2. 2
Operating Room Ventilation
The supply of air to an operating room has four main functions:
⢠To dilute airborne contamination.
⢠To control air movement within the suite such that the
transfer of airborne contaminants from less clean to cleaner
areas is minimised.
⢠To control the temperature and, if necessary, the humidity of
the space.
⢠To assist the removal of, and dilute, waste anaesthetic gases.
5. 5
Inventors of Ultra Clean Ventilation
⢠In the early 1960s
Howorth Air
Technology Ltd,
working closely with
Sir John Charnley,
developed the worldâs
first UCV
6. 6
Ultra Clean Ventilation
⢠UCV â Ultra Clean Ventilation
⢠Laminar (Unidirectional) Air Systems
⢠Ultra Clean Operating Room
⢠Ultraclean Air Systems
⢠Clean Air Canopy
⢠Ultra Clean Canopy
⢠Cleanroom
⢠Charnley-Howorth System
Common Names
7. 7
Ultra Clean Air - Definition
âUltra-clean air is defined
as that containing not more
than 10 CFU/m3 â
Generally Accepted Definition
Colony-forming unit (CFU) is a measure of viable
bacterial or fungal numbers, CFU measures only
viable (live) cells
(0.3 CFU/ft3)
8. 8
Where are UCVs Used?
⢠Orthopaedics
⢠Ophthalmology
⢠Cardiothoracic Surgery
⢠Neurosurgery
⢠Transplant Surgery
⢠Endoscopy
⢠Plastic Surgery
⢠Various Day Surgeries
⢠Any invasive âCleanâ Surgery
What types of surgery are performed
under Ultra Clean Ventilation Systems?
9. 9
UCV use in Orthopaedic Surgery
⢠UCV systems are used extensively in orthopaedic operating
rooms
⢠Although Arthroplastic procedures are where UCVs are most
frequently employed. Other types of orthopaedic surgery,
including, spinal surgery and the repair of major fractures
also utilise ultra clean air systems
10. 10
The Worldâs 1st UCV System
⢠Charnleyâs solution was the
Ultra Clean Ventilation (UCV)
system
⢠Known affectionately as the
âgreenhouseâ, the system
enclosed both the patient and
the surgical team
⢠Where they were bathed in a
constant supply of filtered
clean air
12. 12
Types of UCV System in Common Use
⢠Horizontal Systems have been largely discredited and are
only very occasionally used
⢠Vertical systems fall into two main classesâŚ
⢠Utilise main ventilation air with no
additional fans
⢠Low number of air changes per hour,
typically 15 â 30 ACH
⢠Downflow velocity typically low, i.e.
less than 0.2 m/s (40 fpm)
Low Flow Systems
⢠Supplement the main ventilation air
supply with auxiliary fans
⢠High number of air changes per
hour, typically >100 ACH
⢠Downflow velocity medium to high,
i.e. 0.2 â 0.5 m/s (40 - 100 fpm)
High Flow Systems
13. 13
Air Curtain UCV
⢠The best systems utilise a central laminar air diffuser surrounded on all
four sides by an air curtain diffuser
⢠Many systems are low flow and therefore suffer from not being able to
provide adequate dilution
15. 15
Comments
⢠Developed from a cleanroom system
⢠Canadian design to Canadian & US Standards
⢠Relatively Low Velocity in centre, below HTM-03-01
requirements
⢠High velocity of air curtain air causes entrainment. (See
smoke pattern below)
⢠No examples in UK although being considered for project in
Ireland
16. 16
Partial Wall UCV with Low Level Returns
⢠Can provide good performance, providing they have a sufficiently large
area and adequate levels of flow are employed
⢠Low flow systems and undersized systems can suffer from entrainment
and poor levels of dilution
19. 19
Comments - Partial Wall UCV with Low Level Returns
⢠Principally European design
⢠Low velocity systems that need upgrading to match HTM requirements
⢠Low level recirculation ducts around theatre cause obstruction, infection
control issues, and can themselves be obstructed by theatre equipment
⢠Usually square, but can be made to different configurations
⢠Tend to utilise nylon CG screens as diffuser which are difficult to clean
and therefore present another potential infection control issue
⢠Usually a 50% recirculation of supply air means higher running costs
⢠Several units have integral cooling coils to combat air buoyancy to
achieve HTM compliance
⢠Can be costly to install due to increased infrastructure & service
requirements i.e. additional recirculation ductwork, cooling coils, chilled
water pipework etc.
20. 20
Fully Enclosed UCV
⢠Provides very good protection providing suitable flow rates are utilised
⢠Obvious disadvantage is the restricted work area for the surgical team
⢠Rarely seen in modern operating rooms
22. 22
Comments
⢠Excellent downflow & non-entrainment characteristics.
⢠Lower CFU count at wound site than standard UCVs
⢠Extremely constricting for the theatre staff and for
equipment usage.
23. 23
Partial Wall Style of UCV
⢠This type of system is used extensively in the UK and many parts of
Europe
⢠This system utilises a partial wall and ceiling mounted returns to develop
the air flow pattern
26. 26
Comments
⢠Fully compliant with HTM 03-01
⢠Recognised standard in all orthopaedic ORs in UK
⢠Usually available in 3.5 x 3.5 m, 3.2 x 3.2m, 2.8 x 2.8m clean
zones. Although other sizes can be made to order.
⢠Side screens prevent entrainment although can be restrictive
to OR equipment choice. Sliding screen options are available
to combat this problem.
⢠Usually steel perforated diffusers which are easily cleaned
⢠No requirement for low level recirculation
⢠Modular construction of UCV allows speedy installation
⢠Performance well understood by validation engineers
27. 27
Screenless Canopy â Low Level Recirculation
⢠This type of system is used extensively in Europe, but as yet is largely
unproven in the UK
⢠This system utilises low level recirculation to develop the air flow pattern
29. 29
Low Level - Return Air Ducts
Return Duct
Inlets
Fan Housing
30. 30
Comments
⢠Principally European design
⢠Low velocity systems that need upgrading to match HTM requirements
⢠Low level recirculation ducts around theatre cause obstruction, infection
control issues, and can themselves be obstructed by theatre equipment.
⢠Usually square, but can be made to different configurations. See image
⢠Tend to utilise nylon CG screens as diffuser which are difficult to clean
and therefore present another potential infection control issue
⢠Usually a 50% recirculation of supply air means higher running costs.
⢠Several units have integral cooling coils to combat air buoyancy to
achieve HTM compliance.
⢠Can be costly to install & maintain due to increased infrastructure &
service requirements i.e. additional recirculation ductwork, cooling coils,
chilled water pipework etc.
⢠Lack of side screens improves equipment selection.
31. 31
Screenless Canopy â Integrated Recirculation
⢠The partial wall(screened) version of this system used throughout the UK
⢠This improved screenless system requires no partial wall or low level
recirculation ducts. It utilises ceiling mounted returns & patented coanda
technology to develop the air flow pattern
33. 33
Comments
⢠Fully compliant with HTM 03-01
⢠Developed & improved from standard UCV technology
therefore maintenance, running costs are low and reliability
is proven
⢠Fully integrated system i.e. no need for low level
recirculation ducts, additional fans or cooling coils.
⢠Independently validated
⢠Patented coanda technology ensures no entrainment
⢠Lack of side screens improves equipment selections
⢠Unique system to market, designed & manufactured in the
UK.
36. 36
Exflow â Exclusive Benefits
⢠Unique Exponential airflow
pattern
⢠No entrainment, even
without full side walls
⢠Up to 500 air changes an
hour
⢠Larger clean zone protects
instruments
⢠Graded air flow, higher
central velocity overcomes
thermal plumes
37. 37
Exflow â Further Benefits
⢠Greater patient protection
⢠Improved OR staff comfort
⢠Reductions in post-operative
infection
⢠Less revision surgery
⢠Improved OR utilisation
⢠Reduced litigation risk
40. 40
Body Exhaust Systems
⢠Originally invented by Sir John Charnley & Hugh Howorth at
the same time as the first UCV
⢠Designed to remove contaminants from the
immediate vicinity of the surgeon before
they become airborne
⢠Works by generating a local vacuum, pulling
in shedded skin cells through a distribution
pipe worn on the body
⢠The pipe is connected back to the UCV
41. 41
Body Exhaust Systems
⢠A more advanced version
incorporates a mask &
helmet
⢠This improves patient
protection & adds a comms
system
⢠It also affords the surgeon a
level of protection from
blood splatter & flying bone
debris
42. 42
Body Exhaust Systems
⢠Numerous trials have indicated that the body exhaust
system can provide an enhanced level of operating room air
cleanliness
⢠In use with Howorthâs Exflow system, level of less than 1
CFU/m3 have been measured
43. 43
Microbiological Air Sampling â Typical Results
1
10
100
CFU/Cubicmeter
Normal OR Exflow Exflow + OC Exflow + BEX
OR - Operating Room BEX â Body Exhaust
OC â Occlusive Clothing CFU â Colony Forming Unit
Key
50 - 250
5 - 10
< 5
1
45. 45
Relevant European Guidelines
⢠HTM 03-01, Specialised ventilation for healthcare premises
â A UK Guideline that is extensively followed, Revised in 2007
⢠VDI 2167, Building services in hospitals, HVAC Code of
Practice
â A German standard also adopted in some other European Countries
⢠DIN 1946 T4
â A German standard also adopted in some other
European Countries, has just had a major rewrite
and has adopted many aspects of HTM-030-01