Inspection # 221114015
1566 Olive Ave. Chula Vista, CA 91911
Buyer
Irving Velazquez –irving17@hotmail.com
Buyer Agent
Dilia A. Cade – diliabesthomes@gmail.com
Harry R. Caruso, III CRI
Inspector Caruso
Home Inspections
760-498-3357/ (858)342-0616
www.inspectorcaruso.com
Inspection Agreement
(Please Read Carefully)
This Agreement is made and entered into by and between Inspector Caruso, referred to as “Inspector”, Irving Velazquez, referred to as “Client.”
In consideration of the promise and terms of this Agreement, the parties agree as follows:
1. The inspector will perform a visual inspection and prepare a digital report of the apparent condition of the readily accessible installed systems and components of the property, existing at the time
of inspection. Latent and concealed defects and deficiencies are excluded from the inspection. Photographs and video of this inspection are the sole property of inspector.
2. The client will pay the sum of $325.00 for the inspection of the “Property and Garage” being inspected if applicable, located at 1566 Olive Ave. Chula Vista, CA 91911.
3. The parties agree that the “Standards of Practice” (NAHI Standards) shall define the standard of duty and the conditions, limitations, and exclusions of the inspection and are incorporated by the
reference herein. If the State /Province where the inspection is performed imposes more stringent standards or administrative rule, then those standards shall define the standards of duty and the
conditions, limitations, and exclusions of the inspection.
4. The parties agree and understand that the Inspector and its employees and its agents assume no liability or responsibility for the costs of repairing or replacing any unreported defects or
deficiencies either current or arising in the future or any property damage, consequential damage or bodily injury of any nature. If repairs or replacement are done without giving the Inspector the
required notice, the Inspector will have no liability to the client. The Client further agrees that the Inspector is liable only up to the cost of the inspection.
5. The parties agree and understand the Inspector is not an insurer nor guarantor against defects in the structure, items, components, or systems inspected. The INSPECTOR MAKES NO
WARRANTY, EXPRESSED OR IMPLIED, AS TO THE FITNESS OF USE, CONDITION, PERFORMANCE OR ADEQUACY OF ANY INSPECTED STRUCTURE, ITEM, COMPONENT, OR SYSTEM CONDITION
AT TIME OF INSPECTION.
6. If client is married, Client represents that this obligation is a family obligation incurred in the interest of the family.
7. This agreement, including the additional terms and conditions, represent the entire agreement between the parties and there are no other agreements either written or oral between them. This
Agreement shall be amended only by written agreement signed by both parties. This Agreement shall be construed and enforced in accordance with the laws of the State of California, San Diego
County.
Client has read this entire Agreement and accepts and understands this Agreement as herby acknowledged.
This report adheres to the NAHI Standards, which are available upon request and on line at www.inspectorcaruso.com.
Additional Terms, Conditions, and Limitations
8. Systems, items, and conditions which are not within the scope of the building inspection include, but are not limited to: radon, formaldehyde, lead paint, asbestos, toxic or flammable materials, molds, fungi, other
environmental hazards; pest infestation; security and fire protection systems; household appliances; humidifiers; paint, wallpaper and other treatments to windows, interior walls, ceilings, and floors; recreational
equipment or facilities; pool/spa water purification systems (ozone generator/saltwater, etc.); underground storage tanks, energy efficiency measurements; motion or photo-electric sensor lighting; concealed or
private secured systems; water wells; all overflow drains; heating system's accessories; solar heating systems; heat exchangers; sprinkling systems; water softener or purification systems; central vacuum
systems; telephone, intercom or cable TV systems; antennae, lightning arrestors, load controllers; trees or plants; governing codes, ordinances, statutes, and covenants; and manufacturer specifications, recalls,
and EIFS. Client understands that these systems, items, and conditions are excluded from this inspection. Any general comments about these systems, items, and conditions of the written or digital reports are
informal only and DOES NOT represent an inspection.
9. The Inspection and report are performed and prepared for the sole and exclusive use and possession of the Client. No other person or entity may rely on the report issued pursuant to this Agreement. In the
event that any person, not a party to this Agreement, makes any claim against Inspector, its employees or agents, arising out of the services performed by Inspector under this Agreement, the Client agrees to
indemnify, defend, and hold harmless Inspector from any and all damages, expenses, costs, and attorney fees arising from such a claim.
10. The Inspection will not include an appraisal of the value or a survey. The written report is not a compliance inspection or certification for past or present governmental codes or regulations of any kind.
11. In the event of a claim by the Client that an installed system or component of the premises which was inspected by the Inspector was not in the condition reported by the Inspector, the Client agrees to notify the
Inspector at least 72 hours prior to repairing or replacing such system or component. The Client further agrees that the Inspector is liable only if there has been a complete failure to follow the standards adhered to
in the report or State/Province law. Furthermore, any legal action must be brought within two (2) years from the date of the inspection, or will be deemed waived and forever barred.
12. This inspection does not determine whether the property is insurable.
13. These definitions will be documented on the report:
A. Apparent Condition: Systems and components are rated as follows:
SATISFACTORY (S) - Indicates the component is functionally consistent with its original purpose but may show signs of normal wear and tear and deterioration.
MARGINAL (M) - Indicates the component will probably require repair or replacement anytime within five years.
POOR (P)- Indicates the component will need repair or replacement now or very near future.
SIGNIFICANT ISSUES (SI) - A system or component that is considered significantly deficient, inoperable or is unsafe.
SAFETY HAZARD - Denotes a condition that is unsafe and in need of prompt attention.
B. Installed systems and components: structural components; exterior; interior; roofing; plumbing; electrical; heating; central air-conditioning (weather permitting); insulation and ventilation.
C. Readily accessible systems and components: only those systems and components where Inspector is not required to remove or move personal items, furniture, equipment, soil, snow, or other items which
obstruct access or visibility.
D. Any component not listed as being deficient in some manner is assumed to be satisfactory.
E. Regardless of the age of the building we recommend inquiring about any permits and inspection records, with final signatures, for the building and for any changes, remodels or additions that
may have been made to the building.
contract, can be commenced against Inspector/Inspection Company or its officers,
agents, or employees more than one year from the date Client discovers, or
through the exercise of reasonable diligence should have discovered, the cause of
action. In no event shall the time for commencement of a legal action or
proceeding exceed two years from the date of the subject inspection. THIS TIME
PERIOD IS SHORTER THAN OTHERWISE PROVIDED BY LAW. This Agreement
shall be binding upon and inure to the benefit of the parties hereto and their heirs,
successors, and assigns. This Agreement constitutes the entire integrated
agreement between the parties hereto pertaining to the subject matter hereof and
may be modified only by a written
agreement signed by all of the parties hereto. No oral agreements, understandings,
or representations shall change, modify, or amend any part of this Agreement.
Each party signing this Agreement warrants and represents that he/she has the full
capacity and authority to execute this Agreement on behalf of the named party. If
this Agreement is executed on behalf of Client by any third party, the person
executing this Agreement expressly represents to Inspector that he/she has the full
and complete authority to execute this Agreement on Client’s behalf and to fully
and completely bind Client to all of the terms, conditions, limitations, exceptions,
and exclusions of this Agreement.
18. SEVERABILITY: Should any provision of this Agreement be held by a court of
competent jurisdiction to be either invalid or unenforceable, the remaining
provisions of this Agreement shall remain in full force and effect, unimpaired by the
court’s holding.
19. MEDIATION: The parties to this Agreement agree to attend, in good faith,
mediation with a retired judge or lawyer with at least 5 years of mediation
experience before any lawsuit is filed. All notices of mediation must be served in
writing by return receipt requested allowing 30 days for response. If no response is
forthcoming the
moving party may then demand binding arbitration under the terms and provisions
set forth below.
20. ARBITRATION: Any dispute concerning the interpretation or enforcement of
this Agreement, the inspection, the inspection report, or any other dispute arising
out of this relationship, shall be resolved between the parties by binding arbitration
conducted in accordance with California Law, except that the parties shall select an
arbitrator who is familiar with the real estate profession. The parties agree that they
shall be entitled to discovery procedures within the discretion of the arbitrator. The
arbitrator shall manage and hear the case applying the laws of the State of
California to all issues submitted in the arbitration proceeding. The award of the
arbitrator shall be final, and a judgment may be entered on it by any court having
jurisdiction. Any disputes are to be arbitrated by: Judicial Arbitration and Mediation
Service (JAMS®).
• 14. SCOPE OF THE INSPECTION: The real estate inspection to be
performed for Client is a survey and basic operation of the systems and
components of a building which can be reached, entered, or viewed without
difficulty, moving obstructions, or requiring any action which may result in
damage to the property or personal injury to the Inspector. The purpose of
the inspection is to provide the Client with information regarding the general
condition of the building(s). Inspector will prepare and provide Client a
written report for the sole use and benefit of Client. The written report shall
document any material defects discovered in the building’s systems and
components which, in the opinion of the Inspector, are safety hazards, are
not functioning properly, or appear to be at the ends of their service lives.
The inspection shall be performed in accordance with the Standards of
Practice of the National Association of Home Inspectors (NAHI), and
incorporated herein by reference, and is limited to those items specified
herein.
• 15. CLIENT’S DUTY: Client agrees to read the entire written report when it
is received and promptly call Inspector with any questions or concerns
regarding the inspection or the written report. The written report shall be the
final and exclusive findings of Inspector. All of the following documents,
where applicable, form a part of this written report: Inspection Agreement,
Inspection Report, Cover Sheet, Worksheets and Photos. Client
acknowledges that Inspector is a generalist and that further investigation of
a reported condition by an appropriate specialist may provide additional
information which can affect Client’s purchase decision. Client agrees to
obtain further evaluation of reported conditions before removing any
investigation contingency and prior to the close of the transaction. In the
event Client becomes aware of a reportable condition which was not
reported by Inspector, Client agrees to promptly notify Inspector and allow
Inspector and/or Inspector’s designated representative(s) to inspect said
condition(s) prior to making any repair, alteration, or replacement. Client
agrees that any failure to so notify Inspector and allow inspection is a
material breach of this Agreement.
• 16. ENVIRONMENTAL CONDITIONS: Client agrees what is being
contracted for is a building inspection and not an environmental
evaluation. The inspection is not intended to detect, identify, or disclose any
health or environmental conditions regarding this building or property,
including, but not limited to: the presence of asbestos, radon, lead, urea
formaldehyde, fungi, molds, mildew, PCBs, or other toxic, reactive,
combustible, or corrosive contaminants, materials, or substances in the
water, air, soil, or building materials. The Inspector is not liable for injury,
health risks, or damage caused or contributed to by these conditions.
• 17. GENERAL PROVISIONS: The written report is not a substitute for any
transferor’s or agent’s disclosure that may be required by law, or a
substitute for Client’s independent duty to reasonably evaluate the property
prior to the close of the transaction. This inspection Agreement, the real
estate inspection, and the written report do not constitute a home warranty,
guarantee, or insurance policy of any kind whatsoever. No legal action or
proceeding of any kind, including those sounding in tort or
Name of Client:
Irving Velazquez
Property Address:
1566 Olive Ave
Chula Vista, CA 91911
Report Number:
221114015
Inspection Fee: $325.00
Inspection Date:
November 22, 2014
Approximate Age: 48 years
Built 1967
1,611 Sq.ft.
State of Occupancy:
Vacant
Weather Conditions:
Clear, Dry
Inspection Verses Warranty
AN INSPECTION VERSUS A WARRANTY
A home inspection is just what the name indicates, an inspection of a home...usually a home that is being purchased.
The purpose of the inspection is to determine the condition of the various systems and structures of the home. While an
inspection performed by a competent inspection company will determine the condition of the major components of the
home, no inspection will pick up every minute latent defect. The inspectors ability to find all defects is limited by access
to various parts of the property, lack of information about the property and many other factors. A good inspector will do
his or her level best to determine the condition of the home and to report it accurately. The report that is issued is an
opinion as to the condition of the home. This opinion is arrived at by the best technical methods available to the home
inspection industry. It is still only an opinion.
A warranty is a policy sold to the buyer that warrants that specific items in the home are in sound condition and will
remain in sound condition for a specified period of time. Typically, the warranty company never inspects the home. The
warranty company uses actuarial tables to determine the expected life of the warranted items and charges the customer
a fee for the warranty that will hopefully cover any projected loss and make a profit for the warranty seller. It is
essentially an insurance policy.
The service that we have provided you is an inspection. We make no warranty of this property. If you desire warranty
coverage, please see your real estate agent for details about any warranty plan to which their firm may have access.
THE HOUSE IN PERSPECTIVE
Well Built/Lacking Maintenance, Aging Systems.
Items Not Operating / Not Tested
Major Concerns Item(s) that have failed or have potential of failing soon.
Smell of Gas in Water Heater Closet. Must be evaluated and repaired by certified professional. Water Heater Vent pipe through closet door needs to
be repaired, proper access of pipe required. Closet Door is damaged at bottom.
Large Trees close to building, needs to be trimmed back. Recommend removing stump at edge of patio concrete, roots may cause damage.
Moisture present. Sagging sections between beams. One layer of fairly new tile, wood roof should be monitored, repaired or replaced.
Toilet in bathroom 1 does not operate properly while flushing, refer to video link.
Recommend having the oven / range safety strap added. Monitor rust and moisture spots under sink.
Second Floor windows require screens, safety hazard.
Inspection Highlights
Your inspection web page address
https://www.inspectorcaruso.com/1566-olive-ave.html
Deferred / Other Concerns
Items that have reached or are reaching their normal life expectancy or show indications that they may require repair or replacement anytime during
the next five (5) years.
Recommend adding gutter drainage.
Loose insulation in both attics should be upgraded to improve efficiency.
Bathroom 2; Caulking needed, Shower handle missing, Bathroom door handle loose.
All surfaces of untreated wood need regular applications of paint or special chemicals to resist damage
Inspection Highlights
Your inspection web page address
https://www.inspectorcaruso.com/1566-olive-ave.html
Service Walks
Material: Concrete
Condition: Satisfactory
Typical cracking, age. Walkway uneven, cracked which presents a trip hazard. Recommend repair of all cracks and monitor.
Driveway/Parking
Material: Rough Pebbled Asphalt
Condition: Typical cracks, stains
The Driveway/Parking area appears to be in usable condition. Normal cracks for age of driveway, recommend repair / replace and monitor. Possible
moisture stains.
Porch - No
Stoops/Steps: Yes, Front step.
Deck/Balcony: No
Deck/Patio/Porch Covers: Cement back patio, uncovered. Typical cracking for age. Covered in tree debris.
Fence/Wall
Type: Wood, Cement block, Wire
Condition: Satisfactory / Marginal
Gate: Yes - 3
Fencing remarks do not constitute an inspection. Fencing is not part of a home inspection. Wood weathering and damaged along right side, repair
replace. Back boundary fence needs to be repaired, determined and secured. Cinderblock wall, left side is cracked and needs repair.
Landscaping affecting foundation: No visible damage at present. Large stump at edge of patio, trees in front and back may be already heading or
may have already caused non visible damage. Recommend removing.
Retaining wall : No
Hose bibs
Condition: Satisfactory Operable - Yes
Hose bib(s) not equipped with anti-siphon devices.
Grounds / Exterior
Exterior Wood Surfaces: Satisfactory / Marginal
All surfaces of untreated wood need regular applications of paint or special chemicals to resist damage. Recommend painting all wood surfaces and
continue with annual upkeep.
Soffit: Wood, Monitor and paint.
Caulking: Satisfactory / Marginal, continued applications, monitor.
Windows/Screens
Condition: NONE, Recommend adding. Second Floor windows require screens, safety hazard.
Storms Windows: None
Foundation: Concrete Slab, not evaluated
Foundation (stem) wall not visible.
Service Entry: Below Ground
Building(s) Exterior Wall Construction
Building structure not visible due to siding, not evaluated.
Grounds / Exterior
Exterior Doors
1. Main Entrance – Wood with metal, locking screen door.
2. Patio – Sliding with no screen door.
3. Garage – Wood, satisfactory.
Doors and Windows
These can waste an enormous amount of energy. Maintain the caulking around the frames on the exterior. Check for drafts in the winter and improve
the worst offenders first. Wood that exhibits blistering or peeling paint should be examined for possible moisture sources: roof leaks, bad gutters,
interior moisture from baths or laundry. Some paint problems have no logical explanation, but many are a symptom of an underlying problem. A
freshly painted house may mask these symptoms, but after you have lived in the home for a year or two, look for localized paint blistering (peeling). It
may be a clue. New glazing will last longer if the raw wood is treated with boiled linseed oil prior to glazing. It prevents the wood from drawing the
moisture out of the new glazing.
Shut-Off Valve
Most shut-off valves have not been operated for long periods of time. We recommend operating each shut-off valve to: toilet bowl, water heater,
under sinks, main shut-off, hose faucets, and all others. We recommend you have a plumber do this, as some of the valves may need to be repacked
or replaced. Once the valves are in proper operating order, we recommend opening and closing these valves several times a year. Water is in front,
Gas in garage.
Water Pressure
PSI reading was just below 80, normal.
Walkway had some cracking and settlement, should be repaired and/or replaced as needed. Uneven slabs in walks, could be a tripping hazard,
repair and/or replace as needed. Fencing was in need of extensive repair and/or replacement (Fencing remarks do not constitute an inspection.
Fencing is not part of a home inspection). Exterior Wood is aging, monitor repair and repaint as needed.
Grounds / Exterior
Grounds / Exterior
Water Heater Door needs to be repaired. Smell of Gas in Closet.
Grounds / Exterior
Repair, and
monitor driveway.
Grounds / Exterior
Extend drainage. Soffit, front.
Grounds / Exterior
Yard Slopes toward home, add proper
drainage. Uneven walkway, trip hazard.
Grounds / Exterior
Grounds / Exterior
Recommend Stump to
be removed, at edge
of patio cement. Water
Damage. Tree needs
to be trimmed back.
Grounds / Exterior
Grounds / Exterior
Uneven gate latch. Cracked blocks and gaps.
Grounds / Exterior
Cement blocks need repair.
Grounds / Exterior
Gate needs latch. Post is loose.
Grounds / Exterior
Door needs repair around pipe.
Grounds / Exterior
Roof Visibility: Full, Tile Shingle
Inspected From: Roof
Style of Roof
Type: Gable
Pitch: Low
Roof #1: Main Building Type: tile Age: 5-10, Single layer.
Roof #2: Garage, same as main.
Ventilation System
Type: Roof
Flashing
Material: Metal
Condition: Marginal, require cleaning and repair.
Condition of Roof Coverings
Roof #1: Satisfactory/Marginal
Roof #2: Satisfactory
Sections of roof are uneven, rolling or sagging. Have evaluated by a roofing professional. Recommend repairing and adding gutter drainage with
extensions away from unit.
Plumbing Vents: Satisfactory
Lower Roof is sagging/rolling. Debris on roof and flashings needs to be removed. Trim back trees to prevent further debris from falling on roof.
Roof
Roof
Roof
Roof
Roof
These videos are available on your web page at
https://www.inspectorcaruso.com/1566-olive-ave.html
Video Links – Roof
1566 Roof 1 http://youtu.be/DVFZ36DCW7s
1566 Roof 2 http://youtu.be/l4iHmuna2SY
1566 Roof 3 http://youtu.be/4Wrz-iZAYuo
1566 Roof4 http://youtu.be/yDbkDwQofg0
1566 Roof5 http://youtu.be/FC002MeKKD8
1. Type: Attached
2. Automatic Opener: No
3. Safety Reverse: No
4. Roofing: Tile, Same as main building.
5. Gutters/Eaves: No, Recommend adding.
6. Siding: Same as house
7. Trim: None
8. Floor: Cement
9. Sill Plates: Cement
10. Exterior Service Door: Yes
11. Electricity Present: Yes GFCI: NO, Safety Hazard.
12. Fire Separation Walls and Ceiling: Yes
Garage Door not tested, Locked. Floor stains and wood damage, monitor and repair.
Garage
Garage
Shut-Off Valve
Most shut-off valves have not been operated for long periods of time. We recommend operating each shut-off valve to: toilet bowl, water heater, under
sinks, main shut-off, hose faucets, and all others. We recommend you have a plumber do this, as some of the valves may need to be repacked or
replaced. Once the valves are in proper operating order, we recommend opening and closing these valves several times a year.
Laundry Sink: No
Dryer Vented: Hole in Wall, No Dryer Present.
Electric: Outlet present, No GFCI, Safety Hazard.
Washer/Dryer Hook-ups: Yes
Cross Connections: Not present.
Room Vented: Yes
Heat Source Present: No
Appliances:
Washer: No
Dryer: No
Furnace: First floor Hallway Closet
Water Heater: Closet, Front Left
Laundry Room In Garage
Garage
Water Pipes
Galvanized water pipes rust from the inside out and may have to be replaced within 20 to 30 years. This is usually done in two stages: horizontal
piping in the basement first, and vertical pipes throughout the house later as needed. Copper pipes usually have more life expectancy and may last
as long as 60 years before needing to be replaced.
Plumbing
The temperature/pressure valve should be tested several times a year by lifting the valves handle. Caution: very hot water will be discharged. If no
water comes out, the valve is defective and must be replaced. The pressure relief valve on this unit is not extended to the proper location, this is a
safety hazard and needs to be repaired or replaced.
Shut-Off Valve
Most shut-off valves have not been operated for long periods of time. We recommend operating each shut-off valve to: toilet bowl, water heater,
under sinks, main shut-off, hose faucets, and all others. We recommend you have a plumber do this, as some of the valves may need to be repacked
or replaced. Once the valves are in proper operating order, we recommend opening and closing these valves several times a year.
Water Heater Shut-Off Valve: Yes
Main Shut Off: Left Side
Visible water distribution: PVC, Copper.
Water Heater #1
Location: Closet, outside front left.
Brand: Sears Roebuck
Model #: 153.338461
Serial #: F97784808
Capacity: 40
Approx. Age: Installed 1996, 18 years.
Seismic Restraints: Yes
Relief Valve: Yes, Satisfactory.
Slight smell of gas in Water Heater Closet, Have Evaluated, Safety Hazard. Water Heater Vent pipe through closet door needs to be repaired, proper
access of pipe required. Closet Door is damaged at bottom.
Plumbing
Plumbing
Appliances
(If report indicated appliances were operated, the following applies)
Stoves are tested to see that burners are working and oven and broiler get hot. Timer and controls are not tested. Refrigerators are not tested.
Most new dishwashers have the drain line looped automatically and may not be visible on the day of inspection. It is essential for the
dishwasher drain line to have an anti-siphon break to prevent back-flow. No representation is made to continued life expectancy of any
appliance.
Countertops: Satisfactory.
Cabinets: Satisfactory.
Plumbing: Satisfactory / Marginal, Rust and possible moisture spot under sink, monitor. Recommend further evaluation by plumber.
Walls & Ceiling: Satisfactory.
Heating Source: Satisfactory.
Floor: Satisfactory.
Outlets Present: Yes GFCI: Yes
Open Ground/Reverse Polarity: No
Lighting: Satisfactory.
Dishwasher: No
Dishwasher Air gap: N/A
Range and Oven: Yes, back left range automatic light needed assistance, operates recommend cleaning. Requires safety strap.
Window/Doors: Yes, Door to Garage operates and appears to be a fire door with automatic return.
Sink: Yes
Faucet: One Handle
Disposal: No
Oven: Yes, Satisfactory, needs safety strap.
Range: Yes, Satisfactory, needs safety strap.
Trash Compactor: No
Exhaust Fan: Yes, operates
Refrigerator: Yes
Microwave: No
Recommend having the oven / range safety strap added. Caulking recommended. Monitor rust and moisture spots under sink. Left back range
automatic light not operating, does light with help, recommend cleaning. If continues, have further professional evaluation.
Kitchen
Kitchen
Kitchen
Kitchen
Gap in molding.
Kitchen
These videos are available on your web page at
https://www.inspectorcaruso.com/1566-olive-ave.html
Video Links – Kitchen
1566 Kitchen http://youtu.be/5wwSxw_uTK4
Location: Downstairs, Front Middle
Sinks: Operate
Tub: Yes, no curtain.
Toilet: Yes, does not operate properly while flushing, refer to video link.
Whirlpool: No
Shower/Tub Area: Normal water flow. Recommend caulking repair around tub and sink.
Drainage: Satisfactory
Water Flow: Satisfactory
Moisture Stains Present: None
Doors: Satisfactory
Window: Yes
Receptacles Present: Yes GFCI, Yes
Open Ground/Reverse Polarity: No
Heat Source Present: Yes
Exhaust Fan: No
Lighting: Fixture, operates with one bulb out.
Repair Toilet, if continues have a certified plumber evaluate. Tub and sink need regular caulking. Recommend repairing light fixture and covering toilet
secure screw.
Bathroom #1
Bathroom #1
Bulb needs to be replaced.
Toilet clogged, refer to video.
Bathroom #1
Loose doorknob. Caulk.
Bathroom #1
These videos are available on your web page at
https://www.inspectorcaruso.com/1566-olive-ave.html
Video Links – Bathroom1
1566 Kitchen http://youtu.be/HcpnEDBw6p0
Location: Downstairs, Front Left
Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling.
Closet Guide: Marginal
Sliding doors stick, hard to open and close.
Window: Yes, no blinds or screen.
Smoke Detector: No
Walls and ceiling: Drywall
Ceiling Fan: No
Light Fixture: No
Floors: Carpet
Heat Source: Wall Vent
Electrical: Switches: No Outlets: Yes
Open Ground/Reverse Polarity: No
Moisture Stains: No
Bedroom Egress Restricted: No
Doors: Yes (2), one Wood, operates. One Sliding closet, operates slightly sticks.
Bedroom #1
Bedroom #1
No screen.
Location: Downstairs, Back Left
Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling.
Closet Guides: Marginal
Window: Yes, no blinds. Screen needs repair.
Smoke Detector: No
Walls and ceiling: Drywall
Ceiling Fan: No
Light Fixture: No
Floors: Carpet
Heat Source: Wall Vent
Electrical: Switches: No Outlets: Yes
Open Ground/Reverse Polarity: No
Moisture Stains: No
Room Egress Restricted: No
Doors: Yes (2), one Wood, operates. Three panel Sliding, operates.
Bedroom #2
Bedroom #2
No screen.
Location: Downstairs, Left Middle
Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling.
Closet Guides: Marginal
Window: Yes, no blinds or screens.
Smoke Detector: No
Walls and ceiling: Drywall
Ceiling Fan: No
Light Fixture: No
Floors: Carpet
Heat Source: Wall Vent
Electrical: Switches: No Outlets: Yes
Open Ground/Reverse Polarity: No
Moisture Stains: No
Room Egress Restricted: No
Doors: Yes (2), one Wood operates.
Bedroom #3
Bedroom #3
Asbestos and other Hazards
Asbestos fibers in some form are present in many homes, but are often not visible and cannot be identified without testing. If there is reason to
suspect that asbestos may be present and if it is of particular concern, a sample of the material in question may be removed and analyzed in a
laboratory. However, detecting or inspecting for the presence or absence of asbestos is not a part of our inspection. Also excluded from this inspection
and report are the possible presence of, or danger from, radon gas, lead-based paint, urea formaldehyde, toxic or flammable chemicals and all other
similar or potentially harmful substances and environmental hazards.
Windows
A representative number of windows were inspected, Satisfactory. Monitor, caulk and repair when needed. More efficient windows recommended.
Smoke Detectors
Smoke detectors should be tested monthly. At least one detector should be on each level. CO detectors are not required by most states, but for safety
reasons, are highly recommended. This unit does not have both a smoke detector, not tested and CO Detector, not tested.
Doors/Window: Satisfactory.
Carbon Monoxide Detector: No
Walls and ceiling: Drywall
Ceiling Fan: No
Light Fixture: Yes, operates.
Floors: Carpet, prefabricated hardwood veneer.
Heat Source: Wall Vents downstairs. Wall Heater in hallway of second floor hallway, not tested.
Entryway:
Metal security screen door, wood main door. Satisfactory.
No screen, second floor, Safety Hazard. Must Repair.
Interior
Interior
InteriorNo screen.
Interior
No screen,
second floor,
Safety Hazard.
Must Repair.
Location: Second Floor, Back Right
Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling.
Closet Guides: OK
Window: Yes, no blinds, screen needs repair.
Smoke Detector: No
Walls and ceiling: Drywall
Ceiling Fan: Yes, operates.
Light Fixture: No
Floors: Carpet
Heat Source: No
Electrical: Switches: No Outlets: Yes
Open Ground/Reverse Polarity: No
Moisture Stains: No
Room Egress Restricted: No
Doors: Yes (2), one Wood operates, one Sliding
Bedroom #4
Bedroom #4
Location: Upstairs, end of Hallway.
Sinks: Satisfactory
Tub: Yes
Toilet: Yes, operates, not loose.
Whirlpool: No
Shower/Tub Area: Normal water flow. Shower handle missing, recommend repair. Recommend caulking.
Drainage: Satisfactory
Water Flow: Satisfactory
Moisture Stains Present: None
Door: Satisfactory
Window: Yes
Receptacles Present: Yes GFCI Yes.
Open Ground/Reverse Polarity: No
Heat Source Present: Yes
Exhaust Fan: No
Lighting: Fixture
Caulking needed, Shower handle missing, Bathroom door handle loose.
Bathroom #2
Bathroom #2
Caulk. Missing shower handle.
Loose door handle.
Bathroom #2
Caulk
Location: Second Floor, Front Right.
Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling.
Closet Guides: Satisfactory
Window: Yes, no blinds or screen.
Smoke Detector: No
Walls and ceiling: Drywall
Ceiling Fan: No.
Light Fixture: No
Floors: Carpet, stained.
Heat Source: No
Electrical: Switches: Yes Outlets: Yes
Open Ground/Reverse Polarity: No
Moisture Stains: No
Room Egress Restricted: No
Doors: Yes (1), Wood operates.
Bedroom #5
Bedroom #5
Ventilation: Recommended at the rate of one square foot of vent area to 300 square feet of attic floor space, this being divided between soffit and
rooftop. There is ventilation and appears adequate.
Insulation
The recommended insulation in the attic area is R-38, approximately 12". If insulation is added, it is important that the ventilation is proper. There is a
combination of loose and strips of insulation. Recommend removing loose insulation from lighting and other fixtures in attic. Have evaluated and repaired
by HVAC professional. Loose insulation should be upgraded to improve efficiency.
Vapor Barriers
The vapor barrier should be on the warm side of the surface. Most older homes were built without vapor barriers. If the vapor barrier is towards the cold
side of the surface, it should be sliced or removed. Vapor barriers in the attic are covered by insulation and therefore, not visible.
Access: Scuttle hole / Hatch
Inspected from: Ladder
Location: Hallway
Flooring: No
Insulation: Loose and Strips Fiberglass, no access.
Installed: Between ceiling joist.
Fans Exhausted to Attic: No, Outside.
HVAC Duct: Insulated
Chimney Chase: N/A
Structure problems: None observed.
Roof Structure: Wood, Slight moisture present.
Moisture present. Sagging sections between beams. One layer of fairly new tile, wood roof should be repaired or replaced, monitor. Attic is covered with
loose insulation, not accessible. The service and distribution lines are insulated minimally, add, repair, monitor and upkeep. Insulation should be removed
from around lighting. Some nail popping present. Recommend further evaluation.
Attic 1
Ventilation: Recommended at the rate of one square foot of vent area to 300 square feet of attic floor space, this being divided between soffit and
rooftop. There is ventilation and appears adequate.
Insulation
The recommended insulation in the attic area is R-38, approximately 12". If insulation is added, it is important that the ventilation is proper. There is a
combination of loose and strips of insulation. Loose insulation should be upgraded to improve efficiency.
Vapor Barriers
The vapor barrier should be on the warm side of the surface. Most older homes were built without vapor barriers. If the vapor barrier is towards the cold
side of the surface, it should be sliced or removed. Vapor barriers in the attic are covered by insulation and therefore, not visible.
Access: Scuttle hole / Hatch.
Inspected from: Ladder
Location: Hallway
Flooring: No
Insulation: Loose and Strips Fiberglass, no access.
Installed: Between ceiling joist.
Fans Exhausted to Attic: No, Outside.
HVAC Duct: Insulated
Chimney Chase: N/A
Structure problems: None observed.
Roof Structure: Wood, Slight moisture present.
Attic is covered with loose insulation, not accessible. The service and distribution lines are insulated. Insulation should be removed from around lighting.
Recommend further evaluation.
Attic 2
Attic 1
Loose Insulation should be removed from light
fixtures. Sagging, moist wood. Nail popping.
Furnace distribution pips need insulation upkeep.
Attic 2
These videos are available on your web page at
https://www.inspectorcaruso.com/1566-olive-ave.html
Video Link – Attic
1566 Attic 1 http://youtu.be/K1V7qVMGmKc
1566 Attic 2 http://youtu.be/4hl9cN2TCYA
Every effort has been made to evaluate the size of the service. The total amperage can be difficult to determine. We highly recommend that ground fault
circuit interrupters (GFCI) be connected to all outlets around water. This device automatically shuts the circuit off when it senses a current leak to ground.
Federal Pacific Stab-Lok Electrical® panels may be unsafe. See www.google.com (Federal Pacific) Aluminum wiring in general lighting circuits has a
history of overheating, with the potential of a fire. If this type of wiring exists, a licensed electrical contractor should examine the whole system.
Location: Left, side of unit.
Amperage: 120/240, Breakers
Adequate clearance to panel: Satisfactory
Appears Grounded: Yes
GFCI Breaker: No
Main Wire: Copper
Branch Wire: Copper, Aluminum
Double Tapping: None observed
Neutral/Ground Separated: Yes
Outlets were randomly tested and had correct polarity, except as noted. Aluminum wires have been used for branch wiring - recommend licensed
electrician evaluate the system.
Electrical
Electrical
These videos are available on your web page at
https://www.inspectorcaruso.com/1566-olive-ave.html
Video Links – Electrical
1566 Heating http://youtu.be/JQCgpnKIXIU
Gas-fired hot air units that are close to or beyond their normal lives have the potential of becoming a source of carbon monoxide in the home. You may
want to have such a unit checked every year or so to assure yourself that it is still intact. Of course a unit of such an age is a good candidate for
replacement with one of the new, high efficiency furnaces. The fuel savings alone can be very attractive. Forced air systems should have filters
changed every 30 to 60 days of the heating season. A dirty air system can lead to premature failure of your compressor - a $1,500 machine. Read the
instructions for maintaining the humidifier on your furnace. A malfunctioning humidifier can rust out a furnace rather quickly. It is recommended that the
humidifier be serviced at the same time as the furnace, and be cleaned regularly. During a visual inspection it is not possible to determine if the
humidifier is working. Although the unit is currently working, the condition of the ventilation system, wet drywall closet and overall age of this unit I am
recommending having an HVAC technician examine.
Heat exchangers cannot be examined nor their condition determined without being disassembled. Since this is not possible during a visual, non-
technically exhaustive inspection, you may want to obtain a service contract on the unit or contact a furnace technician regarding a more thorough
examination.
Testing pilot safety switch requires blowing out the pilot light. Checking safety limit controls requires disconnecting blower motor or using other means
beyond the scope of this inspection. If the furnace has not been serviced in last 12 months you may want to have a furnace technician examine.
CO Test - This is not part of a non-technical inspection.
Normal lives are:
GAS-FIRED HOT AIR 15-25 years
Oil-Fired HOT AIR 20-30 years
CAST IRON BOILER 30-50 years
STEEL BOILER 30-40 years
COPPER BOILER 10-20 years
CIRCULATING PUMP (Hot water) 10-15 years
AIR CONDITIONING COMPRESSOR 8-12 years
HEAT PUMP 8-12 years
Heating
Energy Source: Unit 1, downstairs hallway closet, Gas. Unit 2, hallway wall upstairs, Gas pilot not light.
Warm Air System: Unit 1, Central System
Controls: Unit 1 downstairs Hallway, operates.
Distribution: Duct
When turned on by Thermostat: Operated. Visual inspection of pilot light.
System Condition: Unit 1, Satisfactory. Unit 2 Recommend evaluation by SDG&E or an HVAC professional.
Brand Name: Rheem
Approx. Age: ?
Model #: ?
Serial # ?
Heating System Remarks: Recommend repairing vent duct insulation. Unit may be nearing expected operating years.
Heating
Heating
These videos are available on your web page at
https://www.inspectorcaruso.com/1566-olive-ave.html
Video Links – Heating
1566 Heating http://youtu.be/GhXxXah9JyQ
I. Foundation and Masonry:
Basements, Exterior Walls: To prevent see page and condensation problems.
a. Check basement for dampness and leakage after wet weather
b. Check chimneys, deteriorated chimney caps, loose, and missing mortar.
c. Maintain grading sloped away from foundation walls.
II. Roofs, Gutters, and Eavestrough:
To prevent roof leaks, condensation, see page and decay problems.
a. Check for damaged, loose, or missing shingles, blisters.
b. Clean gutters, leaders, strainers, window wells, drains. Be sure downspouts direct water away from foundation.
c. Cut back tree limbs.
d. Check flashings around roof stacks, vents, skylights, chimneys as source of leakage.
e. Check vents, louvers and chimneys for birds nests, squirrels, insects.
f. Check fascias and soffits for paint flaking leakage and decay.
III. Exterior Walls:
To prevent paint failure, decay, and moisture penetration problems.
a. Check painted surface for paint flaking or paint failure. Check back shrubs.
b. Check exterior masonry walls for cracks, looseness, missing or broken mortar.
IV. Doors and Windows:
To prevent air and weather penetration problems.
a. Check caulking for decay around doors, windows, corner boards, joints.
b. Re-caulk and weatherstrip as needed. Check glazing putty around windows.
Preventive Maintenance Tips
V. Electrical:
For safe electrical performance, mark and label each circuit.
a. Trip circuit breakers every six months and ground fault circuit interrupters (GFCI.) monthly.
b. Check condition of lamp cords, extension cords and plugs. Replace at first sign of wear and damage.
c. Check exposed wiring and cable for wear or damage.
d. If you experience slight tingling shock from handling or touching any appliance, disconnect the appliance
and have it repaired. If lights flicker or dim, or if appliances go on and off unnecessarily, call a licensed electrician.
VI. Plumbing:
For preventive maintenance.
a. Drain exterior water lines, hose bibs, sprinklers, pool equipment in the fall.
b. Draw off sediment in water heaters monthly or per manufacturer's instructions.
c. Have septic tank cleaned every 2 years.
VII. Heating and Cooling:
For comfort, efficiency, energy conservation and safety.
a. Change or clean furnace filters, air condition filters, electronic filters as needed.
b. Clean and service humidifier. Check periodically and annually.
c. Have oil burning equipment serviced annually.
VIII. Interior
General house maintenance.
a. Check bathroom tile joins, tub grouting and caulking. Be sure all tile joints in bathrooms are kept well sealed
with tile grout to prevent damage to walls, floors, and ceilings below.
b. Close crawl vents in winter and open in summer
c. Check underside of roof for water stains, leaks, dampness & condensation, particularly in attics and around chimneys.
IX. Know the location of:
-Main water shutoff valve.
-Main emergency shutoff switch for the heating system.
-Main electrical disconnect or breaker.
Preventive Maintenance Tips

More Related Content

What's hot (19)

Inspetion agreement
Inspetion agreementInspetion agreement
Inspetion agreement
 
2011 argeement waldo
2011 argeement waldo2011 argeement waldo
2011 argeement waldo
 
Contract
ContractContract
Contract
 
Contract
ContractContract
Contract
 
Pre-Purchase Inspection Contract
Pre-Purchase Inspection ContractPre-Purchase Inspection Contract
Pre-Purchase Inspection Contract
 
TMP20150425-01
TMP20150425-01TMP20150425-01
TMP20150425-01
 
Sample Report
Sample ReportSample Report
Sample Report
 
Inspection Agreement with Thermal Imaging 2013
Inspection Agreement with Thermal Imaging 2013Inspection Agreement with Thermal Imaging 2013
Inspection Agreement with Thermal Imaging 2013
 
Texas.PDF
Texas.PDFTexas.PDF
Texas.PDF
 
Preview inspectionfull
Preview inspectionfullPreview inspectionfull
Preview inspectionfull
 
Sample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlierSample new construction-completed_over_a_year_earlier
Sample new construction-completed_over_a_year_earlier
 
Sample commercial inspection
Sample commercial inspectionSample commercial inspection
Sample commercial inspection
 
W E Gen Srvc Agreement
W E Gen Srvc AgreementW E Gen Srvc Agreement
W E Gen Srvc Agreement
 
Sample newer home
Sample newer homeSample newer home
Sample newer home
 
LG K7 Manual / User Guide
LG K7 Manual / User GuideLG K7 Manual / User Guide
LG K7 Manual / User Guide
 
Sample safety report
Sample safety reportSample safety report
Sample safety report
 
Sample 1994with deferred_maintenance
Sample 1994with deferred_maintenanceSample 1994with deferred_maintenance
Sample 1994with deferred_maintenance
 
2.2 SITTNER NRC REQUIREMENTS 10 CFR 21
2.2 SITTNER NRC REQUIREMENTS 10 CFR 212.2 SITTNER NRC REQUIREMENTS 10 CFR 21
2.2 SITTNER NRC REQUIREMENTS 10 CFR 21
 
2.3 SITTNER NRC REQUIREMENTS RELATED TO INSPECTION OF COMMERCIAL GRADE DEDICA...
2.3 SITTNER NRC REQUIREMENTS RELATED TO INSPECTION OF COMMERCIAL GRADE DEDICA...2.3 SITTNER NRC REQUIREMENTS RELATED TO INSPECTION OF COMMERCIAL GRADE DEDICA...
2.3 SITTNER NRC REQUIREMENTS RELATED TO INSPECTION OF COMMERCIAL GRADE DEDICA...
 

Similar to Inspection Presentation Sample

Ashi mahi pre-inspection agreement
Ashi mahi pre-inspection agreementAshi mahi pre-inspection agreement
Ashi mahi pre-inspection agreement
tk99
 
Residential - buyer or listing contract -- 2006
Residential  - buyer or listing contract -- 2006Residential  - buyer or listing contract -- 2006
Residential - buyer or listing contract -- 2006
dwmeredith
 
Residential - buyer or listing contract -- 2006
Residential  - buyer or listing contract -- 2006Residential  - buyer or listing contract -- 2006
Residential - buyer or listing contract -- 2006
cairoellie
 
Inspection Agreement
Inspection AgreementInspection Agreement
Inspection Agreement
Doncrook
 
Home inspection-agreement
Home inspection-agreementHome inspection-agreement
Home inspection-agreement
greeninspector
 
Sample inspection report copy
Sample inspection report copySample inspection report copy
Sample inspection report copy
Brad Stinson
 
Blank aip inspection agreement
Blank aip inspection agreementBlank aip inspection agreement
Blank aip inspection agreement
brucecarmichael
 
AIP Pool-Spa Inspection Agreement
AIP Pool-Spa Inspection AgreementAIP Pool-Spa Inspection Agreement
AIP Pool-Spa Inspection Agreement
brucecarmichael
 
Accurateinspections sample-report
Accurateinspections sample-reportAccurateinspections sample-report
Accurateinspections sample-report
Doncrook
 
Inspection agreement
Inspection agreementInspection agreement
Inspection agreement
davedewitt
 
Inspection agreement
Inspection agreementInspection agreement
Inspection agreement
davedewitt
 

Similar to Inspection Presentation Sample (20)

Ashi mahi pre-inspection agreement
Ashi mahi pre-inspection agreementAshi mahi pre-inspection agreement
Ashi mahi pre-inspection agreement
 
Inspection agreement 2010
Inspection agreement 2010Inspection agreement 2010
Inspection agreement 2010
 
Sample inspection agreement
Sample inspection agreementSample inspection agreement
Sample inspection agreement
 
Residential - buyer or listing contract -- 2006
Residential  - buyer or listing contract -- 2006Residential  - buyer or listing contract -- 2006
Residential - buyer or listing contract -- 2006
 
Residential - buyer or listing contract -- 2006
Residential  - buyer or listing contract -- 2006Residential  - buyer or listing contract -- 2006
Residential - buyer or listing contract -- 2006
 
Contract 2010 tim hemm inspections
Contract 2010 tim hemm inspectionsContract 2010 tim hemm inspections
Contract 2010 tim hemm inspections
 
Contract 2010 tim hemm inspections
Contract 2010 tim hemm inspectionsContract 2010 tim hemm inspections
Contract 2010 tim hemm inspections
 
Inspection Agreement
Inspection AgreementInspection Agreement
Inspection Agreement
 
Home inspection-agreement
Home inspection-agreementHome inspection-agreement
Home inspection-agreement
 
Sample inspection report copy
Sample inspection report copySample inspection report copy
Sample inspection report copy
 
Contract
ContractContract
Contract
 
Blank aip inspection agreement
Blank aip inspection agreementBlank aip inspection agreement
Blank aip inspection agreement
 
AIP Pool-Spa Inspection Agreement
AIP Pool-Spa Inspection AgreementAIP Pool-Spa Inspection Agreement
AIP Pool-Spa Inspection Agreement
 
Inspection agreement page
Inspection agreement pageInspection agreement page
Inspection agreement page
 
Accurateinspections sample-report
Accurateinspections sample-reportAccurateinspections sample-report
Accurateinspections sample-report
 
Signed and dated_contract_by_landlord_-_ajay_mishra_for_ac_system_replacement...
Signed and dated_contract_by_landlord_-_ajay_mishra_for_ac_system_replacement...Signed and dated_contract_by_landlord_-_ajay_mishra_for_ac_system_replacement...
Signed and dated_contract_by_landlord_-_ajay_mishra_for_ac_system_replacement...
 
CubiScan 25 Operation Manual 1.2.pdf
CubiScan 25 Operation Manual 1.2.pdfCubiScan 25 Operation Manual 1.2.pdf
CubiScan 25 Operation Manual 1.2.pdf
 
Risk Management For Contractors
Risk Management For ContractorsRisk Management For Contractors
Risk Management For Contractors
 
Inspection agreement
Inspection agreementInspection agreement
Inspection agreement
 
Inspection agreement
Inspection agreementInspection agreement
Inspection agreement
 

Inspection Presentation Sample

  • 1. Inspection # 221114015 1566 Olive Ave. Chula Vista, CA 91911 Buyer Irving Velazquez –irving17@hotmail.com Buyer Agent Dilia A. Cade – diliabesthomes@gmail.com Harry R. Caruso, III CRI Inspector Caruso Home Inspections 760-498-3357/ (858)342-0616 www.inspectorcaruso.com
  • 2. Inspection Agreement (Please Read Carefully) This Agreement is made and entered into by and between Inspector Caruso, referred to as “Inspector”, Irving Velazquez, referred to as “Client.” In consideration of the promise and terms of this Agreement, the parties agree as follows: 1. The inspector will perform a visual inspection and prepare a digital report of the apparent condition of the readily accessible installed systems and components of the property, existing at the time of inspection. Latent and concealed defects and deficiencies are excluded from the inspection. Photographs and video of this inspection are the sole property of inspector. 2. The client will pay the sum of $325.00 for the inspection of the “Property and Garage” being inspected if applicable, located at 1566 Olive Ave. Chula Vista, CA 91911. 3. The parties agree that the “Standards of Practice” (NAHI Standards) shall define the standard of duty and the conditions, limitations, and exclusions of the inspection and are incorporated by the reference herein. If the State /Province where the inspection is performed imposes more stringent standards or administrative rule, then those standards shall define the standards of duty and the conditions, limitations, and exclusions of the inspection. 4. The parties agree and understand that the Inspector and its employees and its agents assume no liability or responsibility for the costs of repairing or replacing any unreported defects or deficiencies either current or arising in the future or any property damage, consequential damage or bodily injury of any nature. If repairs or replacement are done without giving the Inspector the required notice, the Inspector will have no liability to the client. The Client further agrees that the Inspector is liable only up to the cost of the inspection. 5. The parties agree and understand the Inspector is not an insurer nor guarantor against defects in the structure, items, components, or systems inspected. The INSPECTOR MAKES NO WARRANTY, EXPRESSED OR IMPLIED, AS TO THE FITNESS OF USE, CONDITION, PERFORMANCE OR ADEQUACY OF ANY INSPECTED STRUCTURE, ITEM, COMPONENT, OR SYSTEM CONDITION AT TIME OF INSPECTION. 6. If client is married, Client represents that this obligation is a family obligation incurred in the interest of the family. 7. This agreement, including the additional terms and conditions, represent the entire agreement between the parties and there are no other agreements either written or oral between them. This Agreement shall be amended only by written agreement signed by both parties. This Agreement shall be construed and enforced in accordance with the laws of the State of California, San Diego County. Client has read this entire Agreement and accepts and understands this Agreement as herby acknowledged. This report adheres to the NAHI Standards, which are available upon request and on line at www.inspectorcaruso.com.
  • 3. Additional Terms, Conditions, and Limitations 8. Systems, items, and conditions which are not within the scope of the building inspection include, but are not limited to: radon, formaldehyde, lead paint, asbestos, toxic or flammable materials, molds, fungi, other environmental hazards; pest infestation; security and fire protection systems; household appliances; humidifiers; paint, wallpaper and other treatments to windows, interior walls, ceilings, and floors; recreational equipment or facilities; pool/spa water purification systems (ozone generator/saltwater, etc.); underground storage tanks, energy efficiency measurements; motion or photo-electric sensor lighting; concealed or private secured systems; water wells; all overflow drains; heating system's accessories; solar heating systems; heat exchangers; sprinkling systems; water softener or purification systems; central vacuum systems; telephone, intercom or cable TV systems; antennae, lightning arrestors, load controllers; trees or plants; governing codes, ordinances, statutes, and covenants; and manufacturer specifications, recalls, and EIFS. Client understands that these systems, items, and conditions are excluded from this inspection. Any general comments about these systems, items, and conditions of the written or digital reports are informal only and DOES NOT represent an inspection. 9. The Inspection and report are performed and prepared for the sole and exclusive use and possession of the Client. No other person or entity may rely on the report issued pursuant to this Agreement. In the event that any person, not a party to this Agreement, makes any claim against Inspector, its employees or agents, arising out of the services performed by Inspector under this Agreement, the Client agrees to indemnify, defend, and hold harmless Inspector from any and all damages, expenses, costs, and attorney fees arising from such a claim. 10. The Inspection will not include an appraisal of the value or a survey. The written report is not a compliance inspection or certification for past or present governmental codes or regulations of any kind. 11. In the event of a claim by the Client that an installed system or component of the premises which was inspected by the Inspector was not in the condition reported by the Inspector, the Client agrees to notify the Inspector at least 72 hours prior to repairing or replacing such system or component. The Client further agrees that the Inspector is liable only if there has been a complete failure to follow the standards adhered to in the report or State/Province law. Furthermore, any legal action must be brought within two (2) years from the date of the inspection, or will be deemed waived and forever barred. 12. This inspection does not determine whether the property is insurable. 13. These definitions will be documented on the report: A. Apparent Condition: Systems and components are rated as follows: SATISFACTORY (S) - Indicates the component is functionally consistent with its original purpose but may show signs of normal wear and tear and deterioration. MARGINAL (M) - Indicates the component will probably require repair or replacement anytime within five years. POOR (P)- Indicates the component will need repair or replacement now or very near future. SIGNIFICANT ISSUES (SI) - A system or component that is considered significantly deficient, inoperable or is unsafe. SAFETY HAZARD - Denotes a condition that is unsafe and in need of prompt attention. B. Installed systems and components: structural components; exterior; interior; roofing; plumbing; electrical; heating; central air-conditioning (weather permitting); insulation and ventilation. C. Readily accessible systems and components: only those systems and components where Inspector is not required to remove or move personal items, furniture, equipment, soil, snow, or other items which obstruct access or visibility. D. Any component not listed as being deficient in some manner is assumed to be satisfactory. E. Regardless of the age of the building we recommend inquiring about any permits and inspection records, with final signatures, for the building and for any changes, remodels or additions that may have been made to the building.
  • 4. contract, can be commenced against Inspector/Inspection Company or its officers, agents, or employees more than one year from the date Client discovers, or through the exercise of reasonable diligence should have discovered, the cause of action. In no event shall the time for commencement of a legal action or proceeding exceed two years from the date of the subject inspection. THIS TIME PERIOD IS SHORTER THAN OTHERWISE PROVIDED BY LAW. This Agreement shall be binding upon and inure to the benefit of the parties hereto and their heirs, successors, and assigns. This Agreement constitutes the entire integrated agreement between the parties hereto pertaining to the subject matter hereof and may be modified only by a written agreement signed by all of the parties hereto. No oral agreements, understandings, or representations shall change, modify, or amend any part of this Agreement. Each party signing this Agreement warrants and represents that he/she has the full capacity and authority to execute this Agreement on behalf of the named party. If this Agreement is executed on behalf of Client by any third party, the person executing this Agreement expressly represents to Inspector that he/she has the full and complete authority to execute this Agreement on Client’s behalf and to fully and completely bind Client to all of the terms, conditions, limitations, exceptions, and exclusions of this Agreement. 18. SEVERABILITY: Should any provision of this Agreement be held by a court of competent jurisdiction to be either invalid or unenforceable, the remaining provisions of this Agreement shall remain in full force and effect, unimpaired by the court’s holding. 19. MEDIATION: The parties to this Agreement agree to attend, in good faith, mediation with a retired judge or lawyer with at least 5 years of mediation experience before any lawsuit is filed. All notices of mediation must be served in writing by return receipt requested allowing 30 days for response. If no response is forthcoming the moving party may then demand binding arbitration under the terms and provisions set forth below. 20. ARBITRATION: Any dispute concerning the interpretation or enforcement of this Agreement, the inspection, the inspection report, or any other dispute arising out of this relationship, shall be resolved between the parties by binding arbitration conducted in accordance with California Law, except that the parties shall select an arbitrator who is familiar with the real estate profession. The parties agree that they shall be entitled to discovery procedures within the discretion of the arbitrator. The arbitrator shall manage and hear the case applying the laws of the State of California to all issues submitted in the arbitration proceeding. The award of the arbitrator shall be final, and a judgment may be entered on it by any court having jurisdiction. Any disputes are to be arbitrated by: Judicial Arbitration and Mediation Service (JAMS®). • 14. SCOPE OF THE INSPECTION: The real estate inspection to be performed for Client is a survey and basic operation of the systems and components of a building which can be reached, entered, or viewed without difficulty, moving obstructions, or requiring any action which may result in damage to the property or personal injury to the Inspector. The purpose of the inspection is to provide the Client with information regarding the general condition of the building(s). Inspector will prepare and provide Client a written report for the sole use and benefit of Client. The written report shall document any material defects discovered in the building’s systems and components which, in the opinion of the Inspector, are safety hazards, are not functioning properly, or appear to be at the ends of their service lives. The inspection shall be performed in accordance with the Standards of Practice of the National Association of Home Inspectors (NAHI), and incorporated herein by reference, and is limited to those items specified herein. • 15. CLIENT’S DUTY: Client agrees to read the entire written report when it is received and promptly call Inspector with any questions or concerns regarding the inspection or the written report. The written report shall be the final and exclusive findings of Inspector. All of the following documents, where applicable, form a part of this written report: Inspection Agreement, Inspection Report, Cover Sheet, Worksheets and Photos. Client acknowledges that Inspector is a generalist and that further investigation of a reported condition by an appropriate specialist may provide additional information which can affect Client’s purchase decision. Client agrees to obtain further evaluation of reported conditions before removing any investigation contingency and prior to the close of the transaction. In the event Client becomes aware of a reportable condition which was not reported by Inspector, Client agrees to promptly notify Inspector and allow Inspector and/or Inspector’s designated representative(s) to inspect said condition(s) prior to making any repair, alteration, or replacement. Client agrees that any failure to so notify Inspector and allow inspection is a material breach of this Agreement. • 16. ENVIRONMENTAL CONDITIONS: Client agrees what is being contracted for is a building inspection and not an environmental evaluation. The inspection is not intended to detect, identify, or disclose any health or environmental conditions regarding this building or property, including, but not limited to: the presence of asbestos, radon, lead, urea formaldehyde, fungi, molds, mildew, PCBs, or other toxic, reactive, combustible, or corrosive contaminants, materials, or substances in the water, air, soil, or building materials. The Inspector is not liable for injury, health risks, or damage caused or contributed to by these conditions. • 17. GENERAL PROVISIONS: The written report is not a substitute for any transferor’s or agent’s disclosure that may be required by law, or a substitute for Client’s independent duty to reasonably evaluate the property prior to the close of the transaction. This inspection Agreement, the real estate inspection, and the written report do not constitute a home warranty, guarantee, or insurance policy of any kind whatsoever. No legal action or proceeding of any kind, including those sounding in tort or Name of Client: Irving Velazquez Property Address: 1566 Olive Ave Chula Vista, CA 91911 Report Number: 221114015 Inspection Fee: $325.00 Inspection Date: November 22, 2014 Approximate Age: 48 years Built 1967 1,611 Sq.ft. State of Occupancy: Vacant Weather Conditions: Clear, Dry
  • 5. Inspection Verses Warranty AN INSPECTION VERSUS A WARRANTY A home inspection is just what the name indicates, an inspection of a home...usually a home that is being purchased. The purpose of the inspection is to determine the condition of the various systems and structures of the home. While an inspection performed by a competent inspection company will determine the condition of the major components of the home, no inspection will pick up every minute latent defect. The inspectors ability to find all defects is limited by access to various parts of the property, lack of information about the property and many other factors. A good inspector will do his or her level best to determine the condition of the home and to report it accurately. The report that is issued is an opinion as to the condition of the home. This opinion is arrived at by the best technical methods available to the home inspection industry. It is still only an opinion. A warranty is a policy sold to the buyer that warrants that specific items in the home are in sound condition and will remain in sound condition for a specified period of time. Typically, the warranty company never inspects the home. The warranty company uses actuarial tables to determine the expected life of the warranted items and charges the customer a fee for the warranty that will hopefully cover any projected loss and make a profit for the warranty seller. It is essentially an insurance policy. The service that we have provided you is an inspection. We make no warranty of this property. If you desire warranty coverage, please see your real estate agent for details about any warranty plan to which their firm may have access.
  • 6. THE HOUSE IN PERSPECTIVE Well Built/Lacking Maintenance, Aging Systems. Items Not Operating / Not Tested Major Concerns Item(s) that have failed or have potential of failing soon. Smell of Gas in Water Heater Closet. Must be evaluated and repaired by certified professional. Water Heater Vent pipe through closet door needs to be repaired, proper access of pipe required. Closet Door is damaged at bottom. Large Trees close to building, needs to be trimmed back. Recommend removing stump at edge of patio concrete, roots may cause damage. Moisture present. Sagging sections between beams. One layer of fairly new tile, wood roof should be monitored, repaired or replaced. Toilet in bathroom 1 does not operate properly while flushing, refer to video link. Recommend having the oven / range safety strap added. Monitor rust and moisture spots under sink. Second Floor windows require screens, safety hazard. Inspection Highlights Your inspection web page address https://www.inspectorcaruso.com/1566-olive-ave.html
  • 7. Deferred / Other Concerns Items that have reached or are reaching their normal life expectancy or show indications that they may require repair or replacement anytime during the next five (5) years. Recommend adding gutter drainage. Loose insulation in both attics should be upgraded to improve efficiency. Bathroom 2; Caulking needed, Shower handle missing, Bathroom door handle loose. All surfaces of untreated wood need regular applications of paint or special chemicals to resist damage Inspection Highlights Your inspection web page address https://www.inspectorcaruso.com/1566-olive-ave.html
  • 8. Service Walks Material: Concrete Condition: Satisfactory Typical cracking, age. Walkway uneven, cracked which presents a trip hazard. Recommend repair of all cracks and monitor. Driveway/Parking Material: Rough Pebbled Asphalt Condition: Typical cracks, stains The Driveway/Parking area appears to be in usable condition. Normal cracks for age of driveway, recommend repair / replace and monitor. Possible moisture stains. Porch - No Stoops/Steps: Yes, Front step. Deck/Balcony: No Deck/Patio/Porch Covers: Cement back patio, uncovered. Typical cracking for age. Covered in tree debris. Fence/Wall Type: Wood, Cement block, Wire Condition: Satisfactory / Marginal Gate: Yes - 3 Fencing remarks do not constitute an inspection. Fencing is not part of a home inspection. Wood weathering and damaged along right side, repair replace. Back boundary fence needs to be repaired, determined and secured. Cinderblock wall, left side is cracked and needs repair. Landscaping affecting foundation: No visible damage at present. Large stump at edge of patio, trees in front and back may be already heading or may have already caused non visible damage. Recommend removing. Retaining wall : No Hose bibs Condition: Satisfactory Operable - Yes Hose bib(s) not equipped with anti-siphon devices. Grounds / Exterior
  • 9. Exterior Wood Surfaces: Satisfactory / Marginal All surfaces of untreated wood need regular applications of paint or special chemicals to resist damage. Recommend painting all wood surfaces and continue with annual upkeep. Soffit: Wood, Monitor and paint. Caulking: Satisfactory / Marginal, continued applications, monitor. Windows/Screens Condition: NONE, Recommend adding. Second Floor windows require screens, safety hazard. Storms Windows: None Foundation: Concrete Slab, not evaluated Foundation (stem) wall not visible. Service Entry: Below Ground Building(s) Exterior Wall Construction Building structure not visible due to siding, not evaluated. Grounds / Exterior
  • 10. Exterior Doors 1. Main Entrance – Wood with metal, locking screen door. 2. Patio – Sliding with no screen door. 3. Garage – Wood, satisfactory. Doors and Windows These can waste an enormous amount of energy. Maintain the caulking around the frames on the exterior. Check for drafts in the winter and improve the worst offenders first. Wood that exhibits blistering or peeling paint should be examined for possible moisture sources: roof leaks, bad gutters, interior moisture from baths or laundry. Some paint problems have no logical explanation, but many are a symptom of an underlying problem. A freshly painted house may mask these symptoms, but after you have lived in the home for a year or two, look for localized paint blistering (peeling). It may be a clue. New glazing will last longer if the raw wood is treated with boiled linseed oil prior to glazing. It prevents the wood from drawing the moisture out of the new glazing. Shut-Off Valve Most shut-off valves have not been operated for long periods of time. We recommend operating each shut-off valve to: toilet bowl, water heater, under sinks, main shut-off, hose faucets, and all others. We recommend you have a plumber do this, as some of the valves may need to be repacked or replaced. Once the valves are in proper operating order, we recommend opening and closing these valves several times a year. Water is in front, Gas in garage. Water Pressure PSI reading was just below 80, normal. Walkway had some cracking and settlement, should be repaired and/or replaced as needed. Uneven slabs in walks, could be a tripping hazard, repair and/or replace as needed. Fencing was in need of extensive repair and/or replacement (Fencing remarks do not constitute an inspection. Fencing is not part of a home inspection). Exterior Wood is aging, monitor repair and repaint as needed. Grounds / Exterior
  • 12. Water Heater Door needs to be repaired. Smell of Gas in Closet. Grounds / Exterior
  • 14. Extend drainage. Soffit, front. Grounds / Exterior
  • 15. Yard Slopes toward home, add proper drainage. Uneven walkway, trip hazard. Grounds / Exterior
  • 16. Grounds / Exterior Recommend Stump to be removed, at edge of patio cement. Water Damage. Tree needs to be trimmed back.
  • 18. Grounds / Exterior Uneven gate latch. Cracked blocks and gaps.
  • 19. Grounds / Exterior Cement blocks need repair.
  • 20. Grounds / Exterior Gate needs latch. Post is loose.
  • 21. Grounds / Exterior Door needs repair around pipe.
  • 23. Roof Visibility: Full, Tile Shingle Inspected From: Roof Style of Roof Type: Gable Pitch: Low Roof #1: Main Building Type: tile Age: 5-10, Single layer. Roof #2: Garage, same as main. Ventilation System Type: Roof Flashing Material: Metal Condition: Marginal, require cleaning and repair. Condition of Roof Coverings Roof #1: Satisfactory/Marginal Roof #2: Satisfactory Sections of roof are uneven, rolling or sagging. Have evaluated by a roofing professional. Recommend repairing and adding gutter drainage with extensions away from unit. Plumbing Vents: Satisfactory Lower Roof is sagging/rolling. Debris on roof and flashings needs to be removed. Trim back trees to prevent further debris from falling on roof. Roof
  • 24. Roof
  • 25. Roof
  • 26. Roof
  • 27. Roof
  • 28. These videos are available on your web page at https://www.inspectorcaruso.com/1566-olive-ave.html Video Links – Roof 1566 Roof 1 http://youtu.be/DVFZ36DCW7s 1566 Roof 2 http://youtu.be/l4iHmuna2SY 1566 Roof 3 http://youtu.be/4Wrz-iZAYuo 1566 Roof4 http://youtu.be/yDbkDwQofg0 1566 Roof5 http://youtu.be/FC002MeKKD8
  • 29. 1. Type: Attached 2. Automatic Opener: No 3. Safety Reverse: No 4. Roofing: Tile, Same as main building. 5. Gutters/Eaves: No, Recommend adding. 6. Siding: Same as house 7. Trim: None 8. Floor: Cement 9. Sill Plates: Cement 10. Exterior Service Door: Yes 11. Electricity Present: Yes GFCI: NO, Safety Hazard. 12. Fire Separation Walls and Ceiling: Yes Garage Door not tested, Locked. Floor stains and wood damage, monitor and repair. Garage
  • 31. Shut-Off Valve Most shut-off valves have not been operated for long periods of time. We recommend operating each shut-off valve to: toilet bowl, water heater, under sinks, main shut-off, hose faucets, and all others. We recommend you have a plumber do this, as some of the valves may need to be repacked or replaced. Once the valves are in proper operating order, we recommend opening and closing these valves several times a year. Laundry Sink: No Dryer Vented: Hole in Wall, No Dryer Present. Electric: Outlet present, No GFCI, Safety Hazard. Washer/Dryer Hook-ups: Yes Cross Connections: Not present. Room Vented: Yes Heat Source Present: No Appliances: Washer: No Dryer: No Furnace: First floor Hallway Closet Water Heater: Closet, Front Left Laundry Room In Garage
  • 33. Water Pipes Galvanized water pipes rust from the inside out and may have to be replaced within 20 to 30 years. This is usually done in two stages: horizontal piping in the basement first, and vertical pipes throughout the house later as needed. Copper pipes usually have more life expectancy and may last as long as 60 years before needing to be replaced. Plumbing The temperature/pressure valve should be tested several times a year by lifting the valves handle. Caution: very hot water will be discharged. If no water comes out, the valve is defective and must be replaced. The pressure relief valve on this unit is not extended to the proper location, this is a safety hazard and needs to be repaired or replaced. Shut-Off Valve Most shut-off valves have not been operated for long periods of time. We recommend operating each shut-off valve to: toilet bowl, water heater, under sinks, main shut-off, hose faucets, and all others. We recommend you have a plumber do this, as some of the valves may need to be repacked or replaced. Once the valves are in proper operating order, we recommend opening and closing these valves several times a year. Water Heater Shut-Off Valve: Yes Main Shut Off: Left Side Visible water distribution: PVC, Copper. Water Heater #1 Location: Closet, outside front left. Brand: Sears Roebuck Model #: 153.338461 Serial #: F97784808 Capacity: 40 Approx. Age: Installed 1996, 18 years. Seismic Restraints: Yes Relief Valve: Yes, Satisfactory. Slight smell of gas in Water Heater Closet, Have Evaluated, Safety Hazard. Water Heater Vent pipe through closet door needs to be repaired, proper access of pipe required. Closet Door is damaged at bottom. Plumbing
  • 35. Appliances (If report indicated appliances were operated, the following applies) Stoves are tested to see that burners are working and oven and broiler get hot. Timer and controls are not tested. Refrigerators are not tested. Most new dishwashers have the drain line looped automatically and may not be visible on the day of inspection. It is essential for the dishwasher drain line to have an anti-siphon break to prevent back-flow. No representation is made to continued life expectancy of any appliance. Countertops: Satisfactory. Cabinets: Satisfactory. Plumbing: Satisfactory / Marginal, Rust and possible moisture spot under sink, monitor. Recommend further evaluation by plumber. Walls & Ceiling: Satisfactory. Heating Source: Satisfactory. Floor: Satisfactory. Outlets Present: Yes GFCI: Yes Open Ground/Reverse Polarity: No Lighting: Satisfactory. Dishwasher: No Dishwasher Air gap: N/A Range and Oven: Yes, back left range automatic light needed assistance, operates recommend cleaning. Requires safety strap. Window/Doors: Yes, Door to Garage operates and appears to be a fire door with automatic return. Sink: Yes Faucet: One Handle Disposal: No Oven: Yes, Satisfactory, needs safety strap. Range: Yes, Satisfactory, needs safety strap. Trash Compactor: No Exhaust Fan: Yes, operates Refrigerator: Yes Microwave: No Recommend having the oven / range safety strap added. Caulking recommended. Monitor rust and moisture spots under sink. Left back range automatic light not operating, does light with help, recommend cleaning. If continues, have further professional evaluation. Kitchen
  • 40. These videos are available on your web page at https://www.inspectorcaruso.com/1566-olive-ave.html Video Links – Kitchen 1566 Kitchen http://youtu.be/5wwSxw_uTK4
  • 41. Location: Downstairs, Front Middle Sinks: Operate Tub: Yes, no curtain. Toilet: Yes, does not operate properly while flushing, refer to video link. Whirlpool: No Shower/Tub Area: Normal water flow. Recommend caulking repair around tub and sink. Drainage: Satisfactory Water Flow: Satisfactory Moisture Stains Present: None Doors: Satisfactory Window: Yes Receptacles Present: Yes GFCI, Yes Open Ground/Reverse Polarity: No Heat Source Present: Yes Exhaust Fan: No Lighting: Fixture, operates with one bulb out. Repair Toilet, if continues have a certified plumber evaluate. Tub and sink need regular caulking. Recommend repairing light fixture and covering toilet secure screw. Bathroom #1
  • 42. Bathroom #1 Bulb needs to be replaced. Toilet clogged, refer to video.
  • 45. These videos are available on your web page at https://www.inspectorcaruso.com/1566-olive-ave.html Video Links – Bathroom1 1566 Kitchen http://youtu.be/HcpnEDBw6p0
  • 46. Location: Downstairs, Front Left Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling. Closet Guide: Marginal Sliding doors stick, hard to open and close. Window: Yes, no blinds or screen. Smoke Detector: No Walls and ceiling: Drywall Ceiling Fan: No Light Fixture: No Floors: Carpet Heat Source: Wall Vent Electrical: Switches: No Outlets: Yes Open Ground/Reverse Polarity: No Moisture Stains: No Bedroom Egress Restricted: No Doors: Yes (2), one Wood, operates. One Sliding closet, operates slightly sticks. Bedroom #1
  • 48. Location: Downstairs, Back Left Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling. Closet Guides: Marginal Window: Yes, no blinds. Screen needs repair. Smoke Detector: No Walls and ceiling: Drywall Ceiling Fan: No Light Fixture: No Floors: Carpet Heat Source: Wall Vent Electrical: Switches: No Outlets: Yes Open Ground/Reverse Polarity: No Moisture Stains: No Room Egress Restricted: No Doors: Yes (2), one Wood, operates. Three panel Sliding, operates. Bedroom #2
  • 50. Location: Downstairs, Left Middle Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling. Closet Guides: Marginal Window: Yes, no blinds or screens. Smoke Detector: No Walls and ceiling: Drywall Ceiling Fan: No Light Fixture: No Floors: Carpet Heat Source: Wall Vent Electrical: Switches: No Outlets: Yes Open Ground/Reverse Polarity: No Moisture Stains: No Room Egress Restricted: No Doors: Yes (2), one Wood operates. Bedroom #3
  • 52. Asbestos and other Hazards Asbestos fibers in some form are present in many homes, but are often not visible and cannot be identified without testing. If there is reason to suspect that asbestos may be present and if it is of particular concern, a sample of the material in question may be removed and analyzed in a laboratory. However, detecting or inspecting for the presence or absence of asbestos is not a part of our inspection. Also excluded from this inspection and report are the possible presence of, or danger from, radon gas, lead-based paint, urea formaldehyde, toxic or flammable chemicals and all other similar or potentially harmful substances and environmental hazards. Windows A representative number of windows were inspected, Satisfactory. Monitor, caulk and repair when needed. More efficient windows recommended. Smoke Detectors Smoke detectors should be tested monthly. At least one detector should be on each level. CO detectors are not required by most states, but for safety reasons, are highly recommended. This unit does not have both a smoke detector, not tested and CO Detector, not tested. Doors/Window: Satisfactory. Carbon Monoxide Detector: No Walls and ceiling: Drywall Ceiling Fan: No Light Fixture: Yes, operates. Floors: Carpet, prefabricated hardwood veneer. Heat Source: Wall Vents downstairs. Wall Heater in hallway of second floor hallway, not tested. Entryway: Metal security screen door, wood main door. Satisfactory. No screen, second floor, Safety Hazard. Must Repair. Interior
  • 56. Location: Second Floor, Back Right Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling. Closet Guides: OK Window: Yes, no blinds, screen needs repair. Smoke Detector: No Walls and ceiling: Drywall Ceiling Fan: Yes, operates. Light Fixture: No Floors: Carpet Heat Source: No Electrical: Switches: No Outlets: Yes Open Ground/Reverse Polarity: No Moisture Stains: No Room Egress Restricted: No Doors: Yes (2), one Wood operates, one Sliding Bedroom #4
  • 58. Location: Upstairs, end of Hallway. Sinks: Satisfactory Tub: Yes Toilet: Yes, operates, not loose. Whirlpool: No Shower/Tub Area: Normal water flow. Shower handle missing, recommend repair. Recommend caulking. Drainage: Satisfactory Water Flow: Satisfactory Moisture Stains Present: None Door: Satisfactory Window: Yes Receptacles Present: Yes GFCI Yes. Open Ground/Reverse Polarity: No Heat Source Present: Yes Exhaust Fan: No Lighting: Fixture Caulking needed, Shower handle missing, Bathroom door handle loose. Bathroom #2
  • 59. Bathroom #2 Caulk. Missing shower handle. Loose door handle.
  • 61. Location: Second Floor, Front Right. Door Stops: No, Missing door stops can result in door knobs breaking through wood paneling. Closet Guides: Satisfactory Window: Yes, no blinds or screen. Smoke Detector: No Walls and ceiling: Drywall Ceiling Fan: No. Light Fixture: No Floors: Carpet, stained. Heat Source: No Electrical: Switches: Yes Outlets: Yes Open Ground/Reverse Polarity: No Moisture Stains: No Room Egress Restricted: No Doors: Yes (1), Wood operates. Bedroom #5
  • 63. Ventilation: Recommended at the rate of one square foot of vent area to 300 square feet of attic floor space, this being divided between soffit and rooftop. There is ventilation and appears adequate. Insulation The recommended insulation in the attic area is R-38, approximately 12". If insulation is added, it is important that the ventilation is proper. There is a combination of loose and strips of insulation. Recommend removing loose insulation from lighting and other fixtures in attic. Have evaluated and repaired by HVAC professional. Loose insulation should be upgraded to improve efficiency. Vapor Barriers The vapor barrier should be on the warm side of the surface. Most older homes were built without vapor barriers. If the vapor barrier is towards the cold side of the surface, it should be sliced or removed. Vapor barriers in the attic are covered by insulation and therefore, not visible. Access: Scuttle hole / Hatch Inspected from: Ladder Location: Hallway Flooring: No Insulation: Loose and Strips Fiberglass, no access. Installed: Between ceiling joist. Fans Exhausted to Attic: No, Outside. HVAC Duct: Insulated Chimney Chase: N/A Structure problems: None observed. Roof Structure: Wood, Slight moisture present. Moisture present. Sagging sections between beams. One layer of fairly new tile, wood roof should be repaired or replaced, monitor. Attic is covered with loose insulation, not accessible. The service and distribution lines are insulated minimally, add, repair, monitor and upkeep. Insulation should be removed from around lighting. Some nail popping present. Recommend further evaluation. Attic 1
  • 64. Ventilation: Recommended at the rate of one square foot of vent area to 300 square feet of attic floor space, this being divided between soffit and rooftop. There is ventilation and appears adequate. Insulation The recommended insulation in the attic area is R-38, approximately 12". If insulation is added, it is important that the ventilation is proper. There is a combination of loose and strips of insulation. Loose insulation should be upgraded to improve efficiency. Vapor Barriers The vapor barrier should be on the warm side of the surface. Most older homes were built without vapor barriers. If the vapor barrier is towards the cold side of the surface, it should be sliced or removed. Vapor barriers in the attic are covered by insulation and therefore, not visible. Access: Scuttle hole / Hatch. Inspected from: Ladder Location: Hallway Flooring: No Insulation: Loose and Strips Fiberglass, no access. Installed: Between ceiling joist. Fans Exhausted to Attic: No, Outside. HVAC Duct: Insulated Chimney Chase: N/A Structure problems: None observed. Roof Structure: Wood, Slight moisture present. Attic is covered with loose insulation, not accessible. The service and distribution lines are insulated. Insulation should be removed from around lighting. Recommend further evaluation. Attic 2
  • 65. Attic 1 Loose Insulation should be removed from light fixtures. Sagging, moist wood. Nail popping. Furnace distribution pips need insulation upkeep.
  • 67. These videos are available on your web page at https://www.inspectorcaruso.com/1566-olive-ave.html Video Link – Attic 1566 Attic 1 http://youtu.be/K1V7qVMGmKc 1566 Attic 2 http://youtu.be/4hl9cN2TCYA
  • 68. Every effort has been made to evaluate the size of the service. The total amperage can be difficult to determine. We highly recommend that ground fault circuit interrupters (GFCI) be connected to all outlets around water. This device automatically shuts the circuit off when it senses a current leak to ground. Federal Pacific Stab-Lok Electrical® panels may be unsafe. See www.google.com (Federal Pacific) Aluminum wiring in general lighting circuits has a history of overheating, with the potential of a fire. If this type of wiring exists, a licensed electrical contractor should examine the whole system. Location: Left, side of unit. Amperage: 120/240, Breakers Adequate clearance to panel: Satisfactory Appears Grounded: Yes GFCI Breaker: No Main Wire: Copper Branch Wire: Copper, Aluminum Double Tapping: None observed Neutral/Ground Separated: Yes Outlets were randomly tested and had correct polarity, except as noted. Aluminum wires have been used for branch wiring - recommend licensed electrician evaluate the system. Electrical
  • 70. These videos are available on your web page at https://www.inspectorcaruso.com/1566-olive-ave.html Video Links – Electrical 1566 Heating http://youtu.be/JQCgpnKIXIU
  • 71. Gas-fired hot air units that are close to or beyond their normal lives have the potential of becoming a source of carbon monoxide in the home. You may want to have such a unit checked every year or so to assure yourself that it is still intact. Of course a unit of such an age is a good candidate for replacement with one of the new, high efficiency furnaces. The fuel savings alone can be very attractive. Forced air systems should have filters changed every 30 to 60 days of the heating season. A dirty air system can lead to premature failure of your compressor - a $1,500 machine. Read the instructions for maintaining the humidifier on your furnace. A malfunctioning humidifier can rust out a furnace rather quickly. It is recommended that the humidifier be serviced at the same time as the furnace, and be cleaned regularly. During a visual inspection it is not possible to determine if the humidifier is working. Although the unit is currently working, the condition of the ventilation system, wet drywall closet and overall age of this unit I am recommending having an HVAC technician examine. Heat exchangers cannot be examined nor their condition determined without being disassembled. Since this is not possible during a visual, non- technically exhaustive inspection, you may want to obtain a service contract on the unit or contact a furnace technician regarding a more thorough examination. Testing pilot safety switch requires blowing out the pilot light. Checking safety limit controls requires disconnecting blower motor or using other means beyond the scope of this inspection. If the furnace has not been serviced in last 12 months you may want to have a furnace technician examine. CO Test - This is not part of a non-technical inspection. Normal lives are: GAS-FIRED HOT AIR 15-25 years Oil-Fired HOT AIR 20-30 years CAST IRON BOILER 30-50 years STEEL BOILER 30-40 years COPPER BOILER 10-20 years CIRCULATING PUMP (Hot water) 10-15 years AIR CONDITIONING COMPRESSOR 8-12 years HEAT PUMP 8-12 years Heating
  • 72. Energy Source: Unit 1, downstairs hallway closet, Gas. Unit 2, hallway wall upstairs, Gas pilot not light. Warm Air System: Unit 1, Central System Controls: Unit 1 downstairs Hallway, operates. Distribution: Duct When turned on by Thermostat: Operated. Visual inspection of pilot light. System Condition: Unit 1, Satisfactory. Unit 2 Recommend evaluation by SDG&E or an HVAC professional. Brand Name: Rheem Approx. Age: ? Model #: ? Serial # ? Heating System Remarks: Recommend repairing vent duct insulation. Unit may be nearing expected operating years. Heating
  • 74. These videos are available on your web page at https://www.inspectorcaruso.com/1566-olive-ave.html Video Links – Heating 1566 Heating http://youtu.be/GhXxXah9JyQ
  • 75. I. Foundation and Masonry: Basements, Exterior Walls: To prevent see page and condensation problems. a. Check basement for dampness and leakage after wet weather b. Check chimneys, deteriorated chimney caps, loose, and missing mortar. c. Maintain grading sloped away from foundation walls. II. Roofs, Gutters, and Eavestrough: To prevent roof leaks, condensation, see page and decay problems. a. Check for damaged, loose, or missing shingles, blisters. b. Clean gutters, leaders, strainers, window wells, drains. Be sure downspouts direct water away from foundation. c. Cut back tree limbs. d. Check flashings around roof stacks, vents, skylights, chimneys as source of leakage. e. Check vents, louvers and chimneys for birds nests, squirrels, insects. f. Check fascias and soffits for paint flaking leakage and decay. III. Exterior Walls: To prevent paint failure, decay, and moisture penetration problems. a. Check painted surface for paint flaking or paint failure. Check back shrubs. b. Check exterior masonry walls for cracks, looseness, missing or broken mortar. IV. Doors and Windows: To prevent air and weather penetration problems. a. Check caulking for decay around doors, windows, corner boards, joints. b. Re-caulk and weatherstrip as needed. Check glazing putty around windows. Preventive Maintenance Tips
  • 76. V. Electrical: For safe electrical performance, mark and label each circuit. a. Trip circuit breakers every six months and ground fault circuit interrupters (GFCI.) monthly. b. Check condition of lamp cords, extension cords and plugs. Replace at first sign of wear and damage. c. Check exposed wiring and cable for wear or damage. d. If you experience slight tingling shock from handling or touching any appliance, disconnect the appliance and have it repaired. If lights flicker or dim, or if appliances go on and off unnecessarily, call a licensed electrician. VI. Plumbing: For preventive maintenance. a. Drain exterior water lines, hose bibs, sprinklers, pool equipment in the fall. b. Draw off sediment in water heaters monthly or per manufacturer's instructions. c. Have septic tank cleaned every 2 years. VII. Heating and Cooling: For comfort, efficiency, energy conservation and safety. a. Change or clean furnace filters, air condition filters, electronic filters as needed. b. Clean and service humidifier. Check periodically and annually. c. Have oil burning equipment serviced annually. VIII. Interior General house maintenance. a. Check bathroom tile joins, tub grouting and caulking. Be sure all tile joints in bathrooms are kept well sealed with tile grout to prevent damage to walls, floors, and ceilings below. b. Close crawl vents in winter and open in summer c. Check underside of roof for water stains, leaks, dampness & condensation, particularly in attics and around chimneys. IX. Know the location of: -Main water shutoff valve. -Main emergency shutoff switch for the heating system. -Main electrical disconnect or breaker. Preventive Maintenance Tips