27. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 2
General Project Data Input
General Project Information
Project file name: C:Usersru_patAppDataLocalElite SoftwareDuctsize 6DSD.dsw
Project title:
Project date: Monday, November 11, 2013
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
28. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 3
System 1 "Lab3" - Input Data - Supply
Project & Default Data Trunks Runouts
Maximum desired velocity (FPM): 900 700
Material Reference: Galv Round English Galv Round English
Height constraint (in): 48 48
Width constraint (in): 0 0
Diameter constraint (in): 48 48
R-Value of insulation (Sq.ft.F/Btuh): 1.66 1.66
Duct shape: Round Round
Sizing method: EF EF
NC criteria: N/A 30
Duct System Data
Maximum system velocity (FPM): 900
Minimum system velocity (FPM): 0
Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 0.000
Temperature of air leaving coil (°F): 55
Design room temperature (°F): 75
Temperature of duct installation space (°F): 65
Altitude (ft): 0
Density (lb/cu.ft): 0.077
Friction loss per 100 ft. (in.wg): 0.100
Est. st. press. loss of central equip. (in.wg): 0.000
Maximum % supply air increase: 0
Allow increasing downstream diameters: No
Show diversified trunk flows: No
Duct diameter interval (in): 0.0
Whole number dimensions: No
Fan Data
Fan description:
Fan static pressure (in.wg): 0.000
Fan CFM: 14,678
Fan efficiency: 85
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 0
Fan blast height (in): 0
Length to first fitting (ft): 0.0
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
29. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 4
System 1 "Lab3" - Trunk Input Data - Supply
Trunk
Ups.
SM
Dia
Hei
Wid
Length
Max.Vel
Fit 1
Fit 2
Junc fit
#Fit
#Fit
#Fit
Shape
Add.Loss
R-Value
Active
Take Off
Per.Div
Material Ref.
Roughness
A1 48.0 6.00 CD3-10 1 Round Yes Galv Round English
FAN 48.0 900 CD3-10 0.00 0 0.00050
EF 0.0 PLENUM 1 1.66 0
O7 48.0 27.50 CD3-10 1 Round Yes Galv Round English
A1 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-19 1 1.66 0
O3 48.0 20.67 ---- Round Yes Galv Round English
O7 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-19 1 1.66 0
O4 48.0 14.34 CD8-1 1 Round Yes Galv Round English
O7 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-24 1 1.66 0
S3 48.0 32.50 ---- Round Yes Galv Round English
O4 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-19 1 1.66 0
R16 48.0 22.50 CD8-1 1 Round Yes Galv Round English
A1 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-18 1 1.66 0
R7 48.0 11.83 ---- Round Yes Galv Round English
R16 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-24 1 1.66 0
R10 48.0 20.00 ---- Round Yes Galv Round English
R7 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-24 1 1.66 0
R13 48.0 20.00 ---- Round Yes Galv Round English
R10 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-19 1 1.66 0
R6 48.0 8.25 ---- Round Yes Galv Round English
R16 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-24 1 1.66 0
R3 48.0 20.00 ---- Round Yes Galv Round English
R6 48.0 900 ---- 0.00 0 0.00050
EF 0.0 SD5-19 1 1.66 0
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
30. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 5
System 1 "Lab3" - Runout Input Data - Supply
Runout
Ups.
SM
Dia
Hei
Wid
Length
Max.Vel
Fit 1
Fit 2
Fit 3
#Fit
#Fit
#Fit
Shape
Add.Loss
R-Value
Active
Take Off
NC Level
Material Ref.
Roughness
Dif.Loss
O1 48.0 15.00 CD3-10 1 Round Yes Galv Round English
O3 48.0 600 ---- 0.00 0 0.00050
EF 0.0 ---- 1.60 19 0.020
O2 48.0 15.00 CD3-10 1 Round Yes Galv Round English
O3 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.60 19 0.020
O5 48.0 15.00 CD3-10 1 Round Yes Galv Round English
O4 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.60 19 0.020
O6 48.0 15.00 CD3-10 1 Round Yes Galv Round English
O4 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.60 19 0.020
S1 48.0 15.00 CD3-10 1 Round Yes Galv Round English
S3 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.60 13 0.020
S2 48.0 15.00 CD3-10 1 Round Yes Galv Round English
S3 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.60 13 0.020
R1 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R3 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R2 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R3 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R4 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R6 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R5 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R6 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R8 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R7 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R9 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R7 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R11 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R10 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R12 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R10 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R14 48.0 10.00 CD3-10 1 Round Yes Galv Round English
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
31. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 6
System 1 "Lab3" - Runout Input Data - Supply (cont'd)
Runout
Ups.
SM
Dia
Hei
Wid
Length
Max.Vel
Fit 1
Fit 2
Fit 3
#Fit
#Fit
#Fit
Shape
Add.Loss
R-Value
Active
Take Off
NC Level
Material Ref.
Roughness
Dif.Loss
R13 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
R15 48.0 10.00 CD3-10 1 Round Yes Galv Round English
R13 48.0 700 ---- 0.00 0 0.00050
EF 0.0 ---- 1.66 30 0.020
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
33. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 8
System 1 "Lab3" - Trunk Output Data - Supply (cont'd)
Trunk
Upstr
Vel
CFM
Dia
Hei
Wid
Len
SM
TOA
Ref
L/100
Reg
Gau
Mat
Shape
Fit.1
Fit.2
Ups.Junc
Qty
Qty
Ups.Sh
Coef
Coef
Coef
Fit
------
Loss
Loss
Loss
Sect1
------
Equip
Add.L
F.Tot
Dynam
Sect2
------
Dynam
Fric
Total
Cumul
------
Vel.P
Stat
Total
Press
------
Veloc
Stat
Total
R6 26.0 EF 0.035 Rnd Rnd 0.000 0.052 0.068 0.046
R16 23.8 0 -0.046 ---- 0.000 0.003 0.058 0.057
844 23.8 22 ---- 0.052 0.055 0.125 0.103
3,112 8.3 Galv Round
English
SD5-18-MN 1.134 0.052 0.052
R3 18.0 EF 0.060 Rnd Rnd 0.000 0.007 0.063 0.050
R6 16.5 0 -0.011 ---- 0.000 0.012 0.081 0.034
881 16.4 24 ---- 0.007 0.019 0.144 0.084
1,556 20.0 Galv Round
English
SD5-24-MN 0.132 0.007 0.007
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includes loss through
central equipment and any loss carried from return system.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstream runout with
highest static pressure minus that of this trunk. For supply, main trunk velocity pressure minus that of this
trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in route starting with
downstream runout with highest static pressure through this trunk. For supply, sum of all upstream trunk
losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
36. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 11
System 1 "Lab3" - Runout Output Data - Supply (cont'd)
Runout
Conn
Vel
CFM
Dia
Hei
Wid
Len
Orif
SM
TOA
Ref
R.NC
L/100
Reg
Gau
Mat
Act.NC
Shape
Fit1
Fit2
Fit3
Ups.Junc
Qty
Qty
Qty
Qty
Ups.Sh
Coef
Coef
Coef
Coef
Fit
------
Loss
Loss
Loss
Loss
Sect1
------
Diff.
Add.L
F.Tot
Dynam
Sect2
------
Dynam
Fric
Total
Cumul
------
Vel.P
Stat
Total
Press
------
Veloc
Stat
Total
R15 16.0 EF 0.030 Rnd Rnd 0.020 0.049 0.093 0.020
R13 14.6 0 -0.019 CD3-10 1 0.067 0.001 0.000 0.003 0.115 0.000
557 14.6 24 ---- 0.029 0.052 0.208 0.020
778 10.0 Galv Round
English
---- 0.049
16.00 30 30 SD5-19-MN 1 1.370 0.027
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser.
"Add.L" = User entered additional static pressure loss.
"F.Tot" = Total of all the fitting static pressure losses.
"Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column.
"Fric" = Static pressure loss due to the inside surface roughness (friction).
"Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply, velocity
pressure of main trunk minus that of this duct.
"Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum of all upstream
trunk losses plus this runout's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit.
"Total" = Velocity pressure plus static pressure available.
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
37. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 12
System 1 "Lab3" - Output Summary - Supply
Number of active trunks: 11
Number of active runouts: 16
Total system weight (lb.) minus fittings: 3,215.92
Total outlet flow 14,680
Total outlet flow after heat gain 14,680
Size of largest trunk: 45.0
Size of smallest trunk: 18.0
Size of largest runout: 20.0
Size of smallest runout: 16.0
Maximum static pressure loss occurs in route to runout: R14
Cumulative static pressure loss at above runout: 0.115
Isolate Return From Supply Option: No
Return SP Loss Added to 1st Trunk of Supply: 0.000
Available static pressure at above runout: 0.000
Fan static pressure: 0.115
Fan velocity pressure: 0.113
Fan total pressure: 0.228
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM
38. Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
Concordia University
Montreal, QC H3G 2E9 Page 13
System 1 "Lab3" - Pressure Changes Graph
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.22
0.24
Pressure,in.wg
Pressure Changes Through Route with Highest Static Pressure Loss
Static Pressure Available
Total Pressure Available
A
B C
D
E
F
G
Note: Return side point values are at entrance of duct, while supply side points are at exit. When a return system is
present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure available at
the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan Exit] is drawn
to show the static pressure available at the exit of the fan.
Point Name Static Pressure Available Total Pressure Available
A [Fan Exit] 0.115 0.228
B A1 0.108 0.221
C R16 0.107 0.158
D R7 0.059 0.104
E R10 0.045 0.090
F R13 0.022 0.072
G R14 0.000 0.020
E:BLDG 471 LABSuntitled folderDSD.dsw Monday, November 11, 2013, 4:15 PM