power factor 16
Multilevel Sensor: Power Report 32
To send report only for Power please set the value to 0.
To send report only for Power and Energy please set the value to 2 (0+2).
To send report for Power, Energy, Voltage, Current, Power Factor please set the value to 30 (0+2+4+8+16).
By default the report are sent for (Power, Energy, Voltage, Current, Power Factor) 0+2+4+8+1630
Default value: 30
Permitted values: From 0 to 62
19
Parameters for monitoring of the electrical network and system calibration.
In order to ensure maximum precision, each device is individually calibrated and the calibration values are
permanently set on the system.
Values relating to Voltage, Current, Power Factor and Energy may also be read by consulting parameters 51
to 55, all of which are read-only parameters, which ignore all settings and return the value of the specific
parameter at the time of the reading.
Parameter No. 51 (0x33): Voltage RMS value (2 byte)
Reading of this parameter returns the value of voltage RMS at the time of the reading expressed in tenths of
Volts.
Parameter No. 52 (0x34): Current RMS value (2 byte)
Returns the value of current RMS expressed in hundredths of Amperes.
Parameter No. 53 (0x35): Power Factor (1 byte)
Returns the value of power factor as a percentage.
Parameter No. 54 (0x36): Total energy consumed (4 byte)
Returns the value of total energy consumed expressed in Wh (thousandths of KWh).
Parameter No. 55 (0x37): Total energy produced (4 byte)
Returns the value of total energy produced expressed in Wh (thousandths of KWh).
20
Other configuration parameters
Parameter No. 60 (0x3C): Start-up status (1 byte) – Defines the status of the device following a restart.
Configuration Device reaction
1 – ON Device on
2 – OFF Device off
3 – PREVIOUS STATUS
(Default value)
Status prior to restart
Parameter No. 61 (0x3D): Configuration reset (1 byte) – Defines which parameters should be reset to
default values.
Configuration Device reaction
0 – FACTORY RESET The device is reset to the original factory settings
1 – ASSOCIATIONS RESET All associations and only the associations are reset
2 – CONFIGURATIONS RESET
The associations are maintained while all other configuration parameters
are reset to the original factory settings, except for the specific configuration.
4 – IGNORE
(Default value)
No action is performed
Parameter No. 62 (0x3E): Type of external switch (1 byte) – Defines the type of external switch connected
to the device.
Configuration Device reaction
0 – IGNORE The external switch is not connected or not present.
1 – BUTTON The external switch is a normally open button
2 – SWITCH The external switch is a traditional switch
4 – AUTOMATIC
RECOGNITION
(Default value)
After the first single click on the external switch, the system automatically
determines the type of external switch used and sets the parameter with the
new value accordingly.
Parameter No. 63 (0x3F): Load control (1 byte) – Defines the load control mode.
Configuration Device reaction
1 – DIRECT CONTROL
(Default value)
The external load is controlled directly by the relay. Reference diagram
local load control.
2 – CONTROL BY MEANS OF A
CONTACTOR WITH NORMALLY
OPEN COMMAND
The external load is controlled by a contactor that in a resting state has
open contacts (load control by means of external contactor).
3 – CONTROL BY MEANS OF A
CONTACTOR WITH NORMALLY
CLOSED COMMAND
The external load is controlled by a contactor that in a resting state has
closed contacts (load control by means of external contactor).
4 – AS AN EXTERNAL
INDICATOR
The relay is only used to control the ignition of an external warning light,
as, for example, in the case of notification of excess loads and surges
(remote load control).
21
Disposing the devices
This product bears the selective sorting symbol for waste electrical and electronic equipment
(WEEE).
This means that this product must be handled pursuant to European Directive 2002/96/EC in
order to be recycled or dismantled to minimize its impact on the environment.
For further information, please contact your local or regional authorities.
Electronic products not included in the selective sorting process are potentially dangerous for
the environment and human health due to the presence of hazardous substances.
Compliance with directives
WiDom devices are built in compliance with directives LVD 2006/95/EC, EMC 2004/108/CE and R&TTE
Widom shall not be held responsible for any damage caused by these devices if they are used in a manner
that is not compliant with the instructions in this manual. WiDom reserves the right to make any changes to
the product that it considers necessary or useful without jeopardising its primary features.
Warranty
This warranty is provided by WiDom srl (hereinafter “WiDom”) based in Quartu S.Elena 09045 (CA), Italy (VAT number
03452490927).
WiDom warrants to the original purchaser (hereinafter “Customer”) that the device sold under this agreement (hereinafter
“Device”) is free from defects in parts and workmanship under normal use for 12 months from date of purchase (“Warranty
Period”).
The original purchase invoice or sales receipt, showing the date of purchase is the proof of date of purchase by the Customer.
If a Device, sold by WiDom to the Customer, has manufacturing defects or in any case of alleged lack of conformity, the
Customer shall send within thirty (30) days from the day in which he discovers such defects, a claim form by using the web
site (www.widom.it) informing WiDom on the full name of the Customer, the nature of the defects and the date in which the
Devices has been purchased.
Warranty Claims received after the expiration of the Warranty Period shall not be considered valid.
Once WiDom, receives the Warranty Claim, it shall inform the Customer by e-mail or letter, if the Warranty is applicable and
the address where the Device shall be sent in order to verify the defects (if any). Customer must prepay shipping and
transportation charges as indicated by WiDom. The Device shall be sent by the Customer to WiDom at its own costs and
expenses, by express courier or hand delivered, and with the original packaging, the supplied accessories (if any) and
documents proving date of purchase. WiDom shall then inform the Customer about the defects and on its repair or replacement
(where applicable). Should WiDom not evidence defects on the Device, the Device shall be returned to the Customer.
Should WiDom notices the defects, and this warranty is applicable, it will remove, at its sole discretion, any defect, free of
charge, by repairing any defective components of the Device with new or regenerated components or by replacing the Device.
The Warranty Period of the replaced or repaired Device shall not be extended.
WiDom will ship the repaired or a replaced Device to Customer freight prepaid.
WiDom will not be liable for damages to property caused by faulty device. WiDom will not be liable for indirect, incidental,
special, consequential or punitive damages, or for any damage, including, inter alia, loss of profits, savings, data, loss of
benefits, claims by third parties and any property damage or personal injuries arising from or related to the use of the Device.
If the Device cannot be replaced with another of the same type (e.g. the Device is no longer in production or no longer available
for selling in the Customer’s country), it may be replaced with a different one having similar technical specifications to the
faulty one. Such replacement shall be considered as a total fulfilment of WiDom’s obligations.
Warranty exclusion
- defects caused by normal wear of parts or especially subject to wear, such as parts that require periodic replacement during
the normal operation of the system (e.g. Batteries);
22
- splits, cracks, scratches, dents, scratched or discolored surfaces and parts, breakage of plastic parts and in general of any
other cosmetic damage;
- damages resulting from use of the system other than that provided, including but not limited to the failure to follow
instructions contained in the operating manual;
- damages caused by accident, abuse, misuse, dirt, viruses, liquid contact, fire, earthquake, improper or inadequate
maintenance or calibration, negligence or other external causes;
- environmental damage and / or defects caused by smoke, dust, dirt, soot, or other external influences;
- damages caused by modifications and alterations in the functionality or features without the written permission of WiDom;
- damages resulting from transportation or inadequate packaging when returning the product to a WiDom or to an authorize
service center;
- defects caused by force majeure events such as lightning, floods, fires, incorrect voltage, improper ventilation;
- damages caused by malfunctioning software, computer virus attack, or by failure to update the software as recommended
by WiDom;
- damages resulting from surges in the power and/or telecommunication network, improper connection to the grid in a manner
inconsistent with the operating manual, or from connecting other devices not recommended by WiDom;
- damages caused by operating or storing the device in extremely adverse conditions, i.e. high humidity, dust, too low (freezing)
or too high ambient temperature;
- products whose serial number has been removed, damaged or rendered illegible;
- expiration of the Warranty Period.
If a defect is not covered by the Warranty, WiDom will inform the Customer about the extra expenses for the repair or
replacement.
This warranty may be subject to changes. Please check at www.widom.it the newest warranty claim procedure.
This guarantee shall not exclude, limit or suspend the Customer rights when the provided product is inconsistent with the
purchase agreement.
© All rights reserved. WiDom is a trademark of WiDom srl. All other brand names, product names, or trademarks belong to
their respective owners. WiDom reserves the right to change product features and specifications at any time without notice,
and is not responsible for typographical or graphical errors that may appear in this document.
Please check at www.widom.it the newest version of this document.
Printed in Italy on low-impact recyclable paper.

More Related Content

What's hot

Widom Z-WAve On/off relay switch 2.5KW manual English
Widom Z-WAve On/off relay switch 2.5KW  manual EnglishWidom Z-WAve On/off relay switch 2.5KW  manual English
Widom Z-WAve On/off relay switch 2.5KW manual EnglishDomotica daVinci
 
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manualWall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manualDomotica daVinci
 
Pse02 - zipato siren user manual v1.2 English
Pse02 - zipato siren user manual v1.2 EnglishPse02 - zipato siren user manual v1.2 English
Pse02 - zipato siren user manual v1.2 EnglishDomotica daVinci
 
Universal Dimmer 250W Z-Wave+ Fibaro Manual
Universal Dimmer 250W  Z-Wave+ Fibaro ManualUniversal Dimmer 250W  Z-Wave+ Fibaro Manual
Universal Dimmer 250W Z-Wave+ Fibaro ManualDomotica daVinci
 
Vision ZG8101 Wireless Garage Door Detector - Installation Manual
Vision ZG8101 Wireless Garage Door Detector - Installation ManualVision ZG8101 Wireless Garage Door Detector - Installation Manual
Vision ZG8101 Wireless Garage Door Detector - Installation ManualDomotica daVinci
 
Manual aeon labs heavy duty smart switch gen5
Manual   aeon labs heavy duty smart switch gen5Manual   aeon labs heavy duty smart switch gen5
Manual aeon labs heavy duty smart switch gen5Domotica daVinci
 
manual vision siren VIS_ZM1601
manual vision siren VIS_ZM1601manual vision siren VIS_ZM1601
manual vision siren VIS_ZM1601Domotica daVinci
 
Manual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - PhilioManual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - PhilioDomotica daVinci
 
Fibaro RGBW controller manual
Fibaro RGBW controller manual Fibaro RGBW controller manual
Fibaro RGBW controller manual Domotica daVinci
 
Manual solar siren - popp_005107
Manual solar siren - popp_005107Manual solar siren - popp_005107
Manual solar siren - popp_005107Domotica daVinci
 
ES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - Fibaro
ES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - FibaroES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - Fibaro
ES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - FibaroDomotica daVinci
 
Fibaro Motion Multisensor Manual
Fibaro Motion Multisensor ManualFibaro Motion Multisensor Manual
Fibaro Motion Multisensor ManualDomotica daVinci
 
Water meter secure start guide
Water meter secure start guideWater meter secure start guide
Water meter secure start guideDomotica daVinci
 
Door lock without handle vision operational manual
Door lock without handle vision operational manualDoor lock without handle vision operational manual
Door lock without handle vision operational manualDomotica daVinci
 

What's hot (20)

Widom Z-WAve On/off relay switch 2.5KW manual English
Widom Z-WAve On/off relay switch 2.5KW  manual EnglishWidom Z-WAve On/off relay switch 2.5KW  manual English
Widom Z-WAve On/off relay switch 2.5KW manual English
 
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manualWall Controller	4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
Wall Controller 4 Buttons rechargeable Remote Z-Wave Plus - Hank manual
 
Pse02 - zipato siren user manual v1.2 English
Pse02 - zipato siren user manual v1.2 EnglishPse02 - zipato siren user manual v1.2 English
Pse02 - zipato siren user manual v1.2 English
 
Mco_tps314
Mco_tps314Mco_tps314
Mco_tps314
 
Mco_tps312
Mco_tps312Mco_tps312
Mco_tps312
 
Universal Dimmer 250W Z-Wave+ Fibaro Manual
Universal Dimmer 250W  Z-Wave+ Fibaro ManualUniversal Dimmer 250W  Z-Wave+ Fibaro Manual
Universal Dimmer 250W Z-Wave+ Fibaro Manual
 
Vision ZG8101 Wireless Garage Door Detector - Installation Manual
Vision ZG8101 Wireless Garage Door Detector - Installation ManualVision ZG8101 Wireless Garage Door Detector - Installation Manual
Vision ZG8101 Wireless Garage Door Detector - Installation Manual
 
Manual aeon labs heavy duty smart switch gen5
Manual   aeon labs heavy duty smart switch gen5Manual   aeon labs heavy duty smart switch gen5
Manual aeon labs heavy duty smart switch gen5
 
manual vision siren VIS_ZM1601
manual vision siren VIS_ZM1601manual vision siren VIS_ZM1601
manual vision siren VIS_ZM1601
 
Manual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - PhilioManual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - Philio
 
Fibaro RGBW controller manual
Fibaro RGBW controller manual Fibaro RGBW controller manual
Fibaro RGBW controller manual
 
FortrezZ wwa 02 Manual
FortrezZ wwa 02 ManualFortrezZ wwa 02 Manual
FortrezZ wwa 02 Manual
 
Eur stellaz manual
Eur stellaz manualEur stellaz manual
Eur stellaz manual
 
Manual solar siren - popp_005107
Manual solar siren - popp_005107Manual solar siren - popp_005107
Manual solar siren - popp_005107
 
Qubino dimmer manual
Qubino dimmer manualQubino dimmer manual
Qubino dimmer manual
 
ES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - Fibaro
ES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - FibaroES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - Fibaro
ES-21-FIB-FGS-222 Micromodule double switch FGS-222 Z-Wave - Fibaro
 
Fibaro Motion Multisensor Manual
Fibaro Motion Multisensor ManualFibaro Motion Multisensor Manual
Fibaro Motion Multisensor Manual
 
Widom smart dimmer
Widom smart dimmerWidom smart dimmer
Widom smart dimmer
 
Water meter secure start guide
Water meter secure start guideWater meter secure start guide
Water meter secure start guide
 
Door lock without handle vision operational manual
Door lock without handle vision operational manualDoor lock without handle vision operational manual
Door lock without handle vision operational manual
 

Similar to WiDom Energy Driven Switch Installation and Operating Instructions

Wall Plug switch with Metering Z-Wave.me ZME_064374 manual english
Wall Plug switch with Metering Z-Wave.me ZME_064374 manual englishWall Plug switch with Metering Z-Wave.me ZME_064374 manual english
Wall Plug switch with Metering Z-Wave.me ZME_064374 manual englishDomotica daVinci
 
Widom Relay withdry contact_en
Widom Relay withdry contact_enWidom Relay withdry contact_en
Widom Relay withdry contact_enDomotica daVinci
 
Manual smart TE dimmer Z-Wave -Widom
Manual  smart TE dimmer Z-Wave -WidomManual  smart TE dimmer Z-Wave -Widom
Manual smart TE dimmer Z-Wave -WidomDomotica daVinci
 
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual english
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual englishMicromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual english
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual englishDomotica daVinci
 
In-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual englishIn-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual englishDomotica daVinci
 
Wall plug switch with metering aeon labs v2 manual
Wall plug switch with metering aeon labs v2 manualWall plug switch with metering aeon labs v2 manual
Wall plug switch with metering aeon labs v2 manualDomotica daVinci
 
Door Opener Controller Z-Wave Plus Manual - PoPP
Door Opener Controller Z-Wave Plus Manual - PoPPDoor Opener Controller Z-Wave Plus Manual - PoPP
Door Opener Controller Z-Wave Plus Manual - PoPPDomotica daVinci
 
Wall plug switch with metering po pp start guide
Wall plug switch with metering po pp start guideWall plug switch with metering po pp start guide
Wall plug switch with metering po pp start guideDomotica daVinci
 
Fibaro Flood Sensor Manual
Fibaro Flood Sensor Manual Fibaro Flood Sensor Manual
Fibaro Flood Sensor Manual Domotica daVinci
 
wiDom Smart dry contact module Z-Wave Plus Manual
wiDom Smart dry contact module Z-Wave Plus ManualwiDom Smart dry contact module Z-Wave Plus Manual
wiDom Smart dry contact module Z-Wave Plus ManualDomotica daVinci
 
Dry contact sensor with temperature sensor start guide
Dry contact sensor with temperature sensor start guideDry contact sensor with temperature sensor start guide
Dry contact sensor with temperature sensor start guideDomotica daVinci
 

Similar to WiDom Energy Driven Switch Installation and Operating Instructions (20)

Wall Plug switch with Metering Z-Wave.me ZME_064374 manual english
Wall Plug switch with Metering Z-Wave.me ZME_064374 manual englishWall Plug switch with Metering Z-Wave.me ZME_064374 manual english
Wall Plug switch with Metering Z-Wave.me ZME_064374 manual english
 
Widom Relay withdry contact_en
Widom Relay withdry contact_enWidom Relay withdry contact_en
Widom Relay withdry contact_en
 
Manual danfos danehc10
Manual danfos danehc10Manual danfos danehc10
Manual danfos danehc10
 
Manual smart TE dimmer Z-Wave -Widom
Manual  smart TE dimmer Z-Wave -WidomManual  smart TE dimmer Z-Wave -Widom
Manual smart TE dimmer Z-Wave -Widom
 
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual english
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual englishMicromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual english
Micromodule Mural On/Off Z-Wave Plus AN179 Smart Home Europe manual english
 
In-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual englishIn-wall dimmer module Z-Wave Plus Smart Home Europe manual english
In-wall dimmer module Z-Wave Plus Smart Home Europe manual english
 
Pop 123610 manual
Pop 123610 manual Pop 123610 manual
Pop 123610 manual
 
manual dimmer - Zipato
manual dimmer - Zipatomanual dimmer - Zipato
manual dimmer - Zipato
 
Wall plug switch with metering aeon labs v2 manual
Wall plug switch with metering aeon labs v2 manualWall plug switch with metering aeon labs v2 manual
Wall plug switch with metering aeon labs v2 manual
 
Door Opener Controller Z-Wave Plus Manual - PoPP
Door Opener Controller Z-Wave Plus Manual - PoPPDoor Opener Controller Z-Wave Plus Manual - PoPP
Door Opener Controller Z-Wave Plus Manual - PoPP
 
duw 05458 manual
duw 05458 manualduw 05458 manual
duw 05458 manual
 
Wall plug switch with metering po pp start guide
Wall plug switch with metering po pp start guideWall plug switch with metering po pp start guide
Wall plug switch with metering po pp start guide
 
Fibaro Flood Sensor Manual
Fibaro Flood Sensor Manual Fibaro Flood Sensor Manual
Fibaro Flood Sensor Manual
 
wiDom Smart dry contact module Z-Wave Plus Manual
wiDom Smart dry contact module Z-Wave Plus ManualwiDom Smart dry contact module Z-Wave Plus Manual
wiDom Smart dry contact module Z-Wave Plus Manual
 
Manual zmnhxd1
Manual zmnhxd1Manual zmnhxd1
Manual zmnhxd1
 
Manual HKZW-FLD01
Manual HKZW-FLD01Manual HKZW-FLD01
Manual HKZW-FLD01
 
For mim olite
For mim oliteFor mim olite
For mim olite
 
Dry contact sensor with temperature sensor start guide
Dry contact sensor with temperature sensor start guideDry contact sensor with temperature sensor start guide
Dry contact sensor with temperature sensor start guide
 
Manual_AD147_20140728.pdf
Manual_AD147_20140728.pdfManual_AD147_20140728.pdf
Manual_AD147_20140728.pdf
 
Duw 05460 manual
Duw 05460 manualDuw 05460 manual
Duw 05460 manual
 

More from Domotica daVinci

Manual de usuario Dongle Zigbee 3.0 Sonoff
Manual de usuario Dongle Zigbee 3.0 SonoffManual de usuario Dongle Zigbee 3.0 Sonoff
Manual de usuario Dongle Zigbee 3.0 SonoffDomotica daVinci
 
2Channel Dimmer Module Zigbee NetPlus Manual
2Channel Dimmer Module Zigbee NetPlus Manual2Channel Dimmer Module Zigbee NetPlus Manual
2Channel Dimmer Module Zigbee NetPlus ManualDomotica daVinci
 
Shelly Qubini Dry Contact Module Z-Wave Manual
Shelly Qubini Dry Contact Module Z-Wave ManualShelly Qubini Dry Contact Module Z-Wave Manual
Shelly Qubini Dry Contact Module Z-Wave ManualDomotica daVinci
 
Zi-Stick UBS Dongle ZIgbee from Aeotec manual
Zi-Stick UBS Dongle ZIgbee from  Aeotec manualZi-Stick UBS Dongle ZIgbee from  Aeotec manual
Zi-Stick UBS Dongle ZIgbee from Aeotec manualDomotica daVinci
 
Manual controlador de pared Zigbee quatro battery.pdf
Manual controlador de pared Zigbee quatro battery.pdfManual controlador de pared Zigbee quatro battery.pdf
Manual controlador de pared Zigbee quatro battery.pdfDomotica daVinci
 
MOES-User-Manual AL23-211223-MHUB-MS.pdf
MOES-User-Manual AL23-211223-MHUB-MS.pdfMOES-User-Manual AL23-211223-MHUB-MS.pdf
MOES-User-Manual AL23-211223-MHUB-MS.pdfDomotica daVinci
 
Tete thermostatique Zigbee MOES BRT-100 V2.pdf
Tete thermostatique Zigbee MOES BRT-100 V2.pdfTete thermostatique Zigbee MOES BRT-100 V2.pdf
Tete thermostatique Zigbee MOES BRT-100 V2.pdfDomotica daVinci
 
Cherubini Meta Z-Wave Double Switch A510083-84-90
Cherubini Meta Z-Wave Double Switch A510083-84-90Cherubini Meta Z-Wave Double Switch A510083-84-90
Cherubini Meta Z-Wave Double Switch A510083-84-90Domotica daVinci
 
Cherubini Meta Z-Wave Smart Plug Manual A510068
Cherubini Meta Z-Wave Smart Plug Manual A510068Cherubini Meta Z-Wave Smart Plug Manual A510068
Cherubini Meta Z-Wave Smart Plug Manual A510068Domotica daVinci
 
Wave_Shutter_user_guide_multilang_print_V3.pdf
Wave_Shutter_user_guide_multilang_print_V3.pdfWave_Shutter_user_guide_multilang_print_V3.pdf
Wave_Shutter_user_guide_multilang_print_V3.pdfDomotica daVinci
 
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdf
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdfQuinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdf
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdfDomotica daVinci
 
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdfZ-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdfDomotica daVinci
 
Manual Eurotronic Thermostatic Valve Comry Z-Wave
Manual Eurotronic Thermostatic Valve Comry Z-WaveManual Eurotronic Thermostatic Valve Comry Z-Wave
Manual Eurotronic Thermostatic Valve Comry Z-WaveDomotica daVinci
 
Manual sensor Zigbee 3.0 MOES ZSS-X-PIRL-C
Manual  sensor Zigbee 3.0 MOES ZSS-X-PIRL-CManual  sensor Zigbee 3.0 MOES ZSS-X-PIRL-C
Manual sensor Zigbee 3.0 MOES ZSS-X-PIRL-CDomotica daVinci
 
zigbee motion sensor user manual NAS-PD07B2.pdf
zigbee motion sensor user manual NAS-PD07B2.pdfzigbee motion sensor user manual NAS-PD07B2.pdf
zigbee motion sensor user manual NAS-PD07B2.pdfDomotica daVinci
 
Range extender 7 - Aeotec - Manual
Range extender 7 - Aeotec - Manual   Range extender 7 - Aeotec - Manual
Range extender 7 - Aeotec - Manual Domotica daVinci
 
wiDom Smart Roller Shutter Z-Wave Plus Module Manual
wiDom Smart Roller Shutter Z-Wave Plus Module ManualwiDom Smart Roller Shutter Z-Wave Plus Module Manual
wiDom Smart Roller Shutter Z-Wave Plus Module ManualDomotica daVinci
 
Super Slim Connected Plug - Zigbee 3.0 - Innr
Super Slim Connected Plug - Zigbee 3.0 - InnrSuper Slim Connected Plug - Zigbee 3.0 - Innr
Super Slim Connected Plug - Zigbee 3.0 - InnrDomotica daVinci
 

More from Domotica daVinci (20)

Manual de usuario Dongle Zigbee 3.0 Sonoff
Manual de usuario Dongle Zigbee 3.0 SonoffManual de usuario Dongle Zigbee 3.0 Sonoff
Manual de usuario Dongle Zigbee 3.0 Sonoff
 
2Channel Dimmer Module Zigbee NetPlus Manual
2Channel Dimmer Module Zigbee NetPlus Manual2Channel Dimmer Module Zigbee NetPlus Manual
2Channel Dimmer Module Zigbee NetPlus Manual
 
Shelly Qubini Dry Contact Module Z-Wave Manual
Shelly Qubini Dry Contact Module Z-Wave ManualShelly Qubini Dry Contact Module Z-Wave Manual
Shelly Qubini Dry Contact Module Z-Wave Manual
 
Zi-Stick UBS Dongle ZIgbee from Aeotec manual
Zi-Stick UBS Dongle ZIgbee from  Aeotec manualZi-Stick UBS Dongle ZIgbee from  Aeotec manual
Zi-Stick UBS Dongle ZIgbee from Aeotec manual
 
Manual controlador de pared Zigbee quatro battery.pdf
Manual controlador de pared Zigbee quatro battery.pdfManual controlador de pared Zigbee quatro battery.pdf
Manual controlador de pared Zigbee quatro battery.pdf
 
MOES-User-Manual AL23-211223-MHUB-MS.pdf
MOES-User-Manual AL23-211223-MHUB-MS.pdfMOES-User-Manual AL23-211223-MHUB-MS.pdf
MOES-User-Manual AL23-211223-MHUB-MS.pdf
 
Tete thermostatique Zigbee MOES BRT-100 V2.pdf
Tete thermostatique Zigbee MOES BRT-100 V2.pdfTete thermostatique Zigbee MOES BRT-100 V2.pdf
Tete thermostatique Zigbee MOES BRT-100 V2.pdf
 
Cherubini Meta Z-Wave Double Switch A510083-84-90
Cherubini Meta Z-Wave Double Switch A510083-84-90Cherubini Meta Z-Wave Double Switch A510083-84-90
Cherubini Meta Z-Wave Double Switch A510083-84-90
 
Cherubini Meta Z-Wave Smart Plug Manual A510068
Cherubini Meta Z-Wave Smart Plug Manual A510068Cherubini Meta Z-Wave Smart Plug Manual A510068
Cherubini Meta Z-Wave Smart Plug Manual A510068
 
Wave_Shutter_user_guide_multilang_print_V3.pdf
Wave_Shutter_user_guide_multilang_print_V3.pdfWave_Shutter_user_guide_multilang_print_V3.pdf
Wave_Shutter_user_guide_multilang_print_V3.pdf
 
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdf
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdfQuinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdf
Quinto Z-Wave Heltun_HE-RS01_User_Manual_B9AH.pdf
 
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdfZ-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
Z-Wave Fan coil Thermostat Heltun_HE-HT01_User_Manual.pdf
 
Manual Eurotronic Thermostatic Valve Comry Z-Wave
Manual Eurotronic Thermostatic Valve Comry Z-WaveManual Eurotronic Thermostatic Valve Comry Z-Wave
Manual Eurotronic Thermostatic Valve Comry Z-Wave
 
Manual sensor Zigbee 3.0 MOES ZSS-X-PIRL-C
Manual  sensor Zigbee 3.0 MOES ZSS-X-PIRL-CManual  sensor Zigbee 3.0 MOES ZSS-X-PIRL-C
Manual sensor Zigbee 3.0 MOES ZSS-X-PIRL-C
 
zigbee motion sensor user manual NAS-PD07B2.pdf
zigbee motion sensor user manual NAS-PD07B2.pdfzigbee motion sensor user manual NAS-PD07B2.pdf
zigbee motion sensor user manual NAS-PD07B2.pdf
 
Range extender 7 - Aeotec - Manual
Range extender 7 - Aeotec - Manual   Range extender 7 - Aeotec - Manual
Range extender 7 - Aeotec - Manual
 
Z stick 7 user guide
Z stick 7 user guideZ stick 7 user guide
Z stick 7 user guide
 
ESB 200 H-Tronic Manual
ESB 200 H-Tronic ManualESB 200 H-Tronic Manual
ESB 200 H-Tronic Manual
 
wiDom Smart Roller Shutter Z-Wave Plus Module Manual
wiDom Smart Roller Shutter Z-Wave Plus Module ManualwiDom Smart Roller Shutter Z-Wave Plus Module Manual
wiDom Smart Roller Shutter Z-Wave Plus Module Manual
 
Super Slim Connected Plug - Zigbee 3.0 - Innr
Super Slim Connected Plug - Zigbee 3.0 - InnrSuper Slim Connected Plug - Zigbee 3.0 - Innr
Super Slim Connected Plug - Zigbee 3.0 - Innr
 

Recently uploaded

Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationSlibray Presentation
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr LapshynFwdays
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationRidwan Fadjar
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticscarlostorres15106
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):comworks
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsMemoori
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piececharlottematthew16
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesZilliz
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Manik S Magar
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machinePadma Pradeep
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubKalema Edgar
 
My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024The Digital Insurer
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfSeasiaInfotech2
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 

Recently uploaded (20)

Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck Presentation
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 Presentation
 
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptxE-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial Buildings
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piece
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector Databases
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machine
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding Club
 
My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024
 
DMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special EditionDMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special Edition
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdf
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 

WiDom Energy Driven Switch Installation and Operating Instructions

  • 1. EN English UME-0304-200115 WPM 1.04 Installation and Operating Instructions Energy Driven Switch
  • 2. II Revision History Rev. Doc. Date Revisor Page Description 1 20/01/2015 RC All Initial Draft
  • 3. 1 Device Description Version C Version S Line Phase connection terminal Null Neutral connection terminal Controlled Line No and Lo Lines controlled by internal relay Ls External switch connection Push Button Service button: 1 click to add the device to the Z-Wave network, 3 clicks to remove it, 6 clicks to reset to factory settings Power Supply Transformer Connection terminals for external Current Transformer Technical Specifications Power Supply 230 VAC±10% 50/60 Hz Maximum Load on Relay 3000 VA – 250VAC – 12.5 A Work Temperature -10 +40 °C Radio Protocol Z-Wave 868,4 MHz Radio Range Up to 100 m outdoor Up to 40 m indoor Dimensions (HxWxD) 37x37x17 mm Consumption < 260 mW in standby < 480 mW with working load Electrical IP Rating IP 20 Actuator element Relay Conformity CE, RoHS Push Button Current transformer Controlled Line Line Null L N No Lo Energy Driven Switch Version C 2 1 WiDom Push Button Line Controlled Line Null Line Signal L N Lo No L Ls Energy Driven Switch Version S WiDom
  • 4. 2 Meter Specifications Parameters Voltage RMS, Current RMS, Active Power, Power Factor, Energy Meter Range Voltage RMS: 250 V Current RMS:  45 A – vers. C  12 A – vers. S Active Power:  ± 11250 W – vers. C  ± 3000 W – vers. S Power Factor: ±1.00 Energy: 2.000.000 kWh Resolution Voltage RMS: 0.1 V Current RMS: 0.01 A Active Power: 0.01 W Power Factor: 0.01 Energy: 0.001 kWh Maximum Error (within the dynamic range) Voltage (dynamic range 20:1): ±0.95% Current (dynamic range 1000:1):  ±0.6% - vers. S  ±2.9% - vers. C Active Power (dynamic range 4000:1):  ±1.6% - vers. S  PF=1: ±4% - vers. C  PF=0.8: ±5.5% - vers. C
  • 5. 3 Introduction WiDom Energy Driven Switch is a device designed to monitor all parameters, usage, faults and overloads of your electrical system. Unlike an ordinary energy meter, WiDom Energy Driven Switch can be installed to monitor an entire electricity network or a section of the latter.  Active Energy-saving management Automatically connects and disconnects a specific load if the established threshold limit is exceeded, or supplies the required power, momentarily excluding non-priority loads.  Management and prevention of electrical faults Identifies malfunctions based on irregular consumptions and to the maximum time of activity.  Electrical overload management Notifies or disconnects non-priority loads in the eventuality of system overloads. External switch1 : External button or switch Events: Actions performed on the external switch: click and hold. Click: If the external switch is a button (when pressed it automatically returns to the initial position), a click corresponds to pushing and releasing the button. If the external switch is a regular switch (when pressed it does not return to the initial position), a single click corresponds to a single flip of the switch. 1 Valid only for version S.
  • 6. 4 Installation INFO: WiDom Energy Driven Switch is designed for installation in flush mounting boxes, close to the loads to be controlled, at the point of entry of the electric network sections to be monitored. WARNING: WiDom Energy Driven Switch must be installed by electricians qualified to operate on electrical systems in compliance with safety requirements set out by current regulations. DANGER: WiDom Energy Driven Switch must be connected to 230V AC voltage mains supplies; please ensure that the general switch is in the OFF position prior to carrying out any operation. DANGER: Any operation requiring the use of service button (B) must only be carried out during the installation phase and must be considered as a service procedure to be performed by qualified personnel. This operation must be carried out by adopting all necessary precautions to operate on areas with a single level of isolation. WARNING: Do not connect loads exceeding the maximum power load permitted by the relay contacts. WARNING: All connections must be performed according to the electrical diagrams provided. WARNING: WiDom Energy Driven Switch must be installed in norm-compliant systems suitably protected from overloads and short circuits. WiDom Driven Switch Activation 1) Ensure that the main power switch is set in the OFF position 2) Connect the device following the diagrams provided 3) Shut the electrical box containing the device 4) Turn the main power switch back on 5) Include the device into the Z-Wave network
  • 7. 5 Electrical Connections The device must be supplied by phase and neutral. Connections must be made according to one of the diagrams below. In devices requiring a current transformer, the latter must be connected by attaching the black wire to terminal 1 and the white wire to terminal 2. The current transformer must be clamped on the phase wire leading to the load and adjusted to have the arrow pointing towards the load to be monitored. Local load control In this mode the load is controlled directly by the internal relay. The opening and closing of the relay contacts are synchronized to take place, respectively, when a zero current or voltage is reached. Versione C LINE IN L N L N No Lo Energy Driven Switch Version C 2 1 WiDom LINE OUT/LOAD Versione S Push Button L N LINE IN L N L N Lo No L Ls Energy Driven Switch Version S WiDom LINE OUT/LOAD
  • 8. 6 Remote load control In this mode the device has no locally connected load, and the measures of current and power are based on all devices connected to the “LINE OUT” section of the system. The devices connected to the “LINE OUT” can be controlled individually based on the configured energy events. Versione C L N LINE IN LINE OUT/LOAD L N L N No Lo Energy Driven Switch Version C 2 1 WiDom Versione S L N LINE IN L N L N Lo No L Ls Energy Driven Switch Version S WiDom LINE OUT/LOAD
  • 9. 7 Load control by external contactor This mode, available only for version C and the use of an external contactor, allows the management of loads up to 45A. The device supports two types of external contactors:  Normally open (in the absence of signal from the relay the “LINE OUT” is disconnected)  Normally close (in the absence of signal from the relay the “LINE OUT” is connected) The load control mode and type of external contactor can be set up with parameter No. 63. Versione C L N LINE IN L N L N No Lo Energy Driven Switch Version C 2 1 WiDom LINE OUT/LOAD
  • 10. 8 Reset to factory settings The device can be reset to the original factory settings by means of one of the following methods: Method 1: Remove the device from the Z-Wave network; Method 2: Six consecutive clicks on (B) button or on the external switch within 1 minute from system start-up; Method 3: Set the parameter 61 to 0 – FACTORY RESET (see Configuration Parameters). INFO: Please use methods 2 and 3 only in the event that the primary controller is missing or otherwise inoperable. INFO: If the device is reset when included in a network, the latter will notify its removal (Device Reset Locally Notification). Conversely, if WiDom Energy Driven Switch receives a notification of removal of another device from the network, this device will be removed from its associations. Including the device into an existing Z-Wave network WiDom Energy Driven Switch can be included into any Z-Wave network and operate with Z-Wave devices from any other manufacturer. WiDom Energy Driven Switch, used as a constantly powered node, will act as a signal repeater to increase the network reliability. The device supports both the Network Wide Inclusion (which offers the opportunity of inclusion into a network even if the device is not directly connected to the controller) and the Normal Inclusion mechanisms. If the device is not included into a Z-Wave network, a single click on the (B) button or on the external switch will launch the process of traditional inclusion. If the device inclusion procedure does not start within 2 seconds, the Network Wide Inclusion network will be launched lasting a variable amount of time between 15-30 seconds. INFO: Through the inclusion procedure, activated with a single click on the external switch2, the system determines the type of external switch (see parameter No. 62). Excluding the device from a Z-Wave network Only a controller can remove a device from the network. WiDom Energy Driven Switch is compatible with all Z-Wave certified controllers. After the exclusion procedure has been activated by the controller, the device can be removed, putting it in Exclusion Mode by three consecutive clicks on the (B) button or on the external switch, when available. Associations WiDom Energy Driven Switch can control other devices such as relays or dimmers. WiDom Energy Driven Switch supports three association groups, each of which supports the association of up to 8 devices: Group ID Group Name Profile Commands received Description 1 LifeLine Group General: LifeLine Basic Report, Device Reset Locally Notification, Meter Report, Multilevel Sensor: Power Report Devices to receive notifications on: status changes; energy and power levels; device local reset 2 Up Power Level Group Sensor: Power Basic Set Devices controlled by the Up Power event 3 Down Power Level Group Sensor: Power Basic Set Devices controlled by the Down Power event 2 Applicable only to version S.
  • 11. 9 TIP: WiDom Energy Driven Switch can control up to 8 devices for every group. In order to prevent the network from slowing down it is advisable to limit the associated devices to no more than 5 per group. Controlling the device with external switch When available, the external switch carries out the same function as the (B) button. Controlling the device through Z-Wave network All Z-Wave controllers can control the device by using the Basic Set command. The behaviour of the device based on its status and the commands received from the network can also be configured. Switch ALL ON/OFF By default, WiDom Energy Driven Switch accepts Switch All ON/OFF commands. Overcurrent Protection The device can be configured to react (opening/closing the integrated relay) to current overloads lasting over a configurable amount of time. See parameters 30 to 32. Zero Crossing Relay open/close switchings always take place when a zero of current or voltage occurs. In this way, electrical stress on the relay contacts is minimized, thus affording a longer duration.
  • 12. 10 Active Energy management Energy Driven Switch is capable of implementing an active energy saving policy by managing electric loads in order to maximize the self-consumption during the greater production period of our wind power or photovoltaic plant, optimizing the net metering and the energy saving. An upper and lower power threshold can be configured which, when exceeded, activates or deactivates the two groups of loads connected to the two thresholds. Predefined loads can be disconnected when the power consumed exceeds a specific threshold for longer than a certain amount of time, or specific loads can be activated when the level of energy produced and not consumed exceeds a second threshold. WiDom Energy Driven Switch allows you to detect irregular consumption in order to prevent or identify faults by means of specific alarms. The product can also be used to set levels of total energy produced above which the user can be notified. This mode allows you, for instance, to manage programmed maintenance interventions based on the actual usage of the systems. For further details about these configurations, please refer to parameters 30 to 50. Electric parameters reading In addition to Power and Energy, the device also provides data for Voltage RMS, Current RMS and Power Factor. These values, together with power and energy measurements, can be obtained through the certified controllers that support the Meter Command Class version 3. These parameters can also be read by means of parameters 51 to 55. Firmware Update The system supports over-the-air firmware updates that do not require the device to be removed from its location. The firmware update can be activated from all certified controllers supporting version 2 of the Firmware Update function. The firmware update procedure must be enabled on the device with four consecutive clicks. The activation lasts 10 seconds, after which the firmware update procedure will need to be re-enabled if it has not been activated in the first instance. WARNING: The system will be rebooted at the end of the firmware update procedure. If a load is connected to the relay output, it will be disconnected and reconnected, depending on the settings configured for system rebooting. It is advisable to carry out the firmware update procedure only when necessary and following careful planning of the intervention.
  • 13. 11 Configurations Device Status Controlling the relay by means of a single click on the external switch or on the integrated button. Parameter No. 1: Device Status (1 byte) Configuration Initial Status Final Status 1 – TOGGLE (Default Value) ON OFF OFF ON 2 – ON ON If the initial status is OFF the system switches to ON; conversely, it maintains its status (ON). OFF 3 – OFF ON If the initial status is ON the system switches to OFF; conversely, it maintains its status (OFF). OFF 4 – IGNORE ON The device maintains the initial status OFF Controlling the device through Z-Wave network The final status achieved by the device when it receives a Basic Set command through the Z-Wave network. Parameter No. 20 (0x14): Device status upon receipt of a Basic Set command (1 byte) Configuration Command received Final Status 1 – AS RECEIVED (Default Value) ON ON OFF OFF 2 – IGNORE IF ON ON Maintains the initial status OFF OFF 3 – IGNORE IF OFF ON ON OFF Maintains the initial status 4 – IGNORE ON Maintains the initial status OFF
  • 14. 12 Overcurrent detector The overcurrent detector determines when the current level remains over a threshold level (OverCurrent Level) for longer than a certain amount of time (OverCurrent Time). When this happens, an Overcurrent Event occurs and it can be associated, for instance, to opening of the relay contacts. Parameter No. 30 (0x1E): Overcurrent level (2 byte) – Sets the current level above which the time spent above that level is measured. Version C: From 0 to 45003 hundredths of Amperes – Default Value: 4500 Hundredths of Amperes Version S: From 0 to 1250 hundredths of Amperes – Default Value: 1250 Hundredths of Amperes Parameter No. 31 (0x1F): Overcurrent time (2 byte) – Sets the time beyond which, in the case of overcurrent at a level higher than that established in parameter 30, an OverCurrent event occurs. From 0 to 10800 Seconds (3 Hours) – Default Value: 10 Seconds Parameter No. 32 (0x20): Next State (1 byte) – Defines the next state of the device if an overcurrent event has occurred. Configuration Next Status 0 – IGNORE (Default Value) The device maintains the initial status. 1 – ON If the initial status is OFF the system switches to ON; conversely, it maintains its status (ON). 2 – OFF If the initial status is ON the system switches to OFF: conversely, it maintains its status (OFF). 3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON. 3 Values above 1250 can only be managed with version C using the configuration “LOAD CONTROLLED BY EXTERNAL CONTACTOR”. OverCurrent Level OverCurrent Time Current OverCurrent Event OverCurrent Event Previous State OverCurrent State Next State OverCurrent Time
  • 15. 13 Energy Management Parameter No. 33 (0x21): Meter Reset (4 byte) Provides total operating time from last meter reset. When set to 0 it resets the cumulated values of energy and total operating time. Configuration Final Status 0 – RESET METER Meter parameters, including total operating time, will be reset Greater than 0 – IGNORE (Default value) The meter will not be reset Parameter No. 34 (0x22): Energy flow (1 byte) Determines whether energy events are related to energy consumed or energy produced. Configuration Final Status 1 – Consumed (Default value) Events will be active for Consumed energy flows to which the positive sign will be attributed 2 – Produced Events will be active for Produced energy flows to which the negative sign will be attributed Upper Limit Power Threshold Detector The upper limit power threshold detector determines when instantaneous power remains above the threshold point (UP Power Level) beyond a specified duration (UP Power Time). When this happens, a UP Power Event occurs. The occurrence of a UP Power event can be configured in order to determine the Next State both of the device and of the devices associated to the UP Power Group. Parameter No. 35 (0x23): UP Power Level (2 byte) – Sets the level of instantaneous power in Watts beyond which time of permanence above this level is calculated. Version C: From 0 to 112504 – Default value: 11250 Version S: From 0 to 3000 – Default value: 3000 Parameter No. 36 (0x24): UP Power Time (2 byte) – Sets the time in seconds beyond which, if instantaneous power remains at levels exceeding threshold defined by parameter 35, a UP Power event occurs. From 0 to 10800 seconds (3 Hours) – Default value: 10 Seconds 4 Values above 3000 may only be managed with the version C using the configuration of “LOAD CONTROLLED BY EXTERNAL CONTACTOR”. UP Power Level Power UP Power Event UP Power Associated UP Power Time UP Power Time Previous State UP Power State Next State Up Power Event Previous State Next State
  • 16. 14 Parameter No. 37 (0x25): UP Power State (1 byte) – Defines the next status of the device in the case of a UP Power event occurring. Configuration Next Status 0 – IGNORE (Default Value) The device maintains the initial status. 1 – ON If the initial status is OFF the system switches to ON; conversely, it maintains its status (ON). 2 – OFF If the initial status is ON the system switches to OFF: conversely, it maintains its status (OFF). 3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON. Parameter No. 38 (0x26): UP Power Associated (1 byte) – Defines the status of associated devices in the presence of a UP Power event. From: 1 to 99 for dimming purpose – 0 (OFF) and -1(ON) for switching ON/OFF. Default: 0 – OFF
  • 17. 15 Lower Limit Power Threshold Detector The lower limit power threshold detector determines when instantaneous power remains below the threshold point (DOWN Power Limit) beyond a specified duration (DOWN Power Time). When this happens, a DOWN Power Event occurs. The occurrence of a DOWN Power event can be configured in order to determine the next state both of the device and of the devices associated to the DOWN Power Group. Parameter No. 39 (0x27): DOWN Power Level (2 byte) – Sets the level of instantaneous power beyond which the time of permanence below this level is calculated. From 0 to 11250 Watt – Default value: 0 W Parameter No. 40 (0x28): DOWN Power Time (2 byte) – Sets the time beyond which, if instantaneous power remains at levels below threshold defined by parameter 39, a DOWN Power event occurs. From 0 to 10800 Seconds (3 Hours) – Default value: 10 Seconds Parameter No. 41 (0x29): DOWN Power State (1 byte) – Defines the next state of the device in the case of a DOWN Power event occurring. Configuration Next Status 0 – IGNORE (Default Value) The device maintains the initial status. 1 – ON If the initial status is OFF the system switches to ON; conversely, it maintains its status (ON). 2 – OFF If the initial status is ON the system switches to OFF: conversely, it maintains its status (OFF). 3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON. Parameter No. 42 (0x2A): DOWN Power Associated (1 byte) – Defines the status of associated devices in the presence of a DOWN Power event. From: 1 to 99 for dimming purpose – 0 (OFF) and -1(ON) for switching ON/OFF. Default: 0 – OFF DOWN Power Level Power DOWN Power Event DOWN Power Associated Power DOWN Power Time DOWN Power Time Previous State DOWN Power State Next State Down Power Event Previous State Next State
  • 18. 16 Detection of exceeded Energy Limits The detection of exceeded energy limits determines when total accumulated energy exceeds a specific threshold (Limit Energy). When this happens, a Limit Energy Event occurs. The occurrence of a Limit Energy event can be configured in order to determine the Next State of the device. Parameter No. 43 (0x2B): Energy Level (4 byte) – Sets the energy level that once exceeded an Energy Limit event occurs. From 0 to 2.000.000 KWh – Default value: 2.000.000 KWh Parameter No. 44 (0x2C): Energy Limit State (1 byte) – Defines the next state of the device in the case of an Energy Limit event occurring. Configuration Next Status 0 – IGNORE (Default Value) The device maintains the initial status. 1 – ON If the initial status is OFF the system switches to ON; conversely, it maintains its status (ON). 2 – OFF If the initial status is ON the system switches to OFF: conversely, it maintains its status (OFF). 3 – TOGGLE If the initial status is ON/OFF the system switches to OFF/ON. Limit Energy Level Energy Limit Energy Event Limit Energy Event Previous State Device Status Next State
  • 19. 17 Automatic meter notifications The system can send automatic notifications listing the values obtained for Power, Energy, Voltage, Current and Power Factor. These reports may be sent following a specific event (over current, voltage out of limit, etc.); subsequent to a variation of one of the parameters beyond a given threshold; following an excessively long time since the sending of the previous report. The table below summarizes all instances covered by automatic notifications. Event Reports sent Configuration parameters affected Percentage variation of instantaneous power 3 Instantaneous Power Reports at a minimum interval of 3 seconds 1 Voltage Report 1 Current Report 1 Power Factor Report 45 Exceeding of Upper/Lower Power limit 1 instantaneous Power Report 1 instantaneous Power Report for each remotely controlled device at a minimum interval of 3 seconds apart Automatic Exceeding of overcurrent limits A series of current reports throughout the duration of the event at a minimum interval of 9 seconds Automatic Voltage out of permitted limits A series of current reports throughout the duration of the event at a minimum interval of 12 seconds 48, 49 Maximum time from the last instantaneous power report 1 Instantaneous Power Report at a minimum interval of 3 seconds 1 Voltage Report 1 Current Report 1 Power Factor Report 46 Variation of total energy 1 Total Energy Report 47 The maximum frequency for all reports, including those relating to change of state of the device, never exceeds 1 report every 3 seconds calculated over a 30-second period. Parameter No. 45 (0x2D): Variation Instantaneous Power (1 byte) – Defines the percentage variation of instantaneous power determining the sending of the report. From: 1 (1%) to 100 (100%) Default value: 10 – 10% Parameter No. 46 (0x2E): Report Time Frequency (1 byte) – Defines the maximum time in minutes since the previous report beyond which an Instantaneous Power Report will still be sent. From: 1 to 100 minutes. Default value: 10 minutes
  • 20. 18 Parameter No. 47 (0x2F): Variation Total Energy (1 byte) – Defines the increase of total energy required to generate a report listing the level of total energy to the devices associated to the Energy Notification Group. Configuration Energy variation generating the issuing of a report 0 – IGNORE No report provided 1 1 thousandth of KWh 2 1 hundredth of KWh 3 (Default value) 1 tenth of KWh 4 1 KWh Parameter No. 48 (0x30): Nominal Voltage (2 byte) – Defines the nominal voltage value in tenths of volts. Together with parameter No. 49 this is used by the automatic notification system to send reports on variations of voltage. Default value: 2300 From: 1100 to 2500 Parameter No. 49 (0x31): Fall in maximum voltage (1 byte) – Defines, as a percentage, the nominal value for permitted fall in maximum voltage. From: 1 (1%) to 100 (100%) Default value: 10 – 10% Parameter No. 50 (0x32): Electric parameters subjected to automatic notification (1 byte) – Defines which electric parameters, other than power, will be subjected to automatic notification. The value to be set for this parameter must be calculated as the sum of values associated to the individual electric parameter indicated in the table. Scale Value Power 0 Energy 2 Voltage 4 Current 8 Power factor 16 Multilevel Sensor: Power Report 32 To send report only for Power please set the value to 0. To send report only for Power and Energy please set the value to 2 (0+2). To send report for Power, Energy, Voltage, Current, Power Factor please set the value to 30 (0+2+4+8+16). By default the report are sent for (Power, Energy, Voltage, Current, Power Factor) 0+2+4+8+1630 Default value: 30 Permitted values: From 0 to 62
  • 21. 19 Parameters for monitoring of the electrical network and system calibration. In order to ensure maximum precision, each device is individually calibrated and the calibration values are permanently set on the system. Values relating to Voltage, Current, Power Factor and Energy may also be read by consulting parameters 51 to 55, all of which are read-only parameters, which ignore all settings and return the value of the specific parameter at the time of the reading. Parameter No. 51 (0x33): Voltage RMS value (2 byte) Reading of this parameter returns the value of voltage RMS at the time of the reading expressed in tenths of Volts. Parameter No. 52 (0x34): Current RMS value (2 byte) Returns the value of current RMS expressed in hundredths of Amperes. Parameter No. 53 (0x35): Power Factor (1 byte) Returns the value of power factor as a percentage. Parameter No. 54 (0x36): Total energy consumed (4 byte) Returns the value of total energy consumed expressed in Wh (thousandths of KWh). Parameter No. 55 (0x37): Total energy produced (4 byte) Returns the value of total energy produced expressed in Wh (thousandths of KWh).
  • 22. 20 Other configuration parameters Parameter No. 60 (0x3C): Start-up status (1 byte) – Defines the status of the device following a restart. Configuration Device reaction 1 – ON Device on 2 – OFF Device off 3 – PREVIOUS STATUS (Default value) Status prior to restart Parameter No. 61 (0x3D): Configuration reset (1 byte) – Defines which parameters should be reset to default values. Configuration Device reaction 0 – FACTORY RESET The device is reset to the original factory settings 1 – ASSOCIATIONS RESET All associations and only the associations are reset 2 – CONFIGURATIONS RESET The associations are maintained while all other configuration parameters are reset to the original factory settings, except for the specific configuration. 4 – IGNORE (Default value) No action is performed Parameter No. 62 (0x3E): Type of external switch (1 byte) – Defines the type of external switch connected to the device. Configuration Device reaction 0 – IGNORE The external switch is not connected or not present. 1 – BUTTON The external switch is a normally open button 2 – SWITCH The external switch is a traditional switch 4 – AUTOMATIC RECOGNITION (Default value) After the first single click on the external switch, the system automatically determines the type of external switch used and sets the parameter with the new value accordingly. Parameter No. 63 (0x3F): Load control (1 byte) – Defines the load control mode. Configuration Device reaction 1 – DIRECT CONTROL (Default value) The external load is controlled directly by the relay. Reference diagram local load control. 2 – CONTROL BY MEANS OF A CONTACTOR WITH NORMALLY OPEN COMMAND The external load is controlled by a contactor that in a resting state has open contacts (load control by means of external contactor). 3 – CONTROL BY MEANS OF A CONTACTOR WITH NORMALLY CLOSED COMMAND The external load is controlled by a contactor that in a resting state has closed contacts (load control by means of external contactor). 4 – AS AN EXTERNAL INDICATOR The relay is only used to control the ignition of an external warning light, as, for example, in the case of notification of excess loads and surges (remote load control).
  • 23. 21 Disposing the devices This product bears the selective sorting symbol for waste electrical and electronic equipment (WEEE). This means that this product must be handled pursuant to European Directive 2002/96/EC in order to be recycled or dismantled to minimize its impact on the environment. For further information, please contact your local or regional authorities. Electronic products not included in the selective sorting process are potentially dangerous for the environment and human health due to the presence of hazardous substances. Compliance with directives WiDom devices are built in compliance with directives LVD 2006/95/EC, EMC 2004/108/CE and R&TTE Widom shall not be held responsible for any damage caused by these devices if they are used in a manner that is not compliant with the instructions in this manual. WiDom reserves the right to make any changes to the product that it considers necessary or useful without jeopardising its primary features. Warranty This warranty is provided by WiDom srl (hereinafter “WiDom”) based in Quartu S.Elena 09045 (CA), Italy (VAT number 03452490927). WiDom warrants to the original purchaser (hereinafter “Customer”) that the device sold under this agreement (hereinafter “Device”) is free from defects in parts and workmanship under normal use for 12 months from date of purchase (“Warranty Period”). The original purchase invoice or sales receipt, showing the date of purchase is the proof of date of purchase by the Customer. If a Device, sold by WiDom to the Customer, has manufacturing defects or in any case of alleged lack of conformity, the Customer shall send within thirty (30) days from the day in which he discovers such defects, a claim form by using the web site (www.widom.it) informing WiDom on the full name of the Customer, the nature of the defects and the date in which the Devices has been purchased. Warranty Claims received after the expiration of the Warranty Period shall not be considered valid. Once WiDom, receives the Warranty Claim, it shall inform the Customer by e-mail or letter, if the Warranty is applicable and the address where the Device shall be sent in order to verify the defects (if any). Customer must prepay shipping and transportation charges as indicated by WiDom. The Device shall be sent by the Customer to WiDom at its own costs and expenses, by express courier or hand delivered, and with the original packaging, the supplied accessories (if any) and documents proving date of purchase. WiDom shall then inform the Customer about the defects and on its repair or replacement (where applicable). Should WiDom not evidence defects on the Device, the Device shall be returned to the Customer. Should WiDom notices the defects, and this warranty is applicable, it will remove, at its sole discretion, any defect, free of charge, by repairing any defective components of the Device with new or regenerated components or by replacing the Device. The Warranty Period of the replaced or repaired Device shall not be extended. WiDom will ship the repaired or a replaced Device to Customer freight prepaid. WiDom will not be liable for damages to property caused by faulty device. WiDom will not be liable for indirect, incidental, special, consequential or punitive damages, or for any damage, including, inter alia, loss of profits, savings, data, loss of benefits, claims by third parties and any property damage or personal injuries arising from or related to the use of the Device. If the Device cannot be replaced with another of the same type (e.g. the Device is no longer in production or no longer available for selling in the Customer’s country), it may be replaced with a different one having similar technical specifications to the faulty one. Such replacement shall be considered as a total fulfilment of WiDom’s obligations. Warranty exclusion - defects caused by normal wear of parts or especially subject to wear, such as parts that require periodic replacement during the normal operation of the system (e.g. Batteries);
  • 24. 22 - splits, cracks, scratches, dents, scratched or discolored surfaces and parts, breakage of plastic parts and in general of any other cosmetic damage; - damages resulting from use of the system other than that provided, including but not limited to the failure to follow instructions contained in the operating manual; - damages caused by accident, abuse, misuse, dirt, viruses, liquid contact, fire, earthquake, improper or inadequate maintenance or calibration, negligence or other external causes; - environmental damage and / or defects caused by smoke, dust, dirt, soot, or other external influences; - damages caused by modifications and alterations in the functionality or features without the written permission of WiDom; - damages resulting from transportation or inadequate packaging when returning the product to a WiDom or to an authorize service center; - defects caused by force majeure events such as lightning, floods, fires, incorrect voltage, improper ventilation; - damages caused by malfunctioning software, computer virus attack, or by failure to update the software as recommended by WiDom; - damages resulting from surges in the power and/or telecommunication network, improper connection to the grid in a manner inconsistent with the operating manual, or from connecting other devices not recommended by WiDom; - damages caused by operating or storing the device in extremely adverse conditions, i.e. high humidity, dust, too low (freezing) or too high ambient temperature; - products whose serial number has been removed, damaged or rendered illegible; - expiration of the Warranty Period. If a defect is not covered by the Warranty, WiDom will inform the Customer about the extra expenses for the repair or replacement. This warranty may be subject to changes. Please check at www.widom.it the newest warranty claim procedure. This guarantee shall not exclude, limit or suspend the Customer rights when the provided product is inconsistent with the purchase agreement. © All rights reserved. WiDom is a trademark of WiDom srl. All other brand names, product names, or trademarks belong to their respective owners. WiDom reserves the right to change product features and specifications at any time without notice, and is not responsible for typographical or graphical errors that may appear in this document. Please check at www.widom.it the newest version of this document. Printed in Italy on low-impact recyclable paper.