 All Thermal, Optical and Ultraviolet IG data is generated
by Lawrence Berkeley Laboratory’s “WINDOW 6.3”
software.
LBL WINDOWS & DAYLIGHTING GROUP
Berkeley, CA (510-486-6844)
• Windows 6.3 (free download)
• Website: http://windows.lbl.gov
• International IG Performance Standard
•1000+ Glass Types As Of September, 2012
SCF World Beyond Low-e
0.00
0.20
0.40
0.60
0.80
1.00
1.20
Single Double Double Low-e
Cubed (#2)
"Triple" SCF Twin
Coat TC88
"Triple" SCF
Double Low-e
TC88
"QuadPane"
Double Low-e
Double TC88
1.02
0.45
0.24
0.14 0.13 0.09
2010 INSULATING GLASS U-VALUE
SCF World Beyond Low-e
0.0
2.0
4.0
6.0
8.0
10.0
12.0
Single Double Double Low-e
Cubed (#2)
"Triple" SCF
Twin Coat TC88
"Triple" SCF
Double Low-e
TC88
"QuadPane"
Double Low-e
Double TC88
1.0
2.2
4.2
7.0
7.9
11.8
2012 INSULATING GLASS R-VALUE
R = 1/U
Air: 1/2”
Argon: 1/2”
Krypton: 3/8 ”
Xenon: 1/4”
0%
10%
20%
30%
40%
50%
60%
Argon (90%) Krypton (90%) Xenon (90%)
25%
43%
53%GAS IMPROVEMENT
IN R-VALUE
(TriPane IG / Double Low-e)
4.0
5.0
6.0
7.0
8.0
9.0
10.0
Air Argon (90%) Krypton
(90%)
Xenon (90%)
5.9
7.4
8.4
9.0
R-VALUE
BY GAS FILL
(TriPane IG / Double Low-e)
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
1 2 3 4
8.3
10.5
12.3
13.2R-VALUE
BY GAS FILL
(QuadPane / Triple Low-e)
0%
10%
20%
30%
40%
50%
60%
Argon (90%) Krypton (90%) Xenon (90%)
26%
48%
58%GAS IMPROVEMENT
IN R-VALUE
(QuadPane/ Triple Low-e)
Insulating Glass "Passive Performance Coefficient"
CONFIGURATION
Label LI-HM88-LI (Ar) LI-2HM88-LI (Kr) C180-2HM88-LI (Kr) Dbl C180 + 3HM88 (Xe)
Outer Light 1/8" Low Iron 1/8" Low Iron 1/8" Low Iron 1/8" C180 (#2)
Triple Versus QuadPane Triple Quad Quad Quint
Interspaces 2 @ 1/2" Argon 3 @ 3/8" Krypton 3 @ 3/8" Krypton 4 @ 1/4" Xenon
(SFC) Suspended Coated Film HM88 Double HM88 Double HM88 Triple HM88 (#4,6,8)
Inner Light 1/8" Low Iron 1/8" Low Iron 1/8" Low Iron 1/8" C180(#9)
PERFORMANCE
U-Value (Winter) 0.20 0.11 0.08 0.050
R-Value 5.0 9.3 12.2 20.0
Solar Heat Gain Coefficient 0.60 0.51 0.44 0.38
"PPC" Passive Performance Coefficient 3.0 4.7 5.3 7.5
Tvis 74% 66% 63% 53%
UV Blockage (to 380 nm) 99.3% 100.0% 100.0% 100.0%
ASHRAE/NFRC "Winter" Glass Temp (oF) 59 Deg F 63 Deg F 65 Deg F 67 Deg F
ASHRAE/NFRC "Summer" Glass Temp (oF) 91 Deg F 94 Deg F 90 Deg F 96 Deg F
All values are Center Of Glass - as calculated by LBNL Window 6 Software
2.0
3.0
4.0
5.0
6.0
7.0
8.0
3.0
4.7
5.3
7.5
"PPC" =
PASSIVE PERFORMANCE
COEFFICIENT = SHGC/U-VALUE
Low Iron Glass
(no green)
Frame-Only U-Values
From: "Residential Windows"
(Carmody/Selkowitz/Arasteh/Heschong)
Low High Average
Aluminum (no break) 1.7 2.4 2.05
Aluminum (thermal break) 0.8 1.3 1.05
Carbon Steel 0.40 0.57 0.49
Insulated Vinyl & Fiberglass 0.2 0.4 0.30
0.00
0.50
1.00
1.50
2.00
2.50
Aluminum (no
break)
Aluminum
(thermal break)
Carbon Steel Insulated Vinyl &
Fiberglass
2.05
1.05
0.49 0.30
WINDOW FRAME AVERAGE U-VALUE
Average Frame + Sash Width: 4.9”
Average Frame + Sash Width: 2.75
GlasTrosch
Optiwin
Passive House Window: 4.89" Versus 2.81" Frame
Reference: Standard NFRC Casement: 47.2 x 59.1
Total Window (Frame) Area = 19.4 SF
4.9" Frame2.8" Frame Variance
Frame % Of Total Area 34% 20% -41%
U-Value (Base: Frame: .20/Glass: .14) 0.18 0.17 -9%
SHGC (Base: Frame: .08 / Glass: .60) 0.42 0.50 17%
VT (Base: 70%) 0.46 0.56 22%
Vision Area As % Of Total 71.8% 85.5% 19%
Fading
Overheating
Too cold on cloudy winter days
Undercooking
Moveable Insulation Burden
Daily temperature swings
Lack of privacy or security
Glare
2012
Hottest Duluth July Since 1935 Dust
Bowl = + 6.1 F Av (+13 Peak)
August = 14 Record High Months
50-Year Projections
Monte Carlo
Simulation?
“Most designers feel safer
specifying low-solar-gain
glazing for the west
elevation.”
Martin Holladay
GreenBuildingAdvisor.com
Outer Glass Light (Full
Worldwide Glass-Tint Freedom)
Air (Argon/Krypton) Interspaces
Suspended Coated Film
(Single Or Double Coated)
Inner Light (Laminated/Frit Options)
Perimeter Sealant Options Include Silicon To Enable Flush Glazing
R-2 1865 Patented Double Glazing Extended To R-12 With Low-E + SCF Technology
 SCF Production: $18.5M Vacuum
“Sputtering” Machine. SFC: 79” Wide
By 5,000’ Long
 10 Different SCF Technologies
Address Residential, Institutional And
Commercial Architecture
 SCF Then Transported To Regional
Insulating Glass Fabricators To Be
Suspended Midway Between Two
Panes Of Glass
 SCF Insulating Glass Production Line:
Glass + Spacer + SCF + Spacer +
Glass = World’s Highest Performance
Glass.
2007 Top-10
Green Building Product
GreenSpec® LISTED
www.BuildingGreen.com
TECHNOLOGY
R-5 to R-20 Insulating Glass
99.5% UV Blockage
Pultrusion Fiberglass Frame
N-S-E-W “Tuning”
Low Profile Sashes
Wood Clad Interior
Dimensional Stability
Meets DOE “2020 Roadmap”
Performance Goal:
(R-10.4 / U-0.96) Overall
Pultrusion Lineal
Mechanical
Corner Sash
Pultrusion “End”
(Al Dueck – Duxton)
University Of Colorado - $63 Visual Arts Center
Super IG + 131” Pultrusion FG Frames
Architects: KMW-Boston & OZ-Colorado
Wood bury Hall – 1890 – Original
Steel – to Interim Aluminum – to
Serious Fiberglass
Six Human Comfort Factors

1. Air Temp
2. Mean Radiant Temp
3. Air Velocity
4. Relative Humidity
5. Activity Level
6. Clothing Factor
CFD Modeling
GOOGLE – New York City
20-Degree Surface Temp Difference
Windows: 6,514
IG Units: 13,028
Glazing: ~160,000 ft2
Start: March, 2010
End: November 2010
ESB Renovation Measure Contributions
1) DDC (Direct Digital Control) 603 36.8%
2) Demand Controlled Ventilation 5 0.3%
3) Tenant Lighting & Plug Load Reduction 424 25.9%
4) Windows 440 26.9%
5) Tenant Energy Management 166 10.1%
Total Tonnage Reduction 1,638 100.0%
Total Avoided HVAC (Chiller) Expenditure $ 17,400,000
Windows Share Of Chiller Savings $ 4,673,993
So, by GSB Valedictorian Mel Hodge Logic, payback is: "Immediate"
$/Ton Savings 10,623 (High?)
Production/Installation Capacity:
35-50 Windows/Night
Traco 9000 Windows Identical To Those Of
111 8th Avenue
Performance: Before
U-Value 0.48
R-value 2.1
SHGC 0.72
Tvis 80%
Winter NFRC Glass Temp
(70 in/0 out/15 mph) 44 °F
Summer NFRC Glass Temp
(75 in/90 out) 95 °F
Overall Thickness 1"
UltraViolet Blockage 46.8%
Performance: After Retrofit Difference
U-Value 0.13 -72%
R-value 7.6 261%
SHGC 0.49 32%
Tvis 64% -20%
Winter NFRC Glass Temp
(70 in/0 out/15 mph) 62 °F + 18 °F
Summer NFRC Glass Temp
(75 in/90 out) 76 °F (LBNL) - 19 °F
Overall Thickness 1" No Change
UltraViolet Blockage 98.6% -111%
NORTH
Performance: After Retrofit Difference
U-Value 0.20 -59%
R-value 5.1 142%
SHGC 0.35 52%
Tvis 62% -23%
Winter NFRC Glass Temp
(70 in/0 out/15 mph) 59 °F + 15 °F
Summer NFRC Glass Temp
(75 in/90 out) 90 °F - 5 °F
Overall Thickness 1" No Change
UltraViolet Blockage 98.6% -111%
SOUTH,
EAST
& WEST
Empire State Building Before And After Glass
Performance
North Elevation (Fifth Avenue Orientation: 29 1/2 Degrees East Of North)
Before After
Clear Uncoated
Double Pane (1992)
"Triple" SCF Glass
Suspended Coated
TC88
Outer Light 3/16" Clear 3/16" Clear
Interspaces And Thickness 1 @ 5/8" 2 @ 5/16"
Suspended Coated Film(s) None
TC-88 (Double Low-
e)
Gas Fill Air
90% Krypton/10%
Oxygen
Inner Light 3/16" Clear 3/16" Clear
Performance
Before After Difference
U-Value 0.48 0.13 -72%
R-value 2.1 7.6 +261%
SHGC 0.72 0.49 +32%
Tvis 80% 64% -20%
Winter NFRC (70 in/0 out/15 mph)
Glass Temp 44 Deg F 62 Deg F
+ 18 Degrees
F
Summer NFRC (75 in/90 out) 95 Deg F 76 Deg F (LBNL) - 19 Degrees F
Overall Thickness 1" 1" No Change
UltraViolet Blockage 46.8% 98.6% -111%
• Pultrusion Fiberglass Casement
Frames
• 1 3/8” SCT Glazing Pocket For
Thermal & Acoustic Performance
• R-8 SCF Glass
• Warm Winter / Cool Summer
• Directionally “Tuned” SCF Glass
• 99.5% UV Blockage
• Inside/Outside Color Freedom
• 1/500th Aluminum Frame Conductivity
• High Volume Pricing
Winnipeg Church In Blizzard – Warm To
The Touch Window Frames
Internal Anchor
Blocks
•SCF North-South-East-West “Tuned” Glazing
•Fiberglass Storefront In High Humidity Galleries
•99.9% UV Blockage
•62 Degree “Winter” Glass Temp
•Perimeter Baseboard Heating Removal
•Payback Under One Year
Florian
Antretter
Larry Kinney, PhD – Boulder
Moveable Insulating Guru
Amory Lovins: All of the
energy pumped through the
Alaska Pipeline each year
goes literally “out America’s
windows.”

More Related Content

Similar to R clarke passive_housedenversep12

Industrial Perspectives on Large-Area TCOs
Industrial Perspectives on Large-Area TCOsIndustrial Perspectives on Large-Area TCOs
Industrial Perspectives on Large-Area TCOscdtpv
 
Window Standards Compared: NFRC, ISO and Passive House Ratings
Window Standards Compared: NFRC, ISO and Passive House RatingsWindow Standards Compared: NFRC, ISO and Passive House Ratings
Window Standards Compared: NFRC, ISO and Passive House RatingsRDH Building Science
 
Astro Poly 72 cells 335 355 w - stave ii-chsm72_p-hc_40mm frame_201711
Astro Poly 72 cells   335 355 w - stave ii-chsm72_p-hc_40mm frame_201711Astro Poly 72 cells   335 355 w - stave ii-chsm72_p-hc_40mm frame_201711
Astro Poly 72 cells 335 355 w - stave ii-chsm72_p-hc_40mm frame_201711Naveed Ahmed
 
Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...energytrustor
 
Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...
Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...
Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...CustomTintSolutionsSanAntonio
 
sunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-ds
sunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-dssunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-ds
sunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-dscarlos chavez
 
Panova Glass
Panova GlassPanova Glass
Panova GlassMurat Can
 
Steuben - When the Going gets Rough Presentation
Steuben - When the Going gets Rough PresentationSteuben - When the Going gets Rough Presentation
Steuben - When the Going gets Rough PresentationJeffrey Steuben
 
Insulated metal panels edc1
Insulated metal panels edc1Insulated metal panels edc1
Insulated metal panels edc1Derrick Teal
 
Detailing : Opening Assemblies
Detailing : Opening AssembliesDetailing : Opening Assemblies
Detailing : Opening AssembliesTodd Wyatt
 
NBEC 2014 - Energy Performance of Windows
NBEC 2014  -  Energy Performance of WindowsNBEC 2014  -  Energy Performance of Windows
NBEC 2014 - Energy Performance of WindowsRDH Building Science
 
Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808
Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808
Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808Nav Ahmed
 
Conformal optical coatings on complex 3D-macrostructures using atomic layer d...
Conformal optical coatings on complex 3D-macrostructures using atomic layer d...Conformal optical coatings on complex 3D-macrostructures using atomic layer d...
Conformal optical coatings on complex 3D-macrostructures using atomic layer d...Beneq
 
Lg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheet
Lg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheetLg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheet
Lg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheetNav Ahmed
 
ICWES15 - Improving the Thermal Performance of Framed Window Systems. Presen...
ICWES15 - Improving the Thermal Performance of Framed Window Systems.  Presen...ICWES15 - Improving the Thermal Performance of Framed Window Systems.  Presen...
ICWES15 - Improving the Thermal Performance of Framed Window Systems. Presen...Engineers Australia
 

Similar to R clarke passive_housedenversep12 (20)

Industrial Perspectives on Large-Area TCOs
Industrial Perspectives on Large-Area TCOsIndustrial Perspectives on Large-Area TCOs
Industrial Perspectives on Large-Area TCOs
 
Window Standards Compared: NFRC, ISO and Passive House Ratings
Window Standards Compared: NFRC, ISO and Passive House RatingsWindow Standards Compared: NFRC, ISO and Passive House Ratings
Window Standards Compared: NFRC, ISO and Passive House Ratings
 
Astro Poly 72 cells 335 355 w - stave ii-chsm72_p-hc_40mm frame_201711
Astro Poly 72 cells   335 355 w - stave ii-chsm72_p-hc_40mm frame_201711Astro Poly 72 cells   335 355 w - stave ii-chsm72_p-hc_40mm frame_201711
Astro Poly 72 cells 335 355 w - stave ii-chsm72_p-hc_40mm frame_201711
 
Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...
 
World One Towers, Mumbai
World One Towers, MumbaiWorld One Towers, Mumbai
World One Towers, Mumbai
 
Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...
Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...
Custom tint-solutions-austin-san-antonio-window-film-hanita solar-zone_datash...
 
AIA Chicago Presentation
AIA Chicago PresentationAIA Chicago Presentation
AIA Chicago Presentation
 
sunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-ds
sunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-dssunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-ds
sunmodule-pro-series-solar-panel-xl-320-mono-33mm-frame-ds
 
Panova Glass
Panova GlassPanova Glass
Panova Glass
 
Steuben - When the Going gets Rough Presentation
Steuben - When the Going gets Rough PresentationSteuben - When the Going gets Rough Presentation
Steuben - When the Going gets Rough Presentation
 
Insulated metal panels edc1
Insulated metal panels edc1Insulated metal panels edc1
Insulated metal panels edc1
 
Detailing : Opening Assemblies
Detailing : Opening AssembliesDetailing : Opening Assemblies
Detailing : Opening Assemblies
 
NBEC 2014 - Energy Performance of Windows
NBEC 2014  -  Energy Performance of WindowsNBEC 2014  -  Energy Performance of Windows
NBEC 2014 - Energy Performance of Windows
 
Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808
Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808
Astro dual chsm6612m 335 _ 360 watt (dg+dgt)_frameless_201808
 
Highly Insulating Windows
Highly Insulating WindowsHighly Insulating Windows
Highly Insulating Windows
 
Conformal optical coatings on complex 3D-macrostructures using atomic layer d...
Conformal optical coatings on complex 3D-macrostructures using atomic layer d...Conformal optical coatings on complex 3D-macrostructures using atomic layer d...
Conformal optical coatings on complex 3D-macrostructures using atomic layer d...
 
Lobel Solar Latetst Specification
Lobel Solar Latetst SpecificationLobel Solar Latetst Specification
Lobel Solar Latetst Specification
 
Lg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheet
Lg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheetLg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheet
Lg solar-ne on-2-mono-silver-frame-lg410n2w-a5-solar-panel-datasheet
 
Corrosion Under Insulation
Corrosion Under InsulationCorrosion Under Insulation
Corrosion Under Insulation
 
ICWES15 - Improving the Thermal Performance of Framed Window Systems. Presen...
ICWES15 - Improving the Thermal Performance of Framed Window Systems.  Presen...ICWES15 - Improving the Thermal Performance of Framed Window Systems.  Presen...
ICWES15 - Improving the Thermal Performance of Framed Window Systems. Presen...
 

R clarke passive_housedenversep12

  • 1.
  • 2.
  • 3.  All Thermal, Optical and Ultraviolet IG data is generated by Lawrence Berkeley Laboratory’s “WINDOW 6.3” software. LBL WINDOWS & DAYLIGHTING GROUP Berkeley, CA (510-486-6844) • Windows 6.3 (free download) • Website: http://windows.lbl.gov • International IG Performance Standard •1000+ Glass Types As Of September, 2012
  • 4. SCF World Beyond Low-e 0.00 0.20 0.40 0.60 0.80 1.00 1.20 Single Double Double Low-e Cubed (#2) "Triple" SCF Twin Coat TC88 "Triple" SCF Double Low-e TC88 "QuadPane" Double Low-e Double TC88 1.02 0.45 0.24 0.14 0.13 0.09 2010 INSULATING GLASS U-VALUE
  • 5. SCF World Beyond Low-e 0.0 2.0 4.0 6.0 8.0 10.0 12.0 Single Double Double Low-e Cubed (#2) "Triple" SCF Twin Coat TC88 "Triple" SCF Double Low-e TC88 "QuadPane" Double Low-e Double TC88 1.0 2.2 4.2 7.0 7.9 11.8 2012 INSULATING GLASS R-VALUE R = 1/U
  • 6. Air: 1/2” Argon: 1/2” Krypton: 3/8 ” Xenon: 1/4”
  • 7. 0% 10% 20% 30% 40% 50% 60% Argon (90%) Krypton (90%) Xenon (90%) 25% 43% 53%GAS IMPROVEMENT IN R-VALUE (TriPane IG / Double Low-e) 4.0 5.0 6.0 7.0 8.0 9.0 10.0 Air Argon (90%) Krypton (90%) Xenon (90%) 5.9 7.4 8.4 9.0 R-VALUE BY GAS FILL (TriPane IG / Double Low-e)
  • 8. 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 1 2 3 4 8.3 10.5 12.3 13.2R-VALUE BY GAS FILL (QuadPane / Triple Low-e) 0% 10% 20% 30% 40% 50% 60% Argon (90%) Krypton (90%) Xenon (90%) 26% 48% 58%GAS IMPROVEMENT IN R-VALUE (QuadPane/ Triple Low-e)
  • 9. Insulating Glass "Passive Performance Coefficient" CONFIGURATION Label LI-HM88-LI (Ar) LI-2HM88-LI (Kr) C180-2HM88-LI (Kr) Dbl C180 + 3HM88 (Xe) Outer Light 1/8" Low Iron 1/8" Low Iron 1/8" Low Iron 1/8" C180 (#2) Triple Versus QuadPane Triple Quad Quad Quint Interspaces 2 @ 1/2" Argon 3 @ 3/8" Krypton 3 @ 3/8" Krypton 4 @ 1/4" Xenon (SFC) Suspended Coated Film HM88 Double HM88 Double HM88 Triple HM88 (#4,6,8) Inner Light 1/8" Low Iron 1/8" Low Iron 1/8" Low Iron 1/8" C180(#9) PERFORMANCE U-Value (Winter) 0.20 0.11 0.08 0.050 R-Value 5.0 9.3 12.2 20.0 Solar Heat Gain Coefficient 0.60 0.51 0.44 0.38 "PPC" Passive Performance Coefficient 3.0 4.7 5.3 7.5 Tvis 74% 66% 63% 53% UV Blockage (to 380 nm) 99.3% 100.0% 100.0% 100.0% ASHRAE/NFRC "Winter" Glass Temp (oF) 59 Deg F 63 Deg F 65 Deg F 67 Deg F ASHRAE/NFRC "Summer" Glass Temp (oF) 91 Deg F 94 Deg F 90 Deg F 96 Deg F All values are Center Of Glass - as calculated by LBNL Window 6 Software 2.0 3.0 4.0 5.0 6.0 7.0 8.0 3.0 4.7 5.3 7.5 "PPC" = PASSIVE PERFORMANCE COEFFICIENT = SHGC/U-VALUE Low Iron Glass (no green)
  • 10. Frame-Only U-Values From: "Residential Windows" (Carmody/Selkowitz/Arasteh/Heschong) Low High Average Aluminum (no break) 1.7 2.4 2.05 Aluminum (thermal break) 0.8 1.3 1.05 Carbon Steel 0.40 0.57 0.49 Insulated Vinyl & Fiberglass 0.2 0.4 0.30 0.00 0.50 1.00 1.50 2.00 2.50 Aluminum (no break) Aluminum (thermal break) Carbon Steel Insulated Vinyl & Fiberglass 2.05 1.05 0.49 0.30 WINDOW FRAME AVERAGE U-VALUE
  • 11. Average Frame + Sash Width: 4.9”
  • 12. Average Frame + Sash Width: 2.75
  • 13. GlasTrosch Optiwin Passive House Window: 4.89" Versus 2.81" Frame Reference: Standard NFRC Casement: 47.2 x 59.1 Total Window (Frame) Area = 19.4 SF 4.9" Frame2.8" Frame Variance Frame % Of Total Area 34% 20% -41% U-Value (Base: Frame: .20/Glass: .14) 0.18 0.17 -9% SHGC (Base: Frame: .08 / Glass: .60) 0.42 0.50 17% VT (Base: 70%) 0.46 0.56 22% Vision Area As % Of Total 71.8% 85.5% 19%
  • 14. Fading Overheating Too cold on cloudy winter days Undercooking Moveable Insulation Burden Daily temperature swings Lack of privacy or security Glare
  • 15. 2012 Hottest Duluth July Since 1935 Dust Bowl = + 6.1 F Av (+13 Peak) August = 14 Record High Months 50-Year Projections Monte Carlo Simulation?
  • 16. “Most designers feel safer specifying low-solar-gain glazing for the west elevation.” Martin Holladay GreenBuildingAdvisor.com
  • 17. Outer Glass Light (Full Worldwide Glass-Tint Freedom) Air (Argon/Krypton) Interspaces Suspended Coated Film (Single Or Double Coated) Inner Light (Laminated/Frit Options) Perimeter Sealant Options Include Silicon To Enable Flush Glazing R-2 1865 Patented Double Glazing Extended To R-12 With Low-E + SCF Technology
  • 18.  SCF Production: $18.5M Vacuum “Sputtering” Machine. SFC: 79” Wide By 5,000’ Long  10 Different SCF Technologies Address Residential, Institutional And Commercial Architecture  SCF Then Transported To Regional Insulating Glass Fabricators To Be Suspended Midway Between Two Panes Of Glass  SCF Insulating Glass Production Line: Glass + Spacer + SCF + Spacer + Glass = World’s Highest Performance Glass.
  • 19.
  • 20. 2007 Top-10 Green Building Product GreenSpec® LISTED www.BuildingGreen.com TECHNOLOGY R-5 to R-20 Insulating Glass 99.5% UV Blockage Pultrusion Fiberglass Frame N-S-E-W “Tuning” Low Profile Sashes Wood Clad Interior Dimensional Stability Meets DOE “2020 Roadmap” Performance Goal: (R-10.4 / U-0.96) Overall
  • 21.
  • 22. Pultrusion Lineal Mechanical Corner Sash Pultrusion “End” (Al Dueck – Duxton)
  • 23. University Of Colorado - $63 Visual Arts Center Super IG + 131” Pultrusion FG Frames Architects: KMW-Boston & OZ-Colorado Wood bury Hall – 1890 – Original Steel – to Interim Aluminum – to Serious Fiberglass
  • 24. Six Human Comfort Factors 1. Air Temp 2. Mean Radiant Temp 3. Air Velocity 4. Relative Humidity 5. Activity Level 6. Clothing Factor CFD Modeling GOOGLE – New York City 20-Degree Surface Temp Difference
  • 25. Windows: 6,514 IG Units: 13,028 Glazing: ~160,000 ft2 Start: March, 2010 End: November 2010 ESB Renovation Measure Contributions 1) DDC (Direct Digital Control) 603 36.8% 2) Demand Controlled Ventilation 5 0.3% 3) Tenant Lighting & Plug Load Reduction 424 25.9% 4) Windows 440 26.9% 5) Tenant Energy Management 166 10.1% Total Tonnage Reduction 1,638 100.0% Total Avoided HVAC (Chiller) Expenditure $ 17,400,000 Windows Share Of Chiller Savings $ 4,673,993 So, by GSB Valedictorian Mel Hodge Logic, payback is: "Immediate" $/Ton Savings 10,623 (High?)
  • 26. Production/Installation Capacity: 35-50 Windows/Night Traco 9000 Windows Identical To Those Of 111 8th Avenue
  • 27. Performance: Before U-Value 0.48 R-value 2.1 SHGC 0.72 Tvis 80% Winter NFRC Glass Temp (70 in/0 out/15 mph) 44 °F Summer NFRC Glass Temp (75 in/90 out) 95 °F Overall Thickness 1" UltraViolet Blockage 46.8%
  • 28. Performance: After Retrofit Difference U-Value 0.13 -72% R-value 7.6 261% SHGC 0.49 32% Tvis 64% -20% Winter NFRC Glass Temp (70 in/0 out/15 mph) 62 °F + 18 °F Summer NFRC Glass Temp (75 in/90 out) 76 °F (LBNL) - 19 °F Overall Thickness 1" No Change UltraViolet Blockage 98.6% -111% NORTH
  • 29. Performance: After Retrofit Difference U-Value 0.20 -59% R-value 5.1 142% SHGC 0.35 52% Tvis 62% -23% Winter NFRC Glass Temp (70 in/0 out/15 mph) 59 °F + 15 °F Summer NFRC Glass Temp (75 in/90 out) 90 °F - 5 °F Overall Thickness 1" No Change UltraViolet Blockage 98.6% -111% SOUTH, EAST & WEST
  • 30. Empire State Building Before And After Glass Performance North Elevation (Fifth Avenue Orientation: 29 1/2 Degrees East Of North) Before After Clear Uncoated Double Pane (1992) "Triple" SCF Glass Suspended Coated TC88 Outer Light 3/16" Clear 3/16" Clear Interspaces And Thickness 1 @ 5/8" 2 @ 5/16" Suspended Coated Film(s) None TC-88 (Double Low- e) Gas Fill Air 90% Krypton/10% Oxygen Inner Light 3/16" Clear 3/16" Clear Performance Before After Difference U-Value 0.48 0.13 -72% R-value 2.1 7.6 +261% SHGC 0.72 0.49 +32% Tvis 80% 64% -20% Winter NFRC (70 in/0 out/15 mph) Glass Temp 44 Deg F 62 Deg F + 18 Degrees F Summer NFRC (75 in/90 out) 95 Deg F 76 Deg F (LBNL) - 19 Degrees F Overall Thickness 1" 1" No Change UltraViolet Blockage 46.8% 98.6% -111%
  • 31. • Pultrusion Fiberglass Casement Frames • 1 3/8” SCT Glazing Pocket For Thermal & Acoustic Performance • R-8 SCF Glass • Warm Winter / Cool Summer • Directionally “Tuned” SCF Glass • 99.5% UV Blockage • Inside/Outside Color Freedom • 1/500th Aluminum Frame Conductivity • High Volume Pricing
  • 32. Winnipeg Church In Blizzard – Warm To The Touch Window Frames Internal Anchor Blocks
  • 33. •SCF North-South-East-West “Tuned” Glazing •Fiberglass Storefront In High Humidity Galleries •99.9% UV Blockage •62 Degree “Winter” Glass Temp •Perimeter Baseboard Heating Removal •Payback Under One Year
  • 34.
  • 35. Florian Antretter Larry Kinney, PhD – Boulder Moveable Insulating Guru
  • 36. Amory Lovins: All of the energy pumped through the Alaska Pipeline each year goes literally “out America’s windows.”