ECINVERTERINVERTER
General
Datatech+ represents the state of the art as regards efficient, precise and
reliable cooling of Data Processing Centres, small and medium-sized com-
puter rooms, laboratories and technological environments in general.
The combination of inverter-controlled brushless DC compressors, EC
electronic switching fans and electronic thermostatic valves together with
a sophisticated control algorithm allows the highest performance to be
achieved as required for the air conditioning of technological equipment.
Quick facts
►► High sensible heat removal rate.
►► Exceptional efficiency at partial loads
►► Regulation of the compressor between 30 and
120% of the rated value.
►► Constancy and precision of control of thermo-
hygrometric variables.
►► Dual power supply available as option
►► Hot gas re-heat available
Precision air conditioners with inverter driven brushless DC compressor 7÷100 kW
Datatech +
Informazioni generali
Datatech+ rappresenta lo stato dell’arte per quanto riguarda il raffrescamento
efficiente, preciso e affidabile di Centri di Elaborazione Dati, piccole e medie
sale informatiche, laboratori, ambienti tecnologici in generale.
L’accoppiamento di compressori ad inverter brushless DC, ventilatori a com-
mutazione elettronica EC, valvole termostatiche elettroniche unitamente a un
sofisticato algoritmo di controllo permette di raggiungere il top delle prestazio-
ni richieste per il condizionamento delle apparecchiature tecnologiche.
Punti di forza
►► Elevata rimozione di calore sensibile.
►► Eccezionale efficienza ai carichi parziali
►► Regolazione del compressore tra il 30 e il 120% del
valore nominale.
►► Costanza e precisione di controllo delle variabili
termoigrometriche.
►► Opzione a doppia alimentazione elettrica disponibile
►► Post riscaldamento gas caldo disponibile
Condizionatori di precisione con compressori brushless DC comandati da inverter 7÷100 kW
43
www.blueboxgroup.com	 	      Blue Box reserves the right to alter specifications.
Image based on DATATECH + with ”led edition” accessory. Immagine riferita al DATATECH + con accessorio ”led edition”.
42
TECHNICAL DATA - DATATECH+ ED
DATI TECNICI - DATATECH+ ED
(1) Air inlet 24°C 50%rh. 45°C saturated condensing temperature;
(2) 20Pa available pressure, ISO Coarse 75% (G4) filters;
(3) Inlet air temperature 20 °C water in/out 80/70 °C.;
(4) 2 m front of the unit, air distribution through raised floor (UNDER) or ducted (OVER).;
(6) Weights referred to downflow (UNDER), water condensed, HH version units;
Gross cooling capacities indicated. For net cooling capacities, subtract fan power input..
This datasheet contains datas referred to the basic and standard version of the products; they could be
modified by the Constructor in any moment. For details please refer to the specific documentation.
No copy is allowed.
(1) Aria in ingresso 24°C 50% UR. Temperatura satura di condensazione 45°C;
(2) Prevalenza utile 20 Pa, filtri ISO Coarse 75% (G4);
(3) Temperatura aria ingresso 20 °C acqua in/out 80/70 °C;
(4) 2 m fronte unità, mandata aria sottopavimento (under) o canalizzata (over);
(6) Pesi riferiti alle versioni a flusso verso il basso (UNDER), condensate ad acqua, versione HH;
Le potenze frigorifere indicate sono lorde. Per la potenza netta, sottrarre la potenza assorbita dal ventilatore.
I valori presentati all’interno del documento sono indicativi e potranno essere modificati dal Costruttore
senza alcun obbligo di preavviso. Per qualunque ulteriore informazione si faccia riferimento alla specifica
documentazione. La riproduzione anche parziale è vietata.
Unit size_Grandezza unità 7.1 m 7.1 t 12.1 16.1 23.1 27.1 33.1 35.2
Cooling
Total cooling capacity_ Potenza frigorifera totale (1) kW 6,94 6,94 11,9 17,2 21,5 27,0 34,6 36,1
Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 6,67 6,67 11,7 15,0 20,5 25,0 31,0 35,0
EER (1),(2) 3,77 3,77 3,59 3,59 3,66 3,59 3,58 3,74
Fans_ Ventilatori
Nominal air capacity_ Portata aria nominale m3
/h 2000 2000 4.000 4.160 6.500 7.650 8000 11500
Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA)
Number_ Quantità n° 1 1 1 1 1 1 1 1
Model_Modello NHNM1135.5 NHNM1135.5 NHNM1145.2 NHNM1145.4 NHNM1245.2 NHNM1245.3 NHNM2335.3 NHNM2335.3
Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW)
Number_ Quantità n° 1 1 1 1 1 1 1 1
Model_Modello n° DGS501AS DGS501AS DGS501CS DGS502BS DGS502CS DGS503BS DGS504BS DGS504BS
Dimensions and weight of basic unit_ Dimensioni e pesi unità base
Cabinet size_ Grandezza struttura SXS SXS XS XS S S S M
Length_ Lunghezza mm 607 607 705 705 1.100 1.100 1.100 1750
Depth_ Profondità mm 500 500 650 650 850 850 850 850
Height_ Altezza mm 1850 1850 1.990 1.990 1.990 1.990 1.990 1990
Unit size_Grandezza unità 36.2 45.2 44.2 58.2 66.3 82.3 100.4
Cooling
Total cooling capacity_ Potenza frigorifera totale (1) kW 34,3 45,4 44,5 56,7 66,8 81,4 96,6
Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 34,1 43,0 42,6 52,3 63,2 76,1 87,1
EER (1),(2) 3,88 3,65 3,77 3,74 3,82 3,70 3,70
Fans_ Ventilatori
Nominal air capacity_ Portata aria nominale m3
/h 11500 13500 13500 14500 20000 23000 23000
Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA)
Number_ Quantità n° 2 1 2 2 2 2 2
Model_Modello NHNM1145.4 NHNM 2245.2 NHNM1245.2 NHNM1245.3
NHNM1245.2
+NHNM2245.2
NHNM1245.3
+NHNM2245.3
NHNM2245.2
Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW)
Number_ Quantità n° 1 1 1 1 1 1 1
Model_Modello n° DGS504BS DGS504CS DGS504CS DGS634CT DGS634CT BDMS802DT BDMS803BT
Dimensions and weight of basic unit_ Dimensioni e pesi unità base
Cabinet size_ Grandezza struttura M M M M L L L
Length_ Lunghezza mm 1750 1750 1750 1750 2650 2650 2650
Depth_ Profondità mm 850 850 850 850 850 850 850
Height_ Altezza mm 1990 1990 1990 1990 1990 1990 1990
50
TECHNICAL DATA - DATATECH+ ED DC
DATI TECNICI - DATATECH+ ED DC
(1) Air inlet 24°C 50%rh. 45°C saturated condensing temperature;
(2) Air inlet 24 °C 50% UR. water in/out 7/12 °C;
(3) 20Pa available pressure, ISO Coarse 75% (G4) filters;
(5) 2 m front of the unit, air distribution through raised floor (UNDER) or ducted (OVER);
(6) Weights referred to downflow (UNDER), water condensed, HH version units;
Gross cooling capacities indicated. For net cooling capacities, subtract fan power input.
This datasheet contains datas referred to the basic and standard version of the products; they could be
modified by the Constructor in any moment. For details please refer to the specific documentation.
No copy is allowed.
(1) Aria in ingresso 24°C 50% UR. Temperatura satura di condensazione 45°C;
(2) Aria ingresso 24 °C 50% UR. Acqua ingresso/uscita 7/12 °C;
(3) Prevalenza utile 20 Pa, filtri ISO Coarse 75% (G4);
(5) 2 m fronte unità, mandata aria sottopavimento (under) o canalizzata (over);
(6) Pesi riferiti alle versioni a flusso verso il basso (UNDER), condensate ad acqua, versione HH;
Le potenze frigorifere indicate sono lorde. Per la potenza netta, sottrarre la potenza assorbita dal ventilatore.
I valori presentati all’interno del documento sono indicativi e potranno essere modificati dal Costruttore
senza alcun obbligo di preavviso. Per qualunque ulteriore informazione si faccia riferimento alla specifica
documentazione. La riproduzione anche parziale è vietata.
Unit size_Grandezza unità 23.1 27.1 35.2 36.2 45.2
Cooling
Total cooling capacity_ Potenza frigorifera totale (1) kW 21,5 27,0 36,1 34,3 45,4
Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 20,5 25,0 35,0 34,1 43,0
EER (1),(3) 3,6 3,6 3,74 3,88 3,65
Total cooling capacity_ Potenza frigorifera totale (2) kW 23,3 25,6 40,4 40,4 52,7
Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 21,1 23,5 36,9 36,9 47,5
Fans_ Ventilatori
Nominal air capacity_ Portata aria nominale m3
/h 6.500 7.650 11500 11500 13500
Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA) (5)
Number_ Quantità n° 1 1 1 1 1
Model_Modello NHNM1245.2 NHNM1245.3 NHNM2335.3 NHNM1145.4 NHNM2245.2
Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) (5)
Number_ Quantità n° 1 1 1 1 1
Model_Modello DGS502CS DGS502CS DGS504BS DGS504BS DGS504CS
Dimensions and weight of basic unit_ Dimensioni e pesi unità base
Cabinet size_ Grandezza struttura S S M M M
Length_ Lunghezza mm 1.100 1.100 1750 1750 1750
Depth_ Profondità mm 850 850 850 850 850
Height_ Altezza mm 1.990 1.990 1990 1990 1990
Unit size_Grandezza unità 44.2 66.3 82.3
Cooling
Total cooling capacity_ Potenza frigorifera totale (1) kW 44,5 66,8 81,4
Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 42,6 63,2 76,1
EER (1),(3) 3,77 3,82 3,70
Total cooling capacity_ Potenza frigorifera totale (2) kW 52,7 88,2 96,7
Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 47,5 74,1 82,2
Fans_ Ventilatori
Nominal air capacity_ Portata aria nominale m3
/h 13500 20000 23000
Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA) (5)
Number_ Quantità n° 1 1 1
Model_Modello NHNM1245.2 NHNM1245.2 NHNM1245.3
Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) (5)
Number_ Quantità n° 1 1 1
Model_Modello DGS504CS DGS634CT BDMS802DT
Dimensions and weight of basic unit_ Dimensioni e pesi unità base
Cabinet size_ Grandezza struttura M L L
Length_ Lunghezza mm 1750 2650 2650
Depth_ Profondità mm 850 850 850
Height_ Altezza mm 1990 1990 1990
51
www.blueboxgroup.com	 	      Blue Box reserves the right to alter specifications.
TECHNICAL DATA - DATATECH+ EDW/FC
DATI TECNICI - DATATECH+ EDW/FC
(1) Air inlet 24°C 50% rh. Condenser water inlet/outlet 35/40°C with 30% ethylene glycol;
(2) Freecoling coil water inlet/outlet temperature 7/12°C with 30% ethylene glycol;
(3) 20Pa available pressure, ISO Coarse 75% (G4) filters;
(5) 2 m front of the unit, air distribution through raised floor (UNDER) or ducted (OVER);
(6) Weights referred to downflow (UNDER), water condensed, HH version units;
Gross cooling capacities indicated. For net cooling capacities, subtract fan power input.
This datasheet contains datas referred to the basic and standard version of the products; they could be
modified by the Constructor in any moment. For details please refer to the specific documentation.
No copy is allowed.
(1) Aria in ingresso 24°C 50% UR. Temperatura di ingresso/uscita acqua al condensatore 35/40°C con 30%
di glicole etilenico;
(2) Temperatura di ingresso/uscita acqua alla batteria free-cooling 7/12°C con 30% di glicole etilenico;
(3) Prevalenza utile 20 Pa, filtri ISO Coarse 75% (G4);
(5) 2 m fronte unità, mandata aria sottopavimento (under) o canalizzata (over);
(6) Pesi riferiti alle versioni a flusso verso il basso (UNDER), condensate ad acqua, versione HH;
Le potenze frigorifere indicate sono lorde. Per la potenza netta, sottrarre la potenza assorbita dal ventilatore.
I valori presentati all’interno del documento sono indicativi e potranno essere modificati dal Costruttore
senza alcun obbligo di preavviso. Per qualunque ulteriore informazione si faccia riferimento alla specifica
documentazione. La riproduzione anche parziale è vietata.
Unit size_Grandezza unità 23.1 27.1 35.2 36.2 45.2
Cooling
Total cooling capacity_ Potenza frigorifera totale (1) kW 21,2 26,7 35,7 33,9 44,8
Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 20,5 25,0 34,9 34 42,8
EER (1),(3) 3,59 3,51 3,50 3,61 3,33
Free-Cooling
Total cooling capacity_ Potenza frigorifera totale (2) kW 20,2 22,5 34,2 34,2 44,6
Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 18,3 20,6 32,1 32,1 41,3
SHR 0,91 0,92 0,94 0,94 0,93
Fans_ Ventilatori
Nominal air capacity_ Portata aria nominale m3
/h 6.500 7.650 11.500 11.500 13.500
Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) (5)
Number_ Quantità n° 1 1 1 1 1
Model_Modello DGS502CS DGS502CS DGS504BS DGS504BS DGS504CS
Dimensions and weight of basic unit_ Dimensioni e pesi unità base
Cabinet size_ Grandezza struttura S S M M M
Length_ Lunghezza mm 1.100 1.100 1750 1750 1750
Depth_ Profondità mm 850 850 850 850 850
Height_ Altezza mm 1.990 1.990 1990 1990 1990
Unit size_Grandezza unità 44.2 66.3 82.3
Cooling
Total cooling capacity_ Potenza frigorifera totale (1) kW 44 66 80,5
Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 42,5 63 75,9
EER (1),(3) 3,45 3,51 3,40
Free-Cooling
Total cooling capacity_ Potenza frigorifera totale (2) kW 44,6 74,6 81,8
Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 41,3 64,5 71,5
SHR 0,93 0,86 0,87
Fans_ Ventilatori
Nominal air capacity_ Portata aria nominale m3
/h 13.500 20.000 23.000
Matchingwithremotedrycoolers(EDWunits)_Accoppiamentoconraffreddatorid’acquaremotiRDC(unitàEDW) (5)
Number_ Quantità n° 1 1 1
Model_Modello DGS504CS DGS634CT BDMS802DT
Dimensions and weight of basic unit_ Dimensioni e pesi unità base
Cabinet size_ Grandezza struttura M L L
Length_ Lunghezza mm 1750 2650 2650
Depth_ Profondità mm 850 850 850
Height_ Altezza mm 1990 1990 1990
52

More Related Content

Similar to Datatech precision

Esperienze di climatizzazione
Esperienze di climatizzazioneEsperienze di climatizzazione
Esperienze di climatizzazioneDavide Truffo
 
Valvola di espansione elettronica su applicazioni in celle refrigerate
Valvola di espansione elettronica su applicazioni in celle refrigerateValvola di espansione elettronica su applicazioni in celle refrigerate
Valvola di espansione elettronica su applicazioni in celle refrigerateCAREL Industries S.p.A
 
Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...
Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...
Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...redazione_livinginterior
 
Incontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLD
Incontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLDIncontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLD
Incontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLDCentro Studi Galileo
 
Stazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plantsStazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plantsPegoraro Gas Technologies Srl
 
Stazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plantsStazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plantsPegoraro Gas Technologies Srl
 
Unicredit Bank office automation
Unicredit Bank office automationUnicredit Bank office automation
Unicredit Bank office automationAlex Cabella
 
Incontri Formativi 17 marzo 2016 - B. Lamanna - CAREL
Incontri Formativi 17 marzo 2016 - B. Lamanna - CARELIncontri Formativi 17 marzo 2016 - B. Lamanna - CAREL
Incontri Formativi 17 marzo 2016 - B. Lamanna - CARELCentro Studi Galileo
 
Catalogo 2013 climatizzatori senza unità esterna IRC
Catalogo 2013 climatizzatori senza unità esterna IRCCatalogo 2013 climatizzatori senza unità esterna IRC
Catalogo 2013 climatizzatori senza unità esterna IRCtermoidraulicarv
 
Depliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuro
Depliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuroDepliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuro
Depliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuroSeppelfricke SD
 
Двигатели QCA-SINCROVERT Oemer Motori
Двигатели QCA-SINCROVERT Oemer MotoriДвигатели QCA-SINCROVERT Oemer Motori
Двигатели QCA-SINCROVERT Oemer MotoriArve
 
NUOVA ANAGRAFE DEL COMUNE DI IMOLA
NUOVA ANAGRAFE DEL COMUNE DI IMOLANUOVA ANAGRAFE DEL COMUNE DI IMOLA
NUOVA ANAGRAFE DEL COMUNE DI IMOLAMarco Bondi
 
Intervento di Massimo Motta, TOSHIBA ITALIA
Intervento di Massimo Motta, TOSHIBA ITALIAIntervento di Massimo Motta, TOSHIBA ITALIA
Intervento di Massimo Motta, TOSHIBA ITALIAinfoprogetto
 
Intervento di Roberto Perego, VORTICE ELETTROSOCIALI SPA
Intervento di Roberto Perego, VORTICE ELETTROSOCIALI SPAIntervento di Roberto Perego, VORTICE ELETTROSOCIALI SPA
Intervento di Roberto Perego, VORTICE ELETTROSOCIALI SPAinfoprogetto
 
Presentazione Xstream
Presentazione XstreamPresentazione Xstream
Presentazione XstreamTrane Italia
 
Aspetti energetici nel sistema edificio-impianto
Aspetti energetici nel sistema  edificio-impiantoAspetti energetici nel sistema  edificio-impianto
Aspetti energetici nel sistema edificio-impiantoConsorzio Q-RAD
 
TECHNICAL DATASHEET FOTOTHERM SERIE AL
TECHNICAL DATASHEET FOTOTHERM SERIE ALTECHNICAL DATASHEET FOTOTHERM SERIE AL
TECHNICAL DATASHEET FOTOTHERM SERIE ALDaniele Palano
 
Presentazione CITY
Presentazione CITYPresentazione CITY
Presentazione CITYTrane Italia
 

Similar to Datatech precision (20)

Esperienze di climatizzazione
Esperienze di climatizzazioneEsperienze di climatizzazione
Esperienze di climatizzazione
 
Smart heating
Smart heatingSmart heating
Smart heating
 
Valvola di espansione elettronica su applicazioni in celle refrigerate
Valvola di espansione elettronica su applicazioni in celle refrigerateValvola di espansione elettronica su applicazioni in celle refrigerate
Valvola di espansione elettronica su applicazioni in celle refrigerate
 
Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...
Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...
Intervento Impianti - Marco Delle Curti, ingegnere, libero professionista, es...
 
Ga7 75 vsd+
Ga7 75 vsd+Ga7 75 vsd+
Ga7 75 vsd+
 
Incontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLD
Incontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLDIncontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLD
Incontri Formativi 17 marzo 2016 - L. Alinovi - FRASCOLD
 
Stazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plantsStazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plants
 
Stazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plantsStazione di trattamento Biogas - Biogas treatment plants
Stazione di trattamento Biogas - Biogas treatment plants
 
Unicredit Bank office automation
Unicredit Bank office automationUnicredit Bank office automation
Unicredit Bank office automation
 
Incontri Formativi 17 marzo 2016 - B. Lamanna - CAREL
Incontri Formativi 17 marzo 2016 - B. Lamanna - CARELIncontri Formativi 17 marzo 2016 - B. Lamanna - CAREL
Incontri Formativi 17 marzo 2016 - B. Lamanna - CAREL
 
Catalogo 2013 climatizzatori senza unità esterna IRC
Catalogo 2013 climatizzatori senza unità esterna IRCCatalogo 2013 climatizzatori senza unità esterna IRC
Catalogo 2013 climatizzatori senza unità esterna IRC
 
Depliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuro
Depliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuroDepliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuro
Depliant Pompe di Calore Seppelfricke SD ed.07.2013 - L'energia del futuro
 
Двигатели QCA-SINCROVERT Oemer Motori
Двигатели QCA-SINCROVERT Oemer MotoriДвигатели QCA-SINCROVERT Oemer Motori
Двигатели QCA-SINCROVERT Oemer Motori
 
NUOVA ANAGRAFE DEL COMUNE DI IMOLA
NUOVA ANAGRAFE DEL COMUNE DI IMOLANUOVA ANAGRAFE DEL COMUNE DI IMOLA
NUOVA ANAGRAFE DEL COMUNE DI IMOLA
 
Intervento di Massimo Motta, TOSHIBA ITALIA
Intervento di Massimo Motta, TOSHIBA ITALIAIntervento di Massimo Motta, TOSHIBA ITALIA
Intervento di Massimo Motta, TOSHIBA ITALIA
 
Intervento di Roberto Perego, VORTICE ELETTROSOCIALI SPA
Intervento di Roberto Perego, VORTICE ELETTROSOCIALI SPAIntervento di Roberto Perego, VORTICE ELETTROSOCIALI SPA
Intervento di Roberto Perego, VORTICE ELETTROSOCIALI SPA
 
Presentazione Xstream
Presentazione XstreamPresentazione Xstream
Presentazione Xstream
 
Aspetti energetici nel sistema edificio-impianto
Aspetti energetici nel sistema  edificio-impiantoAspetti energetici nel sistema  edificio-impianto
Aspetti energetici nel sistema edificio-impianto
 
TECHNICAL DATASHEET FOTOTHERM SERIE AL
TECHNICAL DATASHEET FOTOTHERM SERIE ALTECHNICAL DATASHEET FOTOTHERM SERIE AL
TECHNICAL DATASHEET FOTOTHERM SERIE AL
 
Presentazione CITY
Presentazione CITYPresentazione CITY
Presentazione CITY
 

Recently uploaded

GIORNATA TECNICA DA AQP 18/04 | ZONNO Serena
GIORNATA TECNICA DA AQP 18/04 | ZONNO SerenaGIORNATA TECNICA DA AQP 18/04 | ZONNO Serena
GIORNATA TECNICA DA AQP 18/04 | ZONNO SerenaServizi a rete
 
GIORNATA TECNICA 18/04 | DE ROSA Roberto
GIORNATA TECNICA 18/04 | DE ROSA RobertoGIORNATA TECNICA 18/04 | DE ROSA Roberto
GIORNATA TECNICA 18/04 | DE ROSA RobertoServizi a rete
 
GIORNATA TECNICA DA AQP 18/04 | MOTTA Simone
GIORNATA TECNICA DA AQP 18/04 | MOTTA SimoneGIORNATA TECNICA DA AQP 18/04 | MOTTA Simone
GIORNATA TECNICA DA AQP 18/04 | MOTTA SimoneServizi a rete
 
GIORNATA TECNICA 18/04 | DE LEO Antonio
GIORNATA TECNICA 18/04  | DE LEO AntonioGIORNATA TECNICA 18/04  | DE LEO Antonio
GIORNATA TECNICA 18/04 | DE LEO AntonioServizi a rete
 
GIORNATA TECNICA 18/04 | SPIZZIRRI Massimo
GIORNATA TECNICA 18/04 | SPIZZIRRI MassimoGIORNATA TECNICA 18/04 | SPIZZIRRI Massimo
GIORNATA TECNICA 18/04 | SPIZZIRRI MassimoServizi a rete
 
Presentzione Matematica similitudini circonferenze e omotetie.pptx
Presentzione  Matematica similitudini circonferenze e omotetie.pptxPresentzione  Matematica similitudini circonferenze e omotetie.pptx
Presentzione Matematica similitudini circonferenze e omotetie.pptxfilippoluciani9
 
Descrizione della struttura architettonica Eretteo.pptx
Descrizione della struttura architettonica Eretteo.pptxDescrizione della struttura architettonica Eretteo.pptx
Descrizione della struttura architettonica Eretteo.pptxtecongo2007
 
GIORNATA TECNICA 18/04 | BENANTI Alessandro
GIORNATA TECNICA 18/04 | BENANTI AlessandroGIORNATA TECNICA 18/04 | BENANTI Alessandro
GIORNATA TECNICA 18/04 | BENANTI AlessandroServizi a rete
 
GIORNATA TECNICA 18/04 | LITTERIO Raffaele
GIORNATA TECNICA 18/04 | LITTERIO RaffaeleGIORNATA TECNICA 18/04 | LITTERIO Raffaele
GIORNATA TECNICA 18/04 | LITTERIO RaffaeleServizi a rete
 

Recently uploaded (9)

GIORNATA TECNICA DA AQP 18/04 | ZONNO Serena
GIORNATA TECNICA DA AQP 18/04 | ZONNO SerenaGIORNATA TECNICA DA AQP 18/04 | ZONNO Serena
GIORNATA TECNICA DA AQP 18/04 | ZONNO Serena
 
GIORNATA TECNICA 18/04 | DE ROSA Roberto
GIORNATA TECNICA 18/04 | DE ROSA RobertoGIORNATA TECNICA 18/04 | DE ROSA Roberto
GIORNATA TECNICA 18/04 | DE ROSA Roberto
 
GIORNATA TECNICA DA AQP 18/04 | MOTTA Simone
GIORNATA TECNICA DA AQP 18/04 | MOTTA SimoneGIORNATA TECNICA DA AQP 18/04 | MOTTA Simone
GIORNATA TECNICA DA AQP 18/04 | MOTTA Simone
 
GIORNATA TECNICA 18/04 | DE LEO Antonio
GIORNATA TECNICA 18/04  | DE LEO AntonioGIORNATA TECNICA 18/04  | DE LEO Antonio
GIORNATA TECNICA 18/04 | DE LEO Antonio
 
GIORNATA TECNICA 18/04 | SPIZZIRRI Massimo
GIORNATA TECNICA 18/04 | SPIZZIRRI MassimoGIORNATA TECNICA 18/04 | SPIZZIRRI Massimo
GIORNATA TECNICA 18/04 | SPIZZIRRI Massimo
 
Presentzione Matematica similitudini circonferenze e omotetie.pptx
Presentzione  Matematica similitudini circonferenze e omotetie.pptxPresentzione  Matematica similitudini circonferenze e omotetie.pptx
Presentzione Matematica similitudini circonferenze e omotetie.pptx
 
Descrizione della struttura architettonica Eretteo.pptx
Descrizione della struttura architettonica Eretteo.pptxDescrizione della struttura architettonica Eretteo.pptx
Descrizione della struttura architettonica Eretteo.pptx
 
GIORNATA TECNICA 18/04 | BENANTI Alessandro
GIORNATA TECNICA 18/04 | BENANTI AlessandroGIORNATA TECNICA 18/04 | BENANTI Alessandro
GIORNATA TECNICA 18/04 | BENANTI Alessandro
 
GIORNATA TECNICA 18/04 | LITTERIO Raffaele
GIORNATA TECNICA 18/04 | LITTERIO RaffaeleGIORNATA TECNICA 18/04 | LITTERIO Raffaele
GIORNATA TECNICA 18/04 | LITTERIO Raffaele
 

Datatech precision

  • 1. ECINVERTERINVERTER General Datatech+ represents the state of the art as regards efficient, precise and reliable cooling of Data Processing Centres, small and medium-sized com- puter rooms, laboratories and technological environments in general. The combination of inverter-controlled brushless DC compressors, EC electronic switching fans and electronic thermostatic valves together with a sophisticated control algorithm allows the highest performance to be achieved as required for the air conditioning of technological equipment. Quick facts ►► High sensible heat removal rate. ►► Exceptional efficiency at partial loads ►► Regulation of the compressor between 30 and 120% of the rated value. ►► Constancy and precision of control of thermo- hygrometric variables. ►► Dual power supply available as option ►► Hot gas re-heat available Precision air conditioners with inverter driven brushless DC compressor 7÷100 kW Datatech + Informazioni generali Datatech+ rappresenta lo stato dell’arte per quanto riguarda il raffrescamento efficiente, preciso e affidabile di Centri di Elaborazione Dati, piccole e medie sale informatiche, laboratori, ambienti tecnologici in generale. L’accoppiamento di compressori ad inverter brushless DC, ventilatori a com- mutazione elettronica EC, valvole termostatiche elettroniche unitamente a un sofisticato algoritmo di controllo permette di raggiungere il top delle prestazio- ni richieste per il condizionamento delle apparecchiature tecnologiche. Punti di forza ►► Elevata rimozione di calore sensibile. ►► Eccezionale efficienza ai carichi parziali ►► Regolazione del compressore tra il 30 e il 120% del valore nominale. ►► Costanza e precisione di controllo delle variabili termoigrometriche. ►► Opzione a doppia alimentazione elettrica disponibile ►► Post riscaldamento gas caldo disponibile Condizionatori di precisione con compressori brushless DC comandati da inverter 7÷100 kW 43 www.blueboxgroup.com Blue Box reserves the right to alter specifications.
  • 2. Image based on DATATECH + with ”led edition” accessory. Immagine riferita al DATATECH + con accessorio ”led edition”. 42
  • 3. TECHNICAL DATA - DATATECH+ ED DATI TECNICI - DATATECH+ ED (1) Air inlet 24°C 50%rh. 45°C saturated condensing temperature; (2) 20Pa available pressure, ISO Coarse 75% (G4) filters; (3) Inlet air temperature 20 °C water in/out 80/70 °C.; (4) 2 m front of the unit, air distribution through raised floor (UNDER) or ducted (OVER).; (6) Weights referred to downflow (UNDER), water condensed, HH version units; Gross cooling capacities indicated. For net cooling capacities, subtract fan power input.. This datasheet contains datas referred to the basic and standard version of the products; they could be modified by the Constructor in any moment. For details please refer to the specific documentation. No copy is allowed. (1) Aria in ingresso 24°C 50% UR. Temperatura satura di condensazione 45°C; (2) Prevalenza utile 20 Pa, filtri ISO Coarse 75% (G4); (3) Temperatura aria ingresso 20 °C acqua in/out 80/70 °C; (4) 2 m fronte unità, mandata aria sottopavimento (under) o canalizzata (over); (6) Pesi riferiti alle versioni a flusso verso il basso (UNDER), condensate ad acqua, versione HH; Le potenze frigorifere indicate sono lorde. Per la potenza netta, sottrarre la potenza assorbita dal ventilatore. I valori presentati all’interno del documento sono indicativi e potranno essere modificati dal Costruttore senza alcun obbligo di preavviso. Per qualunque ulteriore informazione si faccia riferimento alla specifica documentazione. La riproduzione anche parziale è vietata. Unit size_Grandezza unità 7.1 m 7.1 t 12.1 16.1 23.1 27.1 33.1 35.2 Cooling Total cooling capacity_ Potenza frigorifera totale (1) kW 6,94 6,94 11,9 17,2 21,5 27,0 34,6 36,1 Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 6,67 6,67 11,7 15,0 20,5 25,0 31,0 35,0 EER (1),(2) 3,77 3,77 3,59 3,59 3,66 3,59 3,58 3,74 Fans_ Ventilatori Nominal air capacity_ Portata aria nominale m3 /h 2000 2000 4.000 4.160 6.500 7.650 8000 11500 Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA) Number_ Quantità n° 1 1 1 1 1 1 1 1 Model_Modello NHNM1135.5 NHNM1135.5 NHNM1145.2 NHNM1145.4 NHNM1245.2 NHNM1245.3 NHNM2335.3 NHNM2335.3 Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) Number_ Quantità n° 1 1 1 1 1 1 1 1 Model_Modello n° DGS501AS DGS501AS DGS501CS DGS502BS DGS502CS DGS503BS DGS504BS DGS504BS Dimensions and weight of basic unit_ Dimensioni e pesi unità base Cabinet size_ Grandezza struttura SXS SXS XS XS S S S M Length_ Lunghezza mm 607 607 705 705 1.100 1.100 1.100 1750 Depth_ Profondità mm 500 500 650 650 850 850 850 850 Height_ Altezza mm 1850 1850 1.990 1.990 1.990 1.990 1.990 1990 Unit size_Grandezza unità 36.2 45.2 44.2 58.2 66.3 82.3 100.4 Cooling Total cooling capacity_ Potenza frigorifera totale (1) kW 34,3 45,4 44,5 56,7 66,8 81,4 96,6 Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 34,1 43,0 42,6 52,3 63,2 76,1 87,1 EER (1),(2) 3,88 3,65 3,77 3,74 3,82 3,70 3,70 Fans_ Ventilatori Nominal air capacity_ Portata aria nominale m3 /h 11500 13500 13500 14500 20000 23000 23000 Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA) Number_ Quantità n° 2 1 2 2 2 2 2 Model_Modello NHNM1145.4 NHNM 2245.2 NHNM1245.2 NHNM1245.3 NHNM1245.2 +NHNM2245.2 NHNM1245.3 +NHNM2245.3 NHNM2245.2 Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) Number_ Quantità n° 1 1 1 1 1 1 1 Model_Modello n° DGS504BS DGS504CS DGS504CS DGS634CT DGS634CT BDMS802DT BDMS803BT Dimensions and weight of basic unit_ Dimensioni e pesi unità base Cabinet size_ Grandezza struttura M M M M L L L Length_ Lunghezza mm 1750 1750 1750 1750 2650 2650 2650 Depth_ Profondità mm 850 850 850 850 850 850 850 Height_ Altezza mm 1990 1990 1990 1990 1990 1990 1990 50
  • 4. TECHNICAL DATA - DATATECH+ ED DC DATI TECNICI - DATATECH+ ED DC (1) Air inlet 24°C 50%rh. 45°C saturated condensing temperature; (2) Air inlet 24 °C 50% UR. water in/out 7/12 °C; (3) 20Pa available pressure, ISO Coarse 75% (G4) filters; (5) 2 m front of the unit, air distribution through raised floor (UNDER) or ducted (OVER); (6) Weights referred to downflow (UNDER), water condensed, HH version units; Gross cooling capacities indicated. For net cooling capacities, subtract fan power input. This datasheet contains datas referred to the basic and standard version of the products; they could be modified by the Constructor in any moment. For details please refer to the specific documentation. No copy is allowed. (1) Aria in ingresso 24°C 50% UR. Temperatura satura di condensazione 45°C; (2) Aria ingresso 24 °C 50% UR. Acqua ingresso/uscita 7/12 °C; (3) Prevalenza utile 20 Pa, filtri ISO Coarse 75% (G4); (5) 2 m fronte unità, mandata aria sottopavimento (under) o canalizzata (over); (6) Pesi riferiti alle versioni a flusso verso il basso (UNDER), condensate ad acqua, versione HH; Le potenze frigorifere indicate sono lorde. Per la potenza netta, sottrarre la potenza assorbita dal ventilatore. I valori presentati all’interno del documento sono indicativi e potranno essere modificati dal Costruttore senza alcun obbligo di preavviso. Per qualunque ulteriore informazione si faccia riferimento alla specifica documentazione. La riproduzione anche parziale è vietata. Unit size_Grandezza unità 23.1 27.1 35.2 36.2 45.2 Cooling Total cooling capacity_ Potenza frigorifera totale (1) kW 21,5 27,0 36,1 34,3 45,4 Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 20,5 25,0 35,0 34,1 43,0 EER (1),(3) 3,6 3,6 3,74 3,88 3,65 Total cooling capacity_ Potenza frigorifera totale (2) kW 23,3 25,6 40,4 40,4 52,7 Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 21,1 23,5 36,9 36,9 47,5 Fans_ Ventilatori Nominal air capacity_ Portata aria nominale m3 /h 6.500 7.650 11500 11500 13500 Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA) (5) Number_ Quantità n° 1 1 1 1 1 Model_Modello NHNM1245.2 NHNM1245.3 NHNM2335.3 NHNM1145.4 NHNM2245.2 Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) (5) Number_ Quantità n° 1 1 1 1 1 Model_Modello DGS502CS DGS502CS DGS504BS DGS504BS DGS504CS Dimensions and weight of basic unit_ Dimensioni e pesi unità base Cabinet size_ Grandezza struttura S S M M M Length_ Lunghezza mm 1.100 1.100 1750 1750 1750 Depth_ Profondità mm 850 850 850 850 850 Height_ Altezza mm 1.990 1.990 1990 1990 1990 Unit size_Grandezza unità 44.2 66.3 82.3 Cooling Total cooling capacity_ Potenza frigorifera totale (1) kW 44,5 66,8 81,4 Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 42,6 63,2 76,1 EER (1),(3) 3,77 3,82 3,70 Total cooling capacity_ Potenza frigorifera totale (2) kW 52,7 88,2 96,7 Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 47,5 74,1 82,2 Fans_ Ventilatori Nominal air capacity_ Portata aria nominale m3 /h 13500 20000 23000 Matching with remote condensers (EDA units)_ Accoppiamento con condensatori remoti (unità EDA) (5) Number_ Quantità n° 1 1 1 Model_Modello NHNM1245.2 NHNM1245.2 NHNM1245.3 Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) (5) Number_ Quantità n° 1 1 1 Model_Modello DGS504CS DGS634CT BDMS802DT Dimensions and weight of basic unit_ Dimensioni e pesi unità base Cabinet size_ Grandezza struttura M L L Length_ Lunghezza mm 1750 2650 2650 Depth_ Profondità mm 850 850 850 Height_ Altezza mm 1990 1990 1990 51 www.blueboxgroup.com Blue Box reserves the right to alter specifications.
  • 5. TECHNICAL DATA - DATATECH+ EDW/FC DATI TECNICI - DATATECH+ EDW/FC (1) Air inlet 24°C 50% rh. Condenser water inlet/outlet 35/40°C with 30% ethylene glycol; (2) Freecoling coil water inlet/outlet temperature 7/12°C with 30% ethylene glycol; (3) 20Pa available pressure, ISO Coarse 75% (G4) filters; (5) 2 m front of the unit, air distribution through raised floor (UNDER) or ducted (OVER); (6) Weights referred to downflow (UNDER), water condensed, HH version units; Gross cooling capacities indicated. For net cooling capacities, subtract fan power input. This datasheet contains datas referred to the basic and standard version of the products; they could be modified by the Constructor in any moment. For details please refer to the specific documentation. No copy is allowed. (1) Aria in ingresso 24°C 50% UR. Temperatura di ingresso/uscita acqua al condensatore 35/40°C con 30% di glicole etilenico; (2) Temperatura di ingresso/uscita acqua alla batteria free-cooling 7/12°C con 30% di glicole etilenico; (3) Prevalenza utile 20 Pa, filtri ISO Coarse 75% (G4); (5) 2 m fronte unità, mandata aria sottopavimento (under) o canalizzata (over); (6) Pesi riferiti alle versioni a flusso verso il basso (UNDER), condensate ad acqua, versione HH; Le potenze frigorifere indicate sono lorde. Per la potenza netta, sottrarre la potenza assorbita dal ventilatore. I valori presentati all’interno del documento sono indicativi e potranno essere modificati dal Costruttore senza alcun obbligo di preavviso. Per qualunque ulteriore informazione si faccia riferimento alla specifica documentazione. La riproduzione anche parziale è vietata. Unit size_Grandezza unità 23.1 27.1 35.2 36.2 45.2 Cooling Total cooling capacity_ Potenza frigorifera totale (1) kW 21,2 26,7 35,7 33,9 44,8 Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 20,5 25,0 34,9 34 42,8 EER (1),(3) 3,59 3,51 3,50 3,61 3,33 Free-Cooling Total cooling capacity_ Potenza frigorifera totale (2) kW 20,2 22,5 34,2 34,2 44,6 Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 18,3 20,6 32,1 32,1 41,3 SHR 0,91 0,92 0,94 0,94 0,93 Fans_ Ventilatori Nominal air capacity_ Portata aria nominale m3 /h 6.500 7.650 11.500 11.500 13.500 Matching with remote drycoolers (EDW units)_ Accoppiamento con raffreddatori d’acqua remoti RDC (unità EDW) (5) Number_ Quantità n° 1 1 1 1 1 Model_Modello DGS502CS DGS502CS DGS504BS DGS504BS DGS504CS Dimensions and weight of basic unit_ Dimensioni e pesi unità base Cabinet size_ Grandezza struttura S S M M M Length_ Lunghezza mm 1.100 1.100 1750 1750 1750 Depth_ Profondità mm 850 850 850 850 850 Height_ Altezza mm 1.990 1.990 1990 1990 1990 Unit size_Grandezza unità 44.2 66.3 82.3 Cooling Total cooling capacity_ Potenza frigorifera totale (1) kW 44 66 80,5 Sensible cooling capacity_ Potenza frigorifera sensibile (1) kW 42,5 63 75,9 EER (1),(3) 3,45 3,51 3,40 Free-Cooling Total cooling capacity_ Potenza frigorifera totale (2) kW 44,6 74,6 81,8 Sensible cooling capacity_ Potenza frigorifera sensibile (2) kW 41,3 64,5 71,5 SHR 0,93 0,86 0,87 Fans_ Ventilatori Nominal air capacity_ Portata aria nominale m3 /h 13.500 20.000 23.000 Matchingwithremotedrycoolers(EDWunits)_Accoppiamentoconraffreddatorid’acquaremotiRDC(unitàEDW) (5) Number_ Quantità n° 1 1 1 Model_Modello DGS504CS DGS634CT BDMS802DT Dimensions and weight of basic unit_ Dimensioni e pesi unità base Cabinet size_ Grandezza struttura M L L Length_ Lunghezza mm 1750 2650 2650 Depth_ Profondità mm 850 850 850 Height_ Altezza mm 1990 1990 1990 52