AFC Defender - Radiation Attenuation Screen Specially developed for Fire Engineers and Architects to be used in lieu of deemed-to-satisfy systems, this solution can also provide security.
Hyderabad ❣️ Call Girl 9748763073 Call Girls in Hyderabad Escort service boo...
Defender screens - fire attenuation screens
1. DEFENDERSCREENSFIRE ATTENUATION SCREENS
Building on a boundary [Class 2-9] OR
BAL FZ [Class 1, 1a & 10] AS3959-2009
Phone: 9399 6957| Address: 17 Williams Road Kelmscott WA 6111 |Email: Sales@AustralianFireControl.com.au
www.AustralianFireControl.com.au
AFCb u i l t f o r f i r e
DefenderBOUNDARY PROTECTION
DEFENDER SCREENS
The AFC Defender system consists of a perimeter aluminum frame
that can be powder coated a standard colour. This is fixed to the
perimeter of the window opening using a continuous angle. The
mesh consists of a 0.9mm thick woven 304 stainless steel which is
coated black to reduce the reflection of light and maximize the
clarity of the view. The free area of the mesh is 42%.
Note that the angle of the light relative to the mesh may reduce
the light into the room more than expected.
AFC Defender Screen provides radiation attenuation to protect
windows close to a boundary [Class 2-9] or to provide BAL FZ
performance to AS3959-2009 for Class 1, 1a & 10 construction.
Fire Engineers use this data in their design and calculations to
determine whether the radiation attenuation is sufficient to
prevent non-piloted ignition and therefore fire spread to nearby
materials/buildings.
AFC Defender - Radiation Attenuation Screen Specially
developed for Fire Engineers and Architects to be used in lieu of
deemed-to-satisfy systems, this solution can also provide security.
10YEARSTRUCTURALWARRANTY
10Y
EARSTRUCTURALWA
RRANTY
10YEAROPERATIONAL
WARRANTY*
10YE
AROPERATIONALWA
RRANTY
Subject to maintenance
programme
DEFENDERSERIESBALF
Z
DEFENDERSERIESBALF
Z
Width Height
750 3000
900 3000
1200 3000
1500 2400
2400 2400
3000 2100
SIZES
• Assessed to AS1530 section 8.1 using radiant heat flux
exposure up to & including 40kW/m2 [BAL40].
• Radiation attenuation achieved 42% to 50% of radiant
heat flux.
• Furnace Temperature > 850C
• Complies with dimensional requirements of AS3959 section
9.5.1.A ‘Construction of Buildings in Bushfire Prone Areas’ - 2009
• Impact resistance equivalent to 4kg mass @15m/s
• 304mm Stainless Steel
• 0.90mm Wire Diameter
• 1.5mm x 1.5mm Aperture
• 10 strands per inch
• 42% Open Area.
facts and figures
• Available with powder coated perimeter frame.
• Can fulfil a security function.
• Allows the use of standard sliding or sash [with restrictor] win-
dows behind.
• Minimal side wall clearance/usage requirements.
advantages
Radiation Attenuation Mesh shall be Australian Fire Control’s (08 9399 6957)
proprietary AFC Defender Radiation Attenuation Screen [System FRBCAFC001] supplied and installed by an accredited installer. System shall be assessed to AS15030 section 8.1 and
comply with AS3959 section 9.5.1.A. Radiation attenuation when subjected to 40kW/m2 radiant heat flux shall be in the range of minimum 42% to maximum 50%.
SIZES
How to specify
SYSTEM DETAIL - SAMPLE SHOP DRAWING
DETAIL CC
DETAIL CC
SECTION AA
A
A
Opening width
Openingheight
Exsitingwindow
(5x25)mm Mushroom head screws with rubber
gromets @ 300mm centers
(40 x 40 x 3 thick) mm angle (four sides)
D8 x 75mm Dynabokt @ 300mm centers
AFC Defender Screen (radiation attenuation screen)
SYSTEM NOTES:
• Assessed to AS1530 section 8.1 using radiant heat flux expo-
sure up to & including 40kW/m2 [BAL40].
• Radiation attenuation achieved 42% to 50% of radiant
heat flux.
• Furnace Temperature > 850C
• Complies with dimensional requirements of AS3959 section
9.5.1.A ‘Construction of Buildings in
Bushfire Prone Areas’ - 2009
• Impact resistance equivalent to 4kg mass @15m/s
• 304mm Stainless Steel
• 0.90mm Wire Diameter
• 1.5mm x 1.5mm Aperture
• 10 strands per inch 42% Open Area.
DEFENDER SCREEN
Width Height
750 3000
900 3000
1200 3000
1500 2400
2400 2400
3000 2100
SIZES
AFCb u i l t f o r f i r e
Phone: 9399 6957
Address: 17 Williams Road
Kelmscott WA 6111
Email: Sales@AustralianFireControl.com.au
“In the game since 1979”
Project Address: ________________________________________________
Project Ref No: ________________________________________________
Opening Width: ________________________________________________
Opening Height: ________________________________________________
Colour Selection:
Anotec® Silver Grey Windspray® Evening Haze® Ironstone® Wilderness® Jasper® Black (C/B Night Sky) Blue Ridge® Surfmist® OTHER PLEASE SPECIFY
IMPORTANT INFORMATION REGARDING THIS SHOP DRAWING.
This is a production document based on our understanding of project requirements.
It is important to note that material will be manufactured from this information.
Whilst we understand that it is our responsibility to determine all manufacturing information we ask that
you review this document as a double check to assist in having the correct product delivered to site.
Drawn by: ______________________________________________ Date: _____/_____/_____
Shop Drawing Approval
Name: _____________________________ Sign: _______________________________ Date: _____/_____/_____
SHOP DRAWING APPROVAL SCALE: NTS