1. SFT
SERIES
HRC-80
Hydrocarbon & Sediment
Cartridge Filter
Transformer Secondary Containment
Water remedial cartridge with smart polymer technology
Hydrocarbons captured & encapsulated in the smart polymer media
Prevents hydrocarbons/sediment from leaving the containment area
Flow rate from 6 to 80 litre / minute
Automatic system shut down at oil saturation point
Easy clean out & low maintenance
HRC cartridges are designed to remove hydrocarbons & sediment
contaminants from groundwater accumulation in liquid transformer
secondary containment systems.
Dielectric fluids are absorbed by the smart filtration technology which bond with the
hydrocarbon molecules to efficiently encapsulate and solidify hydrocarbons internally in
the cartridge and remove the hydrocarbons from the groundwater, filtered groundwater
passes unimpeded through the filter. The discharged water conforms to the EA PPG3
guidelines for discharge to surface drains and water environment, achieving a discharge
concentration of <5mg/litre of oil under standard test conditions.
When the HRC filters start to reach their hydrocarbon absorption capacity the flow of
groundwater will become increasingly restricted until the cartridge automatically shut-
down and therefore prevent any polluted groundwater from leaving the containment area
or entering the filter ensuring that no contaminates are introduced in to the environment.
The hydrocarbons and sediment filters are conveniently enclosed within one cartridge
body eliminating the need for two individual filters (hydrocarbon & sediment) to be
connected in series. The sediment filter is easily accessed for inspection and cleaned by
backflushing the cartridge from the discharge side of the cartridge with clean water.
2. SFT
SERIES
HRC-80
Specification & Technical
Data
The Stables Gattinetts Hadleigh Road East Bergholt Colchester Essex CO7 6QT
e: info@capturegreen.com t: +44 (0)1206 299388 w: capturegreen.com
Code Description
Flow Rate
(litre/min)
Hydrocarbon
Capacity (litre)
Sediment Filter
Size (µm)
Pressure
(bar/psi)
HRC-01 T1.5 T1 HRC Type 1T 6.0* 1.0 150 1 / 14.5
HRC-03 T2.0 T2 HRC Type 2T 15.0* 3.1 150 1 / 14.5
HRC-03 F2.0 T2 HRC Type 2F 15.0* 3.1 150 1 / 14.5
HRF-16 T4.0 T3 HRC Type 3T 80.0** 16.0 150 1 / 14.5
HRF-16 C4.0 T3 HRC Type 3T 80.0** 16.0 150 1 / 14.5
Code Description Fitting
Length
(mm/inch)
Diameter
(mm/inch)
Weight
(kg/lbs)
HRC-01 T1.5 T1 HRC Type 1T 1½” BSP thread 405 / 15.9 100 / 3.94 1.4 / 3.0
HRC-03 T2.0 T2 HRC Type 2T 2” BSP thread 647 / 25.5 114 / 4.5 3.2 / 7.1
HRC-03 F2.0 T2 HRC Type 2F 228 OD flange 400 / 15.7 228 / 9.0 3.3 / 7.3
HRF-16 T4.0 T3 HRC Type 3T 4” BSP thread 520 / 20.5 255 / 10.0 9.7 / 21.4
HRF-16 C4.0 T3 HRC Type 3T 4” Camlock 593.4 / 23.4 284 / 11.18 9.3 / 20.5
Code Description Fitting
Length
(mm/inch)
Depth
(mm/inch)
WFA-CF T1.5 T1 1.5” Wall fitting assembly & isolation valve 165 OD flange 432 / 17.0 245 / 9.7
WFA-CF T2.0 T2 2” Wall fitting assembly & isolation valve 165 OD flange 432 / 17.0 245 / 9.7
Notes: * test result at 150mm.
** test result at 50mm.
Capture Green reserves the right to change or update, without notice, any technical
information contained in this datasheet. Capture Green also reserves the right, without
notice, to change the design or construction of the product and to discontinue
SDS: SFT HRC-80 July 16
Sediment Trap
The filter can be easily
emptied & flushed out during
maintenance.
Smart Polymer Media
The polymer encapsulates & solidifies
the hydrocarbons to prevent their passing.
Filter Discharge Portal
Hydrocarbon presence <5ppm
Sediment particles ≤150µm
Filter Entry
Portal