1. Integrated Controls
Synchronous Generator
Heat Recovery
Inlet Guide Vanes
Recuperator
Turbine
Engine
KEY FEATURES
333 kW Continuous Onsite Electrical Power with Integrated Heat Recovery
CHARACTERISTIC SPECIFICATION
ELECTRICAL PERFORMANCE*
RUGGED GAS TURBINE
SYNCHRONOUS GENERATOR
PATENTED RECUPERATOR
COMBINED HEAT AND POWER
Nominal Heat Rate
(HHV)
11,552 Btu/kWh (12.2 MJ/kWh)
w/o gas booster
11,909 Btu/kWh (12.6 MJ/kWh)
w/ gas booster
Nominal Heat Rate
(LHV)
10,502 Btu/kWh (11.1 MJ/kWh)
w/o gas booster
10,827 Btu/kWh (11.4 MJ/kWh)
w/ gas booster
Voltage 480 VAC / 400 VAC
Frequency 60 Hz / 50 Hz
Type of Service 3 phase, wye, 4 wire
Grid-isolated Regulation
(Steady State)
± 0.50% nominal voltage
± 0.30 Hz nominal frequency
Transient Handling
(Linear Loads)
(Recovery within 5 sec)
± 10% nominal voltage max
± 5 Hz frequency max
EfficiencyLHV(±2pts)
PowerkWe(±15kW)
Air Inlet Ambient Temperature
Efficiency
Power
-40 -29 -18 -7 4 16 27 38 49
°C
22%
25%
28%
31%
34%
37%
40%
-40 -20 0 20 40 60 80 100 120
°F
100
150
200
250
300
350
400
Percent
Percent of Full Power
Fuel Turndown
Turbine Efficiency
20 30 40 50 60 70 80 90 100
0
10
20
30
40
50
60
70
80
90
100
Combustor
FLEX TURBINE™ GT333S
Ultra-clean electricity and useful thermal energy from a rugged and
efficient gas turbine - Now with increased power and efficiency.
• New uprated unit derived from GT250S with over two million hours
of fleet operating experience
• New compressor increases power and efficiency
• New inlet guide vanes increase efficiency at part-load conditions,
ideal for off grid load following
• Synchronous generator ideal for off-grid oil & gas applications
• Grid-parallel, Grid isolated, or Dual-mode operation
• Low emissions exceed stringent environmental standards
• Integrated, variable-output, waste-heat recovery unit available
Electrical efficiency (± 2 pts)
Electrical power** (±15 kW)
32.5% LHV without gas booster
333 kW nominal
* At ISO Conditions (59°F [15°C] @ sea level, 60% RH) unless otherwise noted, pipeline natural gas only.
** Elevation derate of approximately 8.80 kW per 1000 ft (305 m).
There is a 3 kW power reduction when utilizing waste heat recovery (cogen).
• Back-to-back rotating components
• Proven oil-lubricated bearings
• High H2S tolerance up to 6500 ppmv
• Same technology utilities use to power the grid
• High load starting capability up to 125 hp DOL
• Critical to high system efficiency
• Compact rugged design
• Controllable output level
• Integral heat recovery unit contained within turbine
enclosure
• No ducting