1. H
G
F
E
123
D
C
B
A
4568 7
NOTES:
8 7 6 5 4 3 2 1
A
B
C
D
E
F
G
H
APPRCHK'DREV DATE
REVISIONS
DESCRIPTION
IT WAS PRODUCED AND IS SUBJECT TO RECALL AT ANY TIME.
WRITTEN CONSENT IS EXPRESSLY PROHIBITED.
ANY USE, REPRODUCTION, OR DISCLOSURE TO OTHERS WITHOUT
THIS DRAWING IS TO BE USED ONLY FOR WORK FOR WHICH
DWG NO
TITLE
SIZE
PROJECT #
FILE:
BY
DATE
SCALE:
SHEET OF
FIRM INFO
7540 Windsor Drive, Suite 311
Allentown, PA 18195 USA
Tel: 610.366.1744
DRAWN CHECKED APPROVED
C.R. Bard, Inc.
730 Central Avenue
Murray Hill, NJ 07974
2"
2"
2"
6"
HV-18
1"
1" 1"
24" MW
HV-09
1"
HV-08
1"
SET @
4" WC
HV-10
1"
1/2"V
2"
SET @
14" WC
-2" WC
SET @
1 PSIG
3"
2"
1 1/2"
HV-20
1/4"
TK-701
NOTE 12"
HV-27
2"
2"
2"
6"
HV-21
1"
1" 1"
24" MW
PCV
05
HV-12
1"
HV-11
1"
SET @
4" WC
HV-13
1"
1/2"V
2"
SET @
14" WC
-2" WC
SET @
1 PSIG
1 1/2"
HV-23
1/4"
TK-702
2"
24"MW
HV-28
1"N2
1"N2
2"
2"
2"
6"
HV-24
1"
1" 1"
24" MW
PCV
06
HV-15
1"
HV-14
1"
SET @
4" WC
HV-16
1"
1/2"V
2"
SET @
14" WC
-2" WC
SET @
1 PSIG
HV-25
3"
2"
1 1/2"
HV-26
1/4"
TK-703
NOTE 12"
24" MW
HV-29
XV
03
XY
03
1"N2
PCV
07
HV-02
PI
07
HV-01
HV-03
F-700
NITROGEN
HV-06
1"
HV-05
1"
HV-04
1"
P-703
YC
703
HV-34 CV-03
P-702
HV-32 CV-02
P-701
HV-30 CV-01
XYLENE (DISTILLED)
581-PID-702
XYLENE (VIRGIN)
581-PID-702
HEPTANE
581-PID-606
HV-36CV-04
F-701
HV-31
F-702
HV-33
F-703
HV-35
BULK HEPTANE
12,000 GALLON
BULK XYLENE (VIRGIN)
12,000 GALLON
BULK XYLENE (DISTILLED)
12,000 GALLON
XYLENE (DISTILLED)
581-PID-703
XYLENE (D)
N2
FUTURE TANK TK-704
581-PID-701-D.dwg
581
NONE
D
PIPING & INSTRUMENTATION DIAGRAM
ROCM BUILDING 4
AHB SHK
TANK FARM - BULK CHEMICALS
581-PID-701 11/25/14
1 1
A 04/09/14 SCHEMATIC DESIGN DKS SHK
3"
2"
NOTE 1
24"MW
NC
B 10/01/14 REVISED PER ROCM 3 DESIGN DEE SHK
C 11/01/14 REVISED PER PHA DEE SHK
1. DIP PIPE TO TERMINATE MAXIMUM OF 6" FROM BOTTOM OF TANK.
DIP PIPE TO HAVE A 1/8" ANTI-SIPHON HOLE.
2. CONTROL PANEL LOCATED IN TRUCK LOADING/UNLOADING AREA.
3. ALL EQUIPMENT MUST BE GROUNDED AND ALL PROCESS
LINES ELECTRICALLY BONDED.
4. NITROGEN GAS USED TO BLOW OUT LINES FOLLOWING TRANSFER.
5. HOSE EQUIPPED WITH UNIVERSAL (CHICAGO) FITTINGS.
6. SEE DWG 581-PID-704 FOR PANEL DETAILS.
7. CONNECTION FOR PORTABLE DOUBLE DIAPHRAGM AIR PUMP.
8. OTHER E-STOPS ARE TO BE LOCATED IN THE MIX ROOM AND NEAR
THE MEC DIP TANKS.
9. CAM & GROOVE ADAPTER WITH DUST COVER.
COMPRESSED AIR 1"
PCV
08
P-706
HV-49
P-705
HV-47
P-704
YC
704
HV-45
PI
09
HV-42HV-41
HV-40
CV-07
CV-08
1"x3/4"
D - OWNER REVIEW - -
NOT FOR
CONSTRUCTION
NOTE 9
NOTE 9
NOTE 9
GROUND
GROUND
GROUNDGROUND
NOTE 7
PCV
04
PI
08
PI
10
YC
705
YC
706
PI
11
XV
02
XY
02
YC
702
XV
01
XY
01
YC
701
1 1/2"-C7-00
2"-C7-00
1 1/2"-XYLV-00
2"-XYLV-00
2"-XYLD-00
XV
06
2"-XYLV-00
3"-C7-00
NOTE 8
LAHH
01
TK-701
LAH
01
TK-701
XL
01
PU-704
LI
01
TK-701
HS
01
S/S
PU-704
XL
04
XV-04
HS
04
O/C
XV-04
LAH
02
TK-702
LAHH
02
TK-702
LI
02
TK-702
XL
02
PU-705
XL
05
XV-05
LAH
03
TK-703
LAHH
03
TK-703
LI
03
TK-703
XL
03
PU-706
HS
02
S/S
PU-705
HS
05
O/C
XV-05
HS
03
S/S
PU-706
XL
06
XV-06
HS
06
O/C
XV-06
TRUCK LOADING/UNLOADING STATION
HV-07
1"
1"x 3/4"
NOTE 5
HV-39
3/4"x1/2"
NOTE 5
HV-43
HV-48HV-46
HV-37CV-05
HV-38CV-06
HV-44
NOTE 7
1 1/2"-XYLD-00