SECTION 10
Analog Input/Output Option Board
This section describes how to use Analog Input/Output Option Board.
10-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 506
10-2 Part Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 506
10-3 Installation and Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
10-3-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
10-3-2 Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
10-3-3 Removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
10-4 Memory Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508
10-4-1 CIO Area Allocation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508
10-4-2 Auxiliary Area Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508
10-5 Analog Input Option Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 509
10-6 Analog Output Option Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512
10-7 Analog I/O Option Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516
10-8 Startup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520
10-9 Trouble Shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521
10-10 The Use of Analog Option Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521
10-10-1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521
10-10-2 Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522
506
General Specifications Section 10-1
10-1 General Specifications
CP1 series analog option board units are non-isolated analog units which
allow you to easily realize analog input/output function for CP1L-EL/EM series
PLC.
10-2 Part Names
Note Two COM are connected in inner circuit.
LED pattern
Analog Option Board Voltage Input
0V~10V
(Resolution:1/4000)
Current Input
0mA~20mA
(Resolution:1/2000)
Voltage Output
0V~10V
(Resolution:1/4000)
Analog I/O Option Board CP1W-MAB221 2CH 2CH
Analog Input Option Board CP1W-ADB21 2CH ---
Analog Output Option Board CP1W-DAB21V --- 2CH
Analog I/O terminal
Error LED (red)
Terminal Arrangement for CP1W-ADB21
Terminal Arrangement for CP1W-DAB21V
Terminal Arrangement for CP1W-MAB221
II1 VI2 COMII2 COM
VO1 VO2 COM
VI1 II1 VI2 II2 COM
VO2VO1VI1
LED Color Description Status Remark
ERR Red Fault condition indicator
Flash
A communication error with CPU unit has occurred
at the unit.
Lit Other errors except the communication error.
Not lit Operation is normal.
507
Installation and Setting Section 10-3
10-3 Installation and Setting
10-3-1 Installation
The following processing explains how to install and remove an Analog Option
Board.
!Caution Always turn OFF the power supply to the CPU unit and wait until all the oper-
ation indicators go out before installing or removing the analog option board.
Not doing so may result in an unexpected operation.
1,2,3... 1. Press the up/down lock-levers on both sides of the Option Board slot cover
at the same time to unlock the cover, and then pull the cover out.
2. Check the alignment to make the corner cut of the Analog Option Board fit
in the Option Board slot, and firmly press the Analog Option Board in until
it snaps into place.
10-3-2 Setting
To use the analog option board on CP1L-EL/EM series PLC, firstly, it is neces-
sary to set the serial communication settings of the CPU Unit in one of the fol-
lowing two ways.
Method1: Set by Dipswitch on PLC unit.
For CPU Units with 30 and 40 points, switch DipSW4 of the CPU unit to ON, if
the Analog Option Board is mounted on the Option Board slot 1 (left side).
Switch DipSW5 of the CPU unit to ON, if the Analog Option Board is mounted
on the Option Board slot 2 (right side).
For CPU Units with 20 I/O points, switch DipSW4 of the CPU unit to ON.
Note DipSW4 and DipSW5 are OFF at shipment.
Method2: Set the option port communication parameters by PLC settings.
If DipSW4 or DipSW5 is OFF, the relative option port's communication param-
eters can also be set by PLC settings in CX-Programmer.
Please set the baud rate of the relative option port at 115200bps in Toolbus
mode.
10-3-3 Removing
Always turn OFF the power supply to the CPU unit and wait until all the oper-
ation indicators go out.
Press the up/down lock-levers on both sides of the Analog Option Board at
the same time to unlock the Option Board, and then pull it out.
00NC 02 04 06 08 10 00 02 04 06 08 10
01COM 03 05 07 09 11 01 03 05 07 09 11
BKUP
ERR/ALM
LNK/ACT
POWER
RUN
INH
1 2
00 01 02 03 04 06 00 01 03 04 06
COM 02 COM 05 07COMCOM(V+) 05 07
MAC Address:
01234567890A
ANALOG INPUT
V1+ V2+ COM
ON
1 2 3 4 5 6
DipSW4 DipSW5
508
Memory Allocation Section 10-4
10-4 Memory Allocation
10-4-1 CIO Area Allocation
The memory allocation about analog conversion in the CIO area of PLC is
shown as the following diagram.
The beginning CIO channel is shown in the following table.
CP1L-EL/EM series PLC
The details of allocated CIO channels are described in the following table.
10-4-2 Auxiliary Area Allocation
Analog Option Unit Status
Area
Option board status area: A435 (initial value “0000H”)
Note A435.14 or A435.15 sets on if analog option board already worked normally.
Then user can read A/D input data and write D/A output data.
Output off bit: AR500.15
Note This bit will also affect other PLC output channels. Please refer to Appendix D
Auxiliary Area Allocations by Address for more information.
I/O Capacity Option Port Beginning
Channel (m)
Channel Range
20 Port 1 CIO2990 CIO2990 ~ CIO2999
30/40
Port 1 (Left) CIO2980 CIO2980 ~ CIO2989
Port 2 (Right) CIO2990 CIO2990 ~ CIO2999
Channel Contents
CP1W-ADB21 CP1W-DAB21V CP1W-MAB221
m Analog Input 1 --- Analog Input 1
m+1 Analog input 2 --- Analog input 2
m+2 to m+4 --- --- ---
m+5 --- Analog Output 1 Analog Output 1
m+6 --- Analog Output 2 Analog Output 2
m+7 to m+9 --- --- ---
I/O Capacity AR Bits Option Port Content Error Process
20 A435.15 Port 1 I/O option
board run
state
0: Initial state or unit
abnormity state
1: work normally
30/40 A435.14 Port 1 (Left)
A435.15 Port 2 (Right)
AR Bits Content Error Process
A500.15 Output Off Bit
0: output effective
1: analog option board DA output clear
509
Analog Input Option Board Section 10-5
10-5 Analog Input Option Board
Each CP1W-ADB21 Analog Input Option Board provides two analog inputs.
• The analog input signal ranges are 0 to 10 V (with a resolution 1/4,000)
and 0 to 20 mA (with a resolution 1/2,000).
Main Analog Input Option Board Specifications
Analog Input Signal
Ranges
Analog input data is digitally converted according to the input signal range as
shown below.
Note When the input exceeds the specified range, the A/D conversion data will be
fixed at either the lower limit or upper limit.
■ 0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 0FA0 (0
to 4000). The entire data range is 0000 to 0FFF (0 to 4095).
Item Specifications
Voltage Input Current Input
Input signal range 0 V to 10 V 0 mA to 20 mA
Max. rated input 0 V to 15 V 0 mA to 30 mA
External input impedance 200 kΩ min. Approx. 250 Ω
Resolution 1/4000 (full scale) 1/2000 (full scale)
Overall accuracy
25°C: ±0.5% (full scale)
0 to 55°C: ±1.0% (full scale)
25°C: ±0.6% (full scale)
0 to 55°C: ±1.2% (full scale)
A/D conversion data 0000 to 0FA0 hex 0000 to 07D0 hex
Averaging function Not supported
Conversion time
Inner sample time 2ms/point
Refresh time > 6ms basing on baud rate and PLC cycle time
Isolation method None
Current consumption 5 VDC: 20 mA max.
Converted Data
Hexadecimal (Decimal)
10V 10.24V
0FA0(4000)
0FFF(4095)
0000(0)
0V
510
Analog Input Option Board Section 10-5
■ 0 to 20 mA
The 0 to 20 mA range corresponds to the hexadecimal values 0000 to 07D0
(0 to 2000). The possible data range is 0000 to 0FFF (0 to 4095). But it is
strongly suggested that the input current must not exceed 30 mA.
Analog Input Terminal
Arrangement
Note When using current inputs, voltage input terminals must be short-circuited
with current input terminals.
Wiring
Internal Circuits
Converted Data
Hexadecimal (Decimal)
0mA 20mA
07D0(2000)
0000(0)
VI1 Voltage Input 1
Current Input 1
Voltage Input 2
Current Input 2
II1
VI2
II2
COM Input Common
Analog input 2
Analog ground
I I 1
V I 1
COM (−)
I I 2
V I 2
56 kΩ 250 Ω
250 Ω
180 kΩ
180 kΩ
Internalcircuits
Analog input 1
toto
56 kΩ
511
Analog Input Option Board Section 10-5
Applicable Cables and
Terminal Wiring
■ Applicable Cables
Solid wire or ferrules can be used.
• Recommended solid wire
• Recommended ferrules
Note Do not connect bare stranded wires directly to terminals.
■ Terminal Wiring
When wiring the analog I/O terminal block, treat either solid or stranded wires
directly.
• To make the connection, press the release button in with a small flat blade
screwdriver and push the line in while the lock is released. Remove the
screwdriver and lock it inside.
• To disconnect the wiring, press the release button in with a small flat
blade screwdriver and pull the line out while the lock is released.
Note (1) Ferrules with/without plastic sleeve cannot be used.
(2) When using stranded wire, twist the core so that the barbed wires cannot
protrude.
(3) Do not solder-plate the end of cable.
The screwdriver shown below is recommended for wiring.
Wire type Wire size
Solid Wire 0.2mm2
to 0.5mm2
(AWG24 to AWG20)
Manufacturer Model Applicable wire
Phoenix Contact AI-0.5-10 0.5mm2 (AWG20)
Release button
2-conductor shielded
twisted-pair cable
Model Manufacturer
SZS 0.42.5 Phoenix Contact
0.4mm
Side Front
2.5mm
512
Analog Output Option Board Section 10-6
Wiring for Analog Inputs To prevent noise, 2-core shielded twisted-pair cable should be used. And the
shield can be connected to the FG terminal if necessary.
Note (1) If necessary, connect the shield to the FG terminal to prevent noise.
(2) When an input is not being used, short the + and – terminals.
(3) Separate wiring from power lines (AC power supply lines, high-voltage
lines, etc.)
(4) When there is noise in the power supply line, install a noise filter on the
input section and the power supply.
!Caution When connecting the analog option board to an outside analog device, either
ground the 0 V side of the PLC’s external power supply or do not ground the
PLC’s external power supply at all. Otherwise the PLC’s external power sup-
ply may be shorted depending on the connection methods of the outside ana-
log device. DO NOT ground the 24 V side of the PLC's external power supply,
as shown in the following diagram.
10-6 Analog Output Option Board
Each CP1W-DAB21V Analog Output Option Board provides two analog outputs.
• The analog output signal range is 0 to 10 V (with a resolution 1/4,000).
Main Analog Output Option Board Specifications
V IN
COM
I IN
V IN
COM
I IN
Analog
device with
voltage
output
Analog
Input
Option
Board
+
−
+
−
Analog
device with
current
output
Analog
Input
Option
Board
2-core shielded
twisted-pair cable
2-core shielded
twisted-pair cable
FG FG
24 V
0 V 0 V
Non-insulated DC power supply
0 V
Analog Device FGFG FG
Twisted-pair
cable
FG
CPU Unit + Analog Option Board
Item Specifications
Voltage Output Current Output
Output signal range 0 V to 10 V ---
External output allowable load resistance 2 kΩ min. ---
External output impedance 0.5 Ω max. ---
Resolution 1/4,000 (full scale) ---
Overall accuracy 25°C: ±0.5% 0 to 55°C: ±1.0% ---
D/A conversion data 0000 to 0FA0 hex ---
Conversion time
Inner conversion time 2ms/point
Refresh time  6ms basing on baud rate and PLC cycle time
Isolation method None
Current consumption 5 VDC: 60 mA max.
513
Analog Output Option Board Section 10-6
Analog Output Signal
Ranges
The analog values depend on the output signal range, as shown in the follow-
ing diagram.
Note When the output exceeds the specified range, the output signal will be fixed at
either the lower limit or upper limit.
■ 0 to 10 V
The hexadecimal values 0000 to 0FA0 (0 to 4000) correspond to an analog
voltage range of 0 to 10 V. The entire output range is 10 to 10.24 V.
Analog Output Terminal
Arrangement
Wiring
Internal Circuits
0V
10V
0FA0
FFFF
0FFF
(4000) (4095)
0000(0)
Converted Data
Hexadecimal
(Decimal)
10.24V
VO1 Voltage Output 1
VO2 Voltage Output 2
COM Output Common
Analog output 1
Analog ground
V O 1
COM(−)
V O 2
Analog output 2
toto
Internalcircuits
514
Analog Output Option Board Section 10-6
Applicable Cables and
Terminal Wiring
■ Applicable Cables
Solid wire or ferrules can be used.
• Recommended solid wire
• Recommended ferrules
Note Do not connect bare stranded wires directly to terminals.
■ Terminal Wiring
When wiring the analog I/O terminal block, treat either solid or stranded wires
directly.
• To make the connection, press the release button in with a small flat blade
screwdriver and push the line in while the lock is released. Remove the
screwdriver and lock it inside.
• To disconnect the wiring, press the release button in with a small flat
blade screwdriver and pull the line out while the lock is released.
Note (1) Ferrules with/without plastic sleeve cannot be used.
(2) When using stranded wire, twist the core so that the barbed wires cannot
protrude.
(3) Do not solder-plate the end of cable.
The screwdriver shown below is recommended for wiring.
Wire type Wire size
Solid Wire 0.2mm2
to 0.5mm2
(AWG24 to AWG20)
Manufacturer Model Applicable wire
Phoenix Contact AI-0.5-10 0.5mm2 (AWG20)
Release button
2-conductor shielded
twisted-pair cable
Model Manufacturer
SZS 0.42.5 Phoenix Contact
0.4mm
Side Front
2.5mm
515
Analog Output Option Board Section 10-6
Wiring for Analog Outputs To prevent noise, 2-core shielded twisted-pair cable should be used. And the
shield can be connected to the FG terminal if necessary.
Note (1) If necessary, connect the shield to the FG terminal to prevent noise.
(2) Separate wiring from power lines (AC power supply lines, high-voltage
lines, etc.)
(3) When there is noise in the power supply line, install a noise filter on the
input section and the power supply.
(4) When external power is supplied, or when the power is interrupted, there
may be a pulse status analog output of up to 1 ms. If this status is a prob-
lem, take the following measures.
• Turn ON the power to the CP1L-EL/EM CPU Unit, check the operation
status, and then turn ON the power at the load.
• Turn OFF the power to the load and then turn OFF the power to the
CP1L-EL/EM CPU Unit.
!Caution When connecting the analog option board to an outside analog device, either
ground the 0 V side of the PLC’s external power supply or do not ground the
PLC’s external power supply at all. Otherwise the PLC’s external power sup-
ply may be shorted depending on the connection methods of the outside ana-
log device. DO NOT ground the 24 V side of the PLC’s external power supply,
as shown in the following diagram.
COM
V OUT
Analog
output
option
board
Analog
device with
voltage
input
FG
2-core shielded
twisted-pair cable
+
−
24 V
0 V 0 V
Non-insulated DC power supply
0 V
Analog Device FGFG FG
Twisted-pair
cable
FG
CPU Unit + Analog Option Board
516
Analog I/O Option Board Section 10-7
10-7 Analog I/O Option Board
Each CP1W-MAB221 Analog I/O Option Board provides two analog inputs
and two analog outputs.
• The analog input signal ranges are 0 to 10 V (with a resolution 1/4,000)
and 0 to 20 mA (with a resolution 1/2,000).
• The analog output signal ranges are 0 to 10 V (with a resolution 1/4,000).
Main Analog I/O Option Board Specifications
Analog I/O Signal
Ranges
The analog values depend on the I/O signal ranges, as shown in the following
diagrams.
Note When the input exceeds the specified range, the A/D conversion data will be
fixed at either the lower limit or upper limit.
When the output exceeds the specified range, the output signal will be fixed at
either the lower limit or upper limit.
Analog Input Signal
Ranges
■ 0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 0FA0 (0
to 4000). The entire data range is 0000 to 0FFF (0 to 4095).
Item Specifications
Voltage I/O Current I/O
Analog Input Section
Input signal range 0 V to 10 V 0 mA to 20 mA
Max. rated input 0 V to 15 V 0 mA to 30 mA
External input impedance 200 kΩ min. Approx. 250 Ω
Resolution 1/4,000 (full scale) 1/2,000 (full scale)
Overall accuracy
25°C: ±0.5% (full scale)
0 to 55°C: ±1.0% (full scale)
25°C: ±0.6% (full scale)
0 to 55°C: ±1.2% (full scale)
A/D conversion data 0000 to 0FA0 hex 0000 to 07D0 hex
Averaging function Not supported
Analog Output Section
Output signal range 0 V to 10 V ---
External output allowable
load resistance
2 kΩ min. ---
External output impedance 0.5 Ω max. ---
Resolution 1/4,000 (full scale) ---
Overall accuracy 25°C: ±0.5% 0 to 55°C: ±1.0% ---
D/A conversion data 0000 to 0FA0 hex ---
Conversion time
Inner conversion time 6ms (4CH total)
Refresh time  6ms basing on baud rate and PLC cycle time
Isolation method None
Current consumption 5 VDC: 80 mA max.
517
Analog I/O Option Board Section 10-7
■ 0 to 20 mA
The 0 to 20 mA range corresponds to the hexadecimal values 0000 to 07D0
(0 to 2000). The possible data range is 0000 to 0FFF (0 to 4095). But it is
strongly suggested that the input current mustn’t exceed 30 mA.
Analog Input Signal
Ranges
■ 0 to 10 V
The hexadecimal values 0000 to 0FA0 (0 to 4000) correspond to an analog
voltage range of 0 to 10 V. The entire output range is 10 to 10.24 V.
Converted Data
Hexadecimal (Decimal)
10V 10.24V
0FA0(4000)
0FFF(4095)
0000(0)
0V
Converted Data
Hexadecimal (Decimal)
0mA 20mA
07D0(2000)
0000(0)
0V
10V
0FA0
FFFF
0FFF
(4000) (4095)
0000(0)
Converted Data
Hexadecimal
(Decimal)
10.24V
518
Analog I/O Option Board Section 10-7
Analog I/O Terminal
Arrangement
Note When using current inputs, voltage input terminals must be short-circuited
with current input terminals.
Wiring
Internal Circuits
Applicable Cables and
Terminal Wiring
■ Applicable Cables
Solid wire or ferrules can be used.
• Recommended solid wire
• Recommended ferrules
Note Do not connect bare stranded wires directly to terminals.
■ Terminal Wiring
When wiring the analog I/O terminal block, treat either solid or stranded wires
directly.
VI1 Voltage Input 1
II1 Current Input 1
VI2 Voltage Input 2
II2 Current Input 2
COM Analog I/O Common
VO1 Voltage Output 1
VO2 Voltage Output 2
COM Analog I/O Common
Analog input Analog output
Analog input 2
Analog ground
I I 1
V I 1
COM(−)
I I 2
V I 2
56 kΩ 250 Ω
250 Ω
180 kΩ
180 kΩ
Internalcircuits
Analog input 1
to
56 kΩ
Analog output 1
Analog ground
V O 1
COM(−)
V O 2
Analog output 2
toto
to
Internalcircuits
Wire type Wire size
Solid Wire 0.2mm2
to 0.5mm2
(AWG24 to AWG20)
Manufacturer Model Applicable wire
Phoenix Contact AI-0.5-10 0.5mm2 (AWG20)
519
Analog I/O Option Board Section 10-7
• To make the connection, press the release button in with a small flat blade
screwdriver and push the line in while the lock is released. Remove the
screwdriver and lock it inside.
• To disconnect the wiring, press the release button in with a small flat
blade screwdriver and pull the line out while the lock is released.
Note (1) Ferrules with/without plastic sleeve cannot be used.
(2) When using stranded wire, twist the core so that the barbed wires cannot
protrude.
(3) Do not solder-plate the end of cable.
The screwdriver shown below is recommended for wiring.
Wiring for Analog I/O To prevent noise, 2-core shielded twisted-pair cable should be used. And the
shield can be connected to the FG terminal if necesssary.
Wiring for Analog Inputs
Release button
2-conductor shielded
twisted-pair cable
Model Manufacturer
SZS 0.42.5 Phoenix Contact
0.4mm
Side Front
2.5mm
V IN
COM
I IN
V IN
COM
I IN
Analog
device with
voltage
output
Analog
I/O
Option
Board
+
−
+
−
Analog
device with
current
output
Analog
I/O
Option
Board
2-core shielded
twisted-pair cable
2-core shielded
twisted-pair cable
FG FG
520
Startup Operation Section 10-8
Wiring for Analog Outputs
Note (1) If necessary, connect the shield to the FG terminal to prevent noise.
(2) When an input is not being used, short the + and – terminals.
(3) Separate wiring from power lines (AC power supply lines, high-voltage
lines, etc.)
(4) When there is noise in the power supply line, install a noise filter on the
input section and the power supply.
(5) When external power is supplied, or when the power is interrupted, there
may be a pulse status analog output of up to 1 ms. If this status is a prob-
lem, take the following measures.
• Turn ON the power to the CP1L-EL/EM CPU Unit, check the operation
status, and then turn ON the power at the load.
• Turn OFF the power to the load and then turn OFF the power to the
CP1L-EL/EM CPU Unit.
!Caution When connecting the analog option board to an outside analog device, either
ground the 0 V side of the PLC’s external power supply or do not ground the
PLC’s external power supply at all. Otherwise the PLC’s external power sup-
ply may be shorted depending on the connection methods of the outside ana-
log device. DO NOT ground the 24 V side of the PLC’s external power supply,
as shown in the following diagram.
10-8 Startup Operation
After the power is turned ON, analog option board starts the initialization pro-
cess. If the initialization finishes normally, the initialization completed flag in
related status area (Refer to 10-4-2 Auxiliary Area Allocation: A435) will be
set. Therefore, status monitor content must be added in ladder. Only when the
initialization process has finished, user can use the A/D conversion data or
write the output data.
The analog input data will be 0000 until the initial processing is completed.
COM
V OUT
Analog
I/O
Option
Board
Analog
device with
voltage
input
FG
2-core shielded
twisted-pair cable
+
−
24 V
0 V 0 V
Non-insulated DC power supply
0 V
Analog Device FGFG FG
Twisted-pair
cable
FG
CPU Unit + Analog Option Board
521
Trouble Shooting Section 10-9
10-9 Trouble Shooting
Trouble-shooting with Indicators
10-10 The Use of Analog Option Board
10-10-1 Procedure
Mount the analog option board into the option port.
Connect to the analog input/output device.
Two methods:
1. DipSW4/DipSW5 set ON: TOOLBUS auto-detect
2. DipSW4/DipSW5 set OFF: Set communication protocol in PLC settings to
TOOLBUS, 115200bps
Wait until the analog option board finishes initialization and works normally.
Read the analog input data/write the analog output data.
Note (1) If PLC communication protocol setting is error, the option board will al-
ways try to link the PLC, and the error LED will flash.
(2) Only when the initialization process has finished (AR435.14/15 sets on),
user can use the A/D conversion data or write the D/A output data.
ERR
Indicator
Error Probably Cause Correction Auxiliary
Area
Allocations
AD/DA function
Lit CPU Unit service
monitoring error
Service from the
CPU Unit was
not completed
within the fixed
interval.
Check and cor-
rect the CPU
Unit's operating
environment.
Check serial
communication
setting.
A435.14 or
A435.15
will be OFF
AD/DA conversion will stop. The
analog input conversion data
stops refreshing and the analog
output conversion output
becomes 0V.
Option board
error
An error
occurred in the
Analog Option
Board.
Restart the CPU
Unit. Replace
the Analog
Option Board if
the error recurs.
Flashing Communication
error
The communica-
tion between
PLC is out of ser-
vice
Check if PLC is
running normally.
A435.14 or
A435.15
will be OFF
AD/DA conversion will stop. The
analog input conversion data
stops refreshing and the analog
output conversion output
becomes 0V. If the communica-
tion recovers from error, the
AD/DA conversion will start
again.
Connection with the analog
input/output device
Make the ladder program
Mount the analog option
board
Communication protocol
setting
AD/DA convert
522
The Use of Analog Option Board Section 10-10
10-10-2 Program Example
Use the analog option board to carry out 2CH AD inputs and 1CH DA output
at the same time.
The ranges of AD/DA are as follows:
Analog input1: 0~10V
Analog input2: 0~20mA
Analog output1: 0~10V
System composing: CP1L-EM (option port 1) + CP1W-MAB221
2980
D0
MOV(021)
2981
D1
MOV(021)
D2
2985
MOV(021)
Execution
condition
Execution
condition
Execution
condition
← Reads analog input 1's converted value to D0.
← Reads analog input 2's converted value to D1.
← The content of D2 is written to the analog
output 1.
A435.14
A435.14
A435.14
A435.14 sets on if the analog option board (mounted in option port 1) works normally.

More Related Content

What's hot

Advanced motion controls dprnlie 060a400
Advanced motion controls dprnlie 060a400Advanced motion controls dprnlie 060a400
Advanced motion controls dprnlie 060a400Electromate
 
Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400Electromate
 
Advanced motion controls dpranie c100a400
Advanced motion controls dpranie c100a400Advanced motion controls dpranie c100a400
Advanced motion controls dpranie c100a400Electromate
 
Advanced motion controls dpranir c100a400
Advanced motion controls dpranir c100a400Advanced motion controls dpranir c100a400
Advanced motion controls dpranir c100a400Electromate
 
Advanced motion controls dpcants 060b080
Advanced motion controls dpcants 060b080Advanced motion controls dpcants 060b080
Advanced motion controls dpcants 060b080Electromate
 
Advanced motion controls dpranie 060a400
Advanced motion controls dpranie 060a400Advanced motion controls dpranie 060a400
Advanced motion controls dpranie 060a400Electromate
 
Advanced motion controls dprahie c060a400
Advanced motion controls dprahie c060a400Advanced motion controls dprahie c060a400
Advanced motion controls dprahie c060a400Electromate
 
Advanced motion controls dprahia c060a400
Advanced motion controls dprahia c060a400Advanced motion controls dprahia c060a400
Advanced motion controls dprahia c060a400Electromate
 
Advanced motion controls dpcante 015b200
Advanced motion controls dpcante 015b200Advanced motion controls dpcante 015b200
Advanced motion controls dpcante 015b200Electromate
 
Advanced motion controls dprahia c100a400
Advanced motion controls dprahia c100a400Advanced motion controls dprahia c100a400
Advanced motion controls dprahia c100a400Electromate
 
Advanced motion controls dprahis 015s400
Advanced motion controls dprahis 015s400Advanced motion controls dprahis 015s400
Advanced motion controls dprahis 015s400Electromate
 
Advanced motion controls dprahir 015s400
Advanced motion controls dprahir 015s400Advanced motion controls dprahir 015s400
Advanced motion controls dprahir 015s400Electromate
 
Advanced motion controls dprahie 060a400
Advanced motion controls dprahie 060a400Advanced motion controls dprahie 060a400
Advanced motion controls dprahie 060a400Electromate
 
Advanced motion controls dprahir 100a400
Advanced motion controls dprahir 100a400Advanced motion controls dprahir 100a400
Advanced motion controls dprahir 100a400Electromate
 
Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400Electromate
 
Advanced motion controls dpcania c100a400
Advanced motion controls dpcania c100a400Advanced motion controls dpcania c100a400
Advanced motion controls dpcania c100a400Electromate
 
Advanced motion controls dpranie 030n400
Advanced motion controls dpranie 030n400Advanced motion controls dpranie 030n400
Advanced motion controls dpranie 030n400Electromate
 
Advanced motion controls dpcanis 030a800
Advanced motion controls dpcanis 030a800Advanced motion controls dpcanis 030a800
Advanced motion controls dpcanis 030a800Electromate
 
Cp1l p081 e1-2_1_csm1004101-ok
Cp1l p081 e1-2_1_csm1004101-okCp1l p081 e1-2_1_csm1004101-ok
Cp1l p081 e1-2_1_csm1004101-okdeividharo
 
Advanced motion controls dpcanie 015s400
Advanced motion controls dpcanie 015s400Advanced motion controls dpcanie 015s400
Advanced motion controls dpcanie 015s400Electromate
 

What's hot (20)

Advanced motion controls dprnlie 060a400
Advanced motion controls dprnlie 060a400Advanced motion controls dprnlie 060a400
Advanced motion controls dprnlie 060a400
 
Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400Advanced motion controls dpeaniu c100a400
Advanced motion controls dpeaniu c100a400
 
Advanced motion controls dpranie c100a400
Advanced motion controls dpranie c100a400Advanced motion controls dpranie c100a400
Advanced motion controls dpranie c100a400
 
Advanced motion controls dpranir c100a400
Advanced motion controls dpranir c100a400Advanced motion controls dpranir c100a400
Advanced motion controls dpranir c100a400
 
Advanced motion controls dpcants 060b080
Advanced motion controls dpcants 060b080Advanced motion controls dpcants 060b080
Advanced motion controls dpcants 060b080
 
Advanced motion controls dpranie 060a400
Advanced motion controls dpranie 060a400Advanced motion controls dpranie 060a400
Advanced motion controls dpranie 060a400
 
Advanced motion controls dprahie c060a400
Advanced motion controls dprahie c060a400Advanced motion controls dprahie c060a400
Advanced motion controls dprahie c060a400
 
Advanced motion controls dprahia c060a400
Advanced motion controls dprahia c060a400Advanced motion controls dprahia c060a400
Advanced motion controls dprahia c060a400
 
Advanced motion controls dpcante 015b200
Advanced motion controls dpcante 015b200Advanced motion controls dpcante 015b200
Advanced motion controls dpcante 015b200
 
Advanced motion controls dprahia c100a400
Advanced motion controls dprahia c100a400Advanced motion controls dprahia c100a400
Advanced motion controls dprahia c100a400
 
Advanced motion controls dprahis 015s400
Advanced motion controls dprahis 015s400Advanced motion controls dprahis 015s400
Advanced motion controls dprahis 015s400
 
Advanced motion controls dprahir 015s400
Advanced motion controls dprahir 015s400Advanced motion controls dprahir 015s400
Advanced motion controls dprahir 015s400
 
Advanced motion controls dprahie 060a400
Advanced motion controls dprahie 060a400Advanced motion controls dprahie 060a400
Advanced motion controls dprahie 060a400
 
Advanced motion controls dprahir 100a400
Advanced motion controls dprahir 100a400Advanced motion controls dprahir 100a400
Advanced motion controls dprahir 100a400
 
Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400Advanced motion controls dpeaniu c060a400
Advanced motion controls dpeaniu c060a400
 
Advanced motion controls dpcania c100a400
Advanced motion controls dpcania c100a400Advanced motion controls dpcania c100a400
Advanced motion controls dpcania c100a400
 
Advanced motion controls dpranie 030n400
Advanced motion controls dpranie 030n400Advanced motion controls dpranie 030n400
Advanced motion controls dpranie 030n400
 
Advanced motion controls dpcanis 030a800
Advanced motion controls dpcanis 030a800Advanced motion controls dpcanis 030a800
Advanced motion controls dpcanis 030a800
 
Cp1l p081 e1-2_1_csm1004101-ok
Cp1l p081 e1-2_1_csm1004101-okCp1l p081 e1-2_1_csm1004101-ok
Cp1l p081 e1-2_1_csm1004101-ok
 
Advanced motion controls dpcanie 015s400
Advanced motion controls dpcanie 015s400Advanced motion controls dpcanie 015s400
Advanced motion controls dpcanie 015s400
 

Similar to Guide to Using Analog Input/Output Option Boards

VIPA SLIO Introduction
VIPA SLIO IntroductionVIPA SLIO Introduction
VIPA SLIO IntroductionJimmy Hsu
 
DCS PRESENTATION
DCS PRESENTATIONDCS PRESENTATION
DCS PRESENTATIONbvent2005
 
Advanced motion controls bd25a20ac
Advanced motion controls bd25a20acAdvanced motion controls bd25a20ac
Advanced motion controls bd25a20acElectromate
 
Advanced motion controls 50a20dd
Advanced motion controls 50a20ddAdvanced motion controls 50a20dd
Advanced motion controls 50a20ddElectromate
 
Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.
Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.
Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.Portal Eletrônica
 
F5 m instruction manual
F5 m instruction manualF5 m instruction manual
F5 m instruction manualToàn Huỳnh
 
Advanced motion controls bd25a20
Advanced motion controls bd25a20Advanced motion controls bd25a20
Advanced motion controls bd25a20Electromate
 
Advanced motion controls bdc40a20
Advanced motion controls bdc40a20Advanced motion controls bdc40a20
Advanced motion controls bdc40a20Electromate
 
PowerMate15 Technical Specification
PowerMate15 Technical SpecificationPowerMate15 Technical Specification
PowerMate15 Technical SpecificationRimsky Cheng
 
Vacon nxl-brochure-bc00089 d-en
Vacon nxl-brochure-bc00089 d-enVacon nxl-brochure-bc00089 d-en
Vacon nxl-brochure-bc00089 d-enhongkiworld
 
Advanced motion controls b40a40ac
Advanced motion controls b40a40acAdvanced motion controls b40a40ac
Advanced motion controls b40a40acElectromate
 
Amp si3540 specsheet
Amp si3540 specsheetAmp si3540 specsheet
Amp si3540 specsheetElectromate
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comDien Ha The
 
Advanced motion controls 50a8dd
Advanced motion controls 50a8ddAdvanced motion controls 50a8dd
Advanced motion controls 50a8ddElectromate
 
Advanced motion controls bdc30a8
Advanced motion controls bdc30a8Advanced motion controls bdc30a8
Advanced motion controls bdc30a8Electromate
 

Similar to Guide to Using Analog Input/Output Option Boards (20)

Sanyo chassis lb5-a
Sanyo chassis lb5-aSanyo chassis lb5-a
Sanyo chassis lb5-a
 
VIPA SLIO Introduction
VIPA SLIO IntroductionVIPA SLIO Introduction
VIPA SLIO Introduction
 
DCS PRESENTATION
DCS PRESENTATIONDCS PRESENTATION
DCS PRESENTATION
 
Advanced motion controls bd25a20ac
Advanced motion controls bd25a20acAdvanced motion controls bd25a20ac
Advanced motion controls bd25a20ac
 
Advanced motion controls 50a20dd
Advanced motion controls 50a20ddAdvanced motion controls 50a20dd
Advanced motion controls 50a20dd
 
Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.
Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.
Manual de serviço TV SHARP LED/LCD diversos modelos linha LC.
 
F5 m instruction manual
F5 m instruction manualF5 m instruction manual
F5 m instruction manual
 
Advanced motion controls bd25a20
Advanced motion controls bd25a20Advanced motion controls bd25a20
Advanced motion controls bd25a20
 
Datasheet omron clp
Datasheet omron clpDatasheet omron clp
Datasheet omron clp
 
Advanced motion controls bdc40a20
Advanced motion controls bdc40a20Advanced motion controls bdc40a20
Advanced motion controls bdc40a20
 
Pt650 d英文说明书 (1)
Pt650 d英文说明书 (1)Pt650 d英文说明书 (1)
Pt650 d英文说明书 (1)
 
PowerMate15 Technical Specification
PowerMate15 Technical SpecificationPowerMate15 Technical Specification
PowerMate15 Technical Specification
 
Vacon nxl-brochure-bc00089 d-en
Vacon nxl-brochure-bc00089 d-enVacon nxl-brochure-bc00089 d-en
Vacon nxl-brochure-bc00089 d-en
 
Advanced motion controls b40a40ac
Advanced motion controls b40a40acAdvanced motion controls b40a40ac
Advanced motion controls b40a40ac
 
Amp si3540 specsheet
Amp si3540 specsheetAmp si3540 specsheet
Amp si3540 specsheet
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
 
Advanced motion controls 50a8dd
Advanced motion controls 50a8ddAdvanced motion controls 50a8dd
Advanced motion controls 50a8dd
 
Advanced motion controls bdc30a8
Advanced motion controls bdc30a8Advanced motion controls bdc30a8
Advanced motion controls bdc30a8
 
Módulo adc 18f4550
Módulo adc   18f4550Módulo adc   18f4550
Módulo adc 18f4550
 
C2000 m en_20120201
C2000 m en_20120201C2000 m en_20120201
C2000 m en_20120201
 

Recently uploaded

247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

Guide to Using Analog Input/Output Option Boards

  • 1. 505 SECTION 10 Analog Input/Output Option Board This section describes how to use Analog Input/Output Option Board. 10-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 506 10-2 Part Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 506 10-3 Installation and Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507 10-3-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507 10-3-2 Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507 10-3-3 Removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507 10-4 Memory Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508 10-4-1 CIO Area Allocation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508 10-4-2 Auxiliary Area Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508 10-5 Analog Input Option Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 509 10-6 Analog Output Option Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512 10-7 Analog I/O Option Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516 10-8 Startup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520 10-9 Trouble Shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521 10-10 The Use of Analog Option Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521 10-10-1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521 10-10-2 Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522
  • 2. 506 General Specifications Section 10-1 10-1 General Specifications CP1 series analog option board units are non-isolated analog units which allow you to easily realize analog input/output function for CP1L-EL/EM series PLC. 10-2 Part Names Note Two COM are connected in inner circuit. LED pattern Analog Option Board Voltage Input 0V~10V (Resolution:1/4000) Current Input 0mA~20mA (Resolution:1/2000) Voltage Output 0V~10V (Resolution:1/4000) Analog I/O Option Board CP1W-MAB221 2CH 2CH Analog Input Option Board CP1W-ADB21 2CH --- Analog Output Option Board CP1W-DAB21V --- 2CH Analog I/O terminal Error LED (red) Terminal Arrangement for CP1W-ADB21 Terminal Arrangement for CP1W-DAB21V Terminal Arrangement for CP1W-MAB221 II1 VI2 COMII2 COM VO1 VO2 COM VI1 II1 VI2 II2 COM VO2VO1VI1 LED Color Description Status Remark ERR Red Fault condition indicator Flash A communication error with CPU unit has occurred at the unit. Lit Other errors except the communication error. Not lit Operation is normal.
  • 3. 507 Installation and Setting Section 10-3 10-3 Installation and Setting 10-3-1 Installation The following processing explains how to install and remove an Analog Option Board. !Caution Always turn OFF the power supply to the CPU unit and wait until all the oper- ation indicators go out before installing or removing the analog option board. Not doing so may result in an unexpected operation. 1,2,3... 1. Press the up/down lock-levers on both sides of the Option Board slot cover at the same time to unlock the cover, and then pull the cover out. 2. Check the alignment to make the corner cut of the Analog Option Board fit in the Option Board slot, and firmly press the Analog Option Board in until it snaps into place. 10-3-2 Setting To use the analog option board on CP1L-EL/EM series PLC, firstly, it is neces- sary to set the serial communication settings of the CPU Unit in one of the fol- lowing two ways. Method1: Set by Dipswitch on PLC unit. For CPU Units with 30 and 40 points, switch DipSW4 of the CPU unit to ON, if the Analog Option Board is mounted on the Option Board slot 1 (left side). Switch DipSW5 of the CPU unit to ON, if the Analog Option Board is mounted on the Option Board slot 2 (right side). For CPU Units with 20 I/O points, switch DipSW4 of the CPU unit to ON. Note DipSW4 and DipSW5 are OFF at shipment. Method2: Set the option port communication parameters by PLC settings. If DipSW4 or DipSW5 is OFF, the relative option port's communication param- eters can also be set by PLC settings in CX-Programmer. Please set the baud rate of the relative option port at 115200bps in Toolbus mode. 10-3-3 Removing Always turn OFF the power supply to the CPU unit and wait until all the oper- ation indicators go out. Press the up/down lock-levers on both sides of the Analog Option Board at the same time to unlock the Option Board, and then pull it out. 00NC 02 04 06 08 10 00 02 04 06 08 10 01COM 03 05 07 09 11 01 03 05 07 09 11 BKUP ERR/ALM LNK/ACT POWER RUN INH 1 2 00 01 02 03 04 06 00 01 03 04 06 COM 02 COM 05 07COMCOM(V+) 05 07 MAC Address: 01234567890A ANALOG INPUT V1+ V2+ COM ON 1 2 3 4 5 6 DipSW4 DipSW5
  • 4. 508 Memory Allocation Section 10-4 10-4 Memory Allocation 10-4-1 CIO Area Allocation The memory allocation about analog conversion in the CIO area of PLC is shown as the following diagram. The beginning CIO channel is shown in the following table. CP1L-EL/EM series PLC The details of allocated CIO channels are described in the following table. 10-4-2 Auxiliary Area Allocation Analog Option Unit Status Area Option board status area: A435 (initial value “0000H”) Note A435.14 or A435.15 sets on if analog option board already worked normally. Then user can read A/D input data and write D/A output data. Output off bit: AR500.15 Note This bit will also affect other PLC output channels. Please refer to Appendix D Auxiliary Area Allocations by Address for more information. I/O Capacity Option Port Beginning Channel (m) Channel Range 20 Port 1 CIO2990 CIO2990 ~ CIO2999 30/40 Port 1 (Left) CIO2980 CIO2980 ~ CIO2989 Port 2 (Right) CIO2990 CIO2990 ~ CIO2999 Channel Contents CP1W-ADB21 CP1W-DAB21V CP1W-MAB221 m Analog Input 1 --- Analog Input 1 m+1 Analog input 2 --- Analog input 2 m+2 to m+4 --- --- --- m+5 --- Analog Output 1 Analog Output 1 m+6 --- Analog Output 2 Analog Output 2 m+7 to m+9 --- --- --- I/O Capacity AR Bits Option Port Content Error Process 20 A435.15 Port 1 I/O option board run state 0: Initial state or unit abnormity state 1: work normally 30/40 A435.14 Port 1 (Left) A435.15 Port 2 (Right) AR Bits Content Error Process A500.15 Output Off Bit 0: output effective 1: analog option board DA output clear
  • 5. 509 Analog Input Option Board Section 10-5 10-5 Analog Input Option Board Each CP1W-ADB21 Analog Input Option Board provides two analog inputs. • The analog input signal ranges are 0 to 10 V (with a resolution 1/4,000) and 0 to 20 mA (with a resolution 1/2,000). Main Analog Input Option Board Specifications Analog Input Signal Ranges Analog input data is digitally converted according to the input signal range as shown below. Note When the input exceeds the specified range, the A/D conversion data will be fixed at either the lower limit or upper limit. ■ 0 to 10 V The 0 to 10 V range corresponds to the hexadecimal values 0000 to 0FA0 (0 to 4000). The entire data range is 0000 to 0FFF (0 to 4095). Item Specifications Voltage Input Current Input Input signal range 0 V to 10 V 0 mA to 20 mA Max. rated input 0 V to 15 V 0 mA to 30 mA External input impedance 200 kΩ min. Approx. 250 Ω Resolution 1/4000 (full scale) 1/2000 (full scale) Overall accuracy 25°C: ±0.5% (full scale) 0 to 55°C: ±1.0% (full scale) 25°C: ±0.6% (full scale) 0 to 55°C: ±1.2% (full scale) A/D conversion data 0000 to 0FA0 hex 0000 to 07D0 hex Averaging function Not supported Conversion time Inner sample time 2ms/point Refresh time > 6ms basing on baud rate and PLC cycle time Isolation method None Current consumption 5 VDC: 20 mA max. Converted Data Hexadecimal (Decimal) 10V 10.24V 0FA0(4000) 0FFF(4095) 0000(0) 0V
  • 6. 510 Analog Input Option Board Section 10-5 ■ 0 to 20 mA The 0 to 20 mA range corresponds to the hexadecimal values 0000 to 07D0 (0 to 2000). The possible data range is 0000 to 0FFF (0 to 4095). But it is strongly suggested that the input current must not exceed 30 mA. Analog Input Terminal Arrangement Note When using current inputs, voltage input terminals must be short-circuited with current input terminals. Wiring Internal Circuits Converted Data Hexadecimal (Decimal) 0mA 20mA 07D0(2000) 0000(0) VI1 Voltage Input 1 Current Input 1 Voltage Input 2 Current Input 2 II1 VI2 II2 COM Input Common Analog input 2 Analog ground I I 1 V I 1 COM (−) I I 2 V I 2 56 kΩ 250 Ω 250 Ω 180 kΩ 180 kΩ Internalcircuits Analog input 1 toto 56 kΩ
  • 7. 511 Analog Input Option Board Section 10-5 Applicable Cables and Terminal Wiring ■ Applicable Cables Solid wire or ferrules can be used. • Recommended solid wire • Recommended ferrules Note Do not connect bare stranded wires directly to terminals. ■ Terminal Wiring When wiring the analog I/O terminal block, treat either solid or stranded wires directly. • To make the connection, press the release button in with a small flat blade screwdriver and push the line in while the lock is released. Remove the screwdriver and lock it inside. • To disconnect the wiring, press the release button in with a small flat blade screwdriver and pull the line out while the lock is released. Note (1) Ferrules with/without plastic sleeve cannot be used. (2) When using stranded wire, twist the core so that the barbed wires cannot protrude. (3) Do not solder-plate the end of cable. The screwdriver shown below is recommended for wiring. Wire type Wire size Solid Wire 0.2mm2 to 0.5mm2 (AWG24 to AWG20) Manufacturer Model Applicable wire Phoenix Contact AI-0.5-10 0.5mm2 (AWG20) Release button 2-conductor shielded twisted-pair cable Model Manufacturer SZS 0.42.5 Phoenix Contact 0.4mm Side Front 2.5mm
  • 8. 512 Analog Output Option Board Section 10-6 Wiring for Analog Inputs To prevent noise, 2-core shielded twisted-pair cable should be used. And the shield can be connected to the FG terminal if necessary. Note (1) If necessary, connect the shield to the FG terminal to prevent noise. (2) When an input is not being used, short the + and – terminals. (3) Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.) (4) When there is noise in the power supply line, install a noise filter on the input section and the power supply. !Caution When connecting the analog option board to an outside analog device, either ground the 0 V side of the PLC’s external power supply or do not ground the PLC’s external power supply at all. Otherwise the PLC’s external power sup- ply may be shorted depending on the connection methods of the outside ana- log device. DO NOT ground the 24 V side of the PLC's external power supply, as shown in the following diagram. 10-6 Analog Output Option Board Each CP1W-DAB21V Analog Output Option Board provides two analog outputs. • The analog output signal range is 0 to 10 V (with a resolution 1/4,000). Main Analog Output Option Board Specifications V IN COM I IN V IN COM I IN Analog device with voltage output Analog Input Option Board + − + − Analog device with current output Analog Input Option Board 2-core shielded twisted-pair cable 2-core shielded twisted-pair cable FG FG 24 V 0 V 0 V Non-insulated DC power supply 0 V Analog Device FGFG FG Twisted-pair cable FG CPU Unit + Analog Option Board Item Specifications Voltage Output Current Output Output signal range 0 V to 10 V --- External output allowable load resistance 2 kΩ min. --- External output impedance 0.5 Ω max. --- Resolution 1/4,000 (full scale) --- Overall accuracy 25°C: ±0.5% 0 to 55°C: ±1.0% --- D/A conversion data 0000 to 0FA0 hex --- Conversion time Inner conversion time 2ms/point Refresh time 6ms basing on baud rate and PLC cycle time Isolation method None Current consumption 5 VDC: 60 mA max.
  • 9. 513 Analog Output Option Board Section 10-6 Analog Output Signal Ranges The analog values depend on the output signal range, as shown in the follow- ing diagram. Note When the output exceeds the specified range, the output signal will be fixed at either the lower limit or upper limit. ■ 0 to 10 V The hexadecimal values 0000 to 0FA0 (0 to 4000) correspond to an analog voltage range of 0 to 10 V. The entire output range is 10 to 10.24 V. Analog Output Terminal Arrangement Wiring Internal Circuits 0V 10V 0FA0 FFFF 0FFF (4000) (4095) 0000(0) Converted Data Hexadecimal (Decimal) 10.24V VO1 Voltage Output 1 VO2 Voltage Output 2 COM Output Common Analog output 1 Analog ground V O 1 COM(−) V O 2 Analog output 2 toto Internalcircuits
  • 10. 514 Analog Output Option Board Section 10-6 Applicable Cables and Terminal Wiring ■ Applicable Cables Solid wire or ferrules can be used. • Recommended solid wire • Recommended ferrules Note Do not connect bare stranded wires directly to terminals. ■ Terminal Wiring When wiring the analog I/O terminal block, treat either solid or stranded wires directly. • To make the connection, press the release button in with a small flat blade screwdriver and push the line in while the lock is released. Remove the screwdriver and lock it inside. • To disconnect the wiring, press the release button in with a small flat blade screwdriver and pull the line out while the lock is released. Note (1) Ferrules with/without plastic sleeve cannot be used. (2) When using stranded wire, twist the core so that the barbed wires cannot protrude. (3) Do not solder-plate the end of cable. The screwdriver shown below is recommended for wiring. Wire type Wire size Solid Wire 0.2mm2 to 0.5mm2 (AWG24 to AWG20) Manufacturer Model Applicable wire Phoenix Contact AI-0.5-10 0.5mm2 (AWG20) Release button 2-conductor shielded twisted-pair cable Model Manufacturer SZS 0.42.5 Phoenix Contact 0.4mm Side Front 2.5mm
  • 11. 515 Analog Output Option Board Section 10-6 Wiring for Analog Outputs To prevent noise, 2-core shielded twisted-pair cable should be used. And the shield can be connected to the FG terminal if necessary. Note (1) If necessary, connect the shield to the FG terminal to prevent noise. (2) Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.) (3) When there is noise in the power supply line, install a noise filter on the input section and the power supply. (4) When external power is supplied, or when the power is interrupted, there may be a pulse status analog output of up to 1 ms. If this status is a prob- lem, take the following measures. • Turn ON the power to the CP1L-EL/EM CPU Unit, check the operation status, and then turn ON the power at the load. • Turn OFF the power to the load and then turn OFF the power to the CP1L-EL/EM CPU Unit. !Caution When connecting the analog option board to an outside analog device, either ground the 0 V side of the PLC’s external power supply or do not ground the PLC’s external power supply at all. Otherwise the PLC’s external power sup- ply may be shorted depending on the connection methods of the outside ana- log device. DO NOT ground the 24 V side of the PLC’s external power supply, as shown in the following diagram. COM V OUT Analog output option board Analog device with voltage input FG 2-core shielded twisted-pair cable + − 24 V 0 V 0 V Non-insulated DC power supply 0 V Analog Device FGFG FG Twisted-pair cable FG CPU Unit + Analog Option Board
  • 12. 516 Analog I/O Option Board Section 10-7 10-7 Analog I/O Option Board Each CP1W-MAB221 Analog I/O Option Board provides two analog inputs and two analog outputs. • The analog input signal ranges are 0 to 10 V (with a resolution 1/4,000) and 0 to 20 mA (with a resolution 1/2,000). • The analog output signal ranges are 0 to 10 V (with a resolution 1/4,000). Main Analog I/O Option Board Specifications Analog I/O Signal Ranges The analog values depend on the I/O signal ranges, as shown in the following diagrams. Note When the input exceeds the specified range, the A/D conversion data will be fixed at either the lower limit or upper limit. When the output exceeds the specified range, the output signal will be fixed at either the lower limit or upper limit. Analog Input Signal Ranges ■ 0 to 10 V The 0 to 10 V range corresponds to the hexadecimal values 0000 to 0FA0 (0 to 4000). The entire data range is 0000 to 0FFF (0 to 4095). Item Specifications Voltage I/O Current I/O Analog Input Section Input signal range 0 V to 10 V 0 mA to 20 mA Max. rated input 0 V to 15 V 0 mA to 30 mA External input impedance 200 kΩ min. Approx. 250 Ω Resolution 1/4,000 (full scale) 1/2,000 (full scale) Overall accuracy 25°C: ±0.5% (full scale) 0 to 55°C: ±1.0% (full scale) 25°C: ±0.6% (full scale) 0 to 55°C: ±1.2% (full scale) A/D conversion data 0000 to 0FA0 hex 0000 to 07D0 hex Averaging function Not supported Analog Output Section Output signal range 0 V to 10 V --- External output allowable load resistance 2 kΩ min. --- External output impedance 0.5 Ω max. --- Resolution 1/4,000 (full scale) --- Overall accuracy 25°C: ±0.5% 0 to 55°C: ±1.0% --- D/A conversion data 0000 to 0FA0 hex --- Conversion time Inner conversion time 6ms (4CH total) Refresh time 6ms basing on baud rate and PLC cycle time Isolation method None Current consumption 5 VDC: 80 mA max.
  • 13. 517 Analog I/O Option Board Section 10-7 ■ 0 to 20 mA The 0 to 20 mA range corresponds to the hexadecimal values 0000 to 07D0 (0 to 2000). The possible data range is 0000 to 0FFF (0 to 4095). But it is strongly suggested that the input current mustn’t exceed 30 mA. Analog Input Signal Ranges ■ 0 to 10 V The hexadecimal values 0000 to 0FA0 (0 to 4000) correspond to an analog voltage range of 0 to 10 V. The entire output range is 10 to 10.24 V. Converted Data Hexadecimal (Decimal) 10V 10.24V 0FA0(4000) 0FFF(4095) 0000(0) 0V Converted Data Hexadecimal (Decimal) 0mA 20mA 07D0(2000) 0000(0) 0V 10V 0FA0 FFFF 0FFF (4000) (4095) 0000(0) Converted Data Hexadecimal (Decimal) 10.24V
  • 14. 518 Analog I/O Option Board Section 10-7 Analog I/O Terminal Arrangement Note When using current inputs, voltage input terminals must be short-circuited with current input terminals. Wiring Internal Circuits Applicable Cables and Terminal Wiring ■ Applicable Cables Solid wire or ferrules can be used. • Recommended solid wire • Recommended ferrules Note Do not connect bare stranded wires directly to terminals. ■ Terminal Wiring When wiring the analog I/O terminal block, treat either solid or stranded wires directly. VI1 Voltage Input 1 II1 Current Input 1 VI2 Voltage Input 2 II2 Current Input 2 COM Analog I/O Common VO1 Voltage Output 1 VO2 Voltage Output 2 COM Analog I/O Common Analog input Analog output Analog input 2 Analog ground I I 1 V I 1 COM(−) I I 2 V I 2 56 kΩ 250 Ω 250 Ω 180 kΩ 180 kΩ Internalcircuits Analog input 1 to 56 kΩ Analog output 1 Analog ground V O 1 COM(−) V O 2 Analog output 2 toto to Internalcircuits Wire type Wire size Solid Wire 0.2mm2 to 0.5mm2 (AWG24 to AWG20) Manufacturer Model Applicable wire Phoenix Contact AI-0.5-10 0.5mm2 (AWG20)
  • 15. 519 Analog I/O Option Board Section 10-7 • To make the connection, press the release button in with a small flat blade screwdriver and push the line in while the lock is released. Remove the screwdriver and lock it inside. • To disconnect the wiring, press the release button in with a small flat blade screwdriver and pull the line out while the lock is released. Note (1) Ferrules with/without plastic sleeve cannot be used. (2) When using stranded wire, twist the core so that the barbed wires cannot protrude. (3) Do not solder-plate the end of cable. The screwdriver shown below is recommended for wiring. Wiring for Analog I/O To prevent noise, 2-core shielded twisted-pair cable should be used. And the shield can be connected to the FG terminal if necesssary. Wiring for Analog Inputs Release button 2-conductor shielded twisted-pair cable Model Manufacturer SZS 0.42.5 Phoenix Contact 0.4mm Side Front 2.5mm V IN COM I IN V IN COM I IN Analog device with voltage output Analog I/O Option Board + − + − Analog device with current output Analog I/O Option Board 2-core shielded twisted-pair cable 2-core shielded twisted-pair cable FG FG
  • 16. 520 Startup Operation Section 10-8 Wiring for Analog Outputs Note (1) If necessary, connect the shield to the FG terminal to prevent noise. (2) When an input is not being used, short the + and – terminals. (3) Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.) (4) When there is noise in the power supply line, install a noise filter on the input section and the power supply. (5) When external power is supplied, or when the power is interrupted, there may be a pulse status analog output of up to 1 ms. If this status is a prob- lem, take the following measures. • Turn ON the power to the CP1L-EL/EM CPU Unit, check the operation status, and then turn ON the power at the load. • Turn OFF the power to the load and then turn OFF the power to the CP1L-EL/EM CPU Unit. !Caution When connecting the analog option board to an outside analog device, either ground the 0 V side of the PLC’s external power supply or do not ground the PLC’s external power supply at all. Otherwise the PLC’s external power sup- ply may be shorted depending on the connection methods of the outside ana- log device. DO NOT ground the 24 V side of the PLC’s external power supply, as shown in the following diagram. 10-8 Startup Operation After the power is turned ON, analog option board starts the initialization pro- cess. If the initialization finishes normally, the initialization completed flag in related status area (Refer to 10-4-2 Auxiliary Area Allocation: A435) will be set. Therefore, status monitor content must be added in ladder. Only when the initialization process has finished, user can use the A/D conversion data or write the output data. The analog input data will be 0000 until the initial processing is completed. COM V OUT Analog I/O Option Board Analog device with voltage input FG 2-core shielded twisted-pair cable + − 24 V 0 V 0 V Non-insulated DC power supply 0 V Analog Device FGFG FG Twisted-pair cable FG CPU Unit + Analog Option Board
  • 17. 521 Trouble Shooting Section 10-9 10-9 Trouble Shooting Trouble-shooting with Indicators 10-10 The Use of Analog Option Board 10-10-1 Procedure Mount the analog option board into the option port. Connect to the analog input/output device. Two methods: 1. DipSW4/DipSW5 set ON: TOOLBUS auto-detect 2. DipSW4/DipSW5 set OFF: Set communication protocol in PLC settings to TOOLBUS, 115200bps Wait until the analog option board finishes initialization and works normally. Read the analog input data/write the analog output data. Note (1) If PLC communication protocol setting is error, the option board will al- ways try to link the PLC, and the error LED will flash. (2) Only when the initialization process has finished (AR435.14/15 sets on), user can use the A/D conversion data or write the D/A output data. ERR Indicator Error Probably Cause Correction Auxiliary Area Allocations AD/DA function Lit CPU Unit service monitoring error Service from the CPU Unit was not completed within the fixed interval. Check and cor- rect the CPU Unit's operating environment. Check serial communication setting. A435.14 or A435.15 will be OFF AD/DA conversion will stop. The analog input conversion data stops refreshing and the analog output conversion output becomes 0V. Option board error An error occurred in the Analog Option Board. Restart the CPU Unit. Replace the Analog Option Board if the error recurs. Flashing Communication error The communica- tion between PLC is out of ser- vice Check if PLC is running normally. A435.14 or A435.15 will be OFF AD/DA conversion will stop. The analog input conversion data stops refreshing and the analog output conversion output becomes 0V. If the communica- tion recovers from error, the AD/DA conversion will start again. Connection with the analog input/output device Make the ladder program Mount the analog option board Communication protocol setting AD/DA convert
  • 18. 522 The Use of Analog Option Board Section 10-10 10-10-2 Program Example Use the analog option board to carry out 2CH AD inputs and 1CH DA output at the same time. The ranges of AD/DA are as follows: Analog input1: 0~10V Analog input2: 0~20mA Analog output1: 0~10V System composing: CP1L-EM (option port 1) + CP1W-MAB221 2980 D0 MOV(021) 2981 D1 MOV(021) D2 2985 MOV(021) Execution condition Execution condition Execution condition ← Reads analog input 1's converted value to D0. ← Reads analog input 2's converted value to D1. ← The content of D2 is written to the analog output 1. A435.14 A435.14 A435.14 A435.14 sets on if the analog option board (mounted in option port 1) works normally.