SlideShare a Scribd company logo
1 of 11
Download to read offline
What is spinning reserve?


                                Yann REBOURS
                               Daniel KIRSCHEN




Abstract
       This document proposes a definition of spinning reserve. It also compares the amount
asked by TSOs in several systems according to this definition.




Release 1
19/09/2005
What is spinning reserve?



Contents
ABSTRACT........................................................................................................................................................... 1
CONTENTS........................................................................................................................................................... 2
FIGURES............................................................................................................................................................... 3
TABLES................................................................................................................................................................. 3
ABBREVIATIONS AND ACRONYMS ............................................................................................................. 3
1       INTRODUCTION ....................................................................................................................................... 4
2       FRAMEWORK FOR DEFINING RESERVES ....................................................................................... 5
    2.1          ORGANISATION OF FREQUENCY CONTROL ............................................................................................ 5
    2.2          RESERVES AND GENERATOR CAPACITY................................................................................................. 6
3       DISCUSSION ON SPINNING RESERVE ............................................................................................... 7
    3.1          CURRENT DIFFICULTIES ........................................................................................................................ 7
    3.2          A GENERAL DEFINITION ........................................................................................................................ 7
    3.3          CONSEQUENCES OF THE SPINNING RESERVE DEFINITION ....................................................................... 7
    3.4          RESERVES AND GENERATOR CAPACITY................................................................................................. 8
    3.5          AMOUNT OF SPINNING RESERVE IN DIFFERENT COUNTRIES ................................................................... 9
4       SUMMARY................................................................................................................................................ 10
CONTACT DETAILS ........................................................................................................................................ 11
REFERENCES.................................................................................................................................................... 11




The University of Manchester                                                    2/11                                                                 Release 1
Yann Rebours, Daniel Kirschen                                                                                                                       19/09/2005
What is spinning reserve?



Figures
Figure 2.1: Framework for frequency regulation within the UCTE .......................................... 5
Figure 2.2: Allocation of the capacity of a generating unit that participates in all three levels
     of frequency control.......................................................................................................... 6
Figure 3.1: Representation of the spinning reserve of a generating unit that participates in all
     three levels of frequency control ...................................................................................... 8

Tables
Table 3.1: Calculation of spinning reserve requirements in different systems .......................... 9

Abbreviations and acronyms
AGC: Automation Generation Control
ISO: Independent System Operator
LFC: Load-Frequency Control
NERC: North American Electric Reliability Council
PJM: Pennsylvania New Jersey-Maryland interconnection
TSO: Transmission System Operator
UCTE: Union for the Co-ordination of Transmission of Electricity




The University of Manchester                                   3/11                                                  Release 1
Yann Rebours, Daniel Kirschen                                                                                       19/09/2005
What is spinning reserve?



   1 Introduction
        The liberalisation of the electricity supply industry and the introduction of competitive
markets for electrical energy have required the definition of ancillary services. The purpose of
these ancillary services is to help maintain the security and the quality of the supply of
electricity. In particular, control of the frequency requires that a certain amount of active
power be kept in reserve to be able to re-establish the balance between load and generation at
all times. In general, reserve can thus be defined as the amount of generation capacity that can
be used to produce active power over a given period of time and which has not yet been
committed to the production of energy during this period. In practice, different types of
reserve services are required to respond to different types of events over different time frames.
In particular, while the term “spinning reserve” is widely used in literature, this service can be
defined in different ways. This may lead to some confusion.
        To help reduce this confusion, this document proposes a definition of spinning
reserve. It then provides the amount of spinning reserve required in several jurisdictions
according to this definition.




The University of Manchester                  4/11                                     Release 1
Yann Rebours, Daniel Kirschen                                                         19/09/2005
What is spinning reserve?



   2 Framework for defining reserves
       This section outlines a framework that will help define spinning reserve.

   2.1 Organisation of frequency control
        The simplified scheme represented in Figure 2.1 illustrates the framework that is
typically used for frequency regulation. This regulation usually involves three levels of
controls. Using UCTE terminology [5], these levels are called Primary, Secondary and
Tertiary. In large interconnected systems, all three forms of control are usually present. In
smaller isolated systems secondary control may not exist as such. For the sake of simplicity,
frequency regulation using demand-side action is not included in this diagram but could be
considered without conceptual changes.

                                      Primary control                                  fnominal
                                      (automatic)
                                                                                               -
                                           Pprimary control                                            f
                                                                    Governor
                                                                                                   +


                                                   +
          Pscheduled             Pdispatched                  Pwanted                 Pproduced            Interconnected
                                                                        Generator
                   +                           +                                                              network
                             +                         +
                                                                                                                 f

                                                                                           f
                  Ptertiary control
                                                                                          Ptie lines
                                                                            LFC
                                                                        (called AGC       ftarget
          Tertiary control                         Psecondary control                                                 Common
          (managed by TSO & genco)                                        in USA)
                                                                                          Pscheduled tie lines       frequency



                  These two
               controls form                       Secondary control
                   the AGC                         (managed directly by TSO)



                       Figure 2.1: Framework for frequency regulation within the UCTE


       Each control can be defined as follow [4]:
   Primary control: local automatic control which delivers reserve power in opposition to
   any frequency change;
   Secondary control: centralised automatic control which delivers reserve power in order to
   bring back the frequency and the interchange programs to their target values;
   Tertiary control: manual change in the dispatching and unit commitment in order to
   restore the secondary control reserve, to manage eventual congestions, and to bring back
   the frequency and the interchange programs to their target if the secondary control reserve
   is not sufficient.




The University of Manchester                                        5/11                                                      Release 1
Yann Rebours, Daniel Kirschen                                                                                                19/09/2005
What is spinning reserve?


   2.2 Reserves and generator capacity
         In theory, a generating unit could participate in all three levels of control. Figure 2.2
illustrates how its capacity would then be divided. In practice, a generating unit might provide
only one, two or none of these reserve services.
                                      Maximum
                                                                          Unused capacity

               Primary control uses this capacity                         Primary control reserve



             Secondary control uses this capacity                         Secondary control reserve




                Tertiary control uses this capacity                       Synchronized tertiary
                                                                          control reserve
                                Scheduled power




                                                                          Energy
                                        Minimum




                                            0 MW

 Figure 2.2: Allocation of the capacity of a generating unit that participates in all three levels of frequency
                                                   control




The University of Manchester                          6/11                                             Release 1
Yann Rebours, Daniel Kirschen                                                                         19/09/2005
What is spinning reserve?


   3 Discussion on spinning reserve
       This section tries to define the concept of spinning reserve.

   3.1 Current difficulties
        Many authors use the term “spinning reserve” without defining it because they assume
that its meaning is obvious and unambiguous. However, a partial survey of the literature
produces very different definitions:
   Hirst and Kirby [2]: “generators online, synchronized to the grid, that can increase output
   immediately in response to a major outage and can reach full capacity within 10 minutes”;
   Wood and Wollenberg [7]: the total synchronised capacity, minus the losses and the load;
   Zhu, Jordan and Ihara [8]: “the unloaded section of synchronized that is able to respond
   immediately to serve load, and is fully available within ten minutes”;
   British Electricity International [1]: “the additional output which is part-loaded generating
   plant is able to supply and sustain within 5 minutes. This category also includes pumped-
   storage plant […] operating in the pumping mode, whose demand can be disconnected
   within 5 minutes”;
   UCTE [6]: tertiary reserve available within 15 minutes “that is provided chiefly by storage
   stations, pumped-storage stations, gas turbines and by thermal power stations operating at
   less than full output (responsibility of the TSO)”;
   NERC [3]: “Unloaded generation that is synchronized and ready to serve additional
   demand”.

       These definitions disagree (or remain silent) on some important issues:
   Who provides spinning reserve? Is it limited to generators or can the demand-side
   participate?
   What is the time frame for responding to a request? When should it start and end?
   How is this reserve activated? Does it happen automatically or is it only done at the
   request of the Transmission System Operator (TSO)?

       Therefore, it seems to be interesting to propose a definition which could fit any
system.

   3.2 A general definition
        In order to get a general definition of spinning reserve, it seems to be essential to
remove the idea of time. In fact, each system has its particularities. However, in any system,
there is a system operator. Therefore, this concept can be used within the proposed definition.
Lastly, it seems to be interesting to get detached from the terms such as “generator” or
“demand-side”, which can introduce more ambiguities.
        We therefore propose the following definition: the spinning reserve is the unused
capacity which can be activated on decision of the system operator and which is provided by
devices which are synchronized to the network and able to affect the active power.

   3.3 Consequences of the spinning reserve definition
       Some important comments should be made on this definition:
   The beginning of the reserve deployment or the reserve deployment duration does not
   appear in the definition, as they are not relevant for a general definition of the spinning
   reserve. In fact, each country has its own definition (e.g. secondary control reserve has to

The University of Manchester                 7/11                                    Release 1
Yann Rebours, Daniel Kirschen                                                       19/09/2005
What is spinning reserve?

   be fully available in 8 minutes in France and in 5 minutes in the USA [4]), depending on
   parameters such as the size of the synchronous network or the market structure;
   The primary control reserve, which is not controlled by the TSO, has to be excluded from
   the spinning reserve. Moreover, the self-regulating effect of the loads, which has an effect
   similar to the primary reserve, is also excluded from the spinning reserve. In fact, these
   two items are more important for network stability than for balancing consumption and
   production;
   Secondary control reserve should be considered as spinning reserve. In fact, the power
   deployed by the TSO through this reserve equilibrates the consumption and the production
   and has to be kept as long as required;
   Spinning reserve includes also synchronized tertiary control reserve, as this reserve is
   deployed on the instruction of the TSO;
   If a generator decides not to provide reserve, its spare synchronized capacity is not
   spinning reserve, as it cannot be activated by the system operator. However, in many
   systems, generators have to bid all their spare synchronized capacity in the balancing
   mechanism. Therefore, in this case, the system operator has the possibility to call all the
   synchronized capacity;
   A consumer can provide spinning reserve, if it agrees to be disconnected or to reduce its
   load upon request by the TSO. Pump loads are prime candidates for the provision of
   spinning reserve from the demand side.

   3.4 Reserves and generator capacity
       Based on the previous discussion, the spinning reserve for a generating unit is
represented in Figure 3.1.
                                      Maximum
                                                                         Unused capacity

                Primary control uses this capacity                       Primary control reserve



              Secondary control uses this capacity                       Secondary control reserve




                Tertiary control uses this capacity                      Synchronized tertiary
                                                                         control reserve
                                Scheduled power




            Spinning reserve
                                                                          Energy
                                        Minimum




                                            0 MW

Figure 3.1: Representation of the spinning reserve of a generating unit that participates in all three levels of
                                             frequency control




The University of Manchester                          8/11                                            Release 1
Yann Rebours, Daniel Kirschen                                                                        19/09/2005
What is spinning reserve?


   3.5 Amount of spinning reserve in different countries
       According to the definition given in Section 3.2 and [4], Table 3.1 lists how (positive)
spinning reserve requirements are calculated in different systems.
             Table 3.1: Calculation of spinning reserve requirements in different systems
       Country                  Calculation of the amount of spinning reserve
                          No specific recommendation. The recommended maximum is
        UCTE
                                                     10 Lmax zone + 150 2 − 150

       Belgium                UCTE rules. Currently at least 460 MW by generators.

       France                           UCTE rules. Currently at least 500 MW.
        The
                                        UCTE rules. Currently at least 300 MW.
     Netherlands
        Spain                                  Between 3 Lmax and 6 Lmax

      California     50% × max(5% × Phydro + 7% × Pother generation ; Plargest contingency ) + Pnon − firm import

         PJM         1.1% of the peak + probabilistic calculation on typical days and hours

       Where:
   Lmax: the maximum load of the system during a given period;
   Lmax zone: the maximum load of the UCTE control area during a given period;
   Phydro: scheduled generation from hydroelectric resources;
   Pother generation: scheduled generation from resources other than hydroelectric;
   Plargest contingency: value of the power imbalance due to the most severe contingency;
   Pnon-firm import: total of all the interruptible imports.

        Lastly, negative spinning reserve was not taken in account in Table 3.1. However, it is
essential for the stability of the network to be able to reduce the active power production in
case of a high frequency. However, since most of the time reducing power production is
easier than increasing it, this problem is not considered further.




The University of Manchester                        9/11                                                Release 1
Yann Rebours, Daniel Kirschen                                                                          19/09/2005
What is spinning reserve?



   4 Summary
       This document proposes a definition of spinning reserve. The spinning reserve is the
unused capacity which can be activated on decision of the system operator and which is
provided by devices that are synchronized to the network and able to affect the active power.
Therefore, spinning reserve corresponds to the UCTE secondary (automatic and central) and
synchronized tertiary control reserves (manual and central).
       This definition can be applied in most power systems. Therefore, it may be used to
compare the spinning reserve requirements in different jurisdictions.




The University of Manchester               10/11                                  Release 1
Yann Rebours, Daniel Kirschen                                                    19/09/2005
What is spinning reserve?



Contact details
If you have any suggestions, comments or questions regarding this document, please contact:

Yann REBOURS
The University of Manchester
School of Electrical and Electronic Engineering
PO Box 88
Manchester M60 1QD
United Kingdom
Tél. : +44 79 81 08 55 87
yann.rebours@postgrad.manchester.ac.uk

References
[1]    British Electricity International, “Modern power station practice: incorporating
       modern power system practice”, Pergamon, 1991.
[2]    Eric Hirst and Brendan Kirby, Unbundling Generation and Transmission Services for
       Competitive Electricity Markets: Ancillary Services, NRRI-98-05, National
       Regulatory Research Institute, Columbus, OH, Jan. 1998;
[3]    NERC, "Operating manual", 15th of June 2004.
[4]    Y. Rebours and D. Kirschen, "A Survey of Definitions and Specifications of Reserve
       Services", Release 1, the University of Manchester, the 19th of September 2005.
[5]    UCTE, "UCTE Operation Handbook", v 2.5E, the 20th of July 2004.
[6]    UCTE,
       http://www.ucte.org/statistics/terms_power_balance/e_default_explanation.asp.
[7]    Allen J Wood and Bruce F Wollenberg, “Power Generation, Operation and Control,”
       2nd edition, Wiley Interscience, 1996.
[8]    J. Zhu, G. Jordan, and S. Ihara, "The market for spinning reserve and its impacts on
       energy prices", proceedings of the IEEE Power Engineering Society Winter Meeting,
       2000.




The University of Manchester               11/11                                  Release 1
Yann Rebours, Daniel Kirschen                                                    19/09/2005

More Related Content

What's hot

Security analysis black and white 2007
Security analysis black and white 2007Security analysis black and white 2007
Security analysis black and white 2007
Viren Pandya
 
An Under frequency Load Shedding Scheme for
An Under frequency Load Shedding Scheme forAn Under frequency Load Shedding Scheme for
An Under frequency Load Shedding Scheme for
Ajay Singh
 

What's hot (18)

Psoc
PsocPsoc
Psoc
 
Generation shift factor and line outage factor
Generation shift factor and line outage factorGeneration shift factor and line outage factor
Generation shift factor and line outage factor
 
Power system contingencies
Power system  contingenciesPower system  contingencies
Power system contingencies
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side management
 
Transient Stability Assessment and Enhancement in Power System
Transient Stability Assessment and Enhancement in Power  SystemTransient Stability Assessment and Enhancement in Power  System
Transient Stability Assessment and Enhancement in Power System
 
Security analysis black and white 2007
Security analysis black and white 2007Security analysis black and white 2007
Security analysis black and white 2007
 
Comparison of Different Design Methods for Power System Stabilizer Design - A...
Comparison of Different Design Methods for Power System Stabilizer Design - A...Comparison of Different Design Methods for Power System Stabilizer Design - A...
Comparison of Different Design Methods for Power System Stabilizer Design - A...
 
Power System Control
Power System ControlPower System Control
Power System Control
 
load shedding
load sheddingload shedding
load shedding
 
Voltage and Frequency Control of the Grid
Voltage and Frequency Control of the GridVoltage and Frequency Control of the Grid
Voltage and Frequency Control of the Grid
 
IRJET- Automatic Load Sharing of Transformer
IRJET- Automatic Load Sharing of TransformerIRJET- Automatic Load Sharing of Transformer
IRJET- Automatic Load Sharing of Transformer
 
Methods for Voltage Stability Enhancement
Methods for Voltage Stability EnhancementMethods for Voltage Stability Enhancement
Methods for Voltage Stability Enhancement
 
Design of power system stabilizer for damping power system oscillations
Design of power system stabilizer for damping power system oscillationsDesign of power system stabilizer for damping power system oscillations
Design of power system stabilizer for damping power system oscillations
 
Frequency Control of Power Systems
Frequency Control of Power SystemsFrequency Control of Power Systems
Frequency Control of Power Systems
 
LOAD FREQUENCY AND VOLTAGE GENERATION CONTROL
LOAD FREQUENCY AND VOLTAGE GENERATION CONTROLLOAD FREQUENCY AND VOLTAGE GENERATION CONTROL
LOAD FREQUENCY AND VOLTAGE GENERATION CONTROL
 
An Under frequency Load Shedding Scheme for
An Under frequency Load Shedding Scheme forAn Under frequency Load Shedding Scheme for
An Under frequency Load Shedding Scheme for
 
SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY
 
Moment of power system reliability
Moment of power system reliabilityMoment of power system reliability
Moment of power system reliability
 

Similar to About spinning reserve

Spinning reserve-120064595535644-2
Spinning reserve-120064595535644-2Spinning reserve-120064595535644-2
Spinning reserve-120064595535644-2
Rasidi Yamin
 
Ijartes v2-i4-001
Ijartes v2-i4-001Ijartes v2-i4-001
Ijartes v2-i4-001
IJARTES
 
Wcdma power control
Wcdma power controlWcdma power control
Wcdma power control
Mostafa Adel
 

Similar to About spinning reserve (20)

R04601113118
R04601113118R04601113118
R04601113118
 
F010434147
F010434147F010434147
F010434147
 
POSOCO.pdf
POSOCO.pdfPOSOCO.pdf
POSOCO.pdf
 
Spinning reserve-120064595535644-2
Spinning reserve-120064595535644-2Spinning reserve-120064595535644-2
Spinning reserve-120064595535644-2
 
Power-Grid Load Balancing by Using Smart Home Appliances
Power-Grid Load Balancing by Using Smart Home AppliancesPower-Grid Load Balancing by Using Smart Home Appliances
Power-Grid Load Balancing by Using Smart Home Appliances
 
Comparative Analysis of Different Controllers in Two–Area Hydrothermal Power ...
Comparative Analysis of Different Controllers in Two–Area Hydrothermal Power ...Comparative Analysis of Different Controllers in Two–Area Hydrothermal Power ...
Comparative Analysis of Different Controllers in Two–Area Hydrothermal Power ...
 
Application_of_numerical_distance_relay.pdf
Application_of_numerical_distance_relay.pdfApplication_of_numerical_distance_relay.pdf
Application_of_numerical_distance_relay.pdf
 
CONTROL OF THREE AREA INTERCONNECTED POWER SYSTEM USING SLIDING MODE CONTROLLER
CONTROL OF THREE AREA INTERCONNECTED POWER SYSTEM USING SLIDING MODE CONTROLLERCONTROL OF THREE AREA INTERCONNECTED POWER SYSTEM USING SLIDING MODE CONTROLLER
CONTROL OF THREE AREA INTERCONNECTED POWER SYSTEM USING SLIDING MODE CONTROLLER
 
How the grid works - spinning reserve
How the grid works - spinning reserveHow the grid works - spinning reserve
How the grid works - spinning reserve
 
Ijartes v2-i4-001
Ijartes v2-i4-001Ijartes v2-i4-001
Ijartes v2-i4-001
 
Ebook - Future Power Systems
Ebook - Future Power SystemsEbook - Future Power Systems
Ebook - Future Power Systems
 
Wcdma power control
Wcdma power controlWcdma power control
Wcdma power control
 
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
 
Kj2518171824
Kj2518171824Kj2518171824
Kj2518171824
 
Kj2518171824
Kj2518171824Kj2518171824
Kj2518171824
 
H8 ACTIVE POWER AND EMERSON EDUARDO RODRIGUES.pdf
H8 ACTIVE POWER AND EMERSON EDUARDO RODRIGUES.pdfH8 ACTIVE POWER AND EMERSON EDUARDO RODRIGUES.pdf
H8 ACTIVE POWER AND EMERSON EDUARDO RODRIGUES.pdf
 
mechine vibration diagnotics for beginer
mechine vibration diagnotics for beginermechine vibration diagnotics for beginer
mechine vibration diagnotics for beginer
 
Report on Power System oscillations experienced in Indian Grid
Report on Power System oscillations experienced in Indian GridReport on Power System oscillations experienced in Indian Grid
Report on Power System oscillations experienced in Indian Grid
 
Fuzzy controlled mine drainage system based on embedded system
Fuzzy controlled mine drainage system based on embedded systemFuzzy controlled mine drainage system based on embedded system
Fuzzy controlled mine drainage system based on embedded system
 
Utilization of DVR with FLC to Inject Voltage in a Transmission Line
Utilization of DVR with FLC to Inject Voltage in a Transmission LineUtilization of DVR with FLC to Inject Voltage in a Transmission Line
Utilization of DVR with FLC to Inject Voltage in a Transmission Line
 

About spinning reserve

  • 1. What is spinning reserve? Yann REBOURS Daniel KIRSCHEN Abstract This document proposes a definition of spinning reserve. It also compares the amount asked by TSOs in several systems according to this definition. Release 1 19/09/2005
  • 2. What is spinning reserve? Contents ABSTRACT........................................................................................................................................................... 1 CONTENTS........................................................................................................................................................... 2 FIGURES............................................................................................................................................................... 3 TABLES................................................................................................................................................................. 3 ABBREVIATIONS AND ACRONYMS ............................................................................................................. 3 1 INTRODUCTION ....................................................................................................................................... 4 2 FRAMEWORK FOR DEFINING RESERVES ....................................................................................... 5 2.1 ORGANISATION OF FREQUENCY CONTROL ............................................................................................ 5 2.2 RESERVES AND GENERATOR CAPACITY................................................................................................. 6 3 DISCUSSION ON SPINNING RESERVE ............................................................................................... 7 3.1 CURRENT DIFFICULTIES ........................................................................................................................ 7 3.2 A GENERAL DEFINITION ........................................................................................................................ 7 3.3 CONSEQUENCES OF THE SPINNING RESERVE DEFINITION ....................................................................... 7 3.4 RESERVES AND GENERATOR CAPACITY................................................................................................. 8 3.5 AMOUNT OF SPINNING RESERVE IN DIFFERENT COUNTRIES ................................................................... 9 4 SUMMARY................................................................................................................................................ 10 CONTACT DETAILS ........................................................................................................................................ 11 REFERENCES.................................................................................................................................................... 11 The University of Manchester 2/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 3. What is spinning reserve? Figures Figure 2.1: Framework for frequency regulation within the UCTE .......................................... 5 Figure 2.2: Allocation of the capacity of a generating unit that participates in all three levels of frequency control.......................................................................................................... 6 Figure 3.1: Representation of the spinning reserve of a generating unit that participates in all three levels of frequency control ...................................................................................... 8 Tables Table 3.1: Calculation of spinning reserve requirements in different systems .......................... 9 Abbreviations and acronyms AGC: Automation Generation Control ISO: Independent System Operator LFC: Load-Frequency Control NERC: North American Electric Reliability Council PJM: Pennsylvania New Jersey-Maryland interconnection TSO: Transmission System Operator UCTE: Union for the Co-ordination of Transmission of Electricity The University of Manchester 3/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 4. What is spinning reserve? 1 Introduction The liberalisation of the electricity supply industry and the introduction of competitive markets for electrical energy have required the definition of ancillary services. The purpose of these ancillary services is to help maintain the security and the quality of the supply of electricity. In particular, control of the frequency requires that a certain amount of active power be kept in reserve to be able to re-establish the balance between load and generation at all times. In general, reserve can thus be defined as the amount of generation capacity that can be used to produce active power over a given period of time and which has not yet been committed to the production of energy during this period. In practice, different types of reserve services are required to respond to different types of events over different time frames. In particular, while the term “spinning reserve” is widely used in literature, this service can be defined in different ways. This may lead to some confusion. To help reduce this confusion, this document proposes a definition of spinning reserve. It then provides the amount of spinning reserve required in several jurisdictions according to this definition. The University of Manchester 4/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 5. What is spinning reserve? 2 Framework for defining reserves This section outlines a framework that will help define spinning reserve. 2.1 Organisation of frequency control The simplified scheme represented in Figure 2.1 illustrates the framework that is typically used for frequency regulation. This regulation usually involves three levels of controls. Using UCTE terminology [5], these levels are called Primary, Secondary and Tertiary. In large interconnected systems, all three forms of control are usually present. In smaller isolated systems secondary control may not exist as such. For the sake of simplicity, frequency regulation using demand-side action is not included in this diagram but could be considered without conceptual changes. Primary control fnominal (automatic) - Pprimary control f Governor + + Pscheduled Pdispatched Pwanted Pproduced Interconnected Generator + + network + + f f Ptertiary control Ptie lines LFC (called AGC ftarget Tertiary control Psecondary control Common (managed by TSO & genco) in USA) Pscheduled tie lines frequency These two controls form Secondary control the AGC (managed directly by TSO) Figure 2.1: Framework for frequency regulation within the UCTE Each control can be defined as follow [4]: Primary control: local automatic control which delivers reserve power in opposition to any frequency change; Secondary control: centralised automatic control which delivers reserve power in order to bring back the frequency and the interchange programs to their target values; Tertiary control: manual change in the dispatching and unit commitment in order to restore the secondary control reserve, to manage eventual congestions, and to bring back the frequency and the interchange programs to their target if the secondary control reserve is not sufficient. The University of Manchester 5/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 6. What is spinning reserve? 2.2 Reserves and generator capacity In theory, a generating unit could participate in all three levels of control. Figure 2.2 illustrates how its capacity would then be divided. In practice, a generating unit might provide only one, two or none of these reserve services. Maximum Unused capacity Primary control uses this capacity Primary control reserve Secondary control uses this capacity Secondary control reserve Tertiary control uses this capacity Synchronized tertiary control reserve Scheduled power Energy Minimum 0 MW Figure 2.2: Allocation of the capacity of a generating unit that participates in all three levels of frequency control The University of Manchester 6/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 7. What is spinning reserve? 3 Discussion on spinning reserve This section tries to define the concept of spinning reserve. 3.1 Current difficulties Many authors use the term “spinning reserve” without defining it because they assume that its meaning is obvious and unambiguous. However, a partial survey of the literature produces very different definitions: Hirst and Kirby [2]: “generators online, synchronized to the grid, that can increase output immediately in response to a major outage and can reach full capacity within 10 minutes”; Wood and Wollenberg [7]: the total synchronised capacity, minus the losses and the load; Zhu, Jordan and Ihara [8]: “the unloaded section of synchronized that is able to respond immediately to serve load, and is fully available within ten minutes”; British Electricity International [1]: “the additional output which is part-loaded generating plant is able to supply and sustain within 5 minutes. This category also includes pumped- storage plant […] operating in the pumping mode, whose demand can be disconnected within 5 minutes”; UCTE [6]: tertiary reserve available within 15 minutes “that is provided chiefly by storage stations, pumped-storage stations, gas turbines and by thermal power stations operating at less than full output (responsibility of the TSO)”; NERC [3]: “Unloaded generation that is synchronized and ready to serve additional demand”. These definitions disagree (or remain silent) on some important issues: Who provides spinning reserve? Is it limited to generators or can the demand-side participate? What is the time frame for responding to a request? When should it start and end? How is this reserve activated? Does it happen automatically or is it only done at the request of the Transmission System Operator (TSO)? Therefore, it seems to be interesting to propose a definition which could fit any system. 3.2 A general definition In order to get a general definition of spinning reserve, it seems to be essential to remove the idea of time. In fact, each system has its particularities. However, in any system, there is a system operator. Therefore, this concept can be used within the proposed definition. Lastly, it seems to be interesting to get detached from the terms such as “generator” or “demand-side”, which can introduce more ambiguities. We therefore propose the following definition: the spinning reserve is the unused capacity which can be activated on decision of the system operator and which is provided by devices which are synchronized to the network and able to affect the active power. 3.3 Consequences of the spinning reserve definition Some important comments should be made on this definition: The beginning of the reserve deployment or the reserve deployment duration does not appear in the definition, as they are not relevant for a general definition of the spinning reserve. In fact, each country has its own definition (e.g. secondary control reserve has to The University of Manchester 7/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 8. What is spinning reserve? be fully available in 8 minutes in France and in 5 minutes in the USA [4]), depending on parameters such as the size of the synchronous network or the market structure; The primary control reserve, which is not controlled by the TSO, has to be excluded from the spinning reserve. Moreover, the self-regulating effect of the loads, which has an effect similar to the primary reserve, is also excluded from the spinning reserve. In fact, these two items are more important for network stability than for balancing consumption and production; Secondary control reserve should be considered as spinning reserve. In fact, the power deployed by the TSO through this reserve equilibrates the consumption and the production and has to be kept as long as required; Spinning reserve includes also synchronized tertiary control reserve, as this reserve is deployed on the instruction of the TSO; If a generator decides not to provide reserve, its spare synchronized capacity is not spinning reserve, as it cannot be activated by the system operator. However, in many systems, generators have to bid all their spare synchronized capacity in the balancing mechanism. Therefore, in this case, the system operator has the possibility to call all the synchronized capacity; A consumer can provide spinning reserve, if it agrees to be disconnected or to reduce its load upon request by the TSO. Pump loads are prime candidates for the provision of spinning reserve from the demand side. 3.4 Reserves and generator capacity Based on the previous discussion, the spinning reserve for a generating unit is represented in Figure 3.1. Maximum Unused capacity Primary control uses this capacity Primary control reserve Secondary control uses this capacity Secondary control reserve Tertiary control uses this capacity Synchronized tertiary control reserve Scheduled power Spinning reserve Energy Minimum 0 MW Figure 3.1: Representation of the spinning reserve of a generating unit that participates in all three levels of frequency control The University of Manchester 8/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 9. What is spinning reserve? 3.5 Amount of spinning reserve in different countries According to the definition given in Section 3.2 and [4], Table 3.1 lists how (positive) spinning reserve requirements are calculated in different systems. Table 3.1: Calculation of spinning reserve requirements in different systems Country Calculation of the amount of spinning reserve No specific recommendation. The recommended maximum is UCTE 10 Lmax zone + 150 2 − 150 Belgium UCTE rules. Currently at least 460 MW by generators. France UCTE rules. Currently at least 500 MW. The UCTE rules. Currently at least 300 MW. Netherlands Spain Between 3 Lmax and 6 Lmax California 50% × max(5% × Phydro + 7% × Pother generation ; Plargest contingency ) + Pnon − firm import PJM 1.1% of the peak + probabilistic calculation on typical days and hours Where: Lmax: the maximum load of the system during a given period; Lmax zone: the maximum load of the UCTE control area during a given period; Phydro: scheduled generation from hydroelectric resources; Pother generation: scheduled generation from resources other than hydroelectric; Plargest contingency: value of the power imbalance due to the most severe contingency; Pnon-firm import: total of all the interruptible imports. Lastly, negative spinning reserve was not taken in account in Table 3.1. However, it is essential for the stability of the network to be able to reduce the active power production in case of a high frequency. However, since most of the time reducing power production is easier than increasing it, this problem is not considered further. The University of Manchester 9/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 10. What is spinning reserve? 4 Summary This document proposes a definition of spinning reserve. The spinning reserve is the unused capacity which can be activated on decision of the system operator and which is provided by devices that are synchronized to the network and able to affect the active power. Therefore, spinning reserve corresponds to the UCTE secondary (automatic and central) and synchronized tertiary control reserves (manual and central). This definition can be applied in most power systems. Therefore, it may be used to compare the spinning reserve requirements in different jurisdictions. The University of Manchester 10/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005
  • 11. What is spinning reserve? Contact details If you have any suggestions, comments or questions regarding this document, please contact: Yann REBOURS The University of Manchester School of Electrical and Electronic Engineering PO Box 88 Manchester M60 1QD United Kingdom Tél. : +44 79 81 08 55 87 yann.rebours@postgrad.manchester.ac.uk References [1] British Electricity International, “Modern power station practice: incorporating modern power system practice”, Pergamon, 1991. [2] Eric Hirst and Brendan Kirby, Unbundling Generation and Transmission Services for Competitive Electricity Markets: Ancillary Services, NRRI-98-05, National Regulatory Research Institute, Columbus, OH, Jan. 1998; [3] NERC, "Operating manual", 15th of June 2004. [4] Y. Rebours and D. Kirschen, "A Survey of Definitions and Specifications of Reserve Services", Release 1, the University of Manchester, the 19th of September 2005. [5] UCTE, "UCTE Operation Handbook", v 2.5E, the 20th of July 2004. [6] UCTE, http://www.ucte.org/statistics/terms_power_balance/e_default_explanation.asp. [7] Allen J Wood and Bruce F Wollenberg, “Power Generation, Operation and Control,” 2nd edition, Wiley Interscience, 1996. [8] J. Zhu, G. Jordan, and S. Ihara, "The market for spinning reserve and its impacts on energy prices", proceedings of the IEEE Power Engineering Society Winter Meeting, 2000. The University of Manchester 11/11 Release 1 Yann Rebours, Daniel Kirschen 19/09/2005