SlideShare a Scribd company logo
1 of 36
T.C
     KOCAELİ ÜNİVERSİTESİ
      MÜHENDİSLİK FAKÜLTESİ
 ELEKTRİK MÜHENDİSLİĞİ BÖLÜMÜ



           PROJE -3-

AKIM VE GERİLİM TRANSFORMATÖRLERİ



        MURAT ŞENDİL
       ELEKTRİK MÜH.(İ.Ö)
          070206045


       PROJE DANIŞMANI

    Yrd.Doç.Dr.MEHLİKA ŞENGÜL




          ARALIK 2011

            KOCAELİ
İÇİNDEKİLER                                                                                Sayfa No

1) GİRİŞ………………………………………………………………………….                                                                 5

 1.1) Transformatörlerin Önemi……………………………………………… ...                                                  5

 1.2)Transformatörlerin Yapısı………………………………………………….                                                    5

 1.3)Transformatörlerin Çalışma Prensibi……………………………………….                                              6

 1.4)Transformatörlerin Dönüştürme Oranları ………………………………….                                            7

 1.5)Transformatörlerde Verimin Bulunması ........................................................    8

2) ÖLÇÜ TRANSFORMATÖRLERİ……………………………………………..                                                          9

 2.1) Ölçü Transformatörlerinin Kullanılış Amacı………………………………..                                        9

3) AKIM TRANSFORMATÖRLERİ…………………………………………….                                                           9

 3.1) Tanımı……………………………………………………………………...                                                             9

 3.2) Genel Yapısı……………………………………………………………….. 10

 3.3) Akım Transformatörü Prensip Şekli……………………………………….                                              11

 3.4) Akım Transformatörü Kullanılma Amaçları………………………………                                            11

 3.5) Akım Transformatörü’nün Özellikleri…………………………………….. 12

 3.6) Akım Transformatörlerinde Polarite………………………………………. 12

 3.7) Kullanıldığı Gerilime Göre Akım Transformatörler Çeşitleri……………. 13

    3.7.1) Alçak Gerilim Akım Transformatörleri………………………………                                          13

    3.7.2) Orta Gerilim Akım Transformatörleri………………………………                                           13

 3.8) Soğutma Şekline Akım Transformatör Çeşitleri………………………….                                        14

 3.8.1) Yağlı Tip………………………………………………………………..                                                          14

 3.8.2) Kuru Tip………………………………………………………………..                                                           14

 3.9)Yapılışlarına Göre Akım Transformatör Çeşitleri………………………….. 14

 3.9.1) Sargılı Tipi……………………………………………………………… 14

 3.9.2) Bara Tipi………………………………………………………………… 15

                                                      2
3.10) Kullanıldıkları Yere Göre Akım Transformatör Çeşitleri………………….     15

    3.10.1 )İç Tip (Bina İçi,Dahili)……………………………………………….                   15

   3.10.2 Dış Tip(Bina Dışı,Harici)………………………………………. .. . ..               15

 3.11) Akım Transformatörü Seçiminde Dikkat Edilecek Hususlar………………. 15
 3.12) Akım Transformatörü Etiket Değerleri…………………………………….. 16
 3.13)Akım Transformatör Testleri………………………………………………... 17
  3.13.1) Polarite Tayini…………………………………………………………..                         17
  3.13.2) Çevirme Oranı Testi…………………………………………………….. 17
4)AKIM TRANSFORMATÖRLERİNİN KARAKTERİSTİK DEĞERLERİ

 4.1)Karakteristik Değerler…………………………………………………………. 18

   4.1.1) İşletme Gerilim Anma Değeri (Un)………………………………………. 19

   4.1.2) Anma Gücü (Nn)………………………………………………………… 19

  4.1.3) Sınıf Klas (Cl)…………………………………………………………….. 20

  4.1.4) Doyma Katsayısı(Saturasyon Kat Sayısı (n)……………………………… 21

   4.1.4.1) Ölçü Akım Trafolarında n<5 ………………………………………… 22
   4.1.4.2) Ölçü Akım Trafolarında n>10………………………………………… 22

  4.1.5) Akım Çevirme Oranı (Akım Oranı) (k) …………………………………. 22

  4.1.6) Anma Akım Değerleri (k)………………………………………………… 22

  4.1.7) Termik Anma Akımı (Ith)………………………………………………… 23

  4.1.8) Dinamik Anma Akımı (Idyn)……………………………………………..                     24

  4.1.9) Akım Transformatörünün Sekonder Sargı Ucunu Açık Kalmamasının Önemi

5)GERİLİM TRANSFORMATÖRLERİ…………………………………………… 25

 5.1 Gerilim Transformatörleri……………………………………………………… 25

  5.1.1) Tanımı……………………………………………………………………… 25

  5.1.2) Şematik Gösterimi………………………………………………………….. 25
  5.1.3) Çalışma İlkesi………………………………………………………………. 25

                                         3
5.1.4)Gerilim Transformatörü Yapısı……………………………………………….                     26

 5.1.5) Gerilim Transformatörü Prensip Şekli……………………………………….                27

 5.1.6) Gerilim Transformatörünün Kullanım Amaçları…………………………….             27

 5.1.7) Gerilim Transformatörü’nün Özellikleri……………………………………..              28

 5.1.8)Kullanıldıkları Yere Göre Gerilim Transformatör Çeşitleri…………………... 28

  5.1.8.1) Faz-Toprak Gerilim Transformatörü……………………………………                  28

  5.1.8.2) Faz-Faz Gerilim Transformatörü………………………………………                    29

 5.1.9) Kombine(Akım ve Gerilim Transformatörü Birlikte) Ölçü ………………….. 29

 5.1.10) Gerilim Transformatörü Siparişinde Dikkat Edilecek Hususlar……………   30

 5.1.11) Gerilim Transformatörü Etiket Değerleri……………………………………              30

5.2) Gerilim Transformatör Testleri…………………………………………………                      31

 5.2.1) Polarite Tayini………………………………………………………………….. 31

 5.2.2) Isınma Sıcaklık Artışı Testi……………………………………………………                    31

6)GERİLİM TRANSFORMATÖRÜNÜN KARAKTERİSTİK DEĞERLERİ

 6.1) Anma Gerilim Değerleri (Up ve Us)……………………………………………                    32

 6.2) Anma Gücü (Nn)…………………………………………………………………. 33

 6.3) Sınıf Klas (Cl)…………………………………………………………………….                             33

 6.4) Dayanma Katsayısı (Uk)…………………………………………………………. 33

7) KAYNAKÇA………………………………………………………………………                                      34




                                         4
GİRİŞ

   1.1) Transformatörlerin Önemi

           Elektrik enerjisinin en önemli özelliklerinden biri de üretildiği yerden çok uzak bölgelere
taşınabilmesidir. Bu taşınmanın verimli bir şekilde yapılabilmesi için gerilimin yeteri kadar yüksek olması
gerekir.

      Bilindiği gibi elektrik doğru veya alternatif akım şeklinde üretebilir. Doğru akımda yüksek gerilimli
enerji iletimi son zamanlarda büyük önem kazanmıştır. Ancak bu konuda istenilen düzeye gelinmemiş olup
çalışmalar sürdürülmektedir. Buna karşılık alternatif akımlı elektrik enerjisinin gerilimi transformatörler
yardımı ile yükseltilip düşürülebildiğinden, enerjinin alternatif akımla taşınması önemini korumaktadır.

      Santrallerde generatörler (alternatörler) yardımı ile üretilen elektrik enerjisinin gerilimi çok yüksek
değildir. Generatör çıkış gerilimleri 0,4 - 3,3 - 6,3 - 10,6 - 13,0 - 14,7 - 15,8 ve 35 kilovolt (kV)
değerlerindedir. Bu gerilimler enerjinin uzak bölgelere taşınmasını sağlayacak kadar yüksek olmadığından
yükseltmeleri gerekir. Gerilimlerin yükseltilmesi ise ancak transformatörlerin yardımı ile gerçekleştirilir.

   Transformatörler, gerilimi alçaltma ve yükseltme şekline göre iki çeşittir.

    Alçaltıcı Transformatörler: Primer sargısına uygulanan gerilimi sekonder sargısından daha alçak bir
şekilde aldığımızda bu tip transformatörlere alçaltıcı tip transformatörler denir.

    Yükseltici Transformatörler: Primer sargısına uygulanan gerilimi sekonder sargısından daha yüksek
bir şekilde aldığımızda bu tip transformatörlere yükseltici tip transformatörler denir.

   1.2) Transformatörlerin Yapısı
           Transformatörler ince özel silisli saçalardan oluşan kapalı bir manyetik gövde ile bunun
üzerine,yalıtılmış iletkenlerle sarılan sargılardan oluşur.En basit şekilde iki sargı bulunur.Bu sargılardan
birine PRİMER veya birinci devre diğerine ise SEKONDER veya ikinci devre adı verilir. Primer ve
sekonder sargılarının birbirlerine elektriksel bir bağlantısı yoktur. Ancak özel olarak yapılan oto
transformatörlerinde her iki sargı elektriksel olarak birbirleri ile bağlantılıdır. Şekil:1–1.’de bir
transformatörün basit yapısı görülmektedir.




                                                           5
Transformatör sargılarına gerilim değerlerine göre alçak gerilim sargısı veya yüksek gerilim sargısı gibi
isimler de verilmektedir. Güvenlik için kullanılan özel yalıtıcı transformatörler dışında, primer ve sekonder
gerilimleri birbirinden farklıdır. Transformatörlerin primer sargıları uygun gerilimdeki bir alternatif akım
devresine bağlandığında sekonder sargılarından değişik değerde fakat aynı frekansta başka bir alternatif
gerilim alınır.
         Primer gerilimi, sekonder geriliminden büyükse, bu çeşit transformatörlere düşürücü veya alçaltıcı
transformatörler primer gerilimi sekonder geriliminden küçükse, bu çeşit transformatörlere yükseltici
transformatörler adı verilir. Buna göre transformatör; sargıların birisinden geçen bir alternatif akım
sistemini, elektromanyetik endüksiyon etkisi ile öteki sargısına aynı frekanslı fakat farklı şiddet ve gerilimde
başka bir akım sistemine dönüştüren statik bir elektrik makinesi olarak tanımlanabilir.
      Manyetik nüvede sargıların bulunduğu kısma ayaklar ve bacaklar denir. Ayakları birleştiren alt ve üst
parçalara ise boyunduruk adı verilir.



   1.3) Transformatörlerin Çalışma Prensibi

      Şekil: 1–1.’ de görülen primer sargılarına alternatif bir gerilim uygulandığında, bu sargı değişken bir
manyetik alan oluşturur. Bu alan üstünde sekonder sargının da bulunduğu manyetik demir nüve üzerinden
devresini tamamlar. Primere uygulanan alternatif gerilimin zamana bağlı olarak her an yön ve şiddeti
değiştiğinden, manyetik alanın da her an yön ve şiddeti değişir. Bu alanın sekonder sargılarını kesmesi
(veya kavraması da denir) ile bu sargılarda alternatif bir gerilim indüklenir. Görüldüğü gibi primer ve
sekonder sargılarının birbirleri ile elektriksel hiç bir bağlantıları olmadığı halde 2.devrede manyetik
endüksiyon yolu ile bir gerilim oluşabilmektedir. Transformatörün primer sargılarına doğru gerilim
uygulandığında, demir nüve üzerinde gene bir manyetik alan oluşur. Ancak bu manyetik alan, sabit bir
alandır. Bu alanın yön ve şiddeti değişmediğinden sekonder sargılarında bir elektro-motor-kuvvet (emk.)
indüklenmesi söz konusu olamaz. Çünkü indüksiyon kurallarına göre, değeri değişen manyetik alanlar

                                                           6
tarafından etkilenen sargılarda endüksiyon gerilimleri oluşabilir. Doğru akımın verilişi ve kesilişi sıralarında
sekonderde endüksiyon gerilimleri görülebilir. Ancak manyetik alanın değişimi sürekli olmadığından,
transformatör doğru akımda kullanılamazlar.

  1.4) Transformatörlerin Dönüştürme Oranları
      Bir iletkende emk indüklenebilmesi için o iletkenin sabit bir manyetik alan içinde hareket ettirilmesi
veya değişen bir manyetik alan içinde bulundurulması gerekir. Birinci durum doğru akım generatörleri’nin
çalışma prensibini, ikinci durum ise transformatörlerin çalışma prensibini oluşturur. Daha önceki konularda
da açıklandığı gibi, bir transformatörün birinci devre sargılarına alternatif bir gerilim uygulandığında ikinci
devre uçlarına bir yük bağlanmasa da yani ikinci devre uçları açık olsa da, birinci devre sargılarından çok
küçük bir boş çalışma akımı (Ib) geçer. Geçen bu akımın oluşturduğu değişken (alternatif) akım, sekonder
sargılarını keserek bu sargılarda alternatif bir emk indüklenir. İndüklenen bu emk’in frekansı, birinci
devreye uygulanan gerilimin frekansına eşittir.

      Transformatör boştaki akımının oluşturduğu manyetik akının sekonder sargılarını kestiği ve boştaki
nüve kayıplarının sıfır olduğu varsayılırsa böyle bir transformatör ideal transformatör olarak tanımlanır.
İdeal transformatörlerde sekonder sargıları kesen kuvvet çizgilerinin tamamı, birinci devre sargılarını da
keser. Bu durumda transformatörün her iki sargısının her bir sarımında aynı değerde gerilim
indüklenir.Buna, her iki sargının sipir başına endüklenen gerilimleri aynıdır diyebiliriz. Primer ve sekonder
sargılarda endüklenen bu gerilimler aynı akı tarafından oluşturulduğundan aralarında bir faz farkı yoktur.
Yani birinci ve ikinci devrede indüksiyon yolu ile oluşan gerilimler aynı fazdadır.

     Transformatörün primerinde oluşan E1 emk’i Lenz kanununa güre kendisini oluşturan U1 gerilimine
ters yönde olup yaklaşık olarak eşit değerdedir. (Gerçekte E1 emk.’i U1 den % 1 ila % 2 kadar küçüktür.)
Transformatörün her iki sargısında sipir başına endüklenen gerilimler aynı olduğundan 1. ve 2. devre emk.
larının birbirine oranı, sipir sayılarının oranına eşit yazılabilir.

         E1 N1                    U1 N1
           =        Bu eşitliği     =           şeklinde de gösterebiliriz. Bu eşitliklerdeki harflerin anlamları
         E2 N2                    U2 N2
şöyledir:

     E1 ... Primerde indüklenen emk (Volt)

     E2 ... Sekonderde indüklenen emk (Volt)

     U1 ….. Primer gerilimi. (Volt)

     U2….. Sekonder gerilimi. (Volt)

     N1 ... Primerin sipir sayısı.

     N2…… Sekonder sipir sayısı.



                                                              7
Transformatörlerin verimleri çok yüksek olduğundan 1. ve 2. devre güçleri birbirine eşit yazılabilir. Buna
göre volt-amper (VA) olarak1. ve 2. devre güçleri,
    S1 = U1 . I1 ; S2 = U2.I2 şeklinde belirtilir. Kayıpsız transformatörde S1= S2 olduğundan U1 .I1 = U2.I2 ve

  U1 I1                              U1 N1
    =   yazılabilir. Bu eşitliği       =   ile birleştirip yazarsak, transformatörlerin (K) ile belirtilen
  U2 I2                              U2 N2
dönüştürme oranlarını bu1muş oluruz. Buna göre transformatörlerde dönüştürme oranı:
        U1 I2 N1
   K =     = =          şeklinde yazılabilir. Transformatörlerin dönüştürme oranları gerilimler bakımından
        U2 I1 N2
şu şekilde yazılır:
                 Transformatörün primer gerilimi
           K =
                Transformatörün sekondergerilimi
   Bir transformatörün dönüştürme oranı bilinirse bundan faydalanarak primer ve sekonder gerilimleri, sipir
sayıları ve akımları bulunabilir.

1.5) Transformatörlerde Verimin Bulunması
    Transformatörlerde verim iki şekilde bulunur:
      a-Direkt metotla verimin bulunması;

    Bu metotla daha çok küçük güçlü transformatörlerde uygulanır.Sekonder yükü sıfırdan başlanarak tam
yüke kadar yavaş yavaş arttırılır.Her yükte primer ve sekonderdeki wattmetreden okunan değerler alınarak
n=P2 / P1 şeklinde verimi bulunuz.

   b-Endirekt metotla verimin bulunması;

    Endirekt metotla verimin bulunması büyük güçlü transformatörlerde uygulanır.Bunun için boş çalışma
deneyi ile, transformatörün demir kayıpları;kısa devre deneyi ile bakır kayıpları bulunur.

Bundan sonrada n=PA / PA + Pk şeklinde verim bulunur.




                                                          8
ÖLÇÜ TRANSFORMATÖRLERİ


2.1) Ölçü Transformatörlerinin Kullanılış Amacı

     Alternatif akımda yüksek gerilim ve büyük akımların ölçü aletleri ile ölçülmesi çok zor ve tehlikelidir.
Çünkü ölçü aletinin yüksek gerilimlerinin yalıtılması ve alet bobinlerinin yüksek akımlara dayanacak
kesitlerde yapılması belli değerlerden sonra mümkün olamaz Bu nedenle yüksek gerilim ve büyük akımların
ölçülmesi için ölçü transformatörlerin kullanılır, Ölçü transformatörleri yardımı ile yüksek gerilimler ve
büyük akımlar, transformatörün ikinci devresinde, ölçü aletlerinin ölçebileceği değerlere inilir. Ölçü
transformatörleri, ölçümlerin güvenlik içinde kolay ve doğru bir şekilde yapılmasını sağladığı gibi,
çalışanları da yüksek gerilimlerden korur.

      Ölçü transformatörlerinin sekonderlerine, ampermetreler, voltmetreler, wattmetreler, çeşitli röleler ve
bazı kontrol aygıtları bağlanabilir. Ölçü transformatörlerinin yüklerine yalnız ölçü aletleri oluşturduğundan,
anma güçleri küçüktür. Buna göre ölçü transformatörlerini, ölçü aletlerin ölçme sınırlarını genişletmek için
kullanılır denebilir.

      Ölçü transformatörleri genel olarak akım ve gerilim ölçmelerde kullanılır. Buna göre iki ayrı özellikte
ölçü transformatörü yapılmıştır.

      Bunlar:

      1 — Akım transformatörleri

      2 — Gerilim transformatörleridir.




                         AKIM TRANSFORMATÖRLERİ
   3.1) Tanımı
     Bağlı oldukları devreden geçen akımı istenen oranda küçülterek, bu akımla sekonder terminallere bağlı
aletleri besleyen ve onları yüksek gerilimden izole eden özel trafolara, akım transformatörleri denilir. Akım
transformatörü şekil 3.1’deki sembollerle gösteril




                                                          9
Şekil 3.1 Akım transformatörlerinin sembolleri



3.2) Genel Yapısı
        Bir akım trafosunun genel olarak yapısı, şekilde görülene benzer olup, bu şekilde işaretlenen
bölümlerden oluşur.




                                 Şekil 3.2 Akım Transformatörünün Yapısı


      Primer Sargı: Demir nüve üzerine sarılmış, bir/iki sipir sayılı ve kesitçe,öngörülen akım değerine
uygun bir sargıdır.

      Sekonder Sargı:Demir nüve üzerinde primere göre ters yönde sarılmış ve sarım sayısı(akım oranı
kadar)fazla,kesitçe küçültülmüş yeterli akım değerinde bir sargıdır.

    Sekonder sargı, akım transformatörünün, ölçü aletlerinin, sayaçların, rölelerin ve benzer aygıtların akım
devrelerini besleyen sargıdır.

   Sargı Terminalleri: Primer sargının ana devreye ve sekonder sargının, (Ölçü / Koruma) devresine
bağlantısını temin etmek üzere gövde dışına çıkarılmış terminallerdir. Primer sargı terminalleri, şekilde
görüldüğü üzere üst bölümde, sekonder sargı terminalleri, alt bölümde ve yanda yer alır.

   Gövde: Geçmişte, içi izolasyon yağı ile doldurulmuş metal gövdeli olarak üretilen; akım trafolarının
yerine, hem gövdeyi ve hem izolasyonu sağlayan (reçine/epoksi türü) katı izolasyon maddelerinin
kullanımına geçilmiştir.

  Demir Nüve: Manyetik akı ortamını sağlayan demir nüvenin kesiti ve diğer nitelikleri, o akım
trafosunun bazı karakteristik değerlerini belirler. Bir akım trafosunun ölçü veya koruma amaçlı
kullanımı, güç, doyma katsayısı ve doğruluk sınıfı gibi karakteristik değerlerin farklı olmasını
gerektirir. Bu nedenlerle; akım trafoları kulanım amaçlarına göre farklı üretilirler. Bir merkezde hem
ölçü ve hem de koruma söz konusu olduğunda, farklı karakteristik değerlere sahip farklı akım
trafolarının kullanımı gerekecektir. Farklı karakteristikli iki akım trafosunun, aynı gövde içinde
üretildiği tipler, ekonomik bir çözüm olarak sunulmaktadır.

                                                         10
Şekil:3.4’te böyle bir akım trafosunun blok şeması görülmektedir.             1 nolu (1s1 ve 1s2) sekonder
terminaller ölçü devresi için, 2 nolu (2s1 ve 2s2) terminaller koruma devresi için kullanılabilir.




                              Şekil 3.4 Koruma ve Ölçme Akım Trafosu




3.3) Akım Transformatörü Prensip Şekli
      Akım transformatörleri çalışma ve parçaları bakımından trafolara çok benzemektedir. Fakat akım
transformatörleri sekonderi kısa devre çalışan ve sekonder çıkış akımı belirli oranda (ölçme ve koruma
röleleri için) sınırlandırılmış özel bir trafodur. Şekil 3.5'te akım transformatörünün prensibi verilmiştir.




                             Şekil 3.5 Akım Transformatörünün Prensip Şekli




3.4) Akım Transformatörü Kullanılma Amaçları
 Akım transformatörlerinin kullanma amaçlarını şu şekilde sıralayabiliriz:

Ölçü aletlerini ve koruma rölelerini primer geriliminden izole ederek, güvenli çalışmaya imkân sağlar.

Değişik primer değerlerine karşılık standart sekonder değerler elde edilir.

                                                           11
Ölçü transformatörlerinin kullanılması, ölçü aletlerinin ve rölelerin küçük boyutlu imal edilmesine
imkan verir.

Büyük akımlar ölçmede daha ekonomik bir çözümdür.

3.5) Akım Transformatörü’nün Özellikleri
  Akım transformatörlerinin en önemli özellikleri şunlardır:

Primer devresinden geçen akımı, dönüştürme oranına göre sekonder devreye aktarır.

Akım transformatörleri sekonder devreleri, kısa devre durumunda çalışır.

Primer sargıları kalın ve az sarımlı veya sadece baradan oluşur.

Sekonder sargıları ise, ince telli ve çok sarımlıdır.

Akım transformatörlerinin primer ve sekonder sargılarının giriş ve çıkış uçları, değişik harflerle ifade
edilir.




              Şekil 3.6.Akım Transformatörünün Giriş ve Çıkış Uçlarının Harflerle Gösterimi

Akım transformatörlerinin bazı ölçü aletleri ile bağlantısında polaritesi önemlidir.

Aynı akım transformatörü ile birkaç ölçü aleti kullanılabilir.

Akım transformatörlerinin, ölçme hassasiyetlerine göre sınıfları: 0,1-0,2-0,5-1 ve 3 olmak üzere
sınıflandırılır.

Koruma devrelerinde 3 sınıfı, sayaçlarda 0,2-0,5 sınıfı, ölçü aletlerinde 1 sınıfı akım transformatörleri
kullanılır.

Akım transformatörlerinin sekonder ucu mutlaka topraklanmalıdır.

Akım transformatörleri nominal akımlarının %20 fazlasına kadar yüklenebilir.

3.6) Akım Transformatörlerinde Polarite
    Bir akım trafosunun primer ve sekonderindeki polarite uçları, primer sargıya akımın giriş veya çıkış
yönüne göre, sekonder sargıdaki akım yönünün belirlenmesi anlamına gelir. Primer sargıya akımın girdiği
veya akımın çıktığı ucu polarite olarak kabul etmek mümkündür. Ancak, akımın primere girdiği ucu polarite
olarak kabul etmiş isek; sekonder sargıdan akımın çıktığı ucu polarite olarak almalıyız.Şekil 3.7 (a)(b)


                                                          12
Akımın primer sargıdan çıktığı ucu polarite olarak kabul etmek de mümkündür. Bu takdirde, sekonderde
polarite ucu, akımın sekonder sargıya girdiği uç olacaktır. Şekil 3.7. (c) ve (d)

    Aşağıdaki şekilde, primer için yapılan polarite kabulüne göre, sekonder polarite uçları belirlenmiş ve
işaretlenmiştir.



    Şekilde de görüleceği üzere, primer akımın giriş yönü dikkate alınmadan;

P2 Primer ucu polarite olarak seçilmişse S2 sekonder polarite ucu olacaktır.

P2 Primer ucu polarite olarak seçilmişse S2 sekonder polarite ucu olacaktır.




                                     Şekil 3.7.Polarite

3.7) Kullanıldığı Gerilime Göre Akım Transformatörler Çeşitleri

3.7.1) Alçak Gerilim Akım Transformatörleri

    Alçak gerilim şebekelerinde kullanılan akım trafolarıdır. Dağıtım transformatörü çıkışı fazlar arası 400
V olan gerilimdir. Bu gerilim ile çalışan iş yerleri ve fabrikalarda kullanılan akım trafolarıdır. Alçak
gerilimde kuru tip akım transformatörleri kullanılır.




                                  Resim 3.1.AG Akım Transformatörleri

3.7.2) Orta Gerilim Akım Transformatörleri
      Alçak gerilim şebekeleriyle yüksek gerilim şebekeleri arasında köprü görevi yapan orta gerilim
şebekeleridir. Enerji iletiminde en çok kullanım alanına sahip şebekelerdir. Ülkemizde 3-36 KV kadar olan
şebekelerdir. Bu şebekelerde kullanılan akım transformatörleri kuru tip akım trafolarıdır.


                                                          13
Resim 3.2.Orta Gerilim Akım Transformatörleri

3.8) Soğutma Şekline Akım Transformatör Çeşitleri
3.8.1) Yağlı Tip

         Bu tip akım transformatörlerinde yalıtkanlığı genellikle izolasyon yağı sağlar. Kuru tip akım
transformatörlerine göre, terleme veya yağ sızıntısı yapmak suretiyle kirlenme gibi kötü özellikleri vardır.
Yüksek gerilimde kullanılan akım transformatörleri yağlı tip transformatörlerdir.

3.8.2) Kuru Tip
        Akım transformatörlerinin iletken kısımları birbirinden ve şaseden katı yalıtkan malzemelerle
yalıtılmışlardır. Bu tip trafolarda yalıtım maddesi olarak zift, kâğıt, reçine ve vb. malzemeler
kullanılmaktadır. Genellikle alçak gerilimde kullanılan akım transformatörleri kuru tip olarak yapılırlar.
Ekonomik bakımdan ucuz, ancak herhangi bir arızada tamirleri zordur.

3.9)Yapılışlarına Göre Akım Transformatör Çeşitleri
3.9.1) Sargılı Tipi
      Bu tip akım transformatörlerinin primer sargıları tek bir iletken değil, sarımlardan oluşur. Primer ve
sekonder sargıları aynı manyetik devre üzerine sarılmıştır.




                                  Şekil 3.8 Sargı Tipi Akım Transformatörü




                                                         14
3.9.2) Bara Tipi

        Bu tip akım transformatörlerinde primer sargıyı şebekedeki faz iletkeni oluşturur. Bara tipi akım
transformatörlerinin bazılarında primer sargı, transformatörün orta kısmına yerleştirilmiş bir iletkendir. Bazı
akım transformatörlerinde orta kısım boştur. Bu orta kısımın içerisinden bara veya iletken
geçirilir.Genellikle panolarda kullanılır.




   Şekil 3.9 Bara Tipi Akım Transformatörü                  Resim 3.3 Buşing Akım Transformatörü

        Bunun yanı sıra bazı güç transformatörlerinin buşinglerine yerleştirilen akım transformatörlerine
buşing tipi akım transformatörü denir.



3.10)Kullanıldıkları Yere Göre Akım Transformatör Çeşitleri
   Akım transformatörleri kullanıldıkları yere göre ikiye ayrılır:
3.10.1 )İç Tip (Bina İçi,Dahili)
      Genellikle dış etkilere karşı mukavemeti az olan transformatörlerdir. Daha ziyade kapalı yerlerde
(transformatör merkezlerindeki kabinler, panolar vb.) kullanılırlar.
3.10.2 Dış Tip(Bina Dışı,Harici)
    Yapılışları bakımından dahili tip akım transformatörlerine göre ortam şartlarına karşı daha dayanıklıdır.
Şalt sahalarında kullanılan akım transformatörleri harici transformatörlerdir.

3.11) Akım Transformatörü Seçiminde Dikkat Edilecek Hususlar
     Bir akım transformatörü siparişi verilirken şunlara dikkat edilmelidir:
Faz-faz arası nominal (anma veya çalışma) gerilimi (34.5 kV gibi)
Dönüştürme oranı (amper) (200/5 gibi)
Sekonder kademe sayısı (100/5-5 gibi)
Sınıfı ve kullanma amacı, (1-3 gibi)
Doyma kat sayısı, n (n ≤5 ölçme, n ≥10 koruma )
Gücü VA olarak veya ohm cinsinden (30 VA, 0.5Ω gibi)
                                                          15
Tipi: (Dahili, harici, geçit, bar, yağlı, kuru gibi)

    3.12) Akım Transformatörü Etiket Değerleri
    Bir akım transformatörü etiketinde şunlar bulunur:
•      Çalışma sınıfı, akım transformatörlerinin hassasiyetlerini belirler, ölçme için 0,1-0,2-0,5-1-3-5, koruma
      için 5P-10P grupları kullanılır.
•      Sekonder anma akımı “Is” (nominal sekonder akımı) trafoların sekonder akımları (özel olarak yapılanlar
      hariç) 1-2-5 ve 10 A olarak yapılır. Sekonder tarafına bağlanan ölçü aletleri bu akımlara göre imal edilir.
      En çok kullanılan sekonder akımı 5 A’dır. Transformatör ve cihazlar arası uzaklık büyükse sekonder
      akımı 1 A olarak alınır.
•       Primer anma akımı ”Ip” (nominal primer akımı), Transformatörün çalışma akımıdır. Primer akımları,
      10-12-5-15-20-25-30-40-50-60-75-100 sayılarının 5 veya 10 katıdır. Akım transformatörleri primer
      akımlarının %20 fazlasına kadar yüklenebilirler. Bu durumda (sekonderi 5A olan trafoda) sekonderinden
      6A geçer.
•      Akım dönüştürme oranı, primer akımının, sekonder akımına oranına denir. Transformatör etiketlerinde
      75/5A, 100/5A, 1000/5A gibi belirtilir.
•     Sargı oranı, “ns” primer ve sekonder sargıların birbirine oranına denir. İdeal bir akım transformatöründe
      sargı oranı ile dönüştürme oranı birbirine eşittir.
•     Kullanma gerilimi “kV”
•     Doyma kat sayısı(aşırı akım faktörü) “n”, ölçü aletlerinde emniyet kat sayısı olarak tanımlanır. Ölçü
      transformatörlerinde n ≤ 5 olmalıdır. Koruma transformatörlerinde n ≥ 10-15-20 olabilir.
•     Anma frekansı ”Hz”, akım transformatörlerinin çalışma frekansıdır.
•     Yalıtkan tipi
•     Termik anma akımı “Ith”, bir akım transformatörünün, bir saniye süre ile hasar görmeden dayanabileceği
      primer akımının efektif değeridir. Bu değer etikette kA veya primer akımının katları şeklinde gösterilir.(10
      kA veya 200 x In gibi)
•     Dinamik anma akımı “Idyn”, primer şebekedeki bir kısa devre anında, ilk periyotta geçecek darbe
      akımının yol açacağı mekanik kuvvetler açısından, akım transformatörünün dayanacağı primer akımın
      maksimum değeridir. Akım transformatörlerinin termik anma akımlarının 2.5 katı kadardır. Akım
      transformatörleri Idyn akımlarına göre izole edilirler. Idyn akımları etikette verilmeyebilir.




                                                              16
3.13)Akım Transformatör Testleri

3.13.1) Polarite Tayini
     Primer ve sekonder terminallerinin       polarite tespitleri imalatçılar tarafından yapılmış durumdadır.
Yukarda belirtilen kurala göre yapılmış       bu işaretleme, polarite uçlarının belirlenmesi için yeterlidir.
Ancak imalatçıların zaman zaman yanlış işaretleme yapmaları sonucu bu kuralın uygulanması yetersiz
kalabilmektedir. İşte bu olasılık nedeniyle, yapılacak basit bir test ile polaritenin tespiti gerekir.
       Bunun için şekil 3.10’daki basit devrenin kurulması gerekli ve yeterli olacaktır. Pilin ve DC
ampermetrenin (+) uçlarının, primer ve sekonder devrelerde varsayılan (P1 ve S1) polarite uçlarına
bağlanmış olmasına dikkat edilmelidir.
    Anahtar kapatılır ve izleyen birkaç saniye içinde ampermetrenin sapması gözlenir.
      Sapma saat ibrelerinin dönüş yönünde ise, yapılan işaretleme doğrudur. Ampermetre ibresi ters
saparsa yapılan işaretleme yanlış demektir. Şekil 3.10 (a)‘da doğru; Şekil 3.10 (b) de ise yanlış bir
işaretlemenin sonuçları gösterilmiştir. Bu durumda, genellikle sekonder polarite ucunun değiştirilerek
S2’nin polarite kabulü edilmesi gerekir.




                                         Şekil 3.10 Polarite Tayini


3.13.2) Çevirme Oranı Testi
     Temel deneylerden olan çevirme oranı ölçümü, hem fabrikalarda hem de sahada kolaylıkla yapılabilen
bir testtir. Transformatör sargılarının sarım sayılarının projeye uygun olup olmadığını tespit edebildiğimiz
tek test olması nedeniyle çok önemlidir. Ayrıca yine bu test yardımı ile trafo sargılarında herhangi
bir iletken kopukluğu ya da kısa devre arızası olup olmadığını kolayca tespit edebiliriz.

     Prensip olarak primer (YG) sargısı sarım sayısının, sekonder (AG) sargısı sarım sayısına oranı şeklinde
düşünülerek test yöntemi geliştirilmiş ve ÇEVİRME ORANI KÖPRÜLERİ imal edilmiştir. Bu köprülerle

                                                            17
test yapılabilmesi için öncelikle testten önce trafoların vektör gruplarının ( ya da bağlantı grubu) bilinmesi
ve fazör diagramlarının incelenmesi gerekmektedir.




          Şekilde görüldüğü gibi paralel vektörlere dikkat etmek gerekir. Uygulanacak gerilimlerde gerilim
vektörlerinin paralelliği şarttır.

       Bu durumda AB arasına bir gerilim uygular ve bu gerilimi ölçerek na arasından ölçtüğümüz gerilime
oranlarsak çevirme oranını,

                                                AB / na = Çevirme Oranı

       Şeklinde bulabiliriz. Daha sonra aynı şekilde sırasıyla BC / nb ve CA / nc oranları ölçülerek bulunur
ve daha önceden hesaplanan teorik oranlarla mukayese edilir. Standartlarda teorik orana nazaran gerçek
oran sapması için ± 0,5 % tolerans verilmiştir. Gerçek oran sapmasının bu toleranslar içinde kalıp
kalmadığına bakılır.

        Transformatöre ait teorik boşta çevirme oranı alet üzerinde kademeli transformatörde ayarlanır, ‰

hata göstergesinde denge oluşuncaya kadar değiştirilir. Bu hata göstergesinde okunan değer
transformatörün gerçek çevirme oranına olan sapmasını ‰ olarak gösterir.

                           AKIM TRANSFORMATÖRLERİNİN

                                KARAKTERİSTİK DEĞERLERİ


4.1)Karakteristik Değerler
     Bir akım trafosunu tanımlayan karakteristik değerlerin bilinmesi ve uygulama alanında gerektikçe
doğru kullanılması önem taşır. Örneğin; hatalı veya eksik değerler ile yapılacak bir sipariş sonucu elinize
geçecek akım trafosu, amaca hizmet etmeyen bir akım trafosu olacaktır.             Aşağıda     sıralanan    bu

                                                         18
karakteristik değerler, akım trafosunun etiketinde belirtilmiş       olduklarından, bu değerlere Etiket
Değerleri demek de mümkündür.

                           1) İletme Gerilim Anma Değeri [Un]

                           2) Anma Gücü [Nn]

                           3) Sınıf (Klas)   [ Cl ]

                           4) Doyma Katsayısı (Saturasyon Katsayısı) [n]

                           5) Akım Çevirme Oranı [k]

                           6) Anma Akım değerleri

                           7) Termik Dayanım Anma Akımı [Ith]

                           8) Dinamik Dayanım Anma Akımı [Idyn]



      Bu değerlerin bir akım trafosunda neyi ifade ettikleri ve bu değerler için kabul edilen standartlar
aşağıda açıklanacaktır.

4.1.1) İşletme Gerilim Anma Değeri (Un)
       Bu değer, akım trafosunun; izolasyon yönünden; kullanılabileceği       işletme geriliminin    ( 6.3,
kV, 10.5 kV, 15 kV, 34.5 kV şeklinde) üst değerini gösterir.

4.1.2) Anma Gücü (Nn)
       Akım Trafosunun sekonderine bağlanabilecek cihazların (akım devreleri) toplam gücü ile, cihaz
bağlantısında kullanılacak kablo gücünün toplamı akım trafosunun gücünü belirler. Bu yüzden sekondere
bağlanacak cihaz güçlerinin bilinmesi ve akım trafosu ile cihazlar (pano) arasında kullanılan kablo
gücünün hesaplanması gerekir. Cihaz bağlantı kablosu gücünün (Nk) hesabı şöyle yapılır. Kablo kesiti (S);
kablo boyu (L) ve iletken cinsi (Cu/Al) bilinen değerlerinden, kablo direnci (Rk) bulunur ve Nk= Is2.R
formülünden hesaplanacak değer kablo gücünü verir.

Sayısal Örnek:

  k = 56 ohm/mm2.m        q = 2,5 mm2 ve L = 100 m ise

  Rk=2 x L / k x q   Rk=1,43 ohm bulunur.

  Nk=Is2.R formülünde Is=5 Amp için, Nk=52 x 1.43        Nk=35,75 VA bulunur.

    Kablo nedeni ile gelen bu ek yük, uzun kablo kullanımının gerekli olduğu (örneğin TR Tank Koruma
yapılan) durumlarda, akım trafosunun 1 Amp sekonder akımlı olarak seçilmesi gerekebilir. Yukarıdaki örnekte
böyle bir trafonun seçilmiş olması durumunda kablo yükü sadece 1.43 VA olacaktır. 2x4 veya 2x6 mm2
gibi daha büyük kesitli kablo kullanımı da çözüm olabilir. Akım trafosunun anma gücü, aynı zamanda

                                                         19
bu akım trafosunun sekonderine seri olarak bağlanabilecek Ohm cinsinden empedansı ifade eder. Bu
nedenle bazı akım trafo etiketlerinde VA cinsinden güç yerine Ohm cinsinden empedans verilir.
Örneğin 1,2 ohm gibi bir değer verilmişse, bu trafo anma gücünün, N n = 52 x 1,2 = 30 VA. olarak verilmesi
ile aynı anlama gelmektedir. Günümüzde kullanılan elektronik teçhizatın, akım trafosundan çektiği
güçler çok düşüktür. Küçük merkezlerde bağlantı kablo boyları da fazla uzun olmadığı için, bu merkezlerde,
korumada kullanılacak akım trafolarının 15 VA. gücünde olması genellikle yeterli olmaktadır.

4.1.3) Sınıf Klas (Cl)
    Bir akım Trafosunun sınıfı (doğruluk sınıfı); primerden anma akımı akarken, sekonderden akan akımın,
olması gerekenden, % olarak, en fazla ne kadar sapabileceğini ifade eder. Bu sapma (+) veya (-) yönde
olabilir.

       Örneğin ; Doğruluk Sınıfı "1" olan bir akım trafosunun primerinden anma akımı geçerken,
sekonderinden, sekonder anma akımının % 99'u ile %101'i arasında bir akım akar. Sekonder 5 Amp ise,
sekonderden       geçecek akım 5 x % 99 = 4,95 Amp ile 5 x %101 = 5,05 Amp arasında olacaktır. Bu değer,
akım trafosunun oran hatasından kaynaklanır. Aslında ,doğruluk sınıfı açı hatasını da kapsar ve toplam hata
bir miktar artar.Ancak açı hatası koruma devrelerinde bir önem tasımaz.Oran ile ilgili hatalar, Primerden
geçen akımın değerine bağlı olarak değisiklik gösterir.

Örneğin;

    1 Sınıfı (Cl:1) bir akım trafosu Primerinden;

     Anma akımının % 10 - 19 ' u geçerken hata % 2

     Anma akımının % 20 - 99 ' u geçerken hata % 1.5

     Anma akımının % 100 - 120 'si geçerken hata % 1 olur.

      Koruma amaçlı akım trafoları genellikle sınıf:3 veya özel durumlar için sınıf:1, ölçü amaçlı akım
trafoları genellikle sınıf:1 veya özel durumlarda sınıf:0,5 olarak üretilirler.

   Yukarıdaki açıklamaya uygun olarak bunların , primer akımın anma değerindeki oran hataları % 3 , % 1
veya % 0,5 dir.

    Ancak bu hatalar , primerden geçen akım, anma değerinin (% 120 ' sinin) üstüne çıktığında artar ve
doyma sınırına ulastığında Sınıfı:3 olanın akım hatası % 10'a ve Sınıfı 1 olanın akım hatası % 5'e ulasır.
Koruma akım trafolarının, doyma noktasına ulasıldığında gösterdikleri bu hata değerleri sınıf belirlemesinde
esas alınarak, bu akım trafolarının doğruluk sınıfları; genellikle "5P" ve "10P" olarak gösterilir.

   Sınıfı 1 olan akım trafo plakalarında Cl:1 veya "5P" , sınıfı 3 olan akım trafolarında Cl:3 veya "10P"
ifadelerine rastlanabilir. TSE tarafından benimsenen gösterilis "5P" ve "10P" dir.




                                                            20
4.1.4) Doyma Katsayısı(Saturasyon Kat Sayısı (n)
    Bir akım trafosunun primerinden geçen akım artırıldıkça, sekonderinden geçen akım da( akım oranının
belirleyeceği ölçüde) artar. Bu artış primer anma akımının üstüne çıktıkça bir süre devam eder. Primer akım
giderek yükseltildiğinde, önce akım oranı bozulur ve daha sonra sekonderde ki yükselme durur. Primer akım
bu değerin üstüne ne kadar çıkarılırsa çıkarılsın, artık sekonderden geçen akım değişmez. Akım oranının
bozulmaya başladığı noktadaki primer akım değerine, Doğruluk Sınırı, sekonder akımın değişmemeye
başladığı noktaya ise Doyma Sınırı denir. Doğruluk sınırı ile doyma sınırı birbirine çok yakın değerlerdir.
Ancak Doyma (saturasyon katsayısı)'na esas olan değer, doğruluk sınırıdır ve doyma katsayısı bu değere
göre tanımlanır.




                               Şekil 4.1 Doyma Katsayısı

Doyma katsayısı (n) , doğruluk sınırının, primer anma akımının kaç katı olduğunu belirleyen bir kat sayıdır.

                                 Id = Ip x n         n = Id / Ip dir.
 Doyma, akım trafosunun nominal gücü ile yüklü olduğu, yani akım trafosunun anma yük empedansını
beslediği durumda tanımlanmıştır.

Sayısal Örnek:
    Anma Gücü 30 VA; akım oranı 100/5 A.olan bir akım trafosunun Doyma kat sayısı n=5’dir. Bu akım
trafosuna 30 VA.toplam gücünde cihazlar bağlı iken; primerinden 2000 Amp çekilmektedir.Akım oranı
k=100 / 5=20 olduğuna göre sekonderden 2000/2=100 A.geçmesi beklenirken, bu akım trafosunun doğruluk
sınırı Id=100 x 5=500 A. olduğundan sekonderden ancak Is=500/20=25 Amp geçecektir. Bu; sekondere
bağlı cihazlardan; 25 Amp’den daha büyük bir akım geçemeyecek demektir. Aynı akım trafosu primerinden
yine 2000Amp çekildiğini, ancak doyma kat sayısının n = 10 olduğunu varsaysak; Doğruluk Sınırı Id = 100
x 10 = 1000 Amp olacak ve sekonderden I s = 1000 / 20 Is = 50 Amp geçecektir.




                                                        21
4.1.4.1) Ölçü Akım Trafolarında n<5
    Ölçü devrelerinde kullanılan akım trafolarında, sekonderden geçecek en büyük akımın sınırlandırılarak
ölçü cihazlarına zarar vermemesi istenir. Bu nedenle ölçü akım trafolarında doyma katsayısının n < 5 veya
en fazla n = 5 olması öngörülür.

4.1.4.2) Ölçü Akım Trafolarında n>10
    Koruma devrelerinde ise durum terstir ve primerden geçen yüksek değerli akımların, akım oranına göre
sekondere yansıması tercih edilir. Böylece; arızadan kaynaklanan bu aşırı akım röle tarafından
algılanabilecek ve bu akım için ayarlanan süre içinde arıza izole edilebilecektir. Ancak bu sayede ters
zamanlı röleler hızlı ve selektif olarak çalısabilir. Bu nedenle koruma akım trafolarında doyma katsayısının
n >10 veya en az n = 10 olması öngörülür.

4.1.5) Akım Çevirme Oranı (Akım Oranı) (k)
      Akım trafoları, primerden geçen akımı değiştirerek (genellikle küçülterek) sekonder devreye aktaran
cihazlardır. Primer akımın hangi oranda değiştirildiğini belirleyen sayıya, (k) o akım trafosunun “Akım
Oranı” denir. Trafolarda bilinen Amper - Sarım Yasası’ na göre, primerden geçen akım ile primer sarım
sayısının çarpımı, sekonderden geçen akım ile sekonder sarım sayısının çarpımına eşit olmak durumundadır.

    Bu yasa; IP x wp = Is x ws eşitliği ile ifade edilir. Eşitliği (Is/Ip) = (ws/ wp) şeklinde düzenlersek, bu
eşitliğin birinci tarafı Akım Oranı, ikinci tarafı ise Sarım Oranı olup birbirlerine eşittirler.

    Akım trafosunun bu karakteristik değeri, sarım sayıları veya sarım oranları ile değil, primer ve sekonder
akımlar veya (Ip/Is şeklinde) akım oranları ile ifade edilir.

   Akım trafo plakalarında, akım değerleri genellikle ayrı ayrı yazılır.

      Örneğin; Primer akım       : 40 Amp

                 Sekonder akım : 5 Amp
     Oysa; proje, malzeme siparişi, arıza bildirimi vb. pratik uygulamalarda genellikle akım oranları, Ip/Is
seklinde ifade edilir. Burada “Ip” 20/5 , 50/5 , 150/5 , 100/5 ……. vb .ve “Is” (genellikle) 5 Amp dir.


4.1.6) Anma Akım Değerleri (k)
                                                                                     kım Trafoları karakteristik
                                                                            değerler       yönünden      belirlenmiş
                                                                            standartlara göre üretilirler. Primer
                                                                            ve sekonder akım için standartların
                                                                            belirlediği       değerler      aşağıda
                                                                            verilmiştir.


                                                           22
Sekonder akımlar ise (Is); Sekonder akım için belirlenen standart değerler 1 Amp, 2 Amp veya 5 Amp dir.

Ancak genellikle kullanılan sekonder akım 5 A.dir. Özel amaçlı bazı trafolarda 1 veya 2 Amp olarak farklı
sekonder akımlar tercih edilebilir. Örneğin bazı hallerde tank koruma akım trafoları sekonder akım 1 Amp
olarak seçilebilmektedir. Sekonder akımın çok uzun mesafelere taşınması gerektiği diğer hallerde de,
sekonder akım 1 Amp olarak seçilebilir.

4.1.7) Termik Anma Akımı (Ith)
     Oluşan kısa devre akımları, akım trafolarını termik bakımdan zorlarlar. Termik anma akımı ; bir akım
trafosunun; 1 saniye süreyle, zarar görmeden taşıyabileceği maksimum akımın etkin değeri olarak tarif
edilir.

    Standartlarda bu değerin; primer akım anma değerinin 100 katı olması öngörülmüştür. Bu değer
Ith=100 In olarak gösterilir. Gösterilmemesi durumunda da bu değer geçerlidir.

     Akım Trafosunun kullanıldığı noktadaki kısa devre akım değeri ve devre koruyucuların arızayı temiz-
leme süreleri dikkate alınarak yapılacak hesaplamalar sonucunda; gerek görülmesi halinde;daha büyük
termik anma akımlı trafolar özel olarak üretilir. (200 In , 300 In vb)

    Termik anma akımı 1 saniye süre için tanımlanmış olmakla birlikte; arıza akımının temizlenme süresi;
bazen 1 saniyeden kısa ve bazen da 1 saniyeden uzun olabilir. Bu durum dikkate alınarak Termik anma
akımının aşağıdaki bağıntı ile kontrol edilmesi gerekir.


                                               bağıntısından


"t"süresi içinde akım trafosunun taşıyabileceği max kısa devre akımı belirlenir ve bu akımın, o noktadaki
(bilinen/hesaplanan) kısa devre akım ile kıyaslaması yapılır.


4.1.8) Dinamik Anma Akımı (Idyn)
                                                           23
Kısa devre akımının ilk periyodunda; kısa devre akımı en büyük tepe değerine ulaşır. Bu değer akım
trafolarını dinamik olarak zorlar. Sargılar arası itme ve çekme kuvvetleri meydana gelir. Akım trafosunun
bu kuvvetlere dayanması gerekir. Bu ilk periyotta zarar görmeyen akım trafosu; izleyen periyotlarda; akım
küçüleceğinden; bunları dinamik yönden rahatça karsılar. Dolayısı ile dinamik zorlanmayı; akımın ilk
periyottaki tepe değeri belirler.
    Standartlarda akım trafolarının; Termik anma akımının 2,5 katına dayanması öngörülmüştür. Özel bir
imalat nedeni ile daha büyük değerler alınmamış ise; akım trafosu etiketinde bu değer belirtilmez.


4.1.9) Akım Transformatörünün Sekonder Sargı UcunuAçık Kalmamasının Önemi
     Eğer, akım transformatörünün sekonder sargısının uçları açılırsa veya açık kalacak olursa, bu sargının
mıknatıs alanını azaltma etkisi ortadan kalkar. Primer sargısının meydana getirdiği alan, olduğu gibi demir
nüveden geçer, yani alan çok büyük bir değer alır. Bunun sonucu olarak fazla doyurulmuş demir nüve de
haddinden fazla ısınarak etrafında sarılı olan sargısını yakar. Bundan başka meydana gelen büyük manyetik
akı, sekonder sargı da hayat için tehlikeli olan yüksek gerilimler indükler. Bu sakıncalardan dolayı, akım
transformatörlerinin sekonder uçları hiçbir zaman açılamayacağı gibi devresine de sigorta konulmaz.
Onarım veya ölçü devresindeki bağlantıları değiştirmek gibi sebeplerden açılması gerekirse, ya primer
akımı kesilir veya sekonder sargı uçları önce kısa devre edilir sonra açılır. Bunun için de akım
transformatörünün sekonder devresine bir kısa devre anahtarı konmuştur. Ayrıca yüksek gerilim
tehlikelerine karşı güvenlik tedbiri olarak sekonderin S1 ucu daima topraklanır.




                            GERİLİM TRANSFORMATÖRLERİ

                                                        24
5.1 Gerilim Transformatörleri
5.1.1) Tanımı
       Gerilim Trafoları; "primer" dediğimiz esas devre gerilimini, manyetik bir kuplaj ile, (genellikle)
küçülterek "sekonder" dediğimiz ikinci devreye aktarır ve bu devreye bağlı cihazların gerilime duyarlı
elemanlarının enerjilenmesini sağlarlar. Örneğin, voltmetrelere, sayaç ve watmetrelerin gerilim devreleri vb.
   Bunun sonucunda; cihazların büyük gerilimler ile zorlanması önlenir.
5.1.2) Şematik Gösterimi
      Elektrik şema ve resimlerde, gerilim trafoları değişik şekillerde gösterilebilirler. Aşağıda bu gösteriliş
şekillerine ait örnekler verilmiştir.




                                Şekil 5.1 Gerilim Transformatörü Şematik Şekli


5.1.3) Çalışma İlkesi
     Çalısma ilkeleri, akım trafolarına benzerdir. Primerde oluşan
manyetik akı ile, gücün sekonder devreye aktarılmasına ilişkin
açıklamalar, gerilim trafoları için de geçerlidir. Manyetik devre (nüve)
kayıpları ihmal edilerek, primer ve sekonder devre güçlerinin eşitliği
  ilkesinin matematiksel ifadesi aşağıdaki gibi olacaktır.




                                                             25
Ayrıca amper sarım yasası uyarınca geçerli olan;



                                                Bağıntısı yazılabilir.



                           (1) (2) bağıntılarından bu bağıntı elde edilir.




Vp/Vs oranına, “Gerilim Çevirme Oranı” veya “Gerilim Oranı”denir.

    Gerilim transformatörlerinde, primer nominal gerilimin sekonder nominal gerilimine oranına "çevirme
oranı"        (nu   =   U1 / U2) denir. Bu oranların değeri primer gerilimine göre değişir. (10/1,     40/1,
100/1.....250/1 gibi). Alette okunan değerler, çevirme oranı ile çarpılırsa primer gerilimi bulunmuş olur.
Örneğin; Primer gerilimi 4.000 V. olan bir gerilim transformatörünün, sekonder gerilimi 100 V. olduğuna
göre, bu transformatörün çevirme oranı 4.000/100 = 40/1' dir. Bu değer 100 V. ile çarpılırsa primerin
nominal gerilimi bulunmuş olur. Sekonder devresine bağlanan voltmetrelerin bazı tipleri; primer gerilimini,
doğrudan doğruya gösterecek şekilde bölümlü olanları da vardır.

5.1.4)Gerilim Transformatörü Yapısı
         Gerilim transformatörünün primer sargıları, akım transformatörünün primer sargılarının tersine, çok
sarımlı ince tellerden oluşmuştur. Sekonder sargı ise, nominal yükte kaybın çok az olmasını temin edecek
kalınlıkta tel ile sarılmıştır. Sarım sayısı primer sargıya göre dönüştürme oranı kadar azdır. Manyetik nüve
kesiti gerilim transformatörünün yükü ile orantılıdır. Gerilim transformatörleri faz-toprak, faz-faz arası
yapılırlar.




                                  Şekil 5.2 Gerilim Trafosu Yapısı


                                                             26
5.1.5) Gerilim Transformatörü Prensip Şekli
 Bir gerilim transformatörü aşağıdaki kısımlardan meydana gelir:

Primer sargı
Sekonder sargı
Manyetik nüve
İzolatör ve yağ kabı
   İzolatör ve yağ kapları, yüksek gerilimde kullanılan gerilim transformatörlerinde bulunur. Ayrıca faz-faz
arası gerilim transformatörlerinde çift izolatör bulunur. Şekil 5.3'te faz-toprak tipi gerilim transformatörünün
kısımları görülmektedir.




                     Şekil 5.3 Gerilim Transformatörünün Kısımları



5.1.6) Gerilim Transformatörünün Kullanım Amaçları
   Gerilim transformatörlerinin kullanım amaçlarını şu şekilde sıralayabiliriz:

Ölçü aletlerini ve koruma rölelerini primer geriliminden izole ederek, güvenli çalışmaya imkan sağlar.

Değişik primer değerlerine karşılık standart sekonder değerler elde edilir.

Ölçü transformatörlerinin kullanılması, ölçü aletlerinin ve rölelerin küçük boyutlu imal edilmesine
imkân verir.

Büyük gerilimleri ölçmede daha ekonomik bir çözümdür.




                                                          27
5.1.7) Gerilim Transformatörü’nün Özellikleri

•   Yüksek gerilimi belli bir oranda düşüren ölçüm trafolarıdır.

•   Sekonder çıkışları açık devre gibi çalışırlar.

•   Bağlantısı yapılırken polaritesine dikkat edilmelidir.

•   Primer devresinden geçen gerilim,dönüştürme oranına göre sekonder devreye aktarır.

•   Primer sargıları ince ve çok sarımlıdır.

•   Gerilim transformatörlerinin primer ve sekonder sargılarının giriş ve çıkış uçları değişik harflerle ifade
    edilir.

•   Gerilim transformatörlerinin bazı ölçü aletleri ile bağlantısında polaritesi önemlidir.

•   Aynı gerilim transformatörü ile birkaç ölçü aleti kullanılabilir.

•   Gerilim transformatörlerinin, ölçme hassasiyetlerine göre sınıfları: 0,1-0,2-0,5-1 ve 3 olmak üzere
    sınıflandırılır.

•   Koruma devrelerinde 3 sınıfı, sayaçlarda 0,2-0,5 sınıfı, ölçü aletlerinde 1 sınıfı gerilim transformatörleri
    kullanılır.

•   Gerilim transformatörlerinin sekonder uçlarından birine sekonderde meydana gelecek bir kısa devre
    önlemek için sigorta konmalıdır.

•   Gerilim transformatörleri nominal akımlarının %20 fazlasına kadar yüklenebilir.

    5.1.8)Kullanıldıkları Yere Göre Gerilim Transformatör Çeşitleri
       Kullanıldıkları yere göre gerilim transformatör çeşitleri ikiye ayrılır:

    5.1.8.1) Faz-Toprak Gerilim Transformatörü
        Bu tip gerilim transformatörleri tek izolatörlü (buşing) gerilim trafolarıdır. Primer sargının çıkış ucu
    (polarite olmayan ucu)doğrudan toprağa bağlanır. Primer sargının giriş ucu (polarite uç) şebekenin faz
    iletkenine bağlanır.




                                    Ş.4 Faz-Toprak Gerilim Transformatörü

                                                             28
5.1.8.2) Faz-Faz Gerilim Transformatörü
      Faz-faz arası gerilim transformatörleri ise, şebekede iki faz arasına bağlanan gerilim trafolarıdır. İki
 faz arasına bağlanacağından dolayı bu tip gerilim transformatörlerinde iki tane izolatör bulunur. Primer
 sargı uçları iki izolatör ile dışarıya çıkartılmıştır. Bu tip gerilim transformatörleri genellikle dengeli yük
 çeken orta gerilim şebekelerinde, üç adet faz-toprak arası gerilim transformatörü kullanmak yerine iki adet
 faz-faz arası gerilim transformatörü kullanarak gerilim belli bir oranda düşürülür. Bu transformatörler
 şekil olarak V harfine benzediklerinden dolayı V tipi gerilim transformatörü de denir.




 Şekil 5.5 Faz-Faz Gerilim Transformatörü                       Resim 5.1 Faz-Faz Gerilim Transformatörü



 5.1.9) Kombine(Akım ve Gerilim Transformatörü Birlikte) Ölçü Transformatörünün
 Tanımı Yapısı
      Aynı yere monte edilmiş akım ve gerilim transformatörlerine kombine ölçü transformatörleri denir.
Ancak bunların yalıtma sorunları oldukça zordur.

       Kombine ölçü transformatörü son zamanlarda SF6 gazı ile yalıtılmış şalt kazanları içerisinde, daha
küçük yer işgal ettiği ve yalıtım sorunu SF6 gazı ile sağlandığı için kullanılmaktadır.




                         Resim 5.2 Kombine Ölçü Transformatörü
                                                           29
5.1.10) Gerilim Transformatörü Siparişinde Dikkat Edilecek Hususlar

      Bir gerilim transformatörü siparişi verilirken gerekli olan bilgiler:
       •   Nominal gerilimi
       •   Dönüştürme oranı
       •   Gücü
       •   Tipi
       •    Aşırı gerilim kat sayısı
       •   Adedi
5.1.11) Gerilim Transformatörü Etiket Değerleri
  Gerilim transformatörünün etiketi üzerinde aşağıdaki değerler yer alır:

  •   Çalışma sınıfı, gerilim transformatörlerinin hassasiyetlerini belirler, ölçme için 0,1-0,2-0,5-1-3-5,
      koruma için 5P-10P grupları kullanılır.
  •   Gerilim dönüştürme oranı, primer geriliminin, sekonder gerilimine oranına denir. Transformatör
      etiketlerinde 1500/100V, 1000/120V gibi belirtilir.
  •   Sargı oranı, “ns” primer ve sekonder sargıların birbirine oranına denir. İdeal bir gerilim
      transformatöründe sargı oranı ile dönüştürme oranı birbirine eşittir.
  •   Anma yalıtma seviyesi (deney gerilimi) kV, gerilim transformatörünün elektriki zorlanmalara karşı
      hasara uğramadan dayanabileceği gerilim.
  •   Çalışma frekansı “Hz”
  •   Primer anma gerilimi (nominal primer gerilimi) ”Up”, transformatörün çalışma gerilimidir.
      Genellikle 0,3-6,3-10,5-15-30-34,5-60-66-154-380 kV değerleridir.
  •   Sekonder anma gerilimi, (nominal sekonder gerilimi) ”Us”, Primer tarafına nominal gerilim
      uygulandığında, sekonderden alınacak gerilimdir. Faz-faz arası gerilim transformatörlerinde
      100-110-115-120 volt, faz-toprak gerilim transformatörlerinde ise bu değerlerin √3’e bölümüdür.
      (100/√3 gibi)
  •   Gücü VA, (3,5 VA gibi)
  •   Kullanım yeri (dahili, harici), firma adı




                                                         30
Şekil 5.6 Gerilim Transformatörü Etiket Değeri

5.2) Gerilim Transformatör Testleri
5.2.1) Polarite Tayini
    Bir gerilim trafosunun primer ve sekonderindeki polarite uçları, primer sargıya gerilimin giriş veya çıkıs
yönüne göre, sekonder sargıdaki gerilim yönünün belirlenmesi anlamına gelir.Şekil 5.7 de Primer polarite
ucunun “A” ve sekonder polarite ucunun “a” olarak alınmış olduğu ve polarite olmayan “b” sekonder
ucunun topraklandığı görülmektedir. Faz-Nötr arasına bağlanan gerilim trafolarının, polarite olmayan
primer ucu “B” de, (çalısma ilkesi gereği) topraklanır.




                                    Şekil 5.7 Polarite Tayini


5.2.2) Isınma Sıcaklık Artışı Testi
    Sıcaklık artışı testinde gerilim transformatörüne uygulanan gerilimler aşağıdaki gibi olmalıdır:

       Anma gerilim yükseltme katsayısı ve gerilim uygulama süresi ne olursa olsun, bir fazlı gerilim
transforma-törlerine birincil anma (faz arası) geriliminin ısıl katsayısına eşit bir gerilim; üç fazlı gerilim
transformatörlerine birincil anma (faz arası) geriliminin 1,2 katına eşit dengeli 3 fazlı bir gerilim
uygulanmalı, teste transformatör kararlı sıcaklığa erişinceye kadar devam edilmelidir. Test sonunda bulunan
sıcaklık artışları standartta belirlenen sınırları aşmamalıdır.

    Testte ölçülen sıcaklıklar, saatte 1 °C den çok artmadığında, gerilim transformatörünün kararlı sıcaklığa
eriştiği kabul edilir. Test esnasında ortam sıcaklığı10° 3 0 °C arasında olmalıdır. Birden fazla ikincil sargı
bulunması halinde test her ikincil sargının anma yükünde yapılmalıdır. Sargıların sıcaklık artışları direnç
değişimi metodu ile ölçülmelidir. Diğer kısımların sıcaklık artışları derece veya ısıl çift (thermocouple) ile

ölçülür.




                                                            31
GERİLİM TRANSFORMATÖRÜNÜN

                               KARAKTERİSTİK DEĞERLERİ


Aşağıda sıralanan bu karakteristik değerler, gerilim Trafosunun etiketinde belirtilmiş olduklarından, bu
değerlere "Etiket Değerleri" demek de mümkündür.

1) Anma Gerilim Değerleri [Up ve Us]

2) Anma Gücü [Nn]

3) Sınıf (Klas) [ Cl ]

4) Dayanma katsayısı [Uk]

   Bu değerlerin bir gerilim trafosunda neyi ifade ettikleri ve bu değerler için kabul edilen standartlar
aşağıda açıklanacaktır.

6.1) Anma Gerilim Değerleri (Up ve Us)
     Trafoların imalatında, bağlanacakları öngörülen şebekenin faz arası standart gerilimleri, gerilim trafola-
rının anma primer gerilimlerinin standardını oluşturur. Dolayısı ile, primer anma gerilimleri, 34,5 kV,15kV,
10,5 kV veya 6,3 kV olacaktır. Bu değerler için üretilmiş gerilim trafolarının, bu değerlere yakın gerilim de-
ğerlerdeki şebekelere bağlanması da mümkündür. Örneğin, 34,5 kV için üretilmiş bir gerilim trafosunun,
33 kV , 31,5 kV veya 30 kV bir şebekeye de bağlanabilir. Ancak, sekonder gerilim de aynı oranda
değişecektir. Talep halinde, var olan farklı şebeke gerilimlerine uygun gerilim trafolarının üretilmesi de
mümkündür. Örneğin 30 kV, 33 kV veya 15,8 kV primer anma değerli trafolar üretilebilir. Anma sekonder
gerilim, faz arasına bağlanan gerilim trafolarında 100 Volt olarak standardize edilmiştir. Faz –Toprak
arasına bağlı geri-lim trafoları sekonder anma gerilimleri, için ise standart değer 100/√3 Volttur.

     Faz-Toprak arasına bağlı bazı gerilim trafolarında; izole şebekelerdeki toprak temasını algılayıp sinyal
vermesini sağlayan rezidüel koruma rölelerini enerjilemek amacı ile ikinci bir sargı bulunabilir. Bu sargının
anma değeri 100/3 V olmaktadır. Bir gerilim trafosunun primer ve sekonder gerilim değerleri, genellikle
Gerilim Oranları formatında belirtilir. 34,5 kV gerilim trafoları için örnekler aşağıdadır.

       Faz arası bağlı gerilim trafolarında                    34,5/0,1 kV

       Faz nötr arası gerilim trafolarında                     (34,5/√3)/(0,1/√3) kV




                                                          32
6.2) Anma Gücü (Nn)
        Gerilim trafosunun sekonderinden çekilmesi öngörülen en büyük güç, o trafonun anma gücüdür.
Üretimler; standartlar uyarınca; 30 VA, 60 VA ve 90 VA değerlerinde yapılır. Sekondere bağlanacak gücün,
o gerilim trafosunun anma gücünü aşmaması gerekmektedir. Başka bir deyişle, bağlanacak empedansın;
anma gücünün, empedans karşılığının altında olmaması gerekir. I = Us /Z genel formülünden de görüleceği
üzere, “Z” küçüldükçe akım (I) büyümektedir. Bu durum, anma akımına göre boyutlandırılmış sargı kesitini
zorlayacaktır. N = U.I bağıntısında, “I“ yerine yukarıdaki eşitini yazarak, N= Us2 / Z bağıntısı ile
gereğinden küçük değerde empedansların, gücü de büyüttüğü görülmektedir. Nüvenin boyutlandırılması,
aktarılacak anma gücüne göre yapıldığından, gücün büyümesi; kesit dışında; nüvenin de zorlanması
anlamına gelir. Gerilim trafolarında kullanılmayan sargının kısa devre edilmemesi kuralının gerekçesi de bu
bağıntı ile açıklanmış olmaktadır. Kısa devre edilmesi Z=0 demektir.

6.3) Sınıf Klas (Cl)
         Bir gerilim trafosunun sınıfı (doğruluk sınıfı); primere uygulanan gerilim sonucu, sekonderde
indüklenen gerilimin, olması gerekenden, % olarak, en fazla, ne kadar sapabileceğini ifade eder. Bu sapma
(+) veya (-) yönde olabilir.

     Örneğin; doğruluk Sınıfı "1" olan bir gerilim trafosunun, sekonder anma geriliminin % 99'u ile % 101'i
arasında bir gerilim indüklenir. Sekonder anma gerilimi 100 V. ise, sekonderden 100 x % 99 =99 V ile 100
x %101 = 101 V arasında değişen bir gerilim alınabilecektir. Gerilim trafoları, doğruluk sınıfı “05”, “1” ve
“3” olan üç kategoride üretilmektedir.

      Ölçü devrelerinde; genellikle; doğruluk sınıfı “1” veya gerekiyorsa “0,5”, koruma devrelerinde ise,
doğruluk sınıfı “3” olan gerilim trafoları kullanılmaktadır.

     Doğruluk sınıfları, primerden anma geriliminin uygulandığı ve sekonderine anma gücünün çekildiği,
durumlar için tanımlanmıstır. Farklı güçlerde, doğruluk sınıf değerinde sapmalar olacaktır.

6.4) Dayanma Katsayısı (Uk)
     Bu değer, (diğerlerinde olduğu gibi) gerilim trafolarının genel karakteristik değerlerinden biri olmayıp,
sadece, izole şebekelerde, faz-nötr arasına bağlanan gerilim trafoları ile ilgili bir değeri ifade eder. İzole
şebekelerde bir fazın toprağa teması durumunda, o gerilimi sıfır olurken diğer faz gerilimleri √3 kat artar.
Bu nedenle, faz toprak arasına bağlı gerilim trafolarının bu gerilime dayanması gerekmektedir. Bu
şebekelere bağlanacak gerilim trafolarının dayanmaları gereken değeri belirleyen bu katsayıya Dayanma
Katsayısı denir ve değeri √3 dür.




                                                          33
SONUÇ


Bu projemde Akım ve Gerilim Transformatörlerinin yapısını,çalışma,şeklini,özelliklerini,kullanım
amaçlarını,çeşitlerini,karakteristik değerlerini ve hangi testlerden geçirildiklerini vb. konu başlıklarıyla
özetlemeye çalıştım.Bu projemde bana destek olan proje danışmanım Yrd.Dç.Dr. Mehlika Şengül hocama
teşekkür ederim.




                                                        34
KAYNAKÇA


•   Akım ve Gerilim Transformatörü Testleri                  Yalçın OYAL Elektrik Y.Mühendisi TEK

•   Ölçü Trafoları ve Sekonder Koruma                        Haldun BÜYÜKDORA

•   Ölçü Transformatörleri                                   Hasan ÖNAL

•   http://www.besttrafo.com.tr

•   Milli Eğitim Bakanlığı Elektrik Elektronik Teknolojisi   Ölçü Transformatörleri Kitabı




                                                       35
36

More Related Content

What's hot

AUTOSAR_EXP_LayeredSoftwareArchitecture.pdf
AUTOSAR_EXP_LayeredSoftwareArchitecture.pdfAUTOSAR_EXP_LayeredSoftwareArchitecture.pdf
AUTOSAR_EXP_LayeredSoftwareArchitecture.pdfSalaheddineelabbassi
 
ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...
ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...
ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...Alfresco Software
 
Project Management- A Beginner's Guide to Managing a Project
Project Management- A Beginner's Guide to Managing a ProjectProject Management- A Beginner's Guide to Managing a Project
Project Management- A Beginner's Guide to Managing a ProjectAshley Goeke
 
Exchange server.pptx
Exchange server.pptxExchange server.pptx
Exchange server.pptxVignesh kumar
 

What's hot (6)

Certificate Management Protocols for 1609.2 Certificates
Certificate Management Protocols for 1609.2 CertificatesCertificate Management Protocols for 1609.2 Certificates
Certificate Management Protocols for 1609.2 Certificates
 
AUTOSAR_EXP_LayeredSoftwareArchitecture.pdf
AUTOSAR_EXP_LayeredSoftwareArchitecture.pdfAUTOSAR_EXP_LayeredSoftwareArchitecture.pdf
AUTOSAR_EXP_LayeredSoftwareArchitecture.pdf
 
ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...
ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...
ECM Decision Matrix - Deciding Between Alfresco Community Edition, Alfresco E...
 
Chapter 3.4.pptx
Chapter 3.4.pptxChapter 3.4.pptx
Chapter 3.4.pptx
 
Project Management- A Beginner's Guide to Managing a Project
Project Management- A Beginner's Guide to Managing a ProjectProject Management- A Beginner's Guide to Managing a Project
Project Management- A Beginner's Guide to Managing a Project
 
Exchange server.pptx
Exchange server.pptxExchange server.pptx
Exchange server.pptx
 

Viewers also liked

Tei̇aş harmonikler 02.11.2009
Tei̇aş harmonikler 02.11.2009Tei̇aş harmonikler 02.11.2009
Tei̇aş harmonikler 02.11.2009ka_ka
 
Primeiros Socorros Em Conflitos Armados e Outras Situações De Violência
Primeiros Socorros Em Conflitos Armados e Outras Situações De ViolênciaPrimeiros Socorros Em Conflitos Armados e Outras Situações De Violência
Primeiros Socorros Em Conflitos Armados e Outras Situações De ViolênciaNilton Anjos
 
Assistive Technology -
Assistive Technology - Assistive Technology -
Assistive Technology - jyoumans14
 
Marine aviation plan fy2012 marine aviation_plan1
Marine aviation plan fy2012 marine aviation_plan1Marine aviation plan fy2012 marine aviation_plan1
Marine aviation plan fy2012 marine aviation_plan1Tom "Blad" Lindblad
 

Viewers also liked (10)

Tei̇aş harmonikler 02.11.2009
Tei̇aş harmonikler 02.11.2009Tei̇aş harmonikler 02.11.2009
Tei̇aş harmonikler 02.11.2009
 
Aht.11.10
Aht.11.10Aht.11.10
Aht.11.10
 
Resume
ResumeResume
Resume
 
Primeiros Socorros Em Conflitos Armados e Outras Situações De Violência
Primeiros Socorros Em Conflitos Armados e Outras Situações De ViolênciaPrimeiros Socorros Em Conflitos Armados e Outras Situações De Violência
Primeiros Socorros Em Conflitos Armados e Outras Situações De Violência
 
13
1313
13
 
Janatreek2
Janatreek2Janatreek2
Janatreek2
 
Assistive Technology -
Assistive Technology - Assistive Technology -
Assistive Technology -
 
Cognitive development
Cognitive developmentCognitive development
Cognitive development
 
Marine aviation plan fy2012 marine aviation_plan1
Marine aviation plan fy2012 marine aviation_plan1Marine aviation plan fy2012 marine aviation_plan1
Marine aviation plan fy2012 marine aviation_plan1
 
Primeros auxilios
Primeros auxiliosPrimeros auxilios
Primeros auxilios
 

Similar to Akim ve geri̇li̇m trans

Yarıiletken tetiklemeli tesla bobini / üreteci
Yarıiletken tetiklemeli tesla bobini / üreteciYarıiletken tetiklemeli tesla bobini / üreteci
Yarıiletken tetiklemeli tesla bobini / üretecimuro61
 
Kopyası staj defteri
Kopyası staj defteriKopyası staj defteri
Kopyası staj defteriBaki Aydın
 
3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)
3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)
3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)Halil Deveci
 
altıfazlıasenkronmotor tasarımı
altıfazlıasenkronmotor tasarımıaltıfazlıasenkronmotor tasarımı
altıfazlıasenkronmotor tasarımıİlker Öztürk
 
Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....
Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....
Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....Mehmet Tosuner Hoca
 
Grup 2 b170100014_alperen dobrucalı tasarım çalışması
Grup 2 b170100014_alperen dobrucalı  tasarım çalışmasıGrup 2 b170100014_alperen dobrucalı  tasarım çalışması
Grup 2 b170100014_alperen dobrucalı tasarım çalışmasıBayram7
 

Similar to Akim ve geri̇li̇m trans (7)

Yarıiletken tetiklemeli tesla bobini / üreteci
Yarıiletken tetiklemeli tesla bobini / üreteciYarıiletken tetiklemeli tesla bobini / üreteci
Yarıiletken tetiklemeli tesla bobini / üreteci
 
Kopyası staj defteri
Kopyası staj defteriKopyası staj defteri
Kopyası staj defteri
 
Baki staj
Baki stajBaki staj
Baki staj
 
3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)
3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)
3-Fazlı Kafes Rotorlu Asenkron Motor Tasarımı(Bitirme Tezi)
 
altıfazlıasenkronmotor tasarımı
altıfazlıasenkronmotor tasarımıaltıfazlıasenkronmotor tasarımı
altıfazlıasenkronmotor tasarımı
 
Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....
Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....
Elektrik motorlarına yol verme ve frenleme ders notum – Mehmet Tosuner – www....
 
Grup 2 b170100014_alperen dobrucalı tasarım çalışması
Grup 2 b170100014_alperen dobrucalı  tasarım çalışmasıGrup 2 b170100014_alperen dobrucalı  tasarım çalışması
Grup 2 b170100014_alperen dobrucalı tasarım çalışması
 

Akim ve geri̇li̇m trans

  • 1. T.C KOCAELİ ÜNİVERSİTESİ MÜHENDİSLİK FAKÜLTESİ ELEKTRİK MÜHENDİSLİĞİ BÖLÜMÜ PROJE -3- AKIM VE GERİLİM TRANSFORMATÖRLERİ MURAT ŞENDİL ELEKTRİK MÜH.(İ.Ö) 070206045 PROJE DANIŞMANI Yrd.Doç.Dr.MEHLİKA ŞENGÜL ARALIK 2011 KOCAELİ
  • 2. İÇİNDEKİLER Sayfa No 1) GİRİŞ…………………………………………………………………………. 5 1.1) Transformatörlerin Önemi……………………………………………… ... 5 1.2)Transformatörlerin Yapısı…………………………………………………. 5 1.3)Transformatörlerin Çalışma Prensibi………………………………………. 6 1.4)Transformatörlerin Dönüştürme Oranları …………………………………. 7 1.5)Transformatörlerde Verimin Bulunması ........................................................ 8 2) ÖLÇÜ TRANSFORMATÖRLERİ…………………………………………….. 9 2.1) Ölçü Transformatörlerinin Kullanılış Amacı……………………………….. 9 3) AKIM TRANSFORMATÖRLERİ……………………………………………. 9 3.1) Tanımı……………………………………………………………………... 9 3.2) Genel Yapısı……………………………………………………………….. 10 3.3) Akım Transformatörü Prensip Şekli………………………………………. 11 3.4) Akım Transformatörü Kullanılma Amaçları……………………………… 11 3.5) Akım Transformatörü’nün Özellikleri…………………………………….. 12 3.6) Akım Transformatörlerinde Polarite………………………………………. 12 3.7) Kullanıldığı Gerilime Göre Akım Transformatörler Çeşitleri……………. 13 3.7.1) Alçak Gerilim Akım Transformatörleri……………………………… 13 3.7.2) Orta Gerilim Akım Transformatörleri……………………………… 13 3.8) Soğutma Şekline Akım Transformatör Çeşitleri…………………………. 14 3.8.1) Yağlı Tip……………………………………………………………….. 14 3.8.2) Kuru Tip……………………………………………………………….. 14 3.9)Yapılışlarına Göre Akım Transformatör Çeşitleri………………………….. 14 3.9.1) Sargılı Tipi……………………………………………………………… 14 3.9.2) Bara Tipi………………………………………………………………… 15 2
  • 3. 3.10) Kullanıldıkları Yere Göre Akım Transformatör Çeşitleri…………………. 15 3.10.1 )İç Tip (Bina İçi,Dahili)………………………………………………. 15 3.10.2 Dış Tip(Bina Dışı,Harici)………………………………………. .. . .. 15 3.11) Akım Transformatörü Seçiminde Dikkat Edilecek Hususlar………………. 15 3.12) Akım Transformatörü Etiket Değerleri…………………………………….. 16 3.13)Akım Transformatör Testleri………………………………………………... 17 3.13.1) Polarite Tayini………………………………………………………….. 17 3.13.2) Çevirme Oranı Testi…………………………………………………….. 17 4)AKIM TRANSFORMATÖRLERİNİN KARAKTERİSTİK DEĞERLERİ 4.1)Karakteristik Değerler…………………………………………………………. 18 4.1.1) İşletme Gerilim Anma Değeri (Un)………………………………………. 19 4.1.2) Anma Gücü (Nn)………………………………………………………… 19 4.1.3) Sınıf Klas (Cl)…………………………………………………………….. 20 4.1.4) Doyma Katsayısı(Saturasyon Kat Sayısı (n)……………………………… 21 4.1.4.1) Ölçü Akım Trafolarında n<5 ………………………………………… 22 4.1.4.2) Ölçü Akım Trafolarında n>10………………………………………… 22 4.1.5) Akım Çevirme Oranı (Akım Oranı) (k) …………………………………. 22 4.1.6) Anma Akım Değerleri (k)………………………………………………… 22 4.1.7) Termik Anma Akımı (Ith)………………………………………………… 23 4.1.8) Dinamik Anma Akımı (Idyn)…………………………………………….. 24 4.1.9) Akım Transformatörünün Sekonder Sargı Ucunu Açık Kalmamasının Önemi 5)GERİLİM TRANSFORMATÖRLERİ…………………………………………… 25 5.1 Gerilim Transformatörleri……………………………………………………… 25 5.1.1) Tanımı……………………………………………………………………… 25 5.1.2) Şematik Gösterimi………………………………………………………….. 25 5.1.3) Çalışma İlkesi………………………………………………………………. 25 3
  • 4. 5.1.4)Gerilim Transformatörü Yapısı………………………………………………. 26 5.1.5) Gerilim Transformatörü Prensip Şekli………………………………………. 27 5.1.6) Gerilim Transformatörünün Kullanım Amaçları……………………………. 27 5.1.7) Gerilim Transformatörü’nün Özellikleri…………………………………….. 28 5.1.8)Kullanıldıkları Yere Göre Gerilim Transformatör Çeşitleri…………………... 28 5.1.8.1) Faz-Toprak Gerilim Transformatörü…………………………………… 28 5.1.8.2) Faz-Faz Gerilim Transformatörü……………………………………… 29 5.1.9) Kombine(Akım ve Gerilim Transformatörü Birlikte) Ölçü ………………….. 29 5.1.10) Gerilim Transformatörü Siparişinde Dikkat Edilecek Hususlar…………… 30 5.1.11) Gerilim Transformatörü Etiket Değerleri…………………………………… 30 5.2) Gerilim Transformatör Testleri………………………………………………… 31 5.2.1) Polarite Tayini………………………………………………………………….. 31 5.2.2) Isınma Sıcaklık Artışı Testi…………………………………………………… 31 6)GERİLİM TRANSFORMATÖRÜNÜN KARAKTERİSTİK DEĞERLERİ 6.1) Anma Gerilim Değerleri (Up ve Us)…………………………………………… 32 6.2) Anma Gücü (Nn)…………………………………………………………………. 33 6.3) Sınıf Klas (Cl)……………………………………………………………………. 33 6.4) Dayanma Katsayısı (Uk)…………………………………………………………. 33 7) KAYNAKÇA……………………………………………………………………… 34 4
  • 5. GİRİŞ 1.1) Transformatörlerin Önemi Elektrik enerjisinin en önemli özelliklerinden biri de üretildiği yerden çok uzak bölgelere taşınabilmesidir. Bu taşınmanın verimli bir şekilde yapılabilmesi için gerilimin yeteri kadar yüksek olması gerekir. Bilindiği gibi elektrik doğru veya alternatif akım şeklinde üretebilir. Doğru akımda yüksek gerilimli enerji iletimi son zamanlarda büyük önem kazanmıştır. Ancak bu konuda istenilen düzeye gelinmemiş olup çalışmalar sürdürülmektedir. Buna karşılık alternatif akımlı elektrik enerjisinin gerilimi transformatörler yardımı ile yükseltilip düşürülebildiğinden, enerjinin alternatif akımla taşınması önemini korumaktadır. Santrallerde generatörler (alternatörler) yardımı ile üretilen elektrik enerjisinin gerilimi çok yüksek değildir. Generatör çıkış gerilimleri 0,4 - 3,3 - 6,3 - 10,6 - 13,0 - 14,7 - 15,8 ve 35 kilovolt (kV) değerlerindedir. Bu gerilimler enerjinin uzak bölgelere taşınmasını sağlayacak kadar yüksek olmadığından yükseltmeleri gerekir. Gerilimlerin yükseltilmesi ise ancak transformatörlerin yardımı ile gerçekleştirilir. Transformatörler, gerilimi alçaltma ve yükseltme şekline göre iki çeşittir. Alçaltıcı Transformatörler: Primer sargısına uygulanan gerilimi sekonder sargısından daha alçak bir şekilde aldığımızda bu tip transformatörlere alçaltıcı tip transformatörler denir. Yükseltici Transformatörler: Primer sargısına uygulanan gerilimi sekonder sargısından daha yüksek bir şekilde aldığımızda bu tip transformatörlere yükseltici tip transformatörler denir. 1.2) Transformatörlerin Yapısı Transformatörler ince özel silisli saçalardan oluşan kapalı bir manyetik gövde ile bunun üzerine,yalıtılmış iletkenlerle sarılan sargılardan oluşur.En basit şekilde iki sargı bulunur.Bu sargılardan birine PRİMER veya birinci devre diğerine ise SEKONDER veya ikinci devre adı verilir. Primer ve sekonder sargılarının birbirlerine elektriksel bir bağlantısı yoktur. Ancak özel olarak yapılan oto transformatörlerinde her iki sargı elektriksel olarak birbirleri ile bağlantılıdır. Şekil:1–1.’de bir transformatörün basit yapısı görülmektedir. 5
  • 6. Transformatör sargılarına gerilim değerlerine göre alçak gerilim sargısı veya yüksek gerilim sargısı gibi isimler de verilmektedir. Güvenlik için kullanılan özel yalıtıcı transformatörler dışında, primer ve sekonder gerilimleri birbirinden farklıdır. Transformatörlerin primer sargıları uygun gerilimdeki bir alternatif akım devresine bağlandığında sekonder sargılarından değişik değerde fakat aynı frekansta başka bir alternatif gerilim alınır. Primer gerilimi, sekonder geriliminden büyükse, bu çeşit transformatörlere düşürücü veya alçaltıcı transformatörler primer gerilimi sekonder geriliminden küçükse, bu çeşit transformatörlere yükseltici transformatörler adı verilir. Buna göre transformatör; sargıların birisinden geçen bir alternatif akım sistemini, elektromanyetik endüksiyon etkisi ile öteki sargısına aynı frekanslı fakat farklı şiddet ve gerilimde başka bir akım sistemine dönüştüren statik bir elektrik makinesi olarak tanımlanabilir. Manyetik nüvede sargıların bulunduğu kısma ayaklar ve bacaklar denir. Ayakları birleştiren alt ve üst parçalara ise boyunduruk adı verilir. 1.3) Transformatörlerin Çalışma Prensibi Şekil: 1–1.’ de görülen primer sargılarına alternatif bir gerilim uygulandığında, bu sargı değişken bir manyetik alan oluşturur. Bu alan üstünde sekonder sargının da bulunduğu manyetik demir nüve üzerinden devresini tamamlar. Primere uygulanan alternatif gerilimin zamana bağlı olarak her an yön ve şiddeti değiştiğinden, manyetik alanın da her an yön ve şiddeti değişir. Bu alanın sekonder sargılarını kesmesi (veya kavraması da denir) ile bu sargılarda alternatif bir gerilim indüklenir. Görüldüğü gibi primer ve sekonder sargılarının birbirleri ile elektriksel hiç bir bağlantıları olmadığı halde 2.devrede manyetik endüksiyon yolu ile bir gerilim oluşabilmektedir. Transformatörün primer sargılarına doğru gerilim uygulandığında, demir nüve üzerinde gene bir manyetik alan oluşur. Ancak bu manyetik alan, sabit bir alandır. Bu alanın yön ve şiddeti değişmediğinden sekonder sargılarında bir elektro-motor-kuvvet (emk.) indüklenmesi söz konusu olamaz. Çünkü indüksiyon kurallarına göre, değeri değişen manyetik alanlar 6
  • 7. tarafından etkilenen sargılarda endüksiyon gerilimleri oluşabilir. Doğru akımın verilişi ve kesilişi sıralarında sekonderde endüksiyon gerilimleri görülebilir. Ancak manyetik alanın değişimi sürekli olmadığından, transformatör doğru akımda kullanılamazlar. 1.4) Transformatörlerin Dönüştürme Oranları Bir iletkende emk indüklenebilmesi için o iletkenin sabit bir manyetik alan içinde hareket ettirilmesi veya değişen bir manyetik alan içinde bulundurulması gerekir. Birinci durum doğru akım generatörleri’nin çalışma prensibini, ikinci durum ise transformatörlerin çalışma prensibini oluşturur. Daha önceki konularda da açıklandığı gibi, bir transformatörün birinci devre sargılarına alternatif bir gerilim uygulandığında ikinci devre uçlarına bir yük bağlanmasa da yani ikinci devre uçları açık olsa da, birinci devre sargılarından çok küçük bir boş çalışma akımı (Ib) geçer. Geçen bu akımın oluşturduğu değişken (alternatif) akım, sekonder sargılarını keserek bu sargılarda alternatif bir emk indüklenir. İndüklenen bu emk’in frekansı, birinci devreye uygulanan gerilimin frekansına eşittir. Transformatör boştaki akımının oluşturduğu manyetik akının sekonder sargılarını kestiği ve boştaki nüve kayıplarının sıfır olduğu varsayılırsa böyle bir transformatör ideal transformatör olarak tanımlanır. İdeal transformatörlerde sekonder sargıları kesen kuvvet çizgilerinin tamamı, birinci devre sargılarını da keser. Bu durumda transformatörün her iki sargısının her bir sarımında aynı değerde gerilim indüklenir.Buna, her iki sargının sipir başına endüklenen gerilimleri aynıdır diyebiliriz. Primer ve sekonder sargılarda endüklenen bu gerilimler aynı akı tarafından oluşturulduğundan aralarında bir faz farkı yoktur. Yani birinci ve ikinci devrede indüksiyon yolu ile oluşan gerilimler aynı fazdadır. Transformatörün primerinde oluşan E1 emk’i Lenz kanununa güre kendisini oluşturan U1 gerilimine ters yönde olup yaklaşık olarak eşit değerdedir. (Gerçekte E1 emk.’i U1 den % 1 ila % 2 kadar küçüktür.) Transformatörün her iki sargısında sipir başına endüklenen gerilimler aynı olduğundan 1. ve 2. devre emk. larının birbirine oranı, sipir sayılarının oranına eşit yazılabilir. E1 N1 U1 N1 = Bu eşitliği = şeklinde de gösterebiliriz. Bu eşitliklerdeki harflerin anlamları E2 N2 U2 N2 şöyledir: E1 ... Primerde indüklenen emk (Volt) E2 ... Sekonderde indüklenen emk (Volt) U1 ….. Primer gerilimi. (Volt) U2….. Sekonder gerilimi. (Volt) N1 ... Primerin sipir sayısı. N2…… Sekonder sipir sayısı. 7
  • 8. Transformatörlerin verimleri çok yüksek olduğundan 1. ve 2. devre güçleri birbirine eşit yazılabilir. Buna göre volt-amper (VA) olarak1. ve 2. devre güçleri, S1 = U1 . I1 ; S2 = U2.I2 şeklinde belirtilir. Kayıpsız transformatörde S1= S2 olduğundan U1 .I1 = U2.I2 ve U1 I1 U1 N1 = yazılabilir. Bu eşitliği = ile birleştirip yazarsak, transformatörlerin (K) ile belirtilen U2 I2 U2 N2 dönüştürme oranlarını bu1muş oluruz. Buna göre transformatörlerde dönüştürme oranı: U1 I2 N1 K = = = şeklinde yazılabilir. Transformatörlerin dönüştürme oranları gerilimler bakımından U2 I1 N2 şu şekilde yazılır: Transformatörün primer gerilimi K = Transformatörün sekondergerilimi Bir transformatörün dönüştürme oranı bilinirse bundan faydalanarak primer ve sekonder gerilimleri, sipir sayıları ve akımları bulunabilir. 1.5) Transformatörlerde Verimin Bulunması Transformatörlerde verim iki şekilde bulunur: a-Direkt metotla verimin bulunması; Bu metotla daha çok küçük güçlü transformatörlerde uygulanır.Sekonder yükü sıfırdan başlanarak tam yüke kadar yavaş yavaş arttırılır.Her yükte primer ve sekonderdeki wattmetreden okunan değerler alınarak n=P2 / P1 şeklinde verimi bulunuz. b-Endirekt metotla verimin bulunması; Endirekt metotla verimin bulunması büyük güçlü transformatörlerde uygulanır.Bunun için boş çalışma deneyi ile, transformatörün demir kayıpları;kısa devre deneyi ile bakır kayıpları bulunur. Bundan sonrada n=PA / PA + Pk şeklinde verim bulunur. 8
  • 9. ÖLÇÜ TRANSFORMATÖRLERİ 2.1) Ölçü Transformatörlerinin Kullanılış Amacı Alternatif akımda yüksek gerilim ve büyük akımların ölçü aletleri ile ölçülmesi çok zor ve tehlikelidir. Çünkü ölçü aletinin yüksek gerilimlerinin yalıtılması ve alet bobinlerinin yüksek akımlara dayanacak kesitlerde yapılması belli değerlerden sonra mümkün olamaz Bu nedenle yüksek gerilim ve büyük akımların ölçülmesi için ölçü transformatörlerin kullanılır, Ölçü transformatörleri yardımı ile yüksek gerilimler ve büyük akımlar, transformatörün ikinci devresinde, ölçü aletlerinin ölçebileceği değerlere inilir. Ölçü transformatörleri, ölçümlerin güvenlik içinde kolay ve doğru bir şekilde yapılmasını sağladığı gibi, çalışanları da yüksek gerilimlerden korur. Ölçü transformatörlerinin sekonderlerine, ampermetreler, voltmetreler, wattmetreler, çeşitli röleler ve bazı kontrol aygıtları bağlanabilir. Ölçü transformatörlerinin yüklerine yalnız ölçü aletleri oluşturduğundan, anma güçleri küçüktür. Buna göre ölçü transformatörlerini, ölçü aletlerin ölçme sınırlarını genişletmek için kullanılır denebilir. Ölçü transformatörleri genel olarak akım ve gerilim ölçmelerde kullanılır. Buna göre iki ayrı özellikte ölçü transformatörü yapılmıştır. Bunlar: 1 — Akım transformatörleri 2 — Gerilim transformatörleridir. AKIM TRANSFORMATÖRLERİ 3.1) Tanımı Bağlı oldukları devreden geçen akımı istenen oranda küçülterek, bu akımla sekonder terminallere bağlı aletleri besleyen ve onları yüksek gerilimden izole eden özel trafolara, akım transformatörleri denilir. Akım transformatörü şekil 3.1’deki sembollerle gösteril 9
  • 10. Şekil 3.1 Akım transformatörlerinin sembolleri 3.2) Genel Yapısı Bir akım trafosunun genel olarak yapısı, şekilde görülene benzer olup, bu şekilde işaretlenen bölümlerden oluşur. Şekil 3.2 Akım Transformatörünün Yapısı Primer Sargı: Demir nüve üzerine sarılmış, bir/iki sipir sayılı ve kesitçe,öngörülen akım değerine uygun bir sargıdır. Sekonder Sargı:Demir nüve üzerinde primere göre ters yönde sarılmış ve sarım sayısı(akım oranı kadar)fazla,kesitçe küçültülmüş yeterli akım değerinde bir sargıdır. Sekonder sargı, akım transformatörünün, ölçü aletlerinin, sayaçların, rölelerin ve benzer aygıtların akım devrelerini besleyen sargıdır. Sargı Terminalleri: Primer sargının ana devreye ve sekonder sargının, (Ölçü / Koruma) devresine bağlantısını temin etmek üzere gövde dışına çıkarılmış terminallerdir. Primer sargı terminalleri, şekilde görüldüğü üzere üst bölümde, sekonder sargı terminalleri, alt bölümde ve yanda yer alır. Gövde: Geçmişte, içi izolasyon yağı ile doldurulmuş metal gövdeli olarak üretilen; akım trafolarının yerine, hem gövdeyi ve hem izolasyonu sağlayan (reçine/epoksi türü) katı izolasyon maddelerinin kullanımına geçilmiştir. Demir Nüve: Manyetik akı ortamını sağlayan demir nüvenin kesiti ve diğer nitelikleri, o akım trafosunun bazı karakteristik değerlerini belirler. Bir akım trafosunun ölçü veya koruma amaçlı kullanımı, güç, doyma katsayısı ve doğruluk sınıfı gibi karakteristik değerlerin farklı olmasını gerektirir. Bu nedenlerle; akım trafoları kulanım amaçlarına göre farklı üretilirler. Bir merkezde hem ölçü ve hem de koruma söz konusu olduğunda, farklı karakteristik değerlere sahip farklı akım trafolarının kullanımı gerekecektir. Farklı karakteristikli iki akım trafosunun, aynı gövde içinde üretildiği tipler, ekonomik bir çözüm olarak sunulmaktadır. 10
  • 11. Şekil:3.4’te böyle bir akım trafosunun blok şeması görülmektedir. 1 nolu (1s1 ve 1s2) sekonder terminaller ölçü devresi için, 2 nolu (2s1 ve 2s2) terminaller koruma devresi için kullanılabilir. Şekil 3.4 Koruma ve Ölçme Akım Trafosu 3.3) Akım Transformatörü Prensip Şekli Akım transformatörleri çalışma ve parçaları bakımından trafolara çok benzemektedir. Fakat akım transformatörleri sekonderi kısa devre çalışan ve sekonder çıkış akımı belirli oranda (ölçme ve koruma röleleri için) sınırlandırılmış özel bir trafodur. Şekil 3.5'te akım transformatörünün prensibi verilmiştir. Şekil 3.5 Akım Transformatörünün Prensip Şekli 3.4) Akım Transformatörü Kullanılma Amaçları Akım transformatörlerinin kullanma amaçlarını şu şekilde sıralayabiliriz: Ölçü aletlerini ve koruma rölelerini primer geriliminden izole ederek, güvenli çalışmaya imkân sağlar. Değişik primer değerlerine karşılık standart sekonder değerler elde edilir. 11
  • 12. Ölçü transformatörlerinin kullanılması, ölçü aletlerinin ve rölelerin küçük boyutlu imal edilmesine imkan verir. Büyük akımlar ölçmede daha ekonomik bir çözümdür. 3.5) Akım Transformatörü’nün Özellikleri Akım transformatörlerinin en önemli özellikleri şunlardır: Primer devresinden geçen akımı, dönüştürme oranına göre sekonder devreye aktarır. Akım transformatörleri sekonder devreleri, kısa devre durumunda çalışır. Primer sargıları kalın ve az sarımlı veya sadece baradan oluşur. Sekonder sargıları ise, ince telli ve çok sarımlıdır. Akım transformatörlerinin primer ve sekonder sargılarının giriş ve çıkış uçları, değişik harflerle ifade edilir. Şekil 3.6.Akım Transformatörünün Giriş ve Çıkış Uçlarının Harflerle Gösterimi Akım transformatörlerinin bazı ölçü aletleri ile bağlantısında polaritesi önemlidir. Aynı akım transformatörü ile birkaç ölçü aleti kullanılabilir. Akım transformatörlerinin, ölçme hassasiyetlerine göre sınıfları: 0,1-0,2-0,5-1 ve 3 olmak üzere sınıflandırılır. Koruma devrelerinde 3 sınıfı, sayaçlarda 0,2-0,5 sınıfı, ölçü aletlerinde 1 sınıfı akım transformatörleri kullanılır. Akım transformatörlerinin sekonder ucu mutlaka topraklanmalıdır. Akım transformatörleri nominal akımlarının %20 fazlasına kadar yüklenebilir. 3.6) Akım Transformatörlerinde Polarite Bir akım trafosunun primer ve sekonderindeki polarite uçları, primer sargıya akımın giriş veya çıkış yönüne göre, sekonder sargıdaki akım yönünün belirlenmesi anlamına gelir. Primer sargıya akımın girdiği veya akımın çıktığı ucu polarite olarak kabul etmek mümkündür. Ancak, akımın primere girdiği ucu polarite olarak kabul etmiş isek; sekonder sargıdan akımın çıktığı ucu polarite olarak almalıyız.Şekil 3.7 (a)(b) 12
  • 13. Akımın primer sargıdan çıktığı ucu polarite olarak kabul etmek de mümkündür. Bu takdirde, sekonderde polarite ucu, akımın sekonder sargıya girdiği uç olacaktır. Şekil 3.7. (c) ve (d) Aşağıdaki şekilde, primer için yapılan polarite kabulüne göre, sekonder polarite uçları belirlenmiş ve işaretlenmiştir. Şekilde de görüleceği üzere, primer akımın giriş yönü dikkate alınmadan; P2 Primer ucu polarite olarak seçilmişse S2 sekonder polarite ucu olacaktır. P2 Primer ucu polarite olarak seçilmişse S2 sekonder polarite ucu olacaktır. Şekil 3.7.Polarite 3.7) Kullanıldığı Gerilime Göre Akım Transformatörler Çeşitleri 3.7.1) Alçak Gerilim Akım Transformatörleri Alçak gerilim şebekelerinde kullanılan akım trafolarıdır. Dağıtım transformatörü çıkışı fazlar arası 400 V olan gerilimdir. Bu gerilim ile çalışan iş yerleri ve fabrikalarda kullanılan akım trafolarıdır. Alçak gerilimde kuru tip akım transformatörleri kullanılır. Resim 3.1.AG Akım Transformatörleri 3.7.2) Orta Gerilim Akım Transformatörleri Alçak gerilim şebekeleriyle yüksek gerilim şebekeleri arasında köprü görevi yapan orta gerilim şebekeleridir. Enerji iletiminde en çok kullanım alanına sahip şebekelerdir. Ülkemizde 3-36 KV kadar olan şebekelerdir. Bu şebekelerde kullanılan akım transformatörleri kuru tip akım trafolarıdır. 13
  • 14. Resim 3.2.Orta Gerilim Akım Transformatörleri 3.8) Soğutma Şekline Akım Transformatör Çeşitleri 3.8.1) Yağlı Tip Bu tip akım transformatörlerinde yalıtkanlığı genellikle izolasyon yağı sağlar. Kuru tip akım transformatörlerine göre, terleme veya yağ sızıntısı yapmak suretiyle kirlenme gibi kötü özellikleri vardır. Yüksek gerilimde kullanılan akım transformatörleri yağlı tip transformatörlerdir. 3.8.2) Kuru Tip Akım transformatörlerinin iletken kısımları birbirinden ve şaseden katı yalıtkan malzemelerle yalıtılmışlardır. Bu tip trafolarda yalıtım maddesi olarak zift, kâğıt, reçine ve vb. malzemeler kullanılmaktadır. Genellikle alçak gerilimde kullanılan akım transformatörleri kuru tip olarak yapılırlar. Ekonomik bakımdan ucuz, ancak herhangi bir arızada tamirleri zordur. 3.9)Yapılışlarına Göre Akım Transformatör Çeşitleri 3.9.1) Sargılı Tipi Bu tip akım transformatörlerinin primer sargıları tek bir iletken değil, sarımlardan oluşur. Primer ve sekonder sargıları aynı manyetik devre üzerine sarılmıştır. Şekil 3.8 Sargı Tipi Akım Transformatörü 14
  • 15. 3.9.2) Bara Tipi Bu tip akım transformatörlerinde primer sargıyı şebekedeki faz iletkeni oluşturur. Bara tipi akım transformatörlerinin bazılarında primer sargı, transformatörün orta kısmına yerleştirilmiş bir iletkendir. Bazı akım transformatörlerinde orta kısım boştur. Bu orta kısımın içerisinden bara veya iletken geçirilir.Genellikle panolarda kullanılır. Şekil 3.9 Bara Tipi Akım Transformatörü Resim 3.3 Buşing Akım Transformatörü Bunun yanı sıra bazı güç transformatörlerinin buşinglerine yerleştirilen akım transformatörlerine buşing tipi akım transformatörü denir. 3.10)Kullanıldıkları Yere Göre Akım Transformatör Çeşitleri Akım transformatörleri kullanıldıkları yere göre ikiye ayrılır: 3.10.1 )İç Tip (Bina İçi,Dahili) Genellikle dış etkilere karşı mukavemeti az olan transformatörlerdir. Daha ziyade kapalı yerlerde (transformatör merkezlerindeki kabinler, panolar vb.) kullanılırlar. 3.10.2 Dış Tip(Bina Dışı,Harici) Yapılışları bakımından dahili tip akım transformatörlerine göre ortam şartlarına karşı daha dayanıklıdır. Şalt sahalarında kullanılan akım transformatörleri harici transformatörlerdir. 3.11) Akım Transformatörü Seçiminde Dikkat Edilecek Hususlar Bir akım transformatörü siparişi verilirken şunlara dikkat edilmelidir: Faz-faz arası nominal (anma veya çalışma) gerilimi (34.5 kV gibi) Dönüştürme oranı (amper) (200/5 gibi) Sekonder kademe sayısı (100/5-5 gibi) Sınıfı ve kullanma amacı, (1-3 gibi) Doyma kat sayısı, n (n ≤5 ölçme, n ≥10 koruma ) Gücü VA olarak veya ohm cinsinden (30 VA, 0.5Ω gibi) 15
  • 16. Tipi: (Dahili, harici, geçit, bar, yağlı, kuru gibi) 3.12) Akım Transformatörü Etiket Değerleri Bir akım transformatörü etiketinde şunlar bulunur: • Çalışma sınıfı, akım transformatörlerinin hassasiyetlerini belirler, ölçme için 0,1-0,2-0,5-1-3-5, koruma için 5P-10P grupları kullanılır. • Sekonder anma akımı “Is” (nominal sekonder akımı) trafoların sekonder akımları (özel olarak yapılanlar hariç) 1-2-5 ve 10 A olarak yapılır. Sekonder tarafına bağlanan ölçü aletleri bu akımlara göre imal edilir. En çok kullanılan sekonder akımı 5 A’dır. Transformatör ve cihazlar arası uzaklık büyükse sekonder akımı 1 A olarak alınır. • Primer anma akımı ”Ip” (nominal primer akımı), Transformatörün çalışma akımıdır. Primer akımları, 10-12-5-15-20-25-30-40-50-60-75-100 sayılarının 5 veya 10 katıdır. Akım transformatörleri primer akımlarının %20 fazlasına kadar yüklenebilirler. Bu durumda (sekonderi 5A olan trafoda) sekonderinden 6A geçer. • Akım dönüştürme oranı, primer akımının, sekonder akımına oranına denir. Transformatör etiketlerinde 75/5A, 100/5A, 1000/5A gibi belirtilir. • Sargı oranı, “ns” primer ve sekonder sargıların birbirine oranına denir. İdeal bir akım transformatöründe sargı oranı ile dönüştürme oranı birbirine eşittir. • Kullanma gerilimi “kV” • Doyma kat sayısı(aşırı akım faktörü) “n”, ölçü aletlerinde emniyet kat sayısı olarak tanımlanır. Ölçü transformatörlerinde n ≤ 5 olmalıdır. Koruma transformatörlerinde n ≥ 10-15-20 olabilir. • Anma frekansı ”Hz”, akım transformatörlerinin çalışma frekansıdır. • Yalıtkan tipi • Termik anma akımı “Ith”, bir akım transformatörünün, bir saniye süre ile hasar görmeden dayanabileceği primer akımının efektif değeridir. Bu değer etikette kA veya primer akımının katları şeklinde gösterilir.(10 kA veya 200 x In gibi) • Dinamik anma akımı “Idyn”, primer şebekedeki bir kısa devre anında, ilk periyotta geçecek darbe akımının yol açacağı mekanik kuvvetler açısından, akım transformatörünün dayanacağı primer akımın maksimum değeridir. Akım transformatörlerinin termik anma akımlarının 2.5 katı kadardır. Akım transformatörleri Idyn akımlarına göre izole edilirler. Idyn akımları etikette verilmeyebilir. 16
  • 17. 3.13)Akım Transformatör Testleri 3.13.1) Polarite Tayini Primer ve sekonder terminallerinin polarite tespitleri imalatçılar tarafından yapılmış durumdadır. Yukarda belirtilen kurala göre yapılmış bu işaretleme, polarite uçlarının belirlenmesi için yeterlidir. Ancak imalatçıların zaman zaman yanlış işaretleme yapmaları sonucu bu kuralın uygulanması yetersiz kalabilmektedir. İşte bu olasılık nedeniyle, yapılacak basit bir test ile polaritenin tespiti gerekir. Bunun için şekil 3.10’daki basit devrenin kurulması gerekli ve yeterli olacaktır. Pilin ve DC ampermetrenin (+) uçlarının, primer ve sekonder devrelerde varsayılan (P1 ve S1) polarite uçlarına bağlanmış olmasına dikkat edilmelidir. Anahtar kapatılır ve izleyen birkaç saniye içinde ampermetrenin sapması gözlenir. Sapma saat ibrelerinin dönüş yönünde ise, yapılan işaretleme doğrudur. Ampermetre ibresi ters saparsa yapılan işaretleme yanlış demektir. Şekil 3.10 (a)‘da doğru; Şekil 3.10 (b) de ise yanlış bir işaretlemenin sonuçları gösterilmiştir. Bu durumda, genellikle sekonder polarite ucunun değiştirilerek S2’nin polarite kabulü edilmesi gerekir. Şekil 3.10 Polarite Tayini 3.13.2) Çevirme Oranı Testi Temel deneylerden olan çevirme oranı ölçümü, hem fabrikalarda hem de sahada kolaylıkla yapılabilen bir testtir. Transformatör sargılarının sarım sayılarının projeye uygun olup olmadığını tespit edebildiğimiz tek test olması nedeniyle çok önemlidir. Ayrıca yine bu test yardımı ile trafo sargılarında herhangi bir iletken kopukluğu ya da kısa devre arızası olup olmadığını kolayca tespit edebiliriz. Prensip olarak primer (YG) sargısı sarım sayısının, sekonder (AG) sargısı sarım sayısına oranı şeklinde düşünülerek test yöntemi geliştirilmiş ve ÇEVİRME ORANI KÖPRÜLERİ imal edilmiştir. Bu köprülerle 17
  • 18. test yapılabilmesi için öncelikle testten önce trafoların vektör gruplarının ( ya da bağlantı grubu) bilinmesi ve fazör diagramlarının incelenmesi gerekmektedir. Şekilde görüldüğü gibi paralel vektörlere dikkat etmek gerekir. Uygulanacak gerilimlerde gerilim vektörlerinin paralelliği şarttır. Bu durumda AB arasına bir gerilim uygular ve bu gerilimi ölçerek na arasından ölçtüğümüz gerilime oranlarsak çevirme oranını, AB / na = Çevirme Oranı Şeklinde bulabiliriz. Daha sonra aynı şekilde sırasıyla BC / nb ve CA / nc oranları ölçülerek bulunur ve daha önceden hesaplanan teorik oranlarla mukayese edilir. Standartlarda teorik orana nazaran gerçek oran sapması için ± 0,5 % tolerans verilmiştir. Gerçek oran sapmasının bu toleranslar içinde kalıp kalmadığına bakılır. Transformatöre ait teorik boşta çevirme oranı alet üzerinde kademeli transformatörde ayarlanır, ‰ hata göstergesinde denge oluşuncaya kadar değiştirilir. Bu hata göstergesinde okunan değer transformatörün gerçek çevirme oranına olan sapmasını ‰ olarak gösterir. AKIM TRANSFORMATÖRLERİNİN KARAKTERİSTİK DEĞERLERİ 4.1)Karakteristik Değerler Bir akım trafosunu tanımlayan karakteristik değerlerin bilinmesi ve uygulama alanında gerektikçe doğru kullanılması önem taşır. Örneğin; hatalı veya eksik değerler ile yapılacak bir sipariş sonucu elinize geçecek akım trafosu, amaca hizmet etmeyen bir akım trafosu olacaktır. Aşağıda sıralanan bu 18
  • 19. karakteristik değerler, akım trafosunun etiketinde belirtilmiş olduklarından, bu değerlere Etiket Değerleri demek de mümkündür. 1) İletme Gerilim Anma Değeri [Un] 2) Anma Gücü [Nn] 3) Sınıf (Klas) [ Cl ] 4) Doyma Katsayısı (Saturasyon Katsayısı) [n] 5) Akım Çevirme Oranı [k] 6) Anma Akım değerleri 7) Termik Dayanım Anma Akımı [Ith] 8) Dinamik Dayanım Anma Akımı [Idyn] Bu değerlerin bir akım trafosunda neyi ifade ettikleri ve bu değerler için kabul edilen standartlar aşağıda açıklanacaktır. 4.1.1) İşletme Gerilim Anma Değeri (Un) Bu değer, akım trafosunun; izolasyon yönünden; kullanılabileceği işletme geriliminin ( 6.3, kV, 10.5 kV, 15 kV, 34.5 kV şeklinde) üst değerini gösterir. 4.1.2) Anma Gücü (Nn) Akım Trafosunun sekonderine bağlanabilecek cihazların (akım devreleri) toplam gücü ile, cihaz bağlantısında kullanılacak kablo gücünün toplamı akım trafosunun gücünü belirler. Bu yüzden sekondere bağlanacak cihaz güçlerinin bilinmesi ve akım trafosu ile cihazlar (pano) arasında kullanılan kablo gücünün hesaplanması gerekir. Cihaz bağlantı kablosu gücünün (Nk) hesabı şöyle yapılır. Kablo kesiti (S); kablo boyu (L) ve iletken cinsi (Cu/Al) bilinen değerlerinden, kablo direnci (Rk) bulunur ve Nk= Is2.R formülünden hesaplanacak değer kablo gücünü verir. Sayısal Örnek: k = 56 ohm/mm2.m q = 2,5 mm2 ve L = 100 m ise Rk=2 x L / k x q Rk=1,43 ohm bulunur. Nk=Is2.R formülünde Is=5 Amp için, Nk=52 x 1.43 Nk=35,75 VA bulunur. Kablo nedeni ile gelen bu ek yük, uzun kablo kullanımının gerekli olduğu (örneğin TR Tank Koruma yapılan) durumlarda, akım trafosunun 1 Amp sekonder akımlı olarak seçilmesi gerekebilir. Yukarıdaki örnekte böyle bir trafonun seçilmiş olması durumunda kablo yükü sadece 1.43 VA olacaktır. 2x4 veya 2x6 mm2 gibi daha büyük kesitli kablo kullanımı da çözüm olabilir. Akım trafosunun anma gücü, aynı zamanda 19
  • 20. bu akım trafosunun sekonderine seri olarak bağlanabilecek Ohm cinsinden empedansı ifade eder. Bu nedenle bazı akım trafo etiketlerinde VA cinsinden güç yerine Ohm cinsinden empedans verilir. Örneğin 1,2 ohm gibi bir değer verilmişse, bu trafo anma gücünün, N n = 52 x 1,2 = 30 VA. olarak verilmesi ile aynı anlama gelmektedir. Günümüzde kullanılan elektronik teçhizatın, akım trafosundan çektiği güçler çok düşüktür. Küçük merkezlerde bağlantı kablo boyları da fazla uzun olmadığı için, bu merkezlerde, korumada kullanılacak akım trafolarının 15 VA. gücünde olması genellikle yeterli olmaktadır. 4.1.3) Sınıf Klas (Cl) Bir akım Trafosunun sınıfı (doğruluk sınıfı); primerden anma akımı akarken, sekonderden akan akımın, olması gerekenden, % olarak, en fazla ne kadar sapabileceğini ifade eder. Bu sapma (+) veya (-) yönde olabilir. Örneğin ; Doğruluk Sınıfı "1" olan bir akım trafosunun primerinden anma akımı geçerken, sekonderinden, sekonder anma akımının % 99'u ile %101'i arasında bir akım akar. Sekonder 5 Amp ise, sekonderden geçecek akım 5 x % 99 = 4,95 Amp ile 5 x %101 = 5,05 Amp arasında olacaktır. Bu değer, akım trafosunun oran hatasından kaynaklanır. Aslında ,doğruluk sınıfı açı hatasını da kapsar ve toplam hata bir miktar artar.Ancak açı hatası koruma devrelerinde bir önem tasımaz.Oran ile ilgili hatalar, Primerden geçen akımın değerine bağlı olarak değisiklik gösterir. Örneğin; 1 Sınıfı (Cl:1) bir akım trafosu Primerinden; Anma akımının % 10 - 19 ' u geçerken hata % 2 Anma akımının % 20 - 99 ' u geçerken hata % 1.5 Anma akımının % 100 - 120 'si geçerken hata % 1 olur. Koruma amaçlı akım trafoları genellikle sınıf:3 veya özel durumlar için sınıf:1, ölçü amaçlı akım trafoları genellikle sınıf:1 veya özel durumlarda sınıf:0,5 olarak üretilirler. Yukarıdaki açıklamaya uygun olarak bunların , primer akımın anma değerindeki oran hataları % 3 , % 1 veya % 0,5 dir. Ancak bu hatalar , primerden geçen akım, anma değerinin (% 120 ' sinin) üstüne çıktığında artar ve doyma sınırına ulastığında Sınıfı:3 olanın akım hatası % 10'a ve Sınıfı 1 olanın akım hatası % 5'e ulasır. Koruma akım trafolarının, doyma noktasına ulasıldığında gösterdikleri bu hata değerleri sınıf belirlemesinde esas alınarak, bu akım trafolarının doğruluk sınıfları; genellikle "5P" ve "10P" olarak gösterilir. Sınıfı 1 olan akım trafo plakalarında Cl:1 veya "5P" , sınıfı 3 olan akım trafolarında Cl:3 veya "10P" ifadelerine rastlanabilir. TSE tarafından benimsenen gösterilis "5P" ve "10P" dir. 20
  • 21. 4.1.4) Doyma Katsayısı(Saturasyon Kat Sayısı (n) Bir akım trafosunun primerinden geçen akım artırıldıkça, sekonderinden geçen akım da( akım oranının belirleyeceği ölçüde) artar. Bu artış primer anma akımının üstüne çıktıkça bir süre devam eder. Primer akım giderek yükseltildiğinde, önce akım oranı bozulur ve daha sonra sekonderde ki yükselme durur. Primer akım bu değerin üstüne ne kadar çıkarılırsa çıkarılsın, artık sekonderden geçen akım değişmez. Akım oranının bozulmaya başladığı noktadaki primer akım değerine, Doğruluk Sınırı, sekonder akımın değişmemeye başladığı noktaya ise Doyma Sınırı denir. Doğruluk sınırı ile doyma sınırı birbirine çok yakın değerlerdir. Ancak Doyma (saturasyon katsayısı)'na esas olan değer, doğruluk sınırıdır ve doyma katsayısı bu değere göre tanımlanır. Şekil 4.1 Doyma Katsayısı Doyma katsayısı (n) , doğruluk sınırının, primer anma akımının kaç katı olduğunu belirleyen bir kat sayıdır. Id = Ip x n n = Id / Ip dir. Doyma, akım trafosunun nominal gücü ile yüklü olduğu, yani akım trafosunun anma yük empedansını beslediği durumda tanımlanmıştır. Sayısal Örnek: Anma Gücü 30 VA; akım oranı 100/5 A.olan bir akım trafosunun Doyma kat sayısı n=5’dir. Bu akım trafosuna 30 VA.toplam gücünde cihazlar bağlı iken; primerinden 2000 Amp çekilmektedir.Akım oranı k=100 / 5=20 olduğuna göre sekonderden 2000/2=100 A.geçmesi beklenirken, bu akım trafosunun doğruluk sınırı Id=100 x 5=500 A. olduğundan sekonderden ancak Is=500/20=25 Amp geçecektir. Bu; sekondere bağlı cihazlardan; 25 Amp’den daha büyük bir akım geçemeyecek demektir. Aynı akım trafosu primerinden yine 2000Amp çekildiğini, ancak doyma kat sayısının n = 10 olduğunu varsaysak; Doğruluk Sınırı Id = 100 x 10 = 1000 Amp olacak ve sekonderden I s = 1000 / 20 Is = 50 Amp geçecektir. 21
  • 22. 4.1.4.1) Ölçü Akım Trafolarında n<5 Ölçü devrelerinde kullanılan akım trafolarında, sekonderden geçecek en büyük akımın sınırlandırılarak ölçü cihazlarına zarar vermemesi istenir. Bu nedenle ölçü akım trafolarında doyma katsayısının n < 5 veya en fazla n = 5 olması öngörülür. 4.1.4.2) Ölçü Akım Trafolarında n>10 Koruma devrelerinde ise durum terstir ve primerden geçen yüksek değerli akımların, akım oranına göre sekondere yansıması tercih edilir. Böylece; arızadan kaynaklanan bu aşırı akım röle tarafından algılanabilecek ve bu akım için ayarlanan süre içinde arıza izole edilebilecektir. Ancak bu sayede ters zamanlı röleler hızlı ve selektif olarak çalısabilir. Bu nedenle koruma akım trafolarında doyma katsayısının n >10 veya en az n = 10 olması öngörülür. 4.1.5) Akım Çevirme Oranı (Akım Oranı) (k) Akım trafoları, primerden geçen akımı değiştirerek (genellikle küçülterek) sekonder devreye aktaran cihazlardır. Primer akımın hangi oranda değiştirildiğini belirleyen sayıya, (k) o akım trafosunun “Akım Oranı” denir. Trafolarda bilinen Amper - Sarım Yasası’ na göre, primerden geçen akım ile primer sarım sayısının çarpımı, sekonderden geçen akım ile sekonder sarım sayısının çarpımına eşit olmak durumundadır. Bu yasa; IP x wp = Is x ws eşitliği ile ifade edilir. Eşitliği (Is/Ip) = (ws/ wp) şeklinde düzenlersek, bu eşitliğin birinci tarafı Akım Oranı, ikinci tarafı ise Sarım Oranı olup birbirlerine eşittirler. Akım trafosunun bu karakteristik değeri, sarım sayıları veya sarım oranları ile değil, primer ve sekonder akımlar veya (Ip/Is şeklinde) akım oranları ile ifade edilir. Akım trafo plakalarında, akım değerleri genellikle ayrı ayrı yazılır. Örneğin; Primer akım : 40 Amp Sekonder akım : 5 Amp Oysa; proje, malzeme siparişi, arıza bildirimi vb. pratik uygulamalarda genellikle akım oranları, Ip/Is seklinde ifade edilir. Burada “Ip” 20/5 , 50/5 , 150/5 , 100/5 ……. vb .ve “Is” (genellikle) 5 Amp dir. 4.1.6) Anma Akım Değerleri (k) kım Trafoları karakteristik değerler yönünden belirlenmiş standartlara göre üretilirler. Primer ve sekonder akım için standartların belirlediği değerler aşağıda verilmiştir. 22
  • 23. Sekonder akımlar ise (Is); Sekonder akım için belirlenen standart değerler 1 Amp, 2 Amp veya 5 Amp dir. Ancak genellikle kullanılan sekonder akım 5 A.dir. Özel amaçlı bazı trafolarda 1 veya 2 Amp olarak farklı sekonder akımlar tercih edilebilir. Örneğin bazı hallerde tank koruma akım trafoları sekonder akım 1 Amp olarak seçilebilmektedir. Sekonder akımın çok uzun mesafelere taşınması gerektiği diğer hallerde de, sekonder akım 1 Amp olarak seçilebilir. 4.1.7) Termik Anma Akımı (Ith) Oluşan kısa devre akımları, akım trafolarını termik bakımdan zorlarlar. Termik anma akımı ; bir akım trafosunun; 1 saniye süreyle, zarar görmeden taşıyabileceği maksimum akımın etkin değeri olarak tarif edilir. Standartlarda bu değerin; primer akım anma değerinin 100 katı olması öngörülmüştür. Bu değer Ith=100 In olarak gösterilir. Gösterilmemesi durumunda da bu değer geçerlidir. Akım Trafosunun kullanıldığı noktadaki kısa devre akım değeri ve devre koruyucuların arızayı temiz- leme süreleri dikkate alınarak yapılacak hesaplamalar sonucunda; gerek görülmesi halinde;daha büyük termik anma akımlı trafolar özel olarak üretilir. (200 In , 300 In vb) Termik anma akımı 1 saniye süre için tanımlanmış olmakla birlikte; arıza akımının temizlenme süresi; bazen 1 saniyeden kısa ve bazen da 1 saniyeden uzun olabilir. Bu durum dikkate alınarak Termik anma akımının aşağıdaki bağıntı ile kontrol edilmesi gerekir. bağıntısından "t"süresi içinde akım trafosunun taşıyabileceği max kısa devre akımı belirlenir ve bu akımın, o noktadaki (bilinen/hesaplanan) kısa devre akım ile kıyaslaması yapılır. 4.1.8) Dinamik Anma Akımı (Idyn) 23
  • 24. Kısa devre akımının ilk periyodunda; kısa devre akımı en büyük tepe değerine ulaşır. Bu değer akım trafolarını dinamik olarak zorlar. Sargılar arası itme ve çekme kuvvetleri meydana gelir. Akım trafosunun bu kuvvetlere dayanması gerekir. Bu ilk periyotta zarar görmeyen akım trafosu; izleyen periyotlarda; akım küçüleceğinden; bunları dinamik yönden rahatça karsılar. Dolayısı ile dinamik zorlanmayı; akımın ilk periyottaki tepe değeri belirler. Standartlarda akım trafolarının; Termik anma akımının 2,5 katına dayanması öngörülmüştür. Özel bir imalat nedeni ile daha büyük değerler alınmamış ise; akım trafosu etiketinde bu değer belirtilmez. 4.1.9) Akım Transformatörünün Sekonder Sargı UcunuAçık Kalmamasının Önemi Eğer, akım transformatörünün sekonder sargısının uçları açılırsa veya açık kalacak olursa, bu sargının mıknatıs alanını azaltma etkisi ortadan kalkar. Primer sargısının meydana getirdiği alan, olduğu gibi demir nüveden geçer, yani alan çok büyük bir değer alır. Bunun sonucu olarak fazla doyurulmuş demir nüve de haddinden fazla ısınarak etrafında sarılı olan sargısını yakar. Bundan başka meydana gelen büyük manyetik akı, sekonder sargı da hayat için tehlikeli olan yüksek gerilimler indükler. Bu sakıncalardan dolayı, akım transformatörlerinin sekonder uçları hiçbir zaman açılamayacağı gibi devresine de sigorta konulmaz. Onarım veya ölçü devresindeki bağlantıları değiştirmek gibi sebeplerden açılması gerekirse, ya primer akımı kesilir veya sekonder sargı uçları önce kısa devre edilir sonra açılır. Bunun için de akım transformatörünün sekonder devresine bir kısa devre anahtarı konmuştur. Ayrıca yüksek gerilim tehlikelerine karşı güvenlik tedbiri olarak sekonderin S1 ucu daima topraklanır. GERİLİM TRANSFORMATÖRLERİ 24
  • 25. 5.1 Gerilim Transformatörleri 5.1.1) Tanımı Gerilim Trafoları; "primer" dediğimiz esas devre gerilimini, manyetik bir kuplaj ile, (genellikle) küçülterek "sekonder" dediğimiz ikinci devreye aktarır ve bu devreye bağlı cihazların gerilime duyarlı elemanlarının enerjilenmesini sağlarlar. Örneğin, voltmetrelere, sayaç ve watmetrelerin gerilim devreleri vb. Bunun sonucunda; cihazların büyük gerilimler ile zorlanması önlenir. 5.1.2) Şematik Gösterimi Elektrik şema ve resimlerde, gerilim trafoları değişik şekillerde gösterilebilirler. Aşağıda bu gösteriliş şekillerine ait örnekler verilmiştir. Şekil 5.1 Gerilim Transformatörü Şematik Şekli 5.1.3) Çalışma İlkesi Çalısma ilkeleri, akım trafolarına benzerdir. Primerde oluşan manyetik akı ile, gücün sekonder devreye aktarılmasına ilişkin açıklamalar, gerilim trafoları için de geçerlidir. Manyetik devre (nüve) kayıpları ihmal edilerek, primer ve sekonder devre güçlerinin eşitliği ilkesinin matematiksel ifadesi aşağıdaki gibi olacaktır. 25
  • 26. Ayrıca amper sarım yasası uyarınca geçerli olan; Bağıntısı yazılabilir. (1) (2) bağıntılarından bu bağıntı elde edilir. Vp/Vs oranına, “Gerilim Çevirme Oranı” veya “Gerilim Oranı”denir. Gerilim transformatörlerinde, primer nominal gerilimin sekonder nominal gerilimine oranına "çevirme oranı" (nu = U1 / U2) denir. Bu oranların değeri primer gerilimine göre değişir. (10/1, 40/1, 100/1.....250/1 gibi). Alette okunan değerler, çevirme oranı ile çarpılırsa primer gerilimi bulunmuş olur. Örneğin; Primer gerilimi 4.000 V. olan bir gerilim transformatörünün, sekonder gerilimi 100 V. olduğuna göre, bu transformatörün çevirme oranı 4.000/100 = 40/1' dir. Bu değer 100 V. ile çarpılırsa primerin nominal gerilimi bulunmuş olur. Sekonder devresine bağlanan voltmetrelerin bazı tipleri; primer gerilimini, doğrudan doğruya gösterecek şekilde bölümlü olanları da vardır. 5.1.4)Gerilim Transformatörü Yapısı Gerilim transformatörünün primer sargıları, akım transformatörünün primer sargılarının tersine, çok sarımlı ince tellerden oluşmuştur. Sekonder sargı ise, nominal yükte kaybın çok az olmasını temin edecek kalınlıkta tel ile sarılmıştır. Sarım sayısı primer sargıya göre dönüştürme oranı kadar azdır. Manyetik nüve kesiti gerilim transformatörünün yükü ile orantılıdır. Gerilim transformatörleri faz-toprak, faz-faz arası yapılırlar. Şekil 5.2 Gerilim Trafosu Yapısı 26
  • 27. 5.1.5) Gerilim Transformatörü Prensip Şekli Bir gerilim transformatörü aşağıdaki kısımlardan meydana gelir: Primer sargı Sekonder sargı Manyetik nüve İzolatör ve yağ kabı İzolatör ve yağ kapları, yüksek gerilimde kullanılan gerilim transformatörlerinde bulunur. Ayrıca faz-faz arası gerilim transformatörlerinde çift izolatör bulunur. Şekil 5.3'te faz-toprak tipi gerilim transformatörünün kısımları görülmektedir. Şekil 5.3 Gerilim Transformatörünün Kısımları 5.1.6) Gerilim Transformatörünün Kullanım Amaçları Gerilim transformatörlerinin kullanım amaçlarını şu şekilde sıralayabiliriz: Ölçü aletlerini ve koruma rölelerini primer geriliminden izole ederek, güvenli çalışmaya imkan sağlar. Değişik primer değerlerine karşılık standart sekonder değerler elde edilir. Ölçü transformatörlerinin kullanılması, ölçü aletlerinin ve rölelerin küçük boyutlu imal edilmesine imkân verir. Büyük gerilimleri ölçmede daha ekonomik bir çözümdür. 27
  • 28. 5.1.7) Gerilim Transformatörü’nün Özellikleri • Yüksek gerilimi belli bir oranda düşüren ölçüm trafolarıdır. • Sekonder çıkışları açık devre gibi çalışırlar. • Bağlantısı yapılırken polaritesine dikkat edilmelidir. • Primer devresinden geçen gerilim,dönüştürme oranına göre sekonder devreye aktarır. • Primer sargıları ince ve çok sarımlıdır. • Gerilim transformatörlerinin primer ve sekonder sargılarının giriş ve çıkış uçları değişik harflerle ifade edilir. • Gerilim transformatörlerinin bazı ölçü aletleri ile bağlantısında polaritesi önemlidir. • Aynı gerilim transformatörü ile birkaç ölçü aleti kullanılabilir. • Gerilim transformatörlerinin, ölçme hassasiyetlerine göre sınıfları: 0,1-0,2-0,5-1 ve 3 olmak üzere sınıflandırılır. • Koruma devrelerinde 3 sınıfı, sayaçlarda 0,2-0,5 sınıfı, ölçü aletlerinde 1 sınıfı gerilim transformatörleri kullanılır. • Gerilim transformatörlerinin sekonder uçlarından birine sekonderde meydana gelecek bir kısa devre önlemek için sigorta konmalıdır. • Gerilim transformatörleri nominal akımlarının %20 fazlasına kadar yüklenebilir. 5.1.8)Kullanıldıkları Yere Göre Gerilim Transformatör Çeşitleri Kullanıldıkları yere göre gerilim transformatör çeşitleri ikiye ayrılır: 5.1.8.1) Faz-Toprak Gerilim Transformatörü Bu tip gerilim transformatörleri tek izolatörlü (buşing) gerilim trafolarıdır. Primer sargının çıkış ucu (polarite olmayan ucu)doğrudan toprağa bağlanır. Primer sargının giriş ucu (polarite uç) şebekenin faz iletkenine bağlanır. Ş.4 Faz-Toprak Gerilim Transformatörü 28
  • 29. 5.1.8.2) Faz-Faz Gerilim Transformatörü Faz-faz arası gerilim transformatörleri ise, şebekede iki faz arasına bağlanan gerilim trafolarıdır. İki faz arasına bağlanacağından dolayı bu tip gerilim transformatörlerinde iki tane izolatör bulunur. Primer sargı uçları iki izolatör ile dışarıya çıkartılmıştır. Bu tip gerilim transformatörleri genellikle dengeli yük çeken orta gerilim şebekelerinde, üç adet faz-toprak arası gerilim transformatörü kullanmak yerine iki adet faz-faz arası gerilim transformatörü kullanarak gerilim belli bir oranda düşürülür. Bu transformatörler şekil olarak V harfine benzediklerinden dolayı V tipi gerilim transformatörü de denir. Şekil 5.5 Faz-Faz Gerilim Transformatörü Resim 5.1 Faz-Faz Gerilim Transformatörü 5.1.9) Kombine(Akım ve Gerilim Transformatörü Birlikte) Ölçü Transformatörünün Tanımı Yapısı Aynı yere monte edilmiş akım ve gerilim transformatörlerine kombine ölçü transformatörleri denir. Ancak bunların yalıtma sorunları oldukça zordur. Kombine ölçü transformatörü son zamanlarda SF6 gazı ile yalıtılmış şalt kazanları içerisinde, daha küçük yer işgal ettiği ve yalıtım sorunu SF6 gazı ile sağlandığı için kullanılmaktadır. Resim 5.2 Kombine Ölçü Transformatörü 29
  • 30. 5.1.10) Gerilim Transformatörü Siparişinde Dikkat Edilecek Hususlar Bir gerilim transformatörü siparişi verilirken gerekli olan bilgiler: • Nominal gerilimi • Dönüştürme oranı • Gücü • Tipi • Aşırı gerilim kat sayısı • Adedi 5.1.11) Gerilim Transformatörü Etiket Değerleri Gerilim transformatörünün etiketi üzerinde aşağıdaki değerler yer alır: • Çalışma sınıfı, gerilim transformatörlerinin hassasiyetlerini belirler, ölçme için 0,1-0,2-0,5-1-3-5, koruma için 5P-10P grupları kullanılır. • Gerilim dönüştürme oranı, primer geriliminin, sekonder gerilimine oranına denir. Transformatör etiketlerinde 1500/100V, 1000/120V gibi belirtilir. • Sargı oranı, “ns” primer ve sekonder sargıların birbirine oranına denir. İdeal bir gerilim transformatöründe sargı oranı ile dönüştürme oranı birbirine eşittir. • Anma yalıtma seviyesi (deney gerilimi) kV, gerilim transformatörünün elektriki zorlanmalara karşı hasara uğramadan dayanabileceği gerilim. • Çalışma frekansı “Hz” • Primer anma gerilimi (nominal primer gerilimi) ”Up”, transformatörün çalışma gerilimidir. Genellikle 0,3-6,3-10,5-15-30-34,5-60-66-154-380 kV değerleridir. • Sekonder anma gerilimi, (nominal sekonder gerilimi) ”Us”, Primer tarafına nominal gerilim uygulandığında, sekonderden alınacak gerilimdir. Faz-faz arası gerilim transformatörlerinde 100-110-115-120 volt, faz-toprak gerilim transformatörlerinde ise bu değerlerin √3’e bölümüdür. (100/√3 gibi) • Gücü VA, (3,5 VA gibi) • Kullanım yeri (dahili, harici), firma adı 30
  • 31. Şekil 5.6 Gerilim Transformatörü Etiket Değeri 5.2) Gerilim Transformatör Testleri 5.2.1) Polarite Tayini Bir gerilim trafosunun primer ve sekonderindeki polarite uçları, primer sargıya gerilimin giriş veya çıkıs yönüne göre, sekonder sargıdaki gerilim yönünün belirlenmesi anlamına gelir.Şekil 5.7 de Primer polarite ucunun “A” ve sekonder polarite ucunun “a” olarak alınmış olduğu ve polarite olmayan “b” sekonder ucunun topraklandığı görülmektedir. Faz-Nötr arasına bağlanan gerilim trafolarının, polarite olmayan primer ucu “B” de, (çalısma ilkesi gereği) topraklanır. Şekil 5.7 Polarite Tayini 5.2.2) Isınma Sıcaklık Artışı Testi Sıcaklık artışı testinde gerilim transformatörüne uygulanan gerilimler aşağıdaki gibi olmalıdır: Anma gerilim yükseltme katsayısı ve gerilim uygulama süresi ne olursa olsun, bir fazlı gerilim transforma-törlerine birincil anma (faz arası) geriliminin ısıl katsayısına eşit bir gerilim; üç fazlı gerilim transformatörlerine birincil anma (faz arası) geriliminin 1,2 katına eşit dengeli 3 fazlı bir gerilim uygulanmalı, teste transformatör kararlı sıcaklığa erişinceye kadar devam edilmelidir. Test sonunda bulunan sıcaklık artışları standartta belirlenen sınırları aşmamalıdır. Testte ölçülen sıcaklıklar, saatte 1 °C den çok artmadığında, gerilim transformatörünün kararlı sıcaklığa eriştiği kabul edilir. Test esnasında ortam sıcaklığı10° 3 0 °C arasında olmalıdır. Birden fazla ikincil sargı bulunması halinde test her ikincil sargının anma yükünde yapılmalıdır. Sargıların sıcaklık artışları direnç değişimi metodu ile ölçülmelidir. Diğer kısımların sıcaklık artışları derece veya ısıl çift (thermocouple) ile ölçülür. 31
  • 32. GERİLİM TRANSFORMATÖRÜNÜN KARAKTERİSTİK DEĞERLERİ Aşağıda sıralanan bu karakteristik değerler, gerilim Trafosunun etiketinde belirtilmiş olduklarından, bu değerlere "Etiket Değerleri" demek de mümkündür. 1) Anma Gerilim Değerleri [Up ve Us] 2) Anma Gücü [Nn] 3) Sınıf (Klas) [ Cl ] 4) Dayanma katsayısı [Uk] Bu değerlerin bir gerilim trafosunda neyi ifade ettikleri ve bu değerler için kabul edilen standartlar aşağıda açıklanacaktır. 6.1) Anma Gerilim Değerleri (Up ve Us) Trafoların imalatında, bağlanacakları öngörülen şebekenin faz arası standart gerilimleri, gerilim trafola- rının anma primer gerilimlerinin standardını oluşturur. Dolayısı ile, primer anma gerilimleri, 34,5 kV,15kV, 10,5 kV veya 6,3 kV olacaktır. Bu değerler için üretilmiş gerilim trafolarının, bu değerlere yakın gerilim de- ğerlerdeki şebekelere bağlanması da mümkündür. Örneğin, 34,5 kV için üretilmiş bir gerilim trafosunun, 33 kV , 31,5 kV veya 30 kV bir şebekeye de bağlanabilir. Ancak, sekonder gerilim de aynı oranda değişecektir. Talep halinde, var olan farklı şebeke gerilimlerine uygun gerilim trafolarının üretilmesi de mümkündür. Örneğin 30 kV, 33 kV veya 15,8 kV primer anma değerli trafolar üretilebilir. Anma sekonder gerilim, faz arasına bağlanan gerilim trafolarında 100 Volt olarak standardize edilmiştir. Faz –Toprak arasına bağlı geri-lim trafoları sekonder anma gerilimleri, için ise standart değer 100/√3 Volttur. Faz-Toprak arasına bağlı bazı gerilim trafolarında; izole şebekelerdeki toprak temasını algılayıp sinyal vermesini sağlayan rezidüel koruma rölelerini enerjilemek amacı ile ikinci bir sargı bulunabilir. Bu sargının anma değeri 100/3 V olmaktadır. Bir gerilim trafosunun primer ve sekonder gerilim değerleri, genellikle Gerilim Oranları formatında belirtilir. 34,5 kV gerilim trafoları için örnekler aşağıdadır. Faz arası bağlı gerilim trafolarında 34,5/0,1 kV Faz nötr arası gerilim trafolarında (34,5/√3)/(0,1/√3) kV 32
  • 33. 6.2) Anma Gücü (Nn) Gerilim trafosunun sekonderinden çekilmesi öngörülen en büyük güç, o trafonun anma gücüdür. Üretimler; standartlar uyarınca; 30 VA, 60 VA ve 90 VA değerlerinde yapılır. Sekondere bağlanacak gücün, o gerilim trafosunun anma gücünü aşmaması gerekmektedir. Başka bir deyişle, bağlanacak empedansın; anma gücünün, empedans karşılığının altında olmaması gerekir. I = Us /Z genel formülünden de görüleceği üzere, “Z” küçüldükçe akım (I) büyümektedir. Bu durum, anma akımına göre boyutlandırılmış sargı kesitini zorlayacaktır. N = U.I bağıntısında, “I“ yerine yukarıdaki eşitini yazarak, N= Us2 / Z bağıntısı ile gereğinden küçük değerde empedansların, gücü de büyüttüğü görülmektedir. Nüvenin boyutlandırılması, aktarılacak anma gücüne göre yapıldığından, gücün büyümesi; kesit dışında; nüvenin de zorlanması anlamına gelir. Gerilim trafolarında kullanılmayan sargının kısa devre edilmemesi kuralının gerekçesi de bu bağıntı ile açıklanmış olmaktadır. Kısa devre edilmesi Z=0 demektir. 6.3) Sınıf Klas (Cl) Bir gerilim trafosunun sınıfı (doğruluk sınıfı); primere uygulanan gerilim sonucu, sekonderde indüklenen gerilimin, olması gerekenden, % olarak, en fazla, ne kadar sapabileceğini ifade eder. Bu sapma (+) veya (-) yönde olabilir. Örneğin; doğruluk Sınıfı "1" olan bir gerilim trafosunun, sekonder anma geriliminin % 99'u ile % 101'i arasında bir gerilim indüklenir. Sekonder anma gerilimi 100 V. ise, sekonderden 100 x % 99 =99 V ile 100 x %101 = 101 V arasında değişen bir gerilim alınabilecektir. Gerilim trafoları, doğruluk sınıfı “05”, “1” ve “3” olan üç kategoride üretilmektedir. Ölçü devrelerinde; genellikle; doğruluk sınıfı “1” veya gerekiyorsa “0,5”, koruma devrelerinde ise, doğruluk sınıfı “3” olan gerilim trafoları kullanılmaktadır. Doğruluk sınıfları, primerden anma geriliminin uygulandığı ve sekonderine anma gücünün çekildiği, durumlar için tanımlanmıstır. Farklı güçlerde, doğruluk sınıf değerinde sapmalar olacaktır. 6.4) Dayanma Katsayısı (Uk) Bu değer, (diğerlerinde olduğu gibi) gerilim trafolarının genel karakteristik değerlerinden biri olmayıp, sadece, izole şebekelerde, faz-nötr arasına bağlanan gerilim trafoları ile ilgili bir değeri ifade eder. İzole şebekelerde bir fazın toprağa teması durumunda, o gerilimi sıfır olurken diğer faz gerilimleri √3 kat artar. Bu nedenle, faz toprak arasına bağlı gerilim trafolarının bu gerilime dayanması gerekmektedir. Bu şebekelere bağlanacak gerilim trafolarının dayanmaları gereken değeri belirleyen bu katsayıya Dayanma Katsayısı denir ve değeri √3 dür. 33
  • 34. SONUÇ Bu projemde Akım ve Gerilim Transformatörlerinin yapısını,çalışma,şeklini,özelliklerini,kullanım amaçlarını,çeşitlerini,karakteristik değerlerini ve hangi testlerden geçirildiklerini vb. konu başlıklarıyla özetlemeye çalıştım.Bu projemde bana destek olan proje danışmanım Yrd.Dç.Dr. Mehlika Şengül hocama teşekkür ederim. 34
  • 35. KAYNAKÇA • Akım ve Gerilim Transformatörü Testleri Yalçın OYAL Elektrik Y.Mühendisi TEK • Ölçü Trafoları ve Sekonder Koruma Haldun BÜYÜKDORA • Ölçü Transformatörleri Hasan ÖNAL • http://www.besttrafo.com.tr • Milli Eğitim Bakanlığı Elektrik Elektronik Teknolojisi Ölçü Transformatörleri Kitabı 35
  • 36. 36