C O M B I V E R T
Original Manual
Mat.No. Rev.
00F6NES-K000 1B
GB Installation Manual COMBIVERT F6 with Safety Function STO
Control Circuit
GB - 3
Table of Contents
1.	Preface...............................................................................................................5
1.1	General.................................................................................................................................. 5
1.2	 Safety Instructions............................................................................................................... 5
1.3	 Validity and liability.............................................................................................................. 5
1.4	Copyright............................................................................................................................... 6
1.5	 Specified application............................................................................................................ 6
1.6	 Product description.............................................................................................................. 6
2.	Control...............................................................................................................8
2.1	 Features of the control......................................................................................................... 8
2.2	Overview................................................................................................................................ 8
2.2.1	 Control terminal strip X2A....................................................................................................... 9
2.2.2	 Safety terminal block X2B....................................................................................................... 9
2.2.3	 CAN terminal block X2C......................................................................................................... 9
2.2.4	 Analog inputs X2D................................................................................................................. 9
2.2.5	 Diagnostic interface X4A......................................................................................................... 9
2.2.6	 Encoder interfaces X3A, X3B................................................................................................. 9
2.3	 Connection of the control.................................................................................................. 10
2.3.1	 Assembly of the wires........................................................................................................... 10
2.4	 Assignment of the terminal strip X2A................................................................................11
2.4.1	 Connection of the digital inputs............................................................................................. 12
2.4.2	 Connection of the digital outputs.......................................................................................... 12
2.5	 Assignment of the STO terminal strip X2B...................................................................... 13
2.5.1	Inputs.................................................................................................................................... 13
2.5.1.1	 Specification of the STO inputs............................................................................................ 13
2.5.1.2	 STO with OSSD signals........................................................................................................ 13
2.5.2	 Output STO........................................................................................................................... 13
2.6	 Assignment of the CAN terminal strip X2C...................................................................... 14
2.7	 Assignment of the terminal strip for analog inputs X2D................................................ 14
2.7.1	 Connection of the analog inputs........................................................................................... 14
2.7.2	Diagnosis/visualisation......................................................................................................... 15
2.7.2.1	 Assignment of the interface X4A........................................................................................... 15
2.7.2.2	 Connection of the RS232 interface....................................................................................... 15
2.7.2.3	 Connection of the RS485 interface....................................................................................... 15
2.7.2.4	 Wiring RS485 full duplex...................................................................................................... 16
2.7.2.5	 Wiring RS485 half duplex..................................................................................................... 16
2.8	 Socket X4C EtherCAT IN and X4B EtherCAT OUT........................................................... 17
2.9	 Encoder Parameter............................................................................................................. 17
2.9.1	 Encoder interfaces X3A and X3B......................................................................................... 18
3.	 Safety Function STO......................................................................................19
3.1	 Emergency stop according EN 60204............................................................................... 20
3.2	 Classification of STO according IEC 61508...................................................................... 21
3.3	 Classification of STO according EN ISO 13849................................................................ 21
3.4	 Additional instructions....................................................................................................... 21
3.5	 Functional Description....................................................................................................... 22
3.6	 Wiring Examples................................................................................................................. 23
GB - 4
Table of Contents
3.6.1	 Direct switching off with emergency stop switch................................................................... 23
3.6.2	 Direct switching off with emergency stop switch and monitoring of the wiring..................... 24
3.6.3	 Direct switching off by safety module with test pulses.......................................................... 25
3.6.4	 Wiring SS1............................................................................................................................ 26
4.	 Certification.....................................................................................................28
4.1	 Annex to the declaration of conformity............................................................................ 28
5.	 Revision history..............................................................................................30
GB - 5
Preface
1.	 Preface
1.1	 General
First we would like to welcome you as a customer of the company Karl E. Brinkmann GmbH
and congratulation to the purchase of this product. You have decided for a product on highest
technical level.
The described hard- and software are developments of the Karl E. Brinkmann GmbH. The
enclosed documents correspond to conditions valid at printing. Misprint, mistakes and techni-
cal changes reserved.
The instruction manual must be made available to the user. Before working with the unit the
user must become familiar with it. This especially applies to the knowledge and observance
of the following safety and warning indications. The used pictograms have following signifi-
cance:
Danger
Is used, if life or health of the user are endangered or sub-
stantial damage to property can occur.
Warning
Caution
Attention
Is used, if a measure is necessary for safe and trouble-free
operation.
observe at
all costs
Information
Is used, if a measure simplifies the handling or operation of
the unit.
Aide
Tip
1.2	 Safety Instructions
Observe safety and
operating instruc-
tions
Condition for all further steps is the knowledge and obser-
vance of the safety, EMC and operating instructions (part 1
„Getting Started“ 0000NEB-0000). This instruction is provi-
ded with the unit or by download of www.keb.de.
Non-observance of the safety instructions leads to the loss of any liability claims. The safety
and warning instructions specified in this manual do not lay claim on completeness. This list
is not exhaustive.
1.3	 Validity and liability
The use of our units in the target products is outside of our control and therefore lies
exclusively in the area of responsibility of the machine manufacturer.
The information contained in the technical documentation, as well as any user-specific advice
in spoken and written and through tests, are made to best of our knowledge and information
about the application. However, they are considered for information only without responsibil-
ity. This also applies to any violation of industrial property rights of a third-party.
Selection of our units in view of their suitability for the intended use must be done generally
by the user.
GB - 6
Preface
Tests can only be done within the application by the machine manufacturer. They must be
repeated, even if only parts of hardware, software or the unit adjustment are modified.
Unauthorised opening and tampering may lead to bodily injury and property damage and
may entail the loss of warranty rights. Original spare parts and authorized accessories by the
manufacturer serve as security. The use of other parts excludes liability for the consequences
arising out of.
The suspension of liability is especially valid also for operation interruption loss, loss of profit,
data loss or other damages. This is also valid, if we referred first to the possibility of such
damages.
If single regulations should be or become void, invalid or impracticable, the effectivity of all
other regulations or agreements is not affected.
1.4	 Copyright
The customer may use the instruction manual as well as further documents or parts from it for
internal purposes. Copyrights are with KEB and remain valid in its entirety.All rights reserved.
KEB®
, COMBIVERT®
, KEB COMBICONTROL®
and COMBIVIS®
are registered trademarks
of Karl E. Brinkmann GmbH.
Other wordmarks or/and logos are trademarks (TM) or registered trademarks (®
)
of their respective owners and are listed in the footnote on the first occurrence.
When creating our documents we pay attention with the utmost care to the rights of third par-
ties.Should we have not marked a trademark or breach a copyright, please inform us in order
to have the possibility of remedy.
1.5	 Specified application
The COMBIVERT F6 serves exclusively for the control and regulation of three-phase motors.
The operation of other electric consumers is prohibited and can lead to the destruction of the
unit. Inverter are components designed for inclusion in electrical installations or machinery.
The used semiconductors and components of KEB are developed and dimensioned for the
use in industrial products. If the KEB COMBIVERT F6 is used in machines, which work under
exceptional conditions or if essential functions, life-supporting measures or an extraordinary
safety step must be fulfilled, the necessary reliability and security must be ensured by the
machine builder. The operation of our products outside the indicated limit values of the techni-
cal data leads to the loss of any liability claims. The safety function is limited to a service life
of 20 years. After this time the unit must be replaced.
1.6	 Product description
The product family COMBIVERT F6 with safety function STO has been developed for the
use in safety-oriented applications. The basic standards as well as application and country-
specific standards must be observed furthermore. The standards referred in this manual must
be observed supplementary !
The safety function STO according to IEC 61800-5-2 contains:
•	 Safe torque off (Safe Torque Off - STO)
GB - 7
Preface
The safety function meet the requirements in accordance with performance level e (ISO13849-
1) and SIL 3 (IEC 61508 and IEC 62061). In case of proper project design, installation and
operation the safety function protects people against mechanical damages.
This accompanying instruction manual contains information for the installation
and connection of the control of the KEB COMBIVERT F6, as well as the safety
technology.
Numerical code:
Control with STO function used in Controller
1KF6Kxx-xxxx frequency inverter up to housing E
(x=variable y=D, E)
xxF6Kxy-xxxx
2KF6Kxx-xxxx
frequency inverter upon housing G
(x=variable y=G…W)
xxF6Kxy-xxxx
Validity of
certificates
The certification of controllers with safety tech-
nology is only valid if the material number cor-
responds with the specified numerical code und
the FS logo is printed on the type plate.
GB - 8
Control
2.	 Control
2.1	 Features of the control
The control provides the following analog and digital functions:
• Hardware allocation of digital and analog inputs and outputs.
• CAN bus interface
• Two field bus interfaces
• Serial interface for connection to a pc
• Two universal encoder interfaces
• Hardware of the control circuit „safety separated“ according to EN 61800-5-1 (base TN-
C/-S mains)
• Safety function STO (two channel torque off)
2.2	 Overview
Control 2KF6
X2A
X2B X2C X2D X4A
X3A
X4B X4C
X3B
Control 1KF6
X2A
X2B X2C X2D
X4A
X3A
X4B X4C
X3B
X2A Control terminal strip X4A Diagnostic interface
X2B Terminal block safety function X4B
Fieldbus interface
X2C CAN interface X4C
X2D Analog inputs
X3A Encoder interface channel 1
X3B Encoder interface channel 2
GB - 9
Control
2.2.1	 Control terminal strip X2A
The control terminal block X2A is designed as double, plug-in terminal block with spring cage
connection. It contains 28 pole.
2.2.2	 Safety terminal block X2B
The safety terminal block X2B is designed as double, plug-in terminal block with spring cage
connection. It contains 10 pole.
2.2.3	 CAN terminal block X2C
The control terminal block X2C is designed as double, plug-in terminal block with spring cage
connection. It contains 4 pole.
2.2.4	 Analog inputs X2D
The safety terminal block X2D is designed as double, plug-in terminal block with spring cage
connection. It contains 6 pole.
2.2.5	 Diagnostic interface X4A
The integrated RS232/485 interface serves for the connection of service tools (e.g. COM-
BIVIS) and displays. Telegram DIN66019II is used as communication protocol.
2.2.6	 Encoder interfaces X3A, X3B
Der COMBIVERT contains two universal encoder interfaces. The interfaces can be adapted
independently by parameter to different encoder.
GB - 10
Control
2.3	 Connection of the control
The following instructions must be observed at connection:
Attention Prevent EMC malfunctions
• Use shielded / drilled cables
• Lay shield on one side of the inverter onto earth potential
• Install control cables and power cables separately (approx. 10…20 cm
distance); Kreuzungen im rechten Winkel verlegen
• To avoid interferences a separate shielding must be provided for analog
and digital control lines. Depending on the use of the relay outputs, an ex-
tra shielding is to be used, too.
• In case of inductive load on the relay outputs a protective wiring must be
provided (e.g. free-wheeling diode)!
The terminals of the control terminal strip and the transmitter inputs are se-
curely isolated in accordance with EN 50178.
2.3.1	 Assembly of the wires
1. Stranded wire rigidly and flexibly max. perm.
cross-sec-
tion
stripping length x =
without wire-end ferrule 1,5 mm² 10 mm
with wire-end ferrule without
plastic collar
1,5 mm² metal ferrule length
with wire-end ferrule with plastic
collar
1 mm² metal ferrule length
+ 2 mm
X
2. Press with screw driver (A) or some-
thing else onto the labelling
3. Plug stranded wire (B) into the
square slot, that no wires can be
seen from the outside.
4. Remove screw driver (A) and check
if the line (B) is fixed. Make sure that
the stranded wire and not the insula-
tion is clamped.
GB - 11
Control
2.4	 Assignment of the terminal strip X2A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
PIN Name Description Specifications
1 Out1 Digital output 1 Imax
=100 mA
2 0V Reference potential for digital output
3 Out2 Digital output 2 Imax
=100 mA
4 0V Reference potential for digital output
5 Out3 Digital output 3 Imax
=100 mA
6 0V Reference potential for digital output
7 Out4 Digital output 4 Imax
=100 mA
8 0V Reference potential for digital output
9 I1 Digital input 1
10 24V Voltage output for the control of the inputs +24 Vdc*
11 I2 Digital input 2
12 24V Voltage output for the control of the inputs +24 Vdc*
13 I3 Digital input 3
14 24V Voltage output for the control of the inputs +24 Vdc*
15 I4 Digital input 4
16 24V Voltage output for the control of the inputs +24 Vdc*
17 I5 Digital input 5
18 24V Voltage output for the control of the inputs +24 Vdc*
19 I6 Digital input 6
20 24V Voltage output for the control of the inputs +24 Vdc*
21 I7 Digital input 7
22 24V Voltage output for the control of the inputs +24 Vdc*
23 I8 Digital input 8
24 24V Voltage output for the control of the inputs +24 Vdc*
25 24Vin Voltage input for external supply
24 Vdc ± 25 %
26 0V Reference potential for 24Vin
27 CRF 10 V Reference voltage for analog inputs 10 Vdc / Imax
= 4 mA
28 AGND Analog mass (do not connect to 0 V)
*) Total current of all 24 Vdc outputs: 100 mA
GB - 12
Control
2.4.1	 Connection of the digital inputs
Examples for the connection of the digital inputs
with internal voltage supply with external voltage supply
18
17
20
19
22
21
24
23
121416
11
10
9 1315
24
23
101214
9
26
251113
+
2.4.2	 Connection of the digital outputs
Examples for the connection of the digital outputs
Connection appliance Connection to an external control
3
4
5
6
7
8
1
2
31
2 4
5
6
7
8
COM DI1 DI3DI2 DI4
GB - 13
Control
2.5	 Assignment of the STO terminal strip X2B
X2B PIN Name I/O
1
2
3 5
6
7
8
9
104
1 STO1+
Input STO channel 1
2 STO1+
3 STO1-
4 STO1-
5 STO2+
Input STO channel 2
6 STO2+
7 STO2-
8 STO2-
9 STO-OUT
Output STO
10 STO-OUT
The individual channels are designed potential-free, so 24V
and 0 V can be connected. The inputs are designed by way that
safety switchgear units with test pulses (OSSD signals) can be
connected. The signals are not evaluated, they are only filtered.
The OSSD test interval is limited to 10 ms.
The reference potential for output STO-OUT (terminals X2B/9
and 10) is the mass of the control 0V (terminal X2A/26).
2.5.1	 Inputs
2.5.1.1	 Specification of the STO inputs
STO
Inputs
Status 0 Status 1
UL [V] IL [mA] UH [V] IH [mA]
max. 5 25 30 25
min. -3 not defined 15 5
The maximum short-term starting current of the input is limited to 300 mA.
2.5.1.2	 STO with OSSD signals
The filter time depends on the minimum input voltage and can be specified as follows:
Input voltage [V] OSSD pulse width [ms]
15 0.1
18 0.8
20 1.1
24 1.5
30 1.8
2.5.2	 Output STO
The short-circuit proof, digital output is specified in accordance with IEC61131-2. The output
rated current is 100 mA at 24 Vdc. The output is 24 Vdc if the inputs STO1 and STO2 are set.
GB - 14
Control
2.6	 Assignment of the CAN terminal strip X2C
X2C PIN Name Notes
1
2
3
4
1 CAN high
internally bridged
2 CAN high
3 CAN low
internally bridged
4 CAN low
2.7	 Assignment of the terminal strip for analog inputs X2D
X2D PIN Name Notes Specification
1
2
3
4
5
6
1 AN1- non-floating
differential input 1
±10 Vdc or
4…20 mA2 AN1+
3 AN2- non-floating
differential input 2
±10 Vdc or
4…20 mA4 AN2+
5 AN3- non-floating
differential input 3
±10 Vdc
6 AN3+
2.7.1	 Connection of the analog inputs
Examples for the connection of the analog setpoint input
628
5
4
3
2
127
R = 0…3/5/10kΩ
4 6
3
2
1 5
28
27
+
*
0…±10Vdc
2
1
4
3
6
5
+
4…20mA
*) Connect potential equalizing line only if a potential difference of >30 V exists
between the controls. The internal resistance is reduced to 30 kΩ.
GB - 15
Control
2.7.2	 Diagnosis/visualisation
The integrated RS232/485 interface serves for the connection of service tools (e.g. COM-
BIVIS) and displays. Telegram DIN66019II is used as communication protocol.
The correct configuration and language file must be loaded for the operation with
COMBIVIS. The downlad can be done via the KEB website.
Interface Standard Connecting cable
RS485 TIA/EIA-485 and ISO 8482
RS232 ANSI TIA/EIA-232 0058025-001D
RS232/USB 0058060-0020
2.7.2.1	 Assignment of the interface X4A
54321
9876
54321
9876
reserved 1 6 reserved
TxD (RS232) 2 7 DGND (reference potential)
RxD (RS232) 3 8 TxD-A (RS485)
RxD-A (RS485) 4 9 TxD-B (RS485)
RxD-B (RS485) 5
2.7.2.2	 Connection of the RS232 interface
A RS232-cable is needed to connect the interface operator with the PC.
Serial cable to connect the operator with a PC
0058025-001D
1
5
6
9
1
5
6
9
2.7.2.3	 Connection of the RS485 interface
The following instructions must be observed in order to prevent interferences at
the RS485 interface:
•	 use CAT 5 cable (in pairs, twisted and shielded cable)
•	 ground at one side (prior at interference-free side)
•	 Connect terminating resistors (120 Ω) at both ends on pair of wires of the
communication bus
If CAT 7 cable is used (by way of derogation from our recommendation) lay the
interior shield each to the transmitter.
GB - 16
Control
A biasing can be used if there are still interferences. However, this should be
done only once at the communication bus (preferably at the master).
2.7.2.4	 Wiring RS485 full duplex
5 4 3 2 1
9 8 7 6
COMBIVERT
5 4 3 2 1
9 8 7 6
COMBIVERT
4 5 8 9 4 5 8 9
Master
TxD-A
TxD-B
RxD-A
RxD-B
R R
R
R
R=120Ω
2.7.2.5	 Wiring RS485 half duplex
5 4 3 2 1
9 8 7 6
COMBIVERT
4 58 9
5 4 3 2 1
9 8 7 6
COMBIVERT
4 58 9
Master
RXD/TxD-A
RXD/TxD-B
R
R
R=120Ω
GB - 17
Control
2.8	 Socket X4C EtherCAT IN and X4B EtherCAT OUT
Description of the LEDs Name Description
Bus speed (yellow)
18
X4B EtherCAT IN
Link/Activity (green)
Bus speed (yellow)
18
X4C EtherCAT OUT
Link/Activity (green)
LED bus speed (yellow) Function
off Transmission error
on EtherCAT ready for operation with 100 MBit
LED Link/Activity (green) Function
off Port closed; no data transfer
on Port opened; no data transfer
flicker Port opened with data transfer
2.9	 Encoder Parameter
The control contains two encoder interfaces. The assignment of the pin connectors is identi-
cal.
The following limitations are valid when operating with two encoders:
•	 The voltage supplies 5V and 8V are generated with one programmable voltage source.
Only encoders with 5V or 8V supply are possible (e.g. BiSS and HIPERFACE are not
possible).
•	 There is only one Endat core on the encoder interface, therefore operation of a digital
EnDat 2.2 encoder together with a EnDat analog encoder is not possible.
GB - 18
Control
2.9.1	 Encoder interfaces X3A and X3B
Do not plug on/remove en-
coder cable during operation
To avoid undefined states do not plug on/remove
the encoder cable during operation.
The integrated encoder interfaces are designed for different encoders. The following table
contains the possible encoders and the appropriate signal assignment of the plug connector.
Pin assignment according to the adjusted encoder interface
(frontview of the control)
2 4 6 8 10 12 14 16 18
1 3 5 7 9 11 13 15 17
encoder
PIN
Inc-TTL Resolver Hiperface SinCos Endat Sin/
Cos-
SSI
Endat
2.2
BiSS
1 A+ COS+ COS+ COS+ COS+
2 A- COS- COS- COS- COS-
3 B+ SIN+ SIN+ SIN+ SIN+
4 B- SIN- SIN- SIN- SIN-
5 N+ Data+ N+ Data+ Data+ Data+ Data+
6 N- Data- N- Data- Data- Data- Data-
7 COS+ Cos_abs+ Clock- Clock- Clock- Clock-
8 COS- Cos_abs-
9 SIN+ Sin_abs+ Clock+ Clock+ Clock+ Clock+
10 SIN- Sin_abs-
11 Exciter+
12 Exciter-
13 COM COM COM COM COM COM COM COM
14 COM
Internal
shielding
COM COM COM COM COM COM
15 8V 8V 8V 8V 8V 8V 8V
16 5.25V 5.25V 5.25V 5.25V 5.25V 5.25V 5.25V
17 24V 24V 24V 24V 24V 24V 24V
18 COM COM COM COM COM COM COM
Shielding open with heat-shrink tube and wire-end ferrule
GB - 19
Safety Function STO
3.	 Safety Function STO
Only
qualified
Staff
Uncontrolled start is possible by improper installation of the safe-
ty technology. This may cause death, serious bodily injuries or
substantial damage to property.
Therefore the safety function may only be installed and put into
operation by qualified personnel which are trained in safety tech-
nology.
Observe
all costs
The COMBIVERT F6 with safety function must not be started
until it is determined that the installation complies with 2006/42/
EC (machine directive) as well as the EMC directive (2004/108/
EC)(note EN60204).
The COMBIVERT F6 with safety function meets the require-
ments of the Low-Voltage Directive 2006/95/EC. The harmo-
nized standard of the series EN 61800‑5‑1 (VDE 0160) is used.
This is a product of limited availability in accordance with IEC
61800-3. This product may cause radio interference in residen-
tial areas. In this case the operator may need to take correspond-
ing measures.
With electronic protection devices the safety function is integrated in the drive control in order
to minimize or eliminate danger by malfunctions in machines. The integrated safety function
replace the complex installation of external safety components. The safety function can be
requested or released by an error.
Regular
checks
In order to ensure permanent security, the function must be
checked in regular intervals according to the results of the risk
analysis.
Installation work or troubleshooting can be necessary in hazard areas, whereby protective
devices such as line- or motor contactors shall not be activated. The safety function STO can
be used there. Depending on the application the use of line or motor contactors can be void
by using STO.
In case of error or request, the power semiconductor of the drive module are switched off and
the drive is not supplied, which causes a rotation or torque (in case of a linear drive move-
ment or force). The unit can be safe switched off and/or remain if an error occurs.
Electric
Shock
Continue mains voltage with active STO function.
Compared to the disconnection by line contactors or motor contactors the integrated safety
function enables a simple integration of drives to functional groups of a system. Thereby safe
torque off can be limited to certain systems. A further advantage is that the recharge and dis-
charge time of the inverter DC link must not be considered. Thus the unit is faster again ready
for operation after an interruption.
Regular electromechanical equipment are liable to abrasion. Loss of these equipment occurs
by using the STO function and the maintenance costs are reduced.
GB - 20
Safety Function STO
Characteristic data for „Safe torque off“
• Power supply for the rotation direction of the motor is interrupted (free-wheeling motor)
• Used when monitoring of standstill is not necessary
• Unintentional starting of the motor is prevented
• No galvanic isolation of the motor from the inverter DC link
What is realized by the STO function related to EN 60204 ?
Emergency stop can be realized by the STO function, since the mains voltage may remain
effective.
Emergency stop can be realized only in connection with a line contactor, which disconnects
the mains voltage !
3.1	 Emergency stop according EN 60204
By using suitable safety switchgear units, stop category 0 and 1 according to EN 60204 can
be reached by the STO function in the system. Note chapter 6 for safety switchgear units.
Stop category 0
„uncontrolled stop“, i.e. stop by immediate removal of power to the
actuators.
Stop category 1
„controlled stop“, i.e. power to the actuators is retained to apply
braking until the stop is achieved. The energy is switched off at
standstill.
Emergency stop to EN 60204 must be functional in all operating modes of the drive module.
The reset of emergency stop may not lead to an uncontrolled start of the drive.
Restart
only after
confirmation
The drive restarts if function STO is no longer released. In order
to comply with EN 60204, it must be ensured by external meas-
ures that the drive restarts only after confirmation.
Without mechanical brake the drive leads to coast; motor is free-wheeling. Additional protec-
tive devices must be installed (e.g.locking systems) if damage to persons or property can
occur.
Ensure coast
of the motor
If danger to persons occur after switching off the motor control
by STO, the entrance to hazard areas must remain closed until
the drive stops.
Jerks in error
case
In case of double malfunction it can lead to unwanted jerk, the
rotation angle is depending on the number of poles of the se-
lected drive and the gear ratio.
Calculation of the jerk:
Rotation angle of the jerk WR [°] =
180°
–––––––––––––––––––––––––––––––––
Pole-pair number p • gear reduction ratio g
GB - 21
Safety Function STO
This behaviour can occur either by a short circuit of the IGBTs or by interconnection (also
short circuit) of the control drivers. The error should be regarded as critical, if the drive re-
mains in STO status.
3.2	 Classification of STO according IEC 61508
PFH 2.6 • 10-12
1/h
PFD 2.3 • 10-7
on demand
Proof-Test-Interval T 20 years
For SIL classification in connection with the applications consider the failure rates of the ex-
ternal switch devices for final evaluation.
3.3	 Classification of STO according EN ISO 13849
Control category 4
MTTFD
>1000 years
DC high
For the classification within a performance level in connection with the applications consider
the failure rates of the external switch devices for final evaluation.
3.4	 Additional instructions
•	 The unit must be isolated from mains by main switch when working on parts under volt-
age.
•	 Mechanical brakes must be installed additionally if external forces have effect to the drive
axis, e.g. vertical axes (hanging loads) or rotary axes with asymmetrical weight distribu-
tion.
•	 For the protection against pollution (pollution degree 2) the installation of the units must
be provided in environment with increased protection (e. g. control cabinet IP 54).
•	 Make sure that no small parts fall into the COMBIVERT during assembly and wiring. This
also applies to mechanical components, which can lose small parts during operation.
•	 Check the safety functions and error responses and generate an acceptance report after
installation.
•	 The start-up can be prevented with interruption of the STO signals. STO may not be
released in case of danger according to EN 60204-1. Also note the instructions to the
external safety switch devices.
•	 Dimension the safety application by way that the corresponding input current of the safety
functions is available for the inputs (see chapter 2.5.1).
Selection of
suitable volt-
age sources
Use for the connection only suitable voltage sources with safe
isolation (SELV / PELV) in accordance with VDE 0100 with nom-
inal voltage of 24 Vdc ± 10%. Pay attention on a sufficient over-
voltage category of the voltage supply.
GB - 22
Safety Function STO
3.5	 Functional Description
The COMBIVERT with integrated safety function meets the following function according to
IEC 61800-5-2:
•	 „Safe torque off“ (Safe Torque Off – STO)
The safety-related disconnection according to STO is reached by a two-cannel opto-coupler
blockage. The supply of the opto-couplers, which are responsible for the commutation of the
connected drive occurs via transformation coupling of the input voltage. This ensures at input
voltage loss that no supply of the opto-couplers is possible. If the opto-couplers are not longer
supplied, no IGBT can be controlled and thus no energy can be supplied to the drive.
The two channels are reached by way that input STO1 prevents the voltage supply (VTRO)
of the upper opto-couplers of the inverter bridge and input STO2 the lower opto-couplers
(VTRU).
Technical data of the STO function
Maximum ON delay (UIN = 15V) 7 ms
Maximum OFF delay (UIN=30 V) at
… active modulation 10 ms
… inactive modulation until safe state of the driver voltage is reached 50 ms
GB - 23
Safety Function STO
3.6	 Wiring Examples
3.6.1	 Direct switching off with emergency stop switch
U V W PE
M
X1A
X4A
1 - STO1+
2 - STO1+
3 - STO1-
4 - STO1-
5 - STO2+
6 - STO2+
7 - STO2-
8 - STO2-
9 - STO-OUT
10 - STO-OUT
Terminal strip X2B
+ -
24Vdc
X2A
X2C
X2D
Diagnosis
X4B
Field bus
X4C
Field bus
Power circuit
Control circuit
Safety module
At operation of an emergency stop unit, when both contacts are connected to-
gether against a positive supply signal, make sure that there are no crossfaults.
The wiring must be suitable arranged.
GB - 24
Safety Function STO
3.6.2	 Direct switching off with emergency stop switch and monitoring of the wiring
U V W PE
M
X1A
Terminal strip X2B
+ -
24Vdc
Power circuit
Control circuit
Safety module
1 - STO1+
2 - STO1+
3 - STO1-
4 - STO1-
5 - STO2+
6 - STO2+
7 - STO2-
8 - STO2-
9 - STO-OUT
10 - STO-OUT
X2A
X2C
X2D
X4A
Diagnosis
X4B
Field bus
X4C
Field bus
The displayed circuit shows wiring errors in the area of the emergency stop unit and supply
line. A possible short circuit on the primary side of the emergency stop switchgear (mass and
24 Vdc) and a short circuit on the secondary side of the unit or within the wiring leads either
directly or with closed contacts to a short circuit of the supply, whereby a series-connected
24V fuse triggers.
Besides the two displayed applications with an emergency stop switchgear, other sensors
(like door switches etc.) can be used similarly.
GB - 25
Safety Function STO
3.6.3	 Direct switching off by safety module with test pulses
U V W PE
M
X1A
Terminal strip X2B
Power circuit
Control circuitopen
closed
S1 S2
Safety device
Receipt
Safety module
1 - STO1+
2 - STO1+
3 - STO1-
4 - STO1-
5 - STO2+
6 - STO2+
7 - STO2-
8 - STO2-
9 - STO-OUT
10 - STO-OUT
X2A
X2C
X2D
X4A
Diagnosis
X4B
Field bus
X4C
Field bus
With operation of the emergency stop unit, e.g. by protection door, the release paths of the
safety module are disconnected. This leads to the loss of the STO signals (X2B.1 and 5) and
thus to energy disconnection of the drive. The safety module makes a consistency check of
all signal paths via test signals (OSSD).
GB - 26
Safety Function STO
3.6.4	 Wiring SS1
At tripping SS1 (Safe Stop 1) the drive is only disconnected from supply when it has reached
a standstill [IEC 61800-5-2]. The stop mode is not directly requested, but the maximum time
until reaching the standstill is estimated. This period is loaded in a safe time relay, which dis-
connects the drive finally from supply.
U V W PE
M
X1A
X4A
Terminal strip X2B
Diagnosis
Power circuit
Control circuitopen
closed
S1 S2
Safety device
Receipt
X2A.13
Safety module
1 - STO1+
2 - STO1+
3 - STO1-
4 - STO1-
5 - STO2+
6 - STO2+
7 - STO2-
8 - STO2-
9 - STO-OUT
10 - STO-OUT
X2A
X2C
X2D
Field bus
Motion
Control
X4B
Field bus
X4C
Field bus
When pressing the emergency stop unit the drive is stopped with a deceleration ramp via
input X2A.13 (I3).
Simultaneously the expiration of the safe time occurs in the safety module. After expiration of
the safe period the control signals STO1+ und STO2+ (X2B.1 and 5) are removed and thus
the energy supply of the drive is disconnected.
The following adjustments must be done in the drive module for the function „drive stop“:
Parameter Adjustment
pn29 „prg. error stop. mode“ (Index 0x2A1D) 1: dec. ramp -> Fault
pn48-59 (0x2A30-0x2A3C) Adjustment of the deceleration and jerk
values for the adjusted error reaction
pn30 „prog. error source“ (Index 0x2A1E) 4: I3 (here in the example)
GB - 27
Safety Function STO
Function: If the selected input becomes active, the drive decelerates with the adjusted decel-
eration ramp and changes then into status 59 „Error prog. input“.
GB - 28
Annex
4.	 Certification
4.1	 Annex to the declaration of conformity
Annex to the declaration of conformity EC for systems with functional safety:
Product designation: Inverter - type series xxF6Kxx-xxxx
Dimension 07 - 36
Voltage class 200 Vac; 400 Vac; 600 Vac
Herewith we declare that the safety module described above corresponds with all relevant
regulations of the machinery safety directive 2006/42/EC.
The above mentioned safety module meets the requirements of the following guidelines and
standards:
• Machinery safety directive 2006/42/EC
• EMC directive 2004/108/EC
• Low-Voltage Directive 2006/95/EC
EN standards Output Text Reference Output
EN 61800-5-1 09/2003 Electrical power drive systems with ad-
justable speed: security requirements
VDE 0160
Part 105
09/2003
informative:
EN 50178 1997 Installation of high voltage systems with
electronic equipment
VDE 0160 04/1998
EN 60664-1 2007 Isolation coordinats for electrical equip-
ment in low-voltage systems
VDE 0110 01/2008
EN 61800-2 10/1998 Basic determinations for AC inverter VDE 0160
Part 102
08/1999
especially for systems with functional safety additionally:
EN 61800-5-2 2007 Electrical power drive systems with ad-
justable speed: functional safety require-
ments
VDE 0160
Part 105-2
04/2008
EN 61508-(1…7) Functional safety of electrical/electronic/
programmable electronic safety-related
systems - Part 1 up to 7
VDE 0803 11/2002
EN 60204-1
+A1
2006
2009
Electrical equipment of machines;
Part1: General requirements  
VDE 0113-1
+A1
2007
10/2009
EN 62061 Safety of machinery
functional security requirements
VDE 0113
Part 50
10/2005
EN 13849-(1, 2) Safety of machinery – 08/2008
GB - 29
Annex
The conformity was confirmed by the TÜV Rheinland with the EC type examination
01/205/5332/13.
The number/address of the indicated constitution:
NB 0035
TÜV Rheinland Industrie Service GmbH
Alboinstr. 56,
12103 Berlin
Germany
Tel.: +49 30 7562-1557
Fax: +49 30 7562-1370
E-Mail: tuvat@de.tuv.com
GB - 30
Revision history
5.	 Revision history
Revision Date Description
Rev.1A 2013-01 First published version
Rev.1B 2013-04 Preface supplemented; common typus corrected; note to potential reference STO-Out
inserted; EtherCAT IN and OUT exchanged (chap. 2.8)
GB - 31
Notices
KEB Antriebstechnik Austria GmbH
Ritzstraße 8 • A-4614 Marchtrenk
fon: +43 7243 53586-0 • fax: +43 7243 53586-21
net: www.keb.at • mail: info@keb.at
KEB Antriebstechnik
Herenveld 2 • B-9500 Geraadsbergen
fon: +32 5443 7860 • fax: +32 5443 7898
mail: vb.belgien@keb.de
KEB Power Transmission Technology (Shanghai) Co.,Ltd.
No. 435 Qianpu Road, Chedun Town, Songjiang District,
CHN-Shanghai 201611, P.R. China
fon: +86 21 37746688 • fax: +86 21 37746600
net: www.keb.cn • mail: info@keb.cn
KEB Antriebstechnik Austria GmbH
Organizační složka
K. Weise 1675/5 • CZ-370 04 České Budějovice
fon: +420 387 699 111 • fax: +420 387 699 119
net: www.keb.cz • mail: info.keb@seznam.cz
KEB Antriebstechnik GmbH
Wildbacher Str. 5 • D–08289 Schneeberg
fon: +49 3772 67-0 • fax: +49 3772 67-281
mail: info@keb-drive.de
KEB España
C/ Mitjer, Nave 8 - Pol. Ind. LA MASIA
E-08798 Sant Cugat Sesgarrigues (Barcelona)
fon: +34 93 897 0268 • fax: +34 93 899 2035
mail: vb.espana@keb.de
Société Française KEB
Z.I. de la Croix St. Nicolas • 14, rue Gustave Eiffel
F-94510 LA QUEUE EN BRIE
fon: +33 1 49620101 • fax: +33 1 45767495
net: www.keb.fr • mail: info@keb.fr
KEB (UK) Ltd.
6 Chieftain Buisiness Park, Morris Close
Park Farm, Wellingborough GB-Northants, NN8 6 XF
fon: +44 1933 402220 • fax: +44 1933 400724
net: www.keb-uk.co.uk • mail: info@keb-uk.co.uk
KEB Italia S.r.l.
Via Newton, 2 • I-20019 Settimo Milanese (Milano)
fon: +39 02 3353531 • fax: +39 02 33500790
net: www.keb.it • mail: kebitalia@keb.it
KEB Japan Ltd.
15–16, 2–Chome, Takanawa Minato-ku
J–Tokyo 108-0074
fon: +81 33 445-8515 • fax: +81 33 445-8215
mail: info@keb.jp
KEB Korea Seoul
Room 1709, 415 Missy 2000
725 Su Seo Dong, Gang Nam Gu
ROK-135-757 Seoul/South Korea
fon: +82 2 6253 6771 • fax: +82 2 6253 6770
mail: vb.korea@keb.de
KEB RUS Ltd.
Lesnaya Str. House 30, Dzerzhinsky (MO)
RUS-140091 Moscow region
fon: +7 495 550 8367 • fax: +7 495 632 0217
net: www.keb.ru • mail: info@keb.ru
KEB Sverige
Box 265 (Bergavägen 19)
S-43093 Hälsö
fon: +46 31 961520 • fax: +46 31 961124
mail: vb.schweden@keb.de
KEB America, Inc.
5100 Valley Industrial Blvd. South
USA-Shakopee, MN 55379
fon: +1 952 224-1400 • fax: +1 952 224-1499
net: www.kebamerica.com • mail: info@kebamerica.com
© KEB
Mat.No. 00F6NES-K000
Rev. 1B
Date 06/2013
More and newest addresses at http://www.keb.de
Karl E. Brinkmann GmbH
Försterweg 36-38 • D-32683 Barntrup
fon: +49 5263 401-0 • fax: +49 5263 401-116
net: www.keb.de • mail: info@keb.de
KEB worldwide…

More Related Content

What's hot

Perkins 2500 series 2506 15 industrial engine (mgb ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mgb ) service repair manualPerkins 2500 series 2506 15 industrial engine (mgb ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mgb ) service repair manualfkjsekksmem
 
Proyecto final de carrera Frío industrial e instalación fotovoltaica
Proyecto final de carrera Frío industrial e instalación fotovoltaicaProyecto final de carrera Frío industrial e instalación fotovoltaica
Proyecto final de carrera Frío industrial e instalación fotovoltaicaManuel Jose Ballesteros
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manualjsnekmse
 
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...fjkfksmemm
 
Perkins 2500 series 2506 15 industrial engine (mga ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mga ) service repair manualPerkins 2500 series 2506 15 industrial engine (mga ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mga ) service repair manualfujsejfkskemem
 
Rvl470 fr paramètre avancé
Rvl470 fr paramètre avancéRvl470 fr paramètre avancé
Rvl470 fr paramètre avancée-genieclimatique
 
CASE IH JX80 TRACTOR Service Repair Manual
CASE IH JX80 TRACTOR Service Repair ManualCASE IH JX80 TRACTOR Service Repair Manual
CASE IH JX80 TRACTOR Service Repair Manualhsemmd uksjemd
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...jksmemd eudkmmd
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...jksnmdm
 
Man f2000 codes
Man f2000 codesMan f2000 codes
Man f2000 codesovidiocr
 
Electronic modular control panel ii + paralleling emcp ii + p systems ope...
Electronic modular control panel ii + paralleling   emcp ii + p   systems ope...Electronic modular control panel ii + paralleling   emcp ii + p   systems ope...
Electronic modular control panel ii + paralleling emcp ii + p systems ope...Otorongosabroso
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manualhfjskefmmmse
 
Manual bosch horno multifunción inox hba42 r451e
Manual bosch   horno multifunción inox hba42 r451eManual bosch   horno multifunción inox hba42 r451e
Manual bosch horno multifunción inox hba42 r451eAlsako Electrodomésticos
 
Guidelines for the procurement and testing of STATCOMS
Guidelines for the procurement and testing of STATCOMSGuidelines for the procurement and testing of STATCOMS
Guidelines for the procurement and testing of STATCOMSPower System Operation
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...jknsmmem
 
Original Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power Integration
Original Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power IntegrationOriginal Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power Integration
Original Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power IntegrationAUTHELECTRONIC
 

What's hot (20)

SR988C1-20101106 Solar Water Heater Controller Manual for Split Solar Water H...
SR988C1-20101106 Solar Water Heater Controller Manual for Split Solar Water H...SR988C1-20101106 Solar Water Heater Controller Manual for Split Solar Water H...
SR988C1-20101106 Solar Water Heater Controller Manual for Split Solar Water H...
 
Perkins 2500 series 2506 15 industrial engine (mgb ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mgb ) service repair manualPerkins 2500 series 2506 15 industrial engine (mgb ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mgb ) service repair manual
 
SR1068 Solar Water Heater Controller
SR1068 Solar Water Heater ControllerSR1068 Solar Water Heater Controller
SR1068 Solar Water Heater Controller
 
Proyecto final de carrera Frío industrial e instalación fotovoltaica
Proyecto final de carrera Frío industrial e instalación fotovoltaicaProyecto final de carrera Frío industrial e instalación fotovoltaica
Proyecto final de carrera Frío industrial e instalación fotovoltaica
 
199506443 manual-de-servicio-power-comand-indio-pdf
199506443 manual-de-servicio-power-comand-indio-pdf199506443 manual-de-servicio-power-comand-indio-pdf
199506443 manual-de-servicio-power-comand-indio-pdf
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
 
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
Cummins onan c110 d5 b generator set with powercommand 1301 controller servic...
 
Perkins 2500 series 2506 15 industrial engine (mga ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mga ) service repair manualPerkins 2500 series 2506 15 industrial engine (mga ) service repair manual
Perkins 2500 series 2506 15 industrial engine (mga ) service repair manual
 
Rvl470 fr paramètre avancé
Rvl470 fr paramètre avancéRvl470 fr paramètre avancé
Rvl470 fr paramètre avancé
 
CASE IH JX80 TRACTOR Service Repair Manual
CASE IH JX80 TRACTOR Service Repair ManualCASE IH JX80 TRACTOR Service Repair Manual
CASE IH JX80 TRACTOR Service Repair Manual
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine)service ...
 
Man f2000 codes
Man f2000 codesMan f2000 codes
Man f2000 codes
 
Electronic modular control panel ii + paralleling emcp ii + p systems ope...
Electronic modular control panel ii + paralleling   emcp ii + p   systems ope...Electronic modular control panel ii + paralleling   emcp ii + p   systems ope...
Electronic modular control panel ii + paralleling emcp ii + p systems ope...
 
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair ManualPERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
PERKINS 2200 SERIES 2206D-E13TA INDUSTRIAL ENGINE Service Repair Manual
 
Manual bosch horno multifunción inox hba42 r451e
Manual bosch   horno multifunción inox hba42 r451eManual bosch   horno multifunción inox hba42 r451e
Manual bosch horno multifunción inox hba42 r451e
 
Guidelines for the procurement and testing of STATCOMS
Guidelines for the procurement and testing of STATCOMSGuidelines for the procurement and testing of STATCOMS
Guidelines for the procurement and testing of STATCOMS
 
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...
Perkins 2200 series 2206 f e13ta industrial engine (model pp3 engine) service...
 
Original Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power Integration
Original Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power IntegrationOriginal Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power Integration
Original Power Supply IC LNK626PG LNK626P LNK626 DIP-7 New Power Integration
 
Perkins 2506 15
Perkins 2506 15Perkins 2506 15
Perkins 2506 15
 

Viewers also liked

Goodrive10 english-manual
Goodrive10 english-manualGoodrive10 english-manual
Goodrive10 english-manualToàn Huỳnh
 
Vlt micro drive fc51
Vlt micro drive fc51Vlt micro drive fc51
Vlt micro drive fc51Toàn Huỳnh
 
Unidrive m200 m201 sheet issue 1
Unidrive m200   m201 sheet issue 1Unidrive m200   m201 sheet issue 1
Unidrive m200 m201 sheet issue 1Toàn Huỳnh
 
En 600stdprg fwmanual
En 600stdprg fwmanualEn 600stdprg fwmanual
En 600stdprg fwmanualToàn Huỳnh
 
VltFC 102 hvac drive operating instructions
VltFC 102  hvac drive  operating instructionsVltFC 102  hvac drive  operating instructions
VltFC 102 hvac drive operating instructionsToàn Huỳnh
 
Affinity quick start guide issue 3
Affinity quick start guide issue 3Affinity quick start guide issue 3
Affinity quick start guide issue 3Toàn Huỳnh
 
Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101Toàn Huỳnh
 
Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]Toàn Huỳnh
 
Vf fs1 instruction manual
Vf fs1 instruction manualVf fs1 instruction manual
Vf fs1 instruction manualToàn Huỳnh
 
Abb acs55-users-guide
Abb acs55-users-guideAbb acs55-users-guide
Abb acs55-users-guideToàn Huỳnh
 
Vf as1 operation-man
Vf as1 operation-manVf as1 operation-man
Vf as1 operation-manToàn Huỳnh
 
Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36Toàn Huỳnh
 

Viewers also liked (18)

Tech pv series
Tech pv seriesTech pv series
Tech pv series
 
Goodrive10 english-manual
Goodrive10 english-manualGoodrive10 english-manual
Goodrive10 english-manual
 
Vlt micro drive fc51
Vlt micro drive fc51Vlt micro drive fc51
Vlt micro drive fc51
 
Unidrive m200 m201 sheet issue 1
Unidrive m200   m201 sheet issue 1Unidrive m200   m201 sheet issue 1
Unidrive m200 m201 sheet issue 1
 
Danfoss vlt-5000
Danfoss vlt-5000Danfoss vlt-5000
Danfoss vlt-5000
 
En 600stdprg fwmanual
En 600stdprg fwmanualEn 600stdprg fwmanual
En 600stdprg fwmanual
 
VltFC 102 hvac drive operating instructions
VltFC 102  hvac drive  operating instructionsVltFC 102  hvac drive  operating instructions
VltFC 102 hvac drive operating instructions
 
Affinity quick start guide issue 3
Affinity quick start guide issue 3Affinity quick start guide issue 3
Affinity quick start guide issue 3
 
Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101
 
Fuji fvr-e9-manual
Fuji fvr-e9-manualFuji fvr-e9-manual
Fuji fvr-e9-manual
 
Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]Ct2000 pro plus_manual_english[1]
Ct2000 pro plus_manual_english[1]
 
Vf fs1 instruction manual
Vf fs1 instruction manualVf fs1 instruction manual
Vf fs1 instruction manual
 
Fr f700
Fr f700Fr f700
Fr f700
 
Abb acs55-users-guide
Abb acs55-users-guideAbb acs55-users-guide
Abb acs55-users-guide
 
Instrucsia chf100 a
Instrucsia chf100 aInstrucsia chf100 a
Instrucsia chf100 a
 
Acs355
Acs355Acs355
Acs355
 
Vf as1 operation-man
Vf as1 operation-manVf as1 operation-man
Vf as1 operation-man
 
Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36Ct2000 v english_ver 1.36
Ct2000 v english_ver 1.36
 

Similar to F6 instruction manual

B 65270 en-07
B 65270 en-07B 65270 en-07
B 65270 en-07mt7038
 
Cummins onan c300 d5 generator set with power command 1302 controller service...
Cummins onan c300 d5 generator set with power command 1302 controller service...Cummins onan c300 d5 generator set with power command 1302 controller service...
Cummins onan c300 d5 generator set with power command 1302 controller service...fjsexswkfkmsem
 
Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...fksefkskemm
 
Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...jjfkksmefm
 
Cummins onan c330 d5 generator set with power command 1302 controller service...
Cummins onan c330 d5 generator set with power command 1302 controller service...Cummins onan c330 d5 generator set with power command 1302 controller service...
Cummins onan c330 d5 generator set with power command 1302 controller service...fjsekksmem
 
Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...fjkskefkemm
 
Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...jfjskeksemmmd
 
Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...fjjskefkksem
 
Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...jfksekfmsme
 
01 890034-02-00-lv-mx3-user-manual-1
01 890034-02-00-lv-mx3-user-manual-101 890034-02-00-lv-mx3-user-manual-1
01 890034-02-00-lv-mx3-user-manual-1cesita95
 
Grupo electrogeno cummins c300 d5 z13 190330133122
Grupo electrogeno cummins c300 d5 z13 190330133122Grupo electrogeno cummins c300 d5 z13 190330133122
Grupo electrogeno cummins c300 d5 z13 190330133122PDVSA Petrodelta
 
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...fjskkddmmmse
 
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...ufsjefkskeme
 
Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...fjsekkmmme
 
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...fjsekkdkmem
 
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...fujsjfjkskekmm
 
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...fusjefjsekksemm
 
Cummins onan dggd generator set with power command 1301 controller service re...
Cummins onan dggd generator set with power command 1301 controller service re...Cummins onan dggd generator set with power command 1301 controller service re...
Cummins onan dggd generator set with power command 1301 controller service re...fusjejfjskerekem
 

Similar to F6 instruction manual (20)

Sr1128-manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-woo...
Sr1128-manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-woo...Sr1128-manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-woo...
Sr1128-manual+ultisolar-new-energy-co-ltd-solar-water-heaters-controllers-woo...
 
B 65270 en-07
B 65270 en-07B 65270 en-07
B 65270 en-07
 
Cummins onan c300 d5 generator set with power command 1302 controller service...
Cummins onan c300 d5 generator set with power command 1302 controller service...Cummins onan c300 d5 generator set with power command 1302 controller service...
Cummins onan c300 d5 generator set with power command 1302 controller service...
 
Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...
 
Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...
 
Cummins onan c330 d5 generator set with power command 1302 controller service...
Cummins onan c330 d5 generator set with power command 1302 controller service...Cummins onan c330 d5 generator set with power command 1302 controller service...
Cummins onan c330 d5 generator set with power command 1302 controller service...
 
Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...
 
Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...Cummins onan c275 d6 generator set with power command 1302 controller service...
Cummins onan c275 d6 generator set with power command 1302 controller service...
 
Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...Cummins onan c275 d5 generator set with power command 1302 controller service...
Cummins onan c275 d5 generator set with power command 1302 controller service...
 
Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...Cummins onan c300 d6 generator set with power command 1302 controller service...
Cummins onan c300 d6 generator set with power command 1302 controller service...
 
01 890034-02-00-lv-mx3-user-manual-1
01 890034-02-00-lv-mx3-user-manual-101 890034-02-00-lv-mx3-user-manual-1
01 890034-02-00-lv-mx3-user-manual-1
 
Grupo electrogeno cummins c300 d5 z13 190330133122
Grupo electrogeno cummins c300 d5 z13 190330133122Grupo electrogeno cummins c300 d5 z13 190330133122
Grupo electrogeno cummins c300 d5 z13 190330133122
 
438 ii-manual
438 ii-manual438 ii-manual
438 ii-manual
 
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
 
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqca generator set with qsk23 g3 engine and power command 2100 c...
 
Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcc generator set with qsk23 g3 engine and power command 2100 c...
 
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
 
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
 
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
Cummins onan dqcb generator set with qsk23 g3 engine and power command 2100 c...
 
Cummins onan dggd generator set with power command 1301 controller service re...
Cummins onan dggd generator set with power command 1301 controller service re...Cummins onan dggd generator set with power command 1301 controller service re...
Cummins onan dggd generator set with power command 1301 controller service re...
 

More from Toàn Huỳnh

Ct2000 f manual_english
Ct2000 f manual_englishCt2000 f manual_english
Ct2000 f manual_englishToàn Huỳnh
 
Ct2000 ev manual_english_version 1.1
Ct2000 ev manual_english_version 1.1Ct2000 ev manual_english_version 1.1
Ct2000 ev manual_english_version 1.1Toàn Huỳnh
 
Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0Toàn Huỳnh
 
En acs800 standard_fw_l
En acs800 standard_fw_lEn acs800 standard_fw_l
En acs800 standard_fw_lToàn Huỳnh
 
En acs150 um rev c_a4_screen
En acs150 um rev c_a4_screenEn acs150 um rev c_a4_screen
En acs150 um rev c_a4_screenToàn Huỳnh
 
En ach550 01_um_f_a4_lo_screenres
En ach550 01_um_f_a4_lo_screenresEn ach550 01_um_f_a4_lo_screenres
En ach550 01_um_f_a4_lo_screenresToàn Huỳnh
 
En acq810 fw manual b
En  acq810 fw manual bEn  acq810 fw manual b
En acq810 fw manual bToàn Huỳnh
 
Abb acs850-04-firmware-manual
Abb acs850-04-firmware-manualAbb acs850-04-firmware-manual
Abb acs850-04-firmware-manualToàn Huỳnh
 
Abb acs310-users-guide
Abb acs310-users-guideAbb acs310-users-guide
Abb acs310-users-guideToàn Huỳnh
 
Sv i s5 user manual-100520
Sv i s5 user manual-100520Sv i s5 user manual-100520
Sv i s5 user manual-100520Toàn Huỳnh
 
Sv i p5a-manual_(english)
Sv i p5a-manual_(english)Sv i p5a-manual_(english)
Sv i p5a-manual_(english)Toàn Huỳnh
 

More from Toàn Huỳnh (20)

Fr f700
Fr f700Fr f700
Fr f700
 
Ct2000 f manual_english
Ct2000 f manual_englishCt2000 f manual_english
Ct2000 f manual_english
 
Ct2000 ev manual_english_version 1.1
Ct2000 ev manual_english_version 1.1Ct2000 ev manual_english_version 1.1
Ct2000 ev manual_english_version 1.1
 
Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0Ct2000 es manual_english_version_1[1].0
Ct2000 es manual_english_version_1[1].0
 
En acs880 fw_man_d
En acs880 fw_man_dEn acs880 fw_man_d
En acs880 fw_man_d
 
En acs800 standard_fw_l
En acs800 standard_fw_lEn acs800 standard_fw_l
En acs800 standard_fw_l
 
En acs150 um rev c_a4_screen
En acs150 um rev c_a4_screenEn acs150 um rev c_a4_screen
En acs150 um rev c_a4_screen
 
En ach550 01_um_f_a4_lo_screenres
En ach550 01_um_f_a4_lo_screenresEn ach550 01_um_f_a4_lo_screenres
En ach550 01_um_f_a4_lo_screenres
 
En acq810 fw manual b
En  acq810 fw manual bEn  acq810 fw manual b
En acq810 fw manual b
 
Acs550 x1-rev e
Acs550 x1-rev eAcs550 x1-rev e
Acs550 x1-rev e
 
Acs550 02-us-04
Acs550 02-us-04Acs550 02-us-04
Acs550 02-us-04
 
Acs355
Acs355Acs355
Acs355
 
Abb acs850-04-firmware-manual
Abb acs850-04-firmware-manualAbb acs850-04-firmware-manual
Abb acs850-04-firmware-manual
 
Abb acs310-users-guide
Abb acs310-users-guideAbb acs310-users-guide
Abb acs310-users-guide
 
Sv i s5 user manual-100520
Sv i s5 user manual-100520Sv i s5 user manual-100520
Sv i s5 user manual-100520
 
Sv i p5a-manual_(english)
Sv i p5a-manual_(english)Sv i p5a-manual_(english)
Sv i p5a-manual_(english)
 
Sv i h
Sv i hSv i h
Sv i h
 
I v5 eng_110526
I v5 eng_110526I v5 eng_110526
I v5 eng_110526
 
I s7 eng_101201
I s7 eng_101201I s7 eng_101201
I s7 eng_101201
 
I g5a
I g5aI g5a
I g5a
 

Recently uploaded

08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking MenDelhi Call girls
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024Rafal Los
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking MenDelhi Call girls
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024The Digital Insurer
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Drew Madelung
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessPixlogix Infotech
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationSafe Software
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonetsnaman860154
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsJoaquim Jorge
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024The Digital Insurer
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking MenDelhi Call girls
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc
 
Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slidevu2urc
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEarley Information Science
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationRadu Cotescu
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 

Recently uploaded (20)

08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
Advantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your BusinessAdvantages of Hiring UIUX Design Service Providers for Your Business
Advantages of Hiring UIUX Design Service Providers for Your Business
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonets
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slide
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 

F6 instruction manual

  • 1. C O M B I V E R T Original Manual Mat.No. Rev. 00F6NES-K000 1B GB Installation Manual COMBIVERT F6 with Safety Function STO Control Circuit
  • 2.
  • 3. GB - 3 Table of Contents 1. Preface...............................................................................................................5 1.1 General.................................................................................................................................. 5 1.2 Safety Instructions............................................................................................................... 5 1.3 Validity and liability.............................................................................................................. 5 1.4 Copyright............................................................................................................................... 6 1.5 Specified application............................................................................................................ 6 1.6 Product description.............................................................................................................. 6 2. Control...............................................................................................................8 2.1 Features of the control......................................................................................................... 8 2.2 Overview................................................................................................................................ 8 2.2.1 Control terminal strip X2A....................................................................................................... 9 2.2.2 Safety terminal block X2B....................................................................................................... 9 2.2.3 CAN terminal block X2C......................................................................................................... 9 2.2.4 Analog inputs X2D................................................................................................................. 9 2.2.5 Diagnostic interface X4A......................................................................................................... 9 2.2.6 Encoder interfaces X3A, X3B................................................................................................. 9 2.3 Connection of the control.................................................................................................. 10 2.3.1 Assembly of the wires........................................................................................................... 10 2.4 Assignment of the terminal strip X2A................................................................................11 2.4.1 Connection of the digital inputs............................................................................................. 12 2.4.2 Connection of the digital outputs.......................................................................................... 12 2.5 Assignment of the STO terminal strip X2B...................................................................... 13 2.5.1 Inputs.................................................................................................................................... 13 2.5.1.1 Specification of the STO inputs............................................................................................ 13 2.5.1.2 STO with OSSD signals........................................................................................................ 13 2.5.2 Output STO........................................................................................................................... 13 2.6 Assignment of the CAN terminal strip X2C...................................................................... 14 2.7 Assignment of the terminal strip for analog inputs X2D................................................ 14 2.7.1 Connection of the analog inputs........................................................................................... 14 2.7.2 Diagnosis/visualisation......................................................................................................... 15 2.7.2.1 Assignment of the interface X4A........................................................................................... 15 2.7.2.2 Connection of the RS232 interface....................................................................................... 15 2.7.2.3 Connection of the RS485 interface....................................................................................... 15 2.7.2.4 Wiring RS485 full duplex...................................................................................................... 16 2.7.2.5 Wiring RS485 half duplex..................................................................................................... 16 2.8 Socket X4C EtherCAT IN and X4B EtherCAT OUT........................................................... 17 2.9 Encoder Parameter............................................................................................................. 17 2.9.1 Encoder interfaces X3A and X3B......................................................................................... 18 3. Safety Function STO......................................................................................19 3.1 Emergency stop according EN 60204............................................................................... 20 3.2 Classification of STO according IEC 61508...................................................................... 21 3.3 Classification of STO according EN ISO 13849................................................................ 21 3.4 Additional instructions....................................................................................................... 21 3.5 Functional Description....................................................................................................... 22 3.6 Wiring Examples................................................................................................................. 23
  • 4. GB - 4 Table of Contents 3.6.1 Direct switching off with emergency stop switch................................................................... 23 3.6.2 Direct switching off with emergency stop switch and monitoring of the wiring..................... 24 3.6.3 Direct switching off by safety module with test pulses.......................................................... 25 3.6.4 Wiring SS1............................................................................................................................ 26 4. Certification.....................................................................................................28 4.1 Annex to the declaration of conformity............................................................................ 28 5. Revision history..............................................................................................30
  • 5. GB - 5 Preface 1. Preface 1.1 General First we would like to welcome you as a customer of the company Karl E. Brinkmann GmbH and congratulation to the purchase of this product. You have decided for a product on highest technical level. The described hard- and software are developments of the Karl E. Brinkmann GmbH. The enclosed documents correspond to conditions valid at printing. Misprint, mistakes and techni- cal changes reserved. The instruction manual must be made available to the user. Before working with the unit the user must become familiar with it. This especially applies to the knowledge and observance of the following safety and warning indications. The used pictograms have following signifi- cance: Danger Is used, if life or health of the user are endangered or sub- stantial damage to property can occur. Warning Caution Attention Is used, if a measure is necessary for safe and trouble-free operation. observe at all costs Information Is used, if a measure simplifies the handling or operation of the unit. Aide Tip 1.2 Safety Instructions Observe safety and operating instruc- tions Condition for all further steps is the knowledge and obser- vance of the safety, EMC and operating instructions (part 1 „Getting Started“ 0000NEB-0000). This instruction is provi- ded with the unit or by download of www.keb.de. Non-observance of the safety instructions leads to the loss of any liability claims. The safety and warning instructions specified in this manual do not lay claim on completeness. This list is not exhaustive. 1.3 Validity and liability The use of our units in the target products is outside of our control and therefore lies exclusively in the area of responsibility of the machine manufacturer. The information contained in the technical documentation, as well as any user-specific advice in spoken and written and through tests, are made to best of our knowledge and information about the application. However, they are considered for information only without responsibil- ity. This also applies to any violation of industrial property rights of a third-party. Selection of our units in view of their suitability for the intended use must be done generally by the user.
  • 6. GB - 6 Preface Tests can only be done within the application by the machine manufacturer. They must be repeated, even if only parts of hardware, software or the unit adjustment are modified. Unauthorised opening and tampering may lead to bodily injury and property damage and may entail the loss of warranty rights. Original spare parts and authorized accessories by the manufacturer serve as security. The use of other parts excludes liability for the consequences arising out of. The suspension of liability is especially valid also for operation interruption loss, loss of profit, data loss or other damages. This is also valid, if we referred first to the possibility of such damages. If single regulations should be or become void, invalid or impracticable, the effectivity of all other regulations or agreements is not affected. 1.4 Copyright The customer may use the instruction manual as well as further documents or parts from it for internal purposes. Copyrights are with KEB and remain valid in its entirety.All rights reserved. KEB® , COMBIVERT® , KEB COMBICONTROL® and COMBIVIS® are registered trademarks of Karl E. Brinkmann GmbH. Other wordmarks or/and logos are trademarks (TM) or registered trademarks (® ) of their respective owners and are listed in the footnote on the first occurrence. When creating our documents we pay attention with the utmost care to the rights of third par- ties.Should we have not marked a trademark or breach a copyright, please inform us in order to have the possibility of remedy. 1.5 Specified application The COMBIVERT F6 serves exclusively for the control and regulation of three-phase motors. The operation of other electric consumers is prohibited and can lead to the destruction of the unit. Inverter are components designed for inclusion in electrical installations or machinery. The used semiconductors and components of KEB are developed and dimensioned for the use in industrial products. If the KEB COMBIVERT F6 is used in machines, which work under exceptional conditions or if essential functions, life-supporting measures or an extraordinary safety step must be fulfilled, the necessary reliability and security must be ensured by the machine builder. The operation of our products outside the indicated limit values of the techni- cal data leads to the loss of any liability claims. The safety function is limited to a service life of 20 years. After this time the unit must be replaced. 1.6 Product description The product family COMBIVERT F6 with safety function STO has been developed for the use in safety-oriented applications. The basic standards as well as application and country- specific standards must be observed furthermore. The standards referred in this manual must be observed supplementary ! The safety function STO according to IEC 61800-5-2 contains: • Safe torque off (Safe Torque Off - STO)
  • 7. GB - 7 Preface The safety function meet the requirements in accordance with performance level e (ISO13849- 1) and SIL 3 (IEC 61508 and IEC 62061). In case of proper project design, installation and operation the safety function protects people against mechanical damages. This accompanying instruction manual contains information for the installation and connection of the control of the KEB COMBIVERT F6, as well as the safety technology. Numerical code: Control with STO function used in Controller 1KF6Kxx-xxxx frequency inverter up to housing E (x=variable y=D, E) xxF6Kxy-xxxx 2KF6Kxx-xxxx frequency inverter upon housing G (x=variable y=G…W) xxF6Kxy-xxxx Validity of certificates The certification of controllers with safety tech- nology is only valid if the material number cor- responds with the specified numerical code und the FS logo is printed on the type plate.
  • 8. GB - 8 Control 2. Control 2.1 Features of the control The control provides the following analog and digital functions: • Hardware allocation of digital and analog inputs and outputs. • CAN bus interface • Two field bus interfaces • Serial interface for connection to a pc • Two universal encoder interfaces • Hardware of the control circuit „safety separated“ according to EN 61800-5-1 (base TN- C/-S mains) • Safety function STO (two channel torque off) 2.2 Overview Control 2KF6 X2A X2B X2C X2D X4A X3A X4B X4C X3B Control 1KF6 X2A X2B X2C X2D X4A X3A X4B X4C X3B X2A Control terminal strip X4A Diagnostic interface X2B Terminal block safety function X4B Fieldbus interface X2C CAN interface X4C X2D Analog inputs X3A Encoder interface channel 1 X3B Encoder interface channel 2
  • 9. GB - 9 Control 2.2.1 Control terminal strip X2A The control terminal block X2A is designed as double, plug-in terminal block with spring cage connection. It contains 28 pole. 2.2.2 Safety terminal block X2B The safety terminal block X2B is designed as double, plug-in terminal block with spring cage connection. It contains 10 pole. 2.2.3 CAN terminal block X2C The control terminal block X2C is designed as double, plug-in terminal block with spring cage connection. It contains 4 pole. 2.2.4 Analog inputs X2D The safety terminal block X2D is designed as double, plug-in terminal block with spring cage connection. It contains 6 pole. 2.2.5 Diagnostic interface X4A The integrated RS232/485 interface serves for the connection of service tools (e.g. COM- BIVIS) and displays. Telegram DIN66019II is used as communication protocol. 2.2.6 Encoder interfaces X3A, X3B Der COMBIVERT contains two universal encoder interfaces. The interfaces can be adapted independently by parameter to different encoder.
  • 10. GB - 10 Control 2.3 Connection of the control The following instructions must be observed at connection: Attention Prevent EMC malfunctions • Use shielded / drilled cables • Lay shield on one side of the inverter onto earth potential • Install control cables and power cables separately (approx. 10…20 cm distance); Kreuzungen im rechten Winkel verlegen • To avoid interferences a separate shielding must be provided for analog and digital control lines. Depending on the use of the relay outputs, an ex- tra shielding is to be used, too. • In case of inductive load on the relay outputs a protective wiring must be provided (e.g. free-wheeling diode)! The terminals of the control terminal strip and the transmitter inputs are se- curely isolated in accordance with EN 50178. 2.3.1 Assembly of the wires 1. Stranded wire rigidly and flexibly max. perm. cross-sec- tion stripping length x = without wire-end ferrule 1,5 mm² 10 mm with wire-end ferrule without plastic collar 1,5 mm² metal ferrule length with wire-end ferrule with plastic collar 1 mm² metal ferrule length + 2 mm X 2. Press with screw driver (A) or some- thing else onto the labelling 3. Plug stranded wire (B) into the square slot, that no wires can be seen from the outside. 4. Remove screw driver (A) and check if the line (B) is fixed. Make sure that the stranded wire and not the insula- tion is clamped.
  • 11. GB - 11 Control 2.4 Assignment of the terminal strip X2A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 PIN Name Description Specifications 1 Out1 Digital output 1 Imax =100 mA 2 0V Reference potential for digital output 3 Out2 Digital output 2 Imax =100 mA 4 0V Reference potential for digital output 5 Out3 Digital output 3 Imax =100 mA 6 0V Reference potential for digital output 7 Out4 Digital output 4 Imax =100 mA 8 0V Reference potential for digital output 9 I1 Digital input 1 10 24V Voltage output for the control of the inputs +24 Vdc* 11 I2 Digital input 2 12 24V Voltage output for the control of the inputs +24 Vdc* 13 I3 Digital input 3 14 24V Voltage output for the control of the inputs +24 Vdc* 15 I4 Digital input 4 16 24V Voltage output for the control of the inputs +24 Vdc* 17 I5 Digital input 5 18 24V Voltage output for the control of the inputs +24 Vdc* 19 I6 Digital input 6 20 24V Voltage output for the control of the inputs +24 Vdc* 21 I7 Digital input 7 22 24V Voltage output for the control of the inputs +24 Vdc* 23 I8 Digital input 8 24 24V Voltage output for the control of the inputs +24 Vdc* 25 24Vin Voltage input for external supply 24 Vdc ± 25 % 26 0V Reference potential for 24Vin 27 CRF 10 V Reference voltage for analog inputs 10 Vdc / Imax = 4 mA 28 AGND Analog mass (do not connect to 0 V) *) Total current of all 24 Vdc outputs: 100 mA
  • 12. GB - 12 Control 2.4.1 Connection of the digital inputs Examples for the connection of the digital inputs with internal voltage supply with external voltage supply 18 17 20 19 22 21 24 23 121416 11 10 9 1315 24 23 101214 9 26 251113 + 2.4.2 Connection of the digital outputs Examples for the connection of the digital outputs Connection appliance Connection to an external control 3 4 5 6 7 8 1 2 31 2 4 5 6 7 8 COM DI1 DI3DI2 DI4
  • 13. GB - 13 Control 2.5 Assignment of the STO terminal strip X2B X2B PIN Name I/O 1 2 3 5 6 7 8 9 104 1 STO1+ Input STO channel 1 2 STO1+ 3 STO1- 4 STO1- 5 STO2+ Input STO channel 2 6 STO2+ 7 STO2- 8 STO2- 9 STO-OUT Output STO 10 STO-OUT The individual channels are designed potential-free, so 24V and 0 V can be connected. The inputs are designed by way that safety switchgear units with test pulses (OSSD signals) can be connected. The signals are not evaluated, they are only filtered. The OSSD test interval is limited to 10 ms. The reference potential for output STO-OUT (terminals X2B/9 and 10) is the mass of the control 0V (terminal X2A/26). 2.5.1 Inputs 2.5.1.1 Specification of the STO inputs STO Inputs Status 0 Status 1 UL [V] IL [mA] UH [V] IH [mA] max. 5 25 30 25 min. -3 not defined 15 5 The maximum short-term starting current of the input is limited to 300 mA. 2.5.1.2 STO with OSSD signals The filter time depends on the minimum input voltage and can be specified as follows: Input voltage [V] OSSD pulse width [ms] 15 0.1 18 0.8 20 1.1 24 1.5 30 1.8 2.5.2 Output STO The short-circuit proof, digital output is specified in accordance with IEC61131-2. The output rated current is 100 mA at 24 Vdc. The output is 24 Vdc if the inputs STO1 and STO2 are set.
  • 14. GB - 14 Control 2.6 Assignment of the CAN terminal strip X2C X2C PIN Name Notes 1 2 3 4 1 CAN high internally bridged 2 CAN high 3 CAN low internally bridged 4 CAN low 2.7 Assignment of the terminal strip for analog inputs X2D X2D PIN Name Notes Specification 1 2 3 4 5 6 1 AN1- non-floating differential input 1 ±10 Vdc or 4…20 mA2 AN1+ 3 AN2- non-floating differential input 2 ±10 Vdc or 4…20 mA4 AN2+ 5 AN3- non-floating differential input 3 ±10 Vdc 6 AN3+ 2.7.1 Connection of the analog inputs Examples for the connection of the analog setpoint input 628 5 4 3 2 127 R = 0…3/5/10kΩ 4 6 3 2 1 5 28 27 + * 0…±10Vdc 2 1 4 3 6 5 + 4…20mA *) Connect potential equalizing line only if a potential difference of >30 V exists between the controls. The internal resistance is reduced to 30 kΩ.
  • 15. GB - 15 Control 2.7.2 Diagnosis/visualisation The integrated RS232/485 interface serves for the connection of service tools (e.g. COM- BIVIS) and displays. Telegram DIN66019II is used as communication protocol. The correct configuration and language file must be loaded for the operation with COMBIVIS. The downlad can be done via the KEB website. Interface Standard Connecting cable RS485 TIA/EIA-485 and ISO 8482 RS232 ANSI TIA/EIA-232 0058025-001D RS232/USB 0058060-0020 2.7.2.1 Assignment of the interface X4A 54321 9876 54321 9876 reserved 1 6 reserved TxD (RS232) 2 7 DGND (reference potential) RxD (RS232) 3 8 TxD-A (RS485) RxD-A (RS485) 4 9 TxD-B (RS485) RxD-B (RS485) 5 2.7.2.2 Connection of the RS232 interface A RS232-cable is needed to connect the interface operator with the PC. Serial cable to connect the operator with a PC 0058025-001D 1 5 6 9 1 5 6 9 2.7.2.3 Connection of the RS485 interface The following instructions must be observed in order to prevent interferences at the RS485 interface: • use CAT 5 cable (in pairs, twisted and shielded cable) • ground at one side (prior at interference-free side) • Connect terminating resistors (120 Ω) at both ends on pair of wires of the communication bus If CAT 7 cable is used (by way of derogation from our recommendation) lay the interior shield each to the transmitter.
  • 16. GB - 16 Control A biasing can be used if there are still interferences. However, this should be done only once at the communication bus (preferably at the master). 2.7.2.4 Wiring RS485 full duplex 5 4 3 2 1 9 8 7 6 COMBIVERT 5 4 3 2 1 9 8 7 6 COMBIVERT 4 5 8 9 4 5 8 9 Master TxD-A TxD-B RxD-A RxD-B R R R R R=120Ω 2.7.2.5 Wiring RS485 half duplex 5 4 3 2 1 9 8 7 6 COMBIVERT 4 58 9 5 4 3 2 1 9 8 7 6 COMBIVERT 4 58 9 Master RXD/TxD-A RXD/TxD-B R R R=120Ω
  • 17. GB - 17 Control 2.8 Socket X4C EtherCAT IN and X4B EtherCAT OUT Description of the LEDs Name Description Bus speed (yellow) 18 X4B EtherCAT IN Link/Activity (green) Bus speed (yellow) 18 X4C EtherCAT OUT Link/Activity (green) LED bus speed (yellow) Function off Transmission error on EtherCAT ready for operation with 100 MBit LED Link/Activity (green) Function off Port closed; no data transfer on Port opened; no data transfer flicker Port opened with data transfer 2.9 Encoder Parameter The control contains two encoder interfaces. The assignment of the pin connectors is identi- cal. The following limitations are valid when operating with two encoders: • The voltage supplies 5V and 8V are generated with one programmable voltage source. Only encoders with 5V or 8V supply are possible (e.g. BiSS and HIPERFACE are not possible). • There is only one Endat core on the encoder interface, therefore operation of a digital EnDat 2.2 encoder together with a EnDat analog encoder is not possible.
  • 18. GB - 18 Control 2.9.1 Encoder interfaces X3A and X3B Do not plug on/remove en- coder cable during operation To avoid undefined states do not plug on/remove the encoder cable during operation. The integrated encoder interfaces are designed for different encoders. The following table contains the possible encoders and the appropriate signal assignment of the plug connector. Pin assignment according to the adjusted encoder interface (frontview of the control) 2 4 6 8 10 12 14 16 18 1 3 5 7 9 11 13 15 17 encoder PIN Inc-TTL Resolver Hiperface SinCos Endat Sin/ Cos- SSI Endat 2.2 BiSS 1 A+ COS+ COS+ COS+ COS+ 2 A- COS- COS- COS- COS- 3 B+ SIN+ SIN+ SIN+ SIN+ 4 B- SIN- SIN- SIN- SIN- 5 N+ Data+ N+ Data+ Data+ Data+ Data+ 6 N- Data- N- Data- Data- Data- Data- 7 COS+ Cos_abs+ Clock- Clock- Clock- Clock- 8 COS- Cos_abs- 9 SIN+ Sin_abs+ Clock+ Clock+ Clock+ Clock+ 10 SIN- Sin_abs- 11 Exciter+ 12 Exciter- 13 COM COM COM COM COM COM COM COM 14 COM Internal shielding COM COM COM COM COM COM 15 8V 8V 8V 8V 8V 8V 8V 16 5.25V 5.25V 5.25V 5.25V 5.25V 5.25V 5.25V 17 24V 24V 24V 24V 24V 24V 24V 18 COM COM COM COM COM COM COM Shielding open with heat-shrink tube and wire-end ferrule
  • 19. GB - 19 Safety Function STO 3. Safety Function STO Only qualified Staff Uncontrolled start is possible by improper installation of the safe- ty technology. This may cause death, serious bodily injuries or substantial damage to property. Therefore the safety function may only be installed and put into operation by qualified personnel which are trained in safety tech- nology. Observe all costs The COMBIVERT F6 with safety function must not be started until it is determined that the installation complies with 2006/42/ EC (machine directive) as well as the EMC directive (2004/108/ EC)(note EN60204). The COMBIVERT F6 with safety function meets the require- ments of the Low-Voltage Directive 2006/95/EC. The harmo- nized standard of the series EN 61800‑5‑1 (VDE 0160) is used. This is a product of limited availability in accordance with IEC 61800-3. This product may cause radio interference in residen- tial areas. In this case the operator may need to take correspond- ing measures. With electronic protection devices the safety function is integrated in the drive control in order to minimize or eliminate danger by malfunctions in machines. The integrated safety function replace the complex installation of external safety components. The safety function can be requested or released by an error. Regular checks In order to ensure permanent security, the function must be checked in regular intervals according to the results of the risk analysis. Installation work or troubleshooting can be necessary in hazard areas, whereby protective devices such as line- or motor contactors shall not be activated. The safety function STO can be used there. Depending on the application the use of line or motor contactors can be void by using STO. In case of error or request, the power semiconductor of the drive module are switched off and the drive is not supplied, which causes a rotation or torque (in case of a linear drive move- ment or force). The unit can be safe switched off and/or remain if an error occurs. Electric Shock Continue mains voltage with active STO function. Compared to the disconnection by line contactors or motor contactors the integrated safety function enables a simple integration of drives to functional groups of a system. Thereby safe torque off can be limited to certain systems. A further advantage is that the recharge and dis- charge time of the inverter DC link must not be considered. Thus the unit is faster again ready for operation after an interruption. Regular electromechanical equipment are liable to abrasion. Loss of these equipment occurs by using the STO function and the maintenance costs are reduced.
  • 20. GB - 20 Safety Function STO Characteristic data for „Safe torque off“ • Power supply for the rotation direction of the motor is interrupted (free-wheeling motor) • Used when monitoring of standstill is not necessary • Unintentional starting of the motor is prevented • No galvanic isolation of the motor from the inverter DC link What is realized by the STO function related to EN 60204 ? Emergency stop can be realized by the STO function, since the mains voltage may remain effective. Emergency stop can be realized only in connection with a line contactor, which disconnects the mains voltage ! 3.1 Emergency stop according EN 60204 By using suitable safety switchgear units, stop category 0 and 1 according to EN 60204 can be reached by the STO function in the system. Note chapter 6 for safety switchgear units. Stop category 0 „uncontrolled stop“, i.e. stop by immediate removal of power to the actuators. Stop category 1 „controlled stop“, i.e. power to the actuators is retained to apply braking until the stop is achieved. The energy is switched off at standstill. Emergency stop to EN 60204 must be functional in all operating modes of the drive module. The reset of emergency stop may not lead to an uncontrolled start of the drive. Restart only after confirmation The drive restarts if function STO is no longer released. In order to comply with EN 60204, it must be ensured by external meas- ures that the drive restarts only after confirmation. Without mechanical brake the drive leads to coast; motor is free-wheeling. Additional protec- tive devices must be installed (e.g.locking systems) if damage to persons or property can occur. Ensure coast of the motor If danger to persons occur after switching off the motor control by STO, the entrance to hazard areas must remain closed until the drive stops. Jerks in error case In case of double malfunction it can lead to unwanted jerk, the rotation angle is depending on the number of poles of the se- lected drive and the gear ratio. Calculation of the jerk: Rotation angle of the jerk WR [°] = 180° ––––––––––––––––––––––––––––––––– Pole-pair number p • gear reduction ratio g
  • 21. GB - 21 Safety Function STO This behaviour can occur either by a short circuit of the IGBTs or by interconnection (also short circuit) of the control drivers. The error should be regarded as critical, if the drive re- mains in STO status. 3.2 Classification of STO according IEC 61508 PFH 2.6 • 10-12 1/h PFD 2.3 • 10-7 on demand Proof-Test-Interval T 20 years For SIL classification in connection with the applications consider the failure rates of the ex- ternal switch devices for final evaluation. 3.3 Classification of STO according EN ISO 13849 Control category 4 MTTFD >1000 years DC high For the classification within a performance level in connection with the applications consider the failure rates of the external switch devices for final evaluation. 3.4 Additional instructions • The unit must be isolated from mains by main switch when working on parts under volt- age. • Mechanical brakes must be installed additionally if external forces have effect to the drive axis, e.g. vertical axes (hanging loads) or rotary axes with asymmetrical weight distribu- tion. • For the protection against pollution (pollution degree 2) the installation of the units must be provided in environment with increased protection (e. g. control cabinet IP 54). • Make sure that no small parts fall into the COMBIVERT during assembly and wiring. This also applies to mechanical components, which can lose small parts during operation. • Check the safety functions and error responses and generate an acceptance report after installation. • The start-up can be prevented with interruption of the STO signals. STO may not be released in case of danger according to EN 60204-1. Also note the instructions to the external safety switch devices. • Dimension the safety application by way that the corresponding input current of the safety functions is available for the inputs (see chapter 2.5.1). Selection of suitable volt- age sources Use for the connection only suitable voltage sources with safe isolation (SELV / PELV) in accordance with VDE 0100 with nom- inal voltage of 24 Vdc ± 10%. Pay attention on a sufficient over- voltage category of the voltage supply.
  • 22. GB - 22 Safety Function STO 3.5 Functional Description The COMBIVERT with integrated safety function meets the following function according to IEC 61800-5-2: • „Safe torque off“ (Safe Torque Off – STO) The safety-related disconnection according to STO is reached by a two-cannel opto-coupler blockage. The supply of the opto-couplers, which are responsible for the commutation of the connected drive occurs via transformation coupling of the input voltage. This ensures at input voltage loss that no supply of the opto-couplers is possible. If the opto-couplers are not longer supplied, no IGBT can be controlled and thus no energy can be supplied to the drive. The two channels are reached by way that input STO1 prevents the voltage supply (VTRO) of the upper opto-couplers of the inverter bridge and input STO2 the lower opto-couplers (VTRU). Technical data of the STO function Maximum ON delay (UIN = 15V) 7 ms Maximum OFF delay (UIN=30 V) at … active modulation 10 ms … inactive modulation until safe state of the driver voltage is reached 50 ms
  • 23. GB - 23 Safety Function STO 3.6 Wiring Examples 3.6.1 Direct switching off with emergency stop switch U V W PE M X1A X4A 1 - STO1+ 2 - STO1+ 3 - STO1- 4 - STO1- 5 - STO2+ 6 - STO2+ 7 - STO2- 8 - STO2- 9 - STO-OUT 10 - STO-OUT Terminal strip X2B + - 24Vdc X2A X2C X2D Diagnosis X4B Field bus X4C Field bus Power circuit Control circuit Safety module At operation of an emergency stop unit, when both contacts are connected to- gether against a positive supply signal, make sure that there are no crossfaults. The wiring must be suitable arranged.
  • 24. GB - 24 Safety Function STO 3.6.2 Direct switching off with emergency stop switch and monitoring of the wiring U V W PE M X1A Terminal strip X2B + - 24Vdc Power circuit Control circuit Safety module 1 - STO1+ 2 - STO1+ 3 - STO1- 4 - STO1- 5 - STO2+ 6 - STO2+ 7 - STO2- 8 - STO2- 9 - STO-OUT 10 - STO-OUT X2A X2C X2D X4A Diagnosis X4B Field bus X4C Field bus The displayed circuit shows wiring errors in the area of the emergency stop unit and supply line. A possible short circuit on the primary side of the emergency stop switchgear (mass and 24 Vdc) and a short circuit on the secondary side of the unit or within the wiring leads either directly or with closed contacts to a short circuit of the supply, whereby a series-connected 24V fuse triggers. Besides the two displayed applications with an emergency stop switchgear, other sensors (like door switches etc.) can be used similarly.
  • 25. GB - 25 Safety Function STO 3.6.3 Direct switching off by safety module with test pulses U V W PE M X1A Terminal strip X2B Power circuit Control circuitopen closed S1 S2 Safety device Receipt Safety module 1 - STO1+ 2 - STO1+ 3 - STO1- 4 - STO1- 5 - STO2+ 6 - STO2+ 7 - STO2- 8 - STO2- 9 - STO-OUT 10 - STO-OUT X2A X2C X2D X4A Diagnosis X4B Field bus X4C Field bus With operation of the emergency stop unit, e.g. by protection door, the release paths of the safety module are disconnected. This leads to the loss of the STO signals (X2B.1 and 5) and thus to energy disconnection of the drive. The safety module makes a consistency check of all signal paths via test signals (OSSD).
  • 26. GB - 26 Safety Function STO 3.6.4 Wiring SS1 At tripping SS1 (Safe Stop 1) the drive is only disconnected from supply when it has reached a standstill [IEC 61800-5-2]. The stop mode is not directly requested, but the maximum time until reaching the standstill is estimated. This period is loaded in a safe time relay, which dis- connects the drive finally from supply. U V W PE M X1A X4A Terminal strip X2B Diagnosis Power circuit Control circuitopen closed S1 S2 Safety device Receipt X2A.13 Safety module 1 - STO1+ 2 - STO1+ 3 - STO1- 4 - STO1- 5 - STO2+ 6 - STO2+ 7 - STO2- 8 - STO2- 9 - STO-OUT 10 - STO-OUT X2A X2C X2D Field bus Motion Control X4B Field bus X4C Field bus When pressing the emergency stop unit the drive is stopped with a deceleration ramp via input X2A.13 (I3). Simultaneously the expiration of the safe time occurs in the safety module. After expiration of the safe period the control signals STO1+ und STO2+ (X2B.1 and 5) are removed and thus the energy supply of the drive is disconnected. The following adjustments must be done in the drive module for the function „drive stop“: Parameter Adjustment pn29 „prg. error stop. mode“ (Index 0x2A1D) 1: dec. ramp -> Fault pn48-59 (0x2A30-0x2A3C) Adjustment of the deceleration and jerk values for the adjusted error reaction pn30 „prog. error source“ (Index 0x2A1E) 4: I3 (here in the example)
  • 27. GB - 27 Safety Function STO Function: If the selected input becomes active, the drive decelerates with the adjusted decel- eration ramp and changes then into status 59 „Error prog. input“.
  • 28. GB - 28 Annex 4. Certification 4.1 Annex to the declaration of conformity Annex to the declaration of conformity EC for systems with functional safety: Product designation: Inverter - type series xxF6Kxx-xxxx Dimension 07 - 36 Voltage class 200 Vac; 400 Vac; 600 Vac Herewith we declare that the safety module described above corresponds with all relevant regulations of the machinery safety directive 2006/42/EC. The above mentioned safety module meets the requirements of the following guidelines and standards: • Machinery safety directive 2006/42/EC • EMC directive 2004/108/EC • Low-Voltage Directive 2006/95/EC EN standards Output Text Reference Output EN 61800-5-1 09/2003 Electrical power drive systems with ad- justable speed: security requirements VDE 0160 Part 105 09/2003 informative: EN 50178 1997 Installation of high voltage systems with electronic equipment VDE 0160 04/1998 EN 60664-1 2007 Isolation coordinats for electrical equip- ment in low-voltage systems VDE 0110 01/2008 EN 61800-2 10/1998 Basic determinations for AC inverter VDE 0160 Part 102 08/1999 especially for systems with functional safety additionally: EN 61800-5-2 2007 Electrical power drive systems with ad- justable speed: functional safety require- ments VDE 0160 Part 105-2 04/2008 EN 61508-(1…7) Functional safety of electrical/electronic/ programmable electronic safety-related systems - Part 1 up to 7 VDE 0803 11/2002 EN 60204-1 +A1 2006 2009 Electrical equipment of machines; Part1: General requirements VDE 0113-1 +A1 2007 10/2009 EN 62061 Safety of machinery functional security requirements VDE 0113 Part 50 10/2005 EN 13849-(1, 2) Safety of machinery – 08/2008
  • 29. GB - 29 Annex The conformity was confirmed by the TÜV Rheinland with the EC type examination 01/205/5332/13. The number/address of the indicated constitution: NB 0035 TÜV Rheinland Industrie Service GmbH Alboinstr. 56, 12103 Berlin Germany Tel.: +49 30 7562-1557 Fax: +49 30 7562-1370 E-Mail: tuvat@de.tuv.com
  • 30. GB - 30 Revision history 5. Revision history Revision Date Description Rev.1A 2013-01 First published version Rev.1B 2013-04 Preface supplemented; common typus corrected; note to potential reference STO-Out inserted; EtherCAT IN and OUT exchanged (chap. 2.8)
  • 32. KEB Antriebstechnik Austria GmbH Ritzstraße 8 • A-4614 Marchtrenk fon: +43 7243 53586-0 • fax: +43 7243 53586-21 net: www.keb.at • mail: info@keb.at KEB Antriebstechnik Herenveld 2 • B-9500 Geraadsbergen fon: +32 5443 7860 • fax: +32 5443 7898 mail: vb.belgien@keb.de KEB Power Transmission Technology (Shanghai) Co.,Ltd. No. 435 Qianpu Road, Chedun Town, Songjiang District, CHN-Shanghai 201611, P.R. China fon: +86 21 37746688 • fax: +86 21 37746600 net: www.keb.cn • mail: info@keb.cn KEB Antriebstechnik Austria GmbH Organizační složka K. Weise 1675/5 • CZ-370 04 České Budějovice fon: +420 387 699 111 • fax: +420 387 699 119 net: www.keb.cz • mail: info.keb@seznam.cz KEB Antriebstechnik GmbH Wildbacher Str. 5 • D–08289 Schneeberg fon: +49 3772 67-0 • fax: +49 3772 67-281 mail: info@keb-drive.de KEB España C/ Mitjer, Nave 8 - Pol. Ind. LA MASIA E-08798 Sant Cugat Sesgarrigues (Barcelona) fon: +34 93 897 0268 • fax: +34 93 899 2035 mail: vb.espana@keb.de Société Française KEB Z.I. de la Croix St. Nicolas • 14, rue Gustave Eiffel F-94510 LA QUEUE EN BRIE fon: +33 1 49620101 • fax: +33 1 45767495 net: www.keb.fr • mail: info@keb.fr KEB (UK) Ltd. 6 Chieftain Buisiness Park, Morris Close Park Farm, Wellingborough GB-Northants, NN8 6 XF fon: +44 1933 402220 • fax: +44 1933 400724 net: www.keb-uk.co.uk • mail: info@keb-uk.co.uk KEB Italia S.r.l. Via Newton, 2 • I-20019 Settimo Milanese (Milano) fon: +39 02 3353531 • fax: +39 02 33500790 net: www.keb.it • mail: kebitalia@keb.it KEB Japan Ltd. 15–16, 2–Chome, Takanawa Minato-ku J–Tokyo 108-0074 fon: +81 33 445-8515 • fax: +81 33 445-8215 mail: info@keb.jp KEB Korea Seoul Room 1709, 415 Missy 2000 725 Su Seo Dong, Gang Nam Gu ROK-135-757 Seoul/South Korea fon: +82 2 6253 6771 • fax: +82 2 6253 6770 mail: vb.korea@keb.de KEB RUS Ltd. Lesnaya Str. House 30, Dzerzhinsky (MO) RUS-140091 Moscow region fon: +7 495 550 8367 • fax: +7 495 632 0217 net: www.keb.ru • mail: info@keb.ru KEB Sverige Box 265 (Bergavägen 19) S-43093 Hälsö fon: +46 31 961520 • fax: +46 31 961124 mail: vb.schweden@keb.de KEB America, Inc. 5100 Valley Industrial Blvd. South USA-Shakopee, MN 55379 fon: +1 952 224-1400 • fax: +1 952 224-1499 net: www.kebamerica.com • mail: info@kebamerica.com © KEB Mat.No. 00F6NES-K000 Rev. 1B Date 06/2013 More and newest addresses at http://www.keb.de Karl E. Brinkmann GmbH Försterweg 36-38 • D-32683 Barntrup fon: +49 5263 401-0 • fax: +49 5263 401-116 net: www.keb.de • mail: info@keb.de KEB worldwide…