11. EMCOR Facilities Services
Summery page
06/12/2014
Cabinet 1:
All batteries are showing good
Cabinet 2:
All batteries are showing good
Cabinet 3:
N/A
Summery:
UPS appears to be in very good working condition. No problems found.
If There are any questions please feel free to contact me
Joe Tate
EMCOR Facilities
Broomfield Brocade
303-884-1536
Replaced Filter Media.
12. UPS Name
Installation
Date:
Age in
months:
Battery Date
Code
Battery Age in
months
DC Oil filled
Capss:
DC_O age in
months
AC Oil filled
Caps:
AC_O age in
months
Filters:
Filters Age in
months:
Firmware:
Firmware age
in months*
DC Electrolitic
Caps
DC_E age in
months
06/17/15
UPS DC1 3/1/2013 28 3/1/2013 28 3/1/2013 28 3/1/2013 28 6/18/2015 0 3/1/2013 28 3/1/2013 28
UPS DC2 6/10/2009 73 1/1/2013 30 6/10/2009 73 6/10/2009 73 6/17/2015 0 1/1/2013 30 6/10/2009 73
UPS OEM 8/22/2003 144 3/1/2014 16 5/24/2010 62 5/24/2010 62 6/16/2015 0 5/24/2010 62 8/22/2003 144
UPS SQA 8/22/2003 144 5/15/2015 1 5/24/2010 62 5/24/2010 62 6/16/2015 0 5/24/2010 62 8/22/2003 144
Watch closely at: 200 48 72 72 9 60 200
Recommend replace: 224 60 84 84 12 80 224
Needs Replacing!!! 248 72 96 96 15 100 248
* Firmware may not be available for older models. Contact OEM for details.
14. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
Inspection Summary
File name UPS DC1 (1).is2 Inspection Date and Time 1/1/2000 3:45:56 PM
Severity
File name UPS DC1 (2).is2 Inspection Date and Time 1/1/2000 3:46:29 PM
Severity
File name UPS DC1 (3).is2 Inspection Date and Time 1/1/2000 3:46:47 PM
Severity
File name UPS DC1 (4).is2 Inspection Date and Time 1/1/2000 3:47:17 PM
Severity
File name UPS DC1 (5).is2 Inspection Date and Time 1/1/2000 3:47:38 PM
Severity
File name UPS DC1 (6).is2 Inspection Date and Time 1/1/2000 3:47:57 PM
Severity
15. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
UPS DC1 (1).is2
1/1/2000 3:45:56 PM Visible Light Image
Graph
Image Info
IR Sensor Size 160 x 120
16. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
UPS DC1 (2).is2
1/1/2000 3:46:29 PM Visible Light Image
Graph
Image Info
IR Sensor Size 160 x 120
17. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
UPS DC1 (3).is2
1/1/2000 3:46:47 PM Visible Light Image
Graph
Image Info
IR Sensor Size 160 x 120
18. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
UPS DC1 (4).is2
1/1/2000 3:47:17 PM Visible Light Image
Graph
Image Info
IR Sensor Size 160 x 120
19. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
UPS DC1 (5).is2
1/1/2000 3:47:38 PM Visible Light Image
Graph
Image Info
IR Sensor Size 160 x 120
20. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
UPS DC1 (6).is2
1/1/2000 3:47:57 PM Visible Light Image
Graph
Image Info
IR Sensor Size 160 x 120
21. 0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | joe_tate@comcast.net
Summary
ref#0480
BRM Broomfield UPS Testing
All Batteriy Temps and associated DC Breakers are within range for the low current that is passing
through them.
Thanks
Joe Tate
EET / Master Electrician