PCSVN1420A
All rights reserved 07/14 SS
c
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a quali ed installer or contractor to install this product. Do not try to install the product by yourself.
Improper installation can result in water or refrigerant leakage, electrical shock re or explosion.
Use only those parts and accessories supplied or speci ed by Daikin. Ask a quali ed installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
sho re or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
notice.
Đại lyù phaân phoái:
Miễn phí cöôùc cuoäc goïi
TRUNG TÂM
DICH VU KHÁCH HÀNG
RNQ26MV1
Outdoor unit
Indoor unit FDMNQ26MV1
RNQ26MY1 RNQ30MV1
FDMNQ30MV1
RNQ30MY1 RNQ36MV1
FDMNQ36MV1
RNQ36MY1 RNQ42MY1
FDMNQ42MV1
RNQ48MY1
FDMNQ48MV1
RNQ21MV1 RNQ26MV1
RNQ18MV1
Outdoor unit
Indoor unit
DUCT
CONNECTION
LOW STATIC
PRESSURE
TYPE
MIDDLE STATIC
PRESSURE
TYPE
FDBNQ18MV1 FDBNQ21MV1 FDBNQ26MV1
RNQ26MY1
RNQ26MY1
RNQ21MV1
RNQ18MV1
Outdoor unit
Indoor unit
CEILING SUSPENDED TYPE
FHNQ18MV1 FHNQ21MV1 FHNQ26MV1 FHNQ30MV1 FHNQ36MV1 FHNQ48MV1
FHNQ42MV1
1 2
26
21
RNQ21MV1 RNQ26MV1
18
RNQ18MV1
13
09
Outdoor unit
Indoor unit
CEILING MOUNTED
CASSETTE TYPE
Round Flow
Series
Pair
FCNQ18MV1
RNQ13MV1
FCNQ13MV1 FCNQ21MV1 FCNQ26MV1
RNQ26MY1
30
RNQ30MV1
FCNQ30MV1
RNQ30MY1
36
RNQ36MV1
RNQ26MV1 RNQ30MV1 RNQ36MV1
FCNQ36MV1
RNQ36MY1
42
RNQ42MY1
FCNQ42MV1
48
26,000
21,000
18,000/17,700*1
13,000
9,200
Btu/h 30,000 36,000/35,000*2
42,600/42,000*2,3
48,000
7.6
6.2
5.3/5.2*1
3.8
2.7
kW 8.8 10.6/10.4*2
12.5/12.3*2,3
14.1
RNQ48MY1
RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1
FCNQ48MV1
Outdoor unit
OUTDOOR UNIT
P r o d u c t L i n e u p
RNQ13MV1
FHNQ13MV1
RNQ13MV1
FDBNQ13MV1
RNQ09MV1
FDBNQ09MV1
New wide lineup of SkyAir series.
Note : *1
Applicable to FDBNQ series. *2
Applicable to FHNQ series. *3
Applicable to FDMNQ series.
RNQ09MV1 RNQ13MV1 RNQ18MV1 RNQ21MV1 RNQ26MV1 RNQ26MY1 RNQ30MV1 RNQ30MY1 RNQ36MV1 RNQ36MY1 RNQ42MY1 RNQ48MY1
Airflow
distribution
Creates uniform
comfort throughout
the space
Comfort enhanced by Round Flow!
With uniform temperature
distribution
Enhanced Comfort
Greater comfort
Improved energy saving
• Condition after exposure
to the smoke of 600
cigarettes in 1 m3
enclosed space.
Treated
surface
Untreated
surface
Grimy
surface
Resists
soiling
External panels are treated with a coating that
repels dirt.
Avoids uneven temperature and discomfort caused by drafts.
To prevent dirt sticking to the
external panels, they have
been coated with a surface
treatment.
Because air flows out from corner outlets, comfort spreads more widely.
360° airflow Air movement is gentle with Round Flow
Condensation does not easily form on and dirt does not
cling to non-flocking flaps.
It is easy to clean.
Non-flocking flaps
Prevents mould and microorganisms growing out of the dust and
moisture that adheres to the filters.
Filter has anti-mould and bactericidal treatment
Grime prevention and bactericidal coating: Make cleaning easier.
Adapts easily to the installation space.
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to
close each unused outlet.
3-way flow
L-shaped
2-way flow
Opposite
2-way flow
(E.g., installed in
a corner)
(E.g., installed in
a long room)
(E.g., installed
near a wall)
(E.g., installed in
middle of ceiling)
4-way flow also possible.
All-round flow
360° airflow can
maintain comfort
even if air
discharge speed is
lower.
Typical flow patterns There are a total of 23 flow patterns.
If you raise the set
temperature by 1 to
1.5°C,and velocity is
decreased by 25%,
you still obtain the same
feeling temperature and
comfort.
Operation sound increases when using 2-way or 3-way flow.
• • • • • *1
• *4
• • • • • • • • *6
Cleanliness
Comfort Work & Servicing Control features Others
Options
Features
Accessory required for indoor unit.
Option
*1
Applicable when wired remote controller is used
*2
Applicable when BRC1E62 is used
*3
Applicable when BRC1C61 is used
*4
Applicable to RNQ30-48M outdoor units
*5
Applicable to RNQ13-26M outdoor units
*6
For the outdoor units
CEILING MOUNTED CASSETTE TYPE
FCNQ13/18/21/26/30/36/42/48MV1
Swing
pattern
selection
Switchable
fan
speed
(2
step)
Auto
swing
Programme
"Dry"
High
ceiling
application
Drain
pump
mechanism
•
Anti-bacterial
air
filter
Pre
charged
for
up
to
15
m
*5
Pre
charged
for
up
to
10
m
Long-life
filter
Filter
sign
Ceiling
soiling
prevention
Ultra
long-life
filter
•
High-efficiency
filter
Fresh
air
intake
kit
Control
by
2
remote
controllers
Auto-restart
Group
control
by
1
remote
controller
•
External
command
control
•
Central
remote
control
•
Interlock
control
•
DIII-NET
communication
standard
Anti
corrosion
treated
heat
exchangers
Two
selectable
temperature-sensors
Round Flow
BRC1E62
Navigation Remote Controller
(Wired Remote Controller)
BRC7F633F
A signal receiver must be added to the indoor unit.
Wireless remote controller and signal
receiver unit are sold as a set.
Wireless LCD remote controller
Signal receiver unit
(Installed type)
Note: Remote controller cable not
included. Cables must be
procured locally.
Note: Remote controller cable not
included. Cables must be
procured locally.
Wired LCD remote controller
BRC1C61
3 4
Remote controller
*2 *2 *2 *2 *3
Setpoint
range
set
Weekly
schedule
timer
Setpoint
auto
reset
Off
timer
(programmed)
On/Off
timer
Cassette air conditioner with 360°
uniform airflow sets the standard
Cassette air conditioner with 360°
uniform airflow sets the standard
43/32dB(A)
FCNQ36M
(220V)
High Low
Sound level
Options required for specific operating environments
High-efficiency filter
Available in two types: 65% and 90% colorimetry.
Using this kit, a
duct can be fitted
to increase the
intake of outdoor
air.
*Connecting ducts, insect nets, fire dampers, air filters, and other
parts should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary.
Optional PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced
through the kit is limited to 10% of the maximum airflow rate of the
indoor unit. Introducing higher quantities will increase the
operating sound and may also influence temperature sending.
Fresh air intake kit
Even in smoky environments where
the air conditioning is on most of
the time, the ultra long-life filter only
has to be changed once a year.
Ultra long-life filter Panel spacer
Use when only minimal space is available between drop
ceilings and ceiling slabs.
Sealing material of air discharge outlet
Sealing material block air discharge openings not used in
2-way or 3-way blow.
Branch duct (direct-connection round duct)
Outside
Note: Use of options will increase operating sound.
The units can be installed in the following different ways.
Note: Some ceiling constructions may hinder installation.
Contact your Daikin Dealer before installing your unit.
Direct installation type
Flexible duct
T-joint pipe
Intake duct
(procured locally)
(duct length: 4 m max.)
Intake duct
(procured locally)
(duct length: 4 m max.)
Connection
chamber
Suction
chamber
Duct flange
(with insulation
material)
Intake duct
(procured locally)
Chamber type
(with T-joint pipe and without fan)
Flexible duct
(procured locally)
T-joint pipe
(procured locally)
Chamber type
(without T-joint pipe and fan)
KDDP55X160
KDDP55B160K
KDDP55B160
Easier to maintain
With Ultra long-life filters (option), maintenance is not required in normal shops or offices
for up to four years.
The condition of the drain pan and
drain water can be checked by
removing the drain plug and
intake grille.
Drain plug
Just open the
intake grille!
40mm
Panel spacer
A round duct can be attached without the need for a chamber.
A flanged port for direct connection of a round duct is
provided. An existing branch duct chamber can also be fitted
(square slit hole).
Connection
chamber
Suction
chamber
Smoky atmosphere: annual filter change
Ordinary store or office: filter change every 4 years
*For dust concentration of 0.3 mg/m3
(Requires separately sold Air Cleaner.)
1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year
*For dust concentration of 0.15 mg/m3
4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years
Note:
Quick and easy to install
Just 256 mm high. Installable in tight
ceiling spaces (13-26M)
Fine square panels Compact body and quiet operation
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a temperature-sensor.
Note : Anechoic chamber
conversion value, measured
according to JIS parameters
and criteria. During
operation these values are
somewhat higher owing to
ambient conditions.
Note: Air direction is set to the standard position when the unit is shipped from the factory.
The position can be changed from the remote controller.
Panel size is same for all models, FCNQ13-48M.
It is easy to maintain a neat appearance when
multiple units are installed.
Optimal comfort and convenience
assured by 2 air discharge modes
Both indoor unit and wired remote controller (option) contain temperature-
sensors. Temperature sensing can be set at the unit or, to further improve
comfort level, closer to the target area at the wired remote control. This
feature must be set during commissioning by the technicians.
Two selectable temperature-sensors
Even in spaces with high ceilings, a comfortable airflow is carried down to
the floor level.
Suitable for high ceilings
Operation starts when the preset time of the ON timer elapses and stops
when the preset time of the OFF timer elapses.
On/Off timer
Indoor unit High Low
dB(A)
13/18M 31 28
21/26M 35 28
30/36M 43 32
42M 44 34
48M 44 36
Same for
all models
Air direction
Auto air
direction control
Settable to 5 different
levels between 15° and 60°
Settable to 5 different
levels between 25° and 60°
Auto-swing between
15° and 60°
Auto-swing between
25° and 60°
Recommended for shops with
light coloured ceilings that
must be kept spotless.
Standard position to
prevent draft.
Standard setting Setting to prevent soiling of ceiling*
The air direction is set automatically to the
memorised position of the previous air direction.
Desired
situation
Auto-swing
5-levels
air direction
setting
*Closing of the corner discharge outlets is recommended.
Number of air discharge outlets used
4-way
flow
3-way
flow
2-way
flow
4-way
flow
3-way
flow
2-way
flow
3.1 m
3.4 m
4.0 m
All round
flow
2.7 m
3.0 m
3.5 m
3.0 m
3.3 m
3.5 m
3.5 m
3.8 m
-
3.4 m
3.9 m
4.5 m
All round
flow
3.2 m
3.6 m
4.2 m
3.6 m
4.0 m
4.2 m
4.2 m
4.2 m
-
Standard
Ceiling
height
High ceiling
High ceiling
Criteria for ceiling height and number of air discharge outlets
950 mm 950 m
m
Note: Factory settings are for standard ceiling height and all-round flow.
High ceiling settings (1) and (2) are set with the remote controller by field setting.
256 mm *1 266 mm *2
*1 298 mm high with 30-48M
*2 308 mm high with 30-48M
All models can be installed without
using lifter because of the light weight.
Drain pump is equipped as standard
accessory with 850 mm lift.
Transparent drain socket
Each corner of the unit has an Adjuster Pocket that
lets you easily adjust the unit's suspended height.
Since the orientation of
the intake grill can be
adjusted after installing,
the direction of the intake
grill lines can be unified
when multiple units
are installed.
Note: If the wireless remote control option is installed, a light receptor
unit is housed in one of the adjuster pockets.
Easy height adjustment
Installable in
any direction
Because the drain socket is
transparent, after the drain piping
has been installed, it is easy to
check if the drain come out
through the socket.
High setting provides maximum reach while low
setting minimises drafts.
Switchable fan speed: High/Low
175 mm
850 mm
30-48M
13-26M
5 6
CEILING MOUNTED CASSETTE TYPE Round Flow
(Ceiling height is reference value)
Connection to a centralised control
system is available without option
* For dust concentration of 0.15 mg/m
3
(mm)
Uses quiet stream fan and other quiet
technologies.
Turbulent flow
is reduced
Straightening
plate
Quiet
stream fan
50°
18/21M 44 40
26/30M 45 40
36/42M 48 42
48M 49 43
Indoor unit High Low
13M 43 39
195
960 1,160
680
Height
Indoor unit
Width
Depth
13M 18/21M
1,400 1,590
26/30M 36/42/48M
Quiet operation
Easier to maintain
Sound operation has been reduced on the exposed
ceiling suspended type unit.
Oil resistant grille
Note: Intended for use in salons, dining rooms, and ordinary sales
floors, this specification is not suitable for kitchens or other
harsh environments.
Oil-resistant plastic is used for the air suction grille.
This satisfies durability in restaurants and other
similar environments.
For all maintenance tasks, access is
from bottom surface.
Two time settings (2500 hrs and 1250 hrs) are available to match
the installation environment. Maintenance time warning is
displayed on the remote controller (filter sign).
It is easy to wipe dirt off the flat side and lower
surfaces of the unit.
Easy-clean, flat surfaces
Long-life filter lasts about 1 year*
Diffuses comfortable air
throughout the room
Installation flexibility for
freedom of design
Dehumidification is microprocessor controlled to prevent abrupt and
uncomfortable changes in air temperature.
Programme "Dry"
Auto-swing (up&down) brings comfort to the room.
Wide air discharge
openings produce a
spreading 100° airflow
Air is blown up to 50° in
the downward direction.
Switchable fan speed: High/Low
Installable on
ceilings 3.5 m high
100°
*Water used in the test-run can now be drained from
the air discharge opening rather than from the side
as was formerly the case.
The unit fits more snugly into tight spaces.
Flexible installation
Uniform height and depth. Compact design for
small-capacity models to meet tighter dimensional
constraints.
30 mm
or more
30 mm
or more
Note : Anechoic chamber conversion value, measured according to JIS
parameters and criteria. During operation these values are somewhat higher
owing to ambient conditions.
(220V) dB(A)
Pipes more easily rigged
Plastic cover is used to conceal piping work holes.
When piping work the cover is easily taken off, and after piping work
easily attached again to conceal the holes.
All wiring and internal servicing can be done from
under the unit
Non-flocking flap
Condensation does not easily
form on and dirt does not
cling to non-flocking flap.
It is easy to clean.
Non-flocking flap
CEILING SUSPENDED TYPE
7 8
Upgrade to a quiet and
compact system.
Upgrade to a quiet and
compact system.
Accessory required for indoor unit.
Option
Wired LCD remote controller
Features
*1
Installable on max. 3.5 m high ceiling
*2Applicable to RNQ30-48M outdoor units
*3Applicable to RNQ13-26M outdoor units
*4
For the outdoor units
• • • *1
• • *4
Cleanliness
Comfort Work & Servicing Control features Others
Switchable
fan
speed
(2
step)
Auto
swing
Programme
"Dry"
High
ceiling
application
•
Anti-bacterial
air
filter
*3
Pre
charged
for
up
to
10
m
*2
Pre
charged
for
up
to
15
m
Long-life
filter
Auto-restart
Anti
corrosion
treated
heat
exchangers
Remote controller
•
On/Off
timer
FHNQ13/18/21/26/30/36/42/48MV1
44/40dB(A)
FHNQ21M
(220V)
High Low
Sound level
BRC7NU66
A signal receiver must be added to the indoor unit.
Note: Remote controller cable not
included. Cables must be
procured locally.
Wireless remote controller and signal
receiver unit are sold as a set.
Wired LCD remote controller
Wireless LCD remote controller
BRC1NU61
Signal receiver unit (Installed type)
Quiet operation Quiet operation
9 10
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Freedom of layout
BRC4C64
A signal receiver must be added to the indoor unit.
Wireless remote controller
and signal receiver unit
are sold as a set.
Wireless LCD remote controller
Wired LCD remote controller
BRC1C61
Accessory required for indoor unit
Option
Signal receiver unit
(Separate type)
Switchable fan speed: High/Low
Drain pipe connection can be done inside
the unit. Refrigerant and drain pipe outlets
are at the same opening.
The duct system allows the efficient location
of discharge outlets in accordance with the
room layout
Duct connection is simpler with standard rear
intake chambers
BRC1E62
Navigation Remote Controller
(Wired Remote Controller)
Indoor unit High Low
21/26M 43 40
09/13/18M 41 38
(220V) dB(A)
Indoor unit High Low
30M 44 36
26M 42 38
42/48M 46 37
36M 45 37
(220V) dB(A)
BRC4C64
A signal receiver must be added to the indoor unit.
Wireless remote controller
and signal receiver unit
are sold as a set.
Wireless LCD remote controller
Wired LCD remote controller
BRC1C61
Accessory required for indoor unit
Option
Signal receiver unit
(Separate type)
BRC1E62
Navigation Remote Controller
(Wired Remote Controller)
FDBNQ09/13/18/21/26MV1 FDMNQ26/30/36/42/48MV1
DUCT CONNECTION LOW STATIC PRESSURE TYPE
45/37dB(A)
FDMNQ36M
(220V)
High Low
Sound level
43/40dB(A)
FDBNQ26M
(220V)
High Low
Sound level
Ideal for quiet, beautiful living spaces Unit can be mounted in the ceiling and air can be
delivered freely by duct.
Suitable for condominiums and apartments,
houses and hotels
• • *1
• • • *4
Comfort Work & Servicing Control features Others
Features
*1
Applicable when wired remote controller is used
*2
Applicable when BRC1E62 is used
*3
Applicable when BRC1C61 is used
*4
For the outdoor units
Switchable
fan
speed
(2
step)
Programme
"Dry"
*4
Pre
charged
for
up
to
10
m
Control
by
2
remote
controllers
Auto-restart
Group
control
by
1
remote
controller
Anti
corrosion
treated
heat
exchangers
Two
selectable
temperature-sensors
Remote controller
*2 *2 *2 *2 *3
Setpoint
range
set
Weekly
schedule
timer
Setpoint
auto
reset
Off
timer
(programmed)
On/Off
timer
• • *1
• • • *6
Comfort Work & Servicing Control features Others
Features
*1
Applicable when wired remote controller is used
*2
Applicable when BRC1E62 is used
*3
Applicable when BRC1C61 is used
*4
Applicable to RNQ30-48M outdoor units
*5
Applicable to RNQ26M outdoor units
*6
For the outdoor units
Switchable
fan
speed
(2
step)
Programme
"Dry"
*4
Pre
charged
for
up
to
15
m
*5
Pre
charged
for
up
to
10
m
Control
by
2
remote
controllers
Auto-restart
Group
control
by
1
remote
controller
Anti
corrosion
treated
heat
exchangers
Two
selectable
temperature-sensors
Remote controller
*2 *2 *2 *2 *3
Setpoint
range
set
Weekly
schedule
timer
Setpoint
auto
reset
Off
timer
(programmed)
On/Off
timer
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
Ventilation grille
Door-installed
ventilation grille
Ventilation grille
Wall-installed
ventilation grille
Under-door cutout
Under-door cutout
When air conditioning two rooms
simultaneously, the air discharged into each
room must be circulated back to the air
conditioner. To achieve this, a ventilation duct
should be installed for each room or one of the
indicated ventilation grilles should be installed
on the partitioning wall or under the door
between the rooms.
Ventilates air through
the partitioning wall.
(See right)
Partitioning wall
Note: The under-door cutout method should be used only when there is a small volume of airflow.
(This feature also applies to duct connection middle static pressure type.)
Compact
Small, lightweight, and easy-to-install indoor unit.
Suction chamber
Air filter
(Note)
[Duct connection]
or more
or more
or more
To prevent increased
operation sound,
avoid installing the
air suction grille
directly below the
suction chamber.
Note : 270 mm is the minimum size.
Extra height is necessary for drain piping slope and insulation.
Note : 325 mm is the minimum size.
Extra height is necessary for drain piping slope and insulation.
Air conditioner
305 mm
Ordinary duct
(procured locally)
Air discharge Air intake
(Note)
or more
or more
or more
325
325 mm
mm
325 mm
Ordinary duct
(procured locally)
OUTDOOR UNIT
Quiet Operation
Fitted with Super Aero Grille
To suppress turbulence
and achieve quiet
operation, the curved
ribs of the grille are
optimised to meet the
outflow of air.
Equipped with scroll compressor
for quiet operation
Smooth running, minimal
vibration, low operating
sound.
Allowed refrigerant piping length and level difference
Max. length
Max. level
difference
Pre charged1
RNQ09/13M RNQ18/21M RNQ26M RNQ30-48M
10 m
30 m
10 m 15 m 20 m 30 m
30 m
(Equivalent length
50m)
50 m
(Equivalent length
70m)
15 m
(Applies to RNQ30-48M)
Installation and
maintenance
Pre charged for up to 15 metres
If refrigerant piping length does not exceed 10m (RNQ09-26M), 15m
(RNQ30-48M), there is no need for on-site gas charging.
Durability
As the bottom frame is subject to corrosion,
corrosion-proof galvarium steel plate is adopted
to enhance the durability.
Heat exchange fins provided with anti-corrosion
treatment
11 12
RNQ09MV1
RNQ13MV1
RNQ18MV1
RNQ21MV1
RNQ26MV1
RNQ26MY1
RNQ30MV1
RNQ30MY1
RNQ36MV1
RNQ36MY1
RNQ42MY1
RNQ48MY1
Operation sound
dB(A)
(Applies to RNQ42-48M)
(Applies to RNQ30-48M)
(Applies to RNQ09-26, 36-48M)
4-direction piping offers greater
layout freedom
The outer panel for the piping connection
part of the front, right side and backside
can be removed and is easier for
post-installation piping work.
(Applies to RNQ30-48M)
Note:
1
Additional refrigerant charging is required if the refrigerant pipe is longer than the
length.
Outdoor unit Sound level
RNQ09MV1 48
RNQ13MV1 49
RNQ18MV1 51
RNQ21MV1 52
RNQ26MV1/RNQ26MY1 54
RNQ30MV1/RNQ30MY1 55
RNQ36MV1/RNQ36MY1 54
RNQ42MY1 56
RNQ48MY1 58
Construction
Non-treated fin
Anti corrosion
treated heat
exchangers
Aluminium
Aluminium
Corrosion resistant
acrylic resin
Hydrophilic film
(In case of RNQ09-21M:220-240 V, RNQ26-36M:220 V/380 V,
240 V/415 V, RNQ42-48M:380 V, 415 V)
Separation
available
Central remote controller
Easily adaptable to large-scale, high-function,
centralised remote control system.
Centralised control, with setting as
simple as it is with a standard
remote controller, of up to 64 groups
(1,024 indoor units) is possible.
DCS302CA61 (Option)
With its high functionality, the full
colour “all-in-one” graphic controller
facilitates management of SkyAir
System in a variety of ways.
DCS601C51 (Option)
Unified on/off controller
Centralised control of on/off by
group or all at once for up to 256
indoor units.
DCS301BA61 (Option)
Schedule timer
Unified control of weekly schedule
for up to 1,024 indoor units.
DST301BA61 (Option)
Schedule timer sets on/off time in 1 minute units
to be executed twice a day for a week at a time.
Simple system provides a diverse assortment of control modes.
Control by 1
remote
controller
Control
pattern
Applicable
model
FCNQ
FDBNQ
FDMNQ
Wired remote controller Wireless remote controller
Control by 2
remote
controllers
Group
control
Control by
external
command
Centralised
remote
control
Interlock
control
with Heat
Reclaim
Ventilator
(Basic system)
Control by 1 wireless remote
controller and 1 wired remote
controller (See note 2, 3)
Signal receiver unit installed
on indoor unit
Signal receiver unit installed
on indoor unit
Can be operated simultaneously
or independently by remote controller
(set by ventilation mode)
Heat Reclaim
Ventilator
Non-polar, double-core
(max. wiring length 500 m)
Connects 2 wired remote
controllers (See note 1)
Automatic address setting function Automatic address setting function
Signal receiver unit installed
on 1 indoor unit
Optional wiring adaptor for
electrical appendices is necessary
Can be operated simultaneously
by remote controller
(set by ventilation mode)
Heat Reclaim
Ventilator
For control from
2 locations such
as in room and
control room,
exits, etc.
For
simultaneous
control of up to
16 indoor units.
Operation and
surveillance is
carried out using
the contact signal
from the operation
control box in the
building
surveillance
(security) room.
Centralised
control of up to
64 indoor
groups from
remote location
up to 1 kilometer
away.
Link by remote
controller group
control.
Zone link control
by centralised
control.
Optional wiring adaptor for
electrical appendices is necessary
Note: 1
BRC1E62 can connect to BRC1E62 only.
2
It is not possible to use two wireless remote controllers.
3
BRC1E62 cannot connect to wireless remote controller.
Heat Reclaim Ventilator for indoor units within
a zone are operated by interlocking Can also
be operated independently by remote
controller.
Central remote controller (option)
Heat Reclaim
Ventilator
Heat Reclaim Ventilator for indoor units within a
zone are operated by interlocking
Central remote controller (option)
Heat Reclaim
Ventilator
Central remote controller (option) Central remote controller (option)
FCNQ only
FCNQ series only
To achieve increased durability by improved resistance to salt corrosion and
atmospheric pollution, Anti corrosion treated heat exchangers (with special
acryl pretreatment) are used for the heat exchanger of the outdoor unit.
LCD REMOTE CONTROLLER Optional accessory
Enables temperature sensing closer to target
area for improved comfort. (When using remote
control from another room, temperature-sensor in
indoor unit's air inlet must be selected.)
Facilitates maintenance and repair
All initial settings can be set from the remote
controller. After interior construction is complete,
ceiling mounted cassette type can be remotely
set without having to use stepladder access for
manual setting.
Setting contents: High ceiling use, air direction, filter type, address
for centralised control (group control address is set automatically).
Remote controller is equipped with model name
and failure display functions. This facilitates
service in the unlikely event of a malfunction.
Ceiling mounted cassette type
shares common control with Heat
Reclaim Ventilator and the other
Daikin air-conditioning units, thus
simplifying interlocking operations.
Easily adaptable to large-scale, high-function,
centralised remote control systems.
Installing and connecting control wiring between
SkyAir and other Daikin air-conditioning
equipment is easy.
LCD panel shows operating status in letters, numbers, and motion.
Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.
Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).
Programming time display
Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows
when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.
Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
DUCT CONNECTION LOW STATIC PRESSURE TYPE
BRC7NU66
BRC7F633F
BRC4C64
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE BRC4C64
Wired remote controller has
built-in temperature-sensor
(Applies to wired remote controllers (BRC1C61/1E62))
(Applies to wired remote controller (BRC1E62))
13 14
Clear Display
Navigation Remote Controller
(Wired Remote Controller BRC1E62)
- 5 actions per day can be scheduled for each day
of the week.
- The holiday function will disable schedule timer
for the days that have been set as holiday.
- 3 independent schedules can be set.
(e.g. summer, winter, mid-season)
Display is available in 11
languages.
Dot matrix display Backlight
display
Convenience
Weekly schedule Multilingual display
Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units.
Remote controller options are shown on the page introducing each indoor unit model.
NEW
(English, German, French, Spanish,
Italian, Portuguese, Greek, Dutch,
Russian, Turkish, and Polish).
NEW
A combination of fine dots
enables various icons.
Large text display is easy to
see.
This simple, modern designed remote controller with fresh
white colour matches your interior design. Operation is
much easier and smoother, just follow the indications on
the navigation remote controller.
Energy saving
NEW
- Sets and saves setting for an increment of time that automatically turns off air
conditioner after a preset period of time for each time operation starts.
- Period can be preset from 30 to 180 minutes in10-minute increments.
Off timer (programmed)
Setpoint range set
NEW Setpoint auto reset
Restaurant sample
Restaurant opened
Temperature is set to 27ºC
27°C
- Saves energy by limiting the
min. and max. set temperature.
- Avoids excessive heating or
cooling.
- This function is convenient when
the remote controller is installed
at a place where any number of
people may operate it.
- Even if the set temperature is changed, it returns to the preset temperature
after apreset period of time.
- Period selectable from 30min/60min/90min/120min.
Full tables at lunchtime
Then is lowered to 24ºC for
crowded room
24°C
After 30 minutes*
Automatically returns to preset
temperature (27ºC)
*Setting possible for after 30, 60, 90, and 120
minutes.
Returns to
27°C
automatically
Signal receiver unit
(For ceiling mounted
cassette type)
Wireless remote controller for each indoor unit type
LCD wireless remote controller
Note: The signal receiver unit shown in the
photograph is for mounting inside
the decoration panel of the ceiling
mounted cassette type.
Wireless remote
controller
BRC7F633F
The wireless remote controller is
supplied in a set with a signal
receiver.
Signal receiver unit is contained
inside decoration panel or indoor
unit.
Shape of signal receiver unit
differs according to the indoor
unit.
The rubber switch and the
oil-resistant plastic casing are
adopted for durability.
Only 17 mm thick. Can be
installed either recessed or
exposed.
Easy to read because of large LCD screen.
Wired LCD remote controller
BRC1C61
Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.
You can turn up to 16 indoor units on/off with a single remote
controller. (When using connected indoor units, the settings
must all be the same and on/off will be simultaneous.)
Group control by 1 remote controller
Two types are available: 65% and 90% colorimetry.
High-efficiency filter unit
You can provide air-conditioning with fresh air from outside.
Convenient for places where a ventilation fan cannot be
installed.
Fresh-air intake kit
Work and Servicing
Control features
Options
Steeper gradient realises more
efficient condensate drainage.
High-lift is especially useful for
long lengths of drain piping.
Maintenance is not required for one year.
The filter is washable and can be reused.
If refrigerant piping length does not exceed 15 m, there is no
need for on-site gas charging.
The filter sign warns you when it is time to clean the filter.
*When using a wired remote controller the sign is displayed in the LCD.
When using a wireless remote controller the filter sign lamp illuminates on
the signal receiver unit.
Drain pump mechanism
Long-life filter
Pre charged for up to 15 metres
Filter sign
Daikin's innovative air discharge mechanism keeps airflow
away from the ceiling. Ceiling cleaning is less frequently
required.
Ceiling soiling prevention function
If there is a power outage while the equipment is operating,
operations will restart in the same mode as before the power
cut when electricity is restored.
Ultra long-life filter
Auto-restart
Optional central remote controller enables centralised control of
up to 1024 indoor units (64 groups) from up to 1 kilometer away.
Central remote control
Enables interlocking control with external equipment such as
Heat Reclaim Ventilator.
Interlock control
Standardly equipped interface enables connection to
centralised control system without need of an adaptor.
DIII-NET communication standard
Using 2 remote controllers you can operate the equipment
locally or from a remote location.
Note: When a wireless remote controller is used, remote control by two
remote controllers is not possible.
Control by 2 remote controllers
RNQ09-26M : 10 m
*Applicable to RNQ30-48M.
Requires no maintenance for about 4 years* (10,000h) in
stores and offices.
*For dust concentration of 0.15 mg/m3
*Connecting ducts, insect nets, fire dampers, air filters, and other parts
should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary.
Optional PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the
kit is limited to 10% of the maximum airflow rate of the indoor unit.
Introducing higher quantities will increase the operating noise and may
also influence temperature sending.
Note:
Others
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated Anti corrosion treated
heat exchangers (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.
In high corrosive areas, regular maintenance needs to be carried out.
Anti corrosion treated heat exchangers
Operation and surveillance is carried out using the contact
signal from the operation control box in the building
surveillance (security) room.
External command control
*An option is required.
15 16
Abundance of functions that provide comfortable
air-conditioning in stores and offices.
Cleanliness
The Air filter has a anti-bacterial treatment to help prevent the growth of bacteria and mould on it.
Anti-bacterial air filter
Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.
Note: Wireless remote controllers have no
temperature-sensor.
Use the temperature-sensor in
the indoor unit when controlling
air conditioning from another
room.
Dehumidification is microprocessor controlled to prevent
abrupt and uncomfortable changes in air temperature. Useful
for reducing uncomfortable humidity without uncomfortable
cooling of the room.
Delivers comfortable
air-conditioning to all areas, near
to and far from the
air-conditioner.
High setting provides maximum reach while low setting
minimises drafts.
Auto-swing
Programme "Dry"
Switchable fan speed
(1) Standard setting
(2) Ceiling soiling prevention
setting
(standard, ceiling soiling prevention)
Note:When units are installed on high ceilings, depending on the model,
various restrictions concerning maximum height, air discharge direction,
and choice of options may apply.
You can freely set 2 air discharge setting by remote controller.
Swing pattern selection
Delivers air-conditioning comfort all the way down to the floor
in air-conditioning zones with high ceilings.
High-ceiling application
Two selectable temperature-sensors
Comfort
The air flow direction can be
fixed at your desited angle
by the remote controller.
Temperature-sensors are included in the indoor unit and
optional wired remote controller. Temperature sensing closer
to target area is possible to further increase the comfort level.
Remote Controller
Sets and saves setting for an increment of time that
automatically turns off air conditioner after a preset period of
time for each time operation starts.
Off timer (programmed)
Operation starts when the preset time of the ON timer elapses
and stops when the preset time of the OFF timer elapses.
On/Off timer
Up to five operation ON/OFF settings can be programmed per
day for each day of the week. Not only can the time be set for
the operation ON setting, but also the temperature.
Weekly schedule timer
Even if the set temperature is changed, it returns to the preset
temperature after a preset period of time.
Saves energy by limiting the minimum and maximum set
temperatures. Avoids excessive heating and cooling.
Setpoint auto reset
Setpoint range set
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
DUCT CONNECTION LOW STATIC PRESSURE TYPE
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
SPECIFICATIONS
43/39
24
White
VP20 (I.Do
/ 20XO.Do
/ 26)
19.4 to 46
o
/ 6.4
49
36 40 49
--------- --------- ---------
1.2
(Charged for 10 m)
0.9
51
1.4
(Charged for 10 m)
1.4
52
1.5
(Charged for 10 m)
1.8
2.0
(Charged for 10 m)
2.2
1.9
(Charged for 15 m)
3.2
(Charged for 15 m)
2.7
2.7
(Charged for 15 m)
3.75
3.2
(Charged for 15 m)
4.5
Ivory white
30
10 15
Hermetically sealed rotary type
o
/ 12.7 o
/ 15.9
o
/ 18.0 (Hole)
°CWB
°CDB
Certified operation range
Certified operation range
Motor output
Compressor
Dimensions (HXWXD)
Colour
mm
dB(A)
kW
Refrigerant charge (R-410A) kg
dB(A)
Sound level3
Dimensions (HXWXD) mm
Machine weight kg
kg
V1
Y1
Piping
connections
mm
Liquid (Flare)
mm
Gas (Flare)
mm
Drain Indoor unit
Outdoor unit
Machine weight kg
Airflow rate (H/L) m3
/min 16/-
565/-
Outdoor
unit
Colour
mm
Heat insulation
Max. interunit piping length
m
m
Max. installation level difference
Type
Sound level (H/L) (220 V)3
Indoor
unit
Both liquid and gas piping
cfm
14 to 23 14 to 25
17 18
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
°CDB
Certified Operation range
Sound level3
°CWB
Certified Operation range
Motor output
Compressor
Dimensions
(HXWXD)
Colour
mm
mm
dB(A)
kW
Refrigerant charge (R-410A)
kg
dB(A)
Dimensions (HXWXD) mm
Machine weight
kg
V1
Y1
Unit
Piping
connections
mm
Liquid (Flare)
mm
Gas (Flare)
mm
Drain Indoor unit
Outdoor unit
Decoration panel
Unit
Decoration panel
Machine
weight kg
kg
Unit
Decoration panel
Airflow rate (H/L) m3
/min
cfm
Outdoor
unit
Colour
mm
Heat insulation
Max. interunit piping length m
m
Max. installation level difference
Type
Sound level (H/L)3
Indoor
unit
Hermetically sealed rotary type Hermetically sealed scroll type
o
/ 6.4
o
/ 15.9
o
/ 12.7
50X950X950
5.5
----------
10 15 20 30
Ivory white
Fresh white
Both liquid and gas piping
30
30
(Equivalent length 50)
30
(Equivalent length 50)
50
(Equivalent length 70)
o
/ 26.0 (Hole)
o
/ 18.0 (Hole)
VP25 (I.Do
/ 25XO.Do
/ 32)
19.4 to 46
o
/ 9.5
21 to 46
14 to 23 14 to 25
0.9 1.4 1.8 2.2 2.7 3.75 4.5
31/28 35/28 43/32 44/34 44/36
49 51 52 54 55 54 56 58
36 40 49 56 77 103 --------- ---------
--------- --------- --------- 56 74 103 107 111
19.5 21 24
256X840X840 298X840X840
1.2
(Charged for 10 m)
1.4
(Charged for 10 m)
1.5
(Charged for 10 m)
2.0
(Charged for 10 m)
1.9
(Charged for 15 m)
3.2
(Charged for 15 m)
2.7
(Charged for 15 m)
3.2
(Charged for 15 m)
13/10 21/13.5 32/20 33/22.5
459/353 741/477 1,130/706 1,165/794
Cooling capacity1,2 kW
Y1
V1
Y1
V1
kW
Power consumption
Model
Name
Indoor unit
Power supply
Cooling1
Btu/h
W/W
COP
13
FCNQ13MV1
RNQ13MV1
3.8
13,000
550X765X285
1.24
3.07
18
FCNQ18MV1
RNQ18MV1
5.3
18,000
595X845X300
1.89
2.80 2.80
21
FCNQ21MV1
RNQ21MV1
--------- --------- ---------
6.2
21,000
2.21
26
FCNQ26MV1
RNQ26MV1
7.6
26,000
735X825X300
735X825X300
2.53
3.00
30
FCNQ30MV1
RNQ30MV1
8.8
30,000
990X940X320
2.73
3.22
36
FCNQ36MV1
RNQ36MV1
RNQ26MY1
26
FHNQ26MV1
RNQ26MV1
RNQ26MY1
RNQ30MY1 RNQ36MY1
10.6
36,000
1,345X900X320
3.31
3.20
42
FCNQ42MV1
---------
12.5
42,600
4.15
3.01
48
FCNQ48MV1
---------
RNQ42MY1 RNQ48MY1
14.1
48,000
5.04
2.80
1 Phase, 220–240 V, 50 Hz
---------
---------
3 Phase, 380–415 V, 50 Hz
Hermetically sealed scroll type
o
/ 9.5
o
/ 26.0 (Hole)
50
(Equivalent length 70)
30
21 to 46
45/40 48/42 49/43
55
54 54 56 58
77
56 103 --------- ---------
74
56
20
103 107 111
195X1,590X680
26-27/22-23 38-40/23-25
918-953/777-812 1,341-1,412/812-883
30
FHNQ30MV1
RNQ30MV1
8.8
30,000
990X940X320
3.07
2.87
7.6
26,000
2.65
36
FHNQ36MV1
RNQ36MV1
RNQ30MY1 RNQ36MY1
10.4
35,000
1,345X900X320
3.64
2.86
42
FHNQ42MV1
---------
12.3
42,000
4.51
2.73
48
FHNQ48MV1
---------
RNQ42MY1 RNQ48MY1
14.1
48,000
5.51
2.56
42-44/24-26
1,483-1,553/847-918
---------
3 Phase, 380–415 V, 50 Hz
Outdoor unit
Outdoor unit
Cooling capacity1,2 kW
Y1
V1
Y1
V1
kW
Power consumption
Model
Name
Indoor unit
Power supply
Cooling1
Btu/h
W/W
COP
13
FHNQ13MV1
RNQ13MV1
195X960X680
3.8
13,000
550X765X285
1.58
2.40
18
FHNQ18MV1
RNQ18MV1
195X1,160X680 195X1,400X680
26 32 35
44/40
777-812/671-706
22-23/19-20
5.3
18,000
595X845X300
2.04
2.60 2.60
21
FHNQ21MV1
RNQ21MV1
--------- --------- ---------
6.2
21,000
2.38
1 Phase, 220–240 V, 50 Hz
---------
Outdoor unit
Outdoor unit
°CDB
°CWB
Certified Operation range
Certified Operation range
Motor output
Compressor
Indoor
unit
Dimensions (HXWXD)
Colour
mm
dB(A)
kW
Refrigerant charge
(R-410A)
Sound level4
Sound level (H/L) (220 V)4
dB(A)
Dimensions (HXWXD) mm
Machine weight
kg
V1
Y1
Piping
connections
mm
Liquid (Flare)
mm
Gas (Flare)
mm
Drain Indoor unit
Machine weight kg
kg
Airflow rate (H/L)3
Fan
Outdoor
unit
Colour
Heat insulation
Max. interunit piping length m
m
Max. installation level difference
Type
----------
Both liquid and gas piping
mm
Outdoor unit
Ivory white
mmH2O
cfm
Rated external static pressure3
10 15 20
19.4 to 46 21 to 46
14 to 23 14 to 25
m3
/min
30
30
(Equivalent length 50 m)
3/4B (I.Do
/ 21.6XO.Do
/ 27.2)
o
/ 6.4 o
/ 9.5
o
/ 12.7
o
/ 9.5 o
/ 15.9
o
/ 18.0 (Hole)
0.65 0.9 1.4 1.8 2.2
25 32
35 36 40 49 56
---------- ---------- ---------- ---------- 56
Hermetically sealed rotary type
0.9
(Charged for 10 m)
1.2
(Charged for 10 m)
1.4
(Charged for 10 m)
1.5
(Charged for 10 m)
2.0
(Charged for 10 m)
459/388
13/11
635/530
18/15
41/38 43/40
48 49 51 52 54
2.0
Y1
V1
Y1
V1
Cooling capacity1,2 kW
kW
Power consumption
Model
Name
Indoor unit
Power supply
Cooling1
Btu/h
W/W
COP
09
FDBNQ09MV1
RNQ09MV1
260X900X580
2.7
9,200
550X765X285
0.86
3.14
13
FDBNQ13MV1
RNQ13MV1
3.8
13,000
1.28
2.97
18
FDBNQ18MV1
RNQ18MV1
5.2
17,700
595X845X300
2.06
2.52
21
FDBNQ21MV1
RNQ21MV1
260X1,300X580
6.2
21,000
2.38
2.60
26
FDBNQ26MV1
RNQ26MV1
--------- --------- --------- --------- RNQ26MY1
7.6
26,000
735X825X300
2.62
2.90
1 Phase, 220–240 V, 50 Hz
--------- 3 Phase, 380–415 V, 50 Hz
Outdoor unit
Outdoor unit
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
Please see fan characteristic document in detail.
4
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
°CDB
°CWB
Certified Operation range
Certified Operation range
Motor output
Compressor
Indoor
unit
Dimensions (HXWXD)
Colour
mm
dB(A)
kW
Refrigerant charge
(R-410A)
Sound level4
Sound level (H/L) (220 V)4
dB(A)
Dimensions (HXWXD) mm
Machine weight
kg
V1
Y1
Piping
connections
mm
Liquid (Flare)
mm
Gas (Flare)
mm
Drain Indoor unit
Machine weight kg
kg
Airflow rate (H)3
Fan
Outdoor
unit
Colour
Heat insulation
Max. interunit piping length m
m
Max. installation level difference
Type
----------
Both liquid and gas piping
mm
Outdoor unit
Ivory white
mmH2O
cfm
Rated external static pressure3
20 30
21 to 46
14 to 25
m3
/min
30
(Equivalent length 50 m)
50
(Equivalent length 70 m)
3/4B (I.Do
/ 21.6XO.Do
/ 27.2)
o
/ 9.5
o
/ 15.9
o
/ 26.0 (Hole)
o
/ 18.0 (Hole)
2.2 2.7 3.75 4.5
43 52
56 77 103 ---------- ----------
56 74 103 107 111
Hermetically sealed rotary type Hermetically sealed scroll type
2.0
(Charged for 10 m)
1.9
(Charged for 15 m)
3.2
(Charged for 15 m)
2.7
(Charged for 15 m)
3.2
(Charged for 15 m)
812
23
1,306
37
1,483
42
42/38 44/36 45/37 46/37
54 55 54 56 58
8.5 9.8 8.0
Y1
V1
Y1
V1
Cooling capacity1,2 kW
kW
Power consumption
Model
Name
Indoor unit
Power supply
Cooling1
Btu/h
W/W
COP
26
FDMNQ26MV1
RNQ26MV1
305X1,350X680
7.6
26,000
735X825X300
2.62
2.90 2.90
30
FDMNQ30MV1
RNQ30MV1
305X1,550X680
8.8
30,000
990X940X320
3.03
36
FDMNQ36MV1
RNQ36MV1
10.6
36,000
3.53
3.00
1,345X900X320
42
FDMNQ42MV1
---------
12.3
42,000
4.49
2.74
48
FDMNQ48MV1
---------
RNQ26MY1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1
14.1
48,000
5.56
2.54
1 Phase, 220–240 V, 50 Hz ---------
3 Phase, 380–415 V, 50 Hz
Outdoor unit
Outdoor unit
For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option
(shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.
A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.
Round flow type: List of optional parts required to achieve different flow patterns
1
In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check
whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.
2
Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position.
3
It is not possible to use panel spacers in a 2-way flow installation.
4
It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.
Panel/grille related
Independently installable optional parts
Operation control related
Auxillary function related
Filter related
Optional accessory parts
Independently installable optional parts
Optional accessory parts
Independently installable optional parts
Optional accessory parts
Panel spacer1
Panel spacer1
o o o
x o
Wireless remote controller o o o
o o
Fresh air intake kit (direct mount) o o o
o o
x o o
x
x
High-efficiency filter2
Filter related Ultra-long-life filter2
o o o
x
x
Ultra-long-life filter2
o o o x
x
High-humidity operation kit
Panel/grille related
Operation control related
Auxillary function related
Panel spacer1
Wireless remote controller
Fresh air intake kit (direct mount)
High-humidity operation kit
All round flow 4-way flow
o3 o3 x
x o3
o3 o
x
x
x
o o
o3 o x
x
o o
x o o x
o3 o o x
x
3-way flow 2-way flow
1-way branch / unit 3-way flow
Branch duct1
(Chamber type)
(Round duct type)
o o o4 x
x o
2-way branch / unit 2-way flow
1-way branch / unit 2-way flow
x o o4 x
x o
x o o4 x
x o
Branch duct connection
Wireless
remote controller
Fresh air intake kit
(direct mount)
High-efficiency
filter2
High-humidity
operation kit
Ultra-long-life
filter2
Panel spacer1 Wireless
remote controller
Fresh air intake kit
(direct mount)
High-efficiency
filter2
High-humidity
operation kit
Ultra-long-life
filter2
Panel spacer1 Wireless
remote controller
Fresh air intake kit
(direct mount)
Fresh air intake kit (Chamber type)1,2
o o o
x o
Fresh air intake kit (Chamber type)1,2
o3 o x
x o
o
o
x
o
o
o3
o
x
x
x
o
o
o
o
Fresh air intake kit
(Chamber type)1,2
Fresh air intake kit
(Chamber type)1,2
Fresh air intake kit
(Chamber type)1,2
High-efficiency
filter2
High-humidity
operation kit
Ultra-long-life
filter2
19 20
Indoor unit Indoor unit
OPTIONS
Outdoor unit
Kit name
RNQ18MV1 RNQ21MV1
RNQ09MV1 RNQ13MV1 RNQ26MV1 RNQ30MV1 RNQ36MV1 ------- -------
------- -------
------- ------- RNQ26MY1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1
Central drain plug
Name of option
KKPJ5F180
-------
------- KKP014A4
Touch Controller4 DCS601C51
Note: 1
Refer to page 6 for the details.
2
Required for installing high-efficiency filter or ultra long-life filter.
3
Wiring for wired remote controller to be procured locally.
4
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
5
Installation box for adaptor PCB (KRP1H98) is necessary.
Note: 1
Wiring for wired remote controller to be procured locally.
Kit name
DCS302CA61
DCS301BA61
DST301BA61
KRP1C63
KDDFP55B160
KDBH55K160F
KDBP55H160FA
KKSJ55KA160
KDDP55B160
KDDP55B160K
KDDP55X160
KRP4AA53
KAFP551K160
KAFP556B80
KAFP557B80
KAFP552B80
KDTP55K80
KDJP55B160
KDJP55B80
BRC7F633F
BRC1C61
KAFP553B80
KDTP55K160
KAFP556B160
KAFP557B160
KAFP552B160
KAFP553B160
BYCP125K-W1
KRP1H98
KAFP55B160
KAFP55H160H
FCNQ21MV1 FCNQ26MV1 FCNQ30MV1
FCNQ13MV1 FCNQ18MV1 FCNQ36MV1 FCNQ42MV1 FCNQ48MV1
Name of option Remark
Chamber
type
Decoration panel
Fresh air
intake kit1
Central remote controller4
Unified ON/OFF controller4
Schedule timer4
Adaptor for wiring5
Without T-joint pipe and fan
With T-joint pipe, without fan
Direct installation type
Sealing material of air discharge outlet
Panel spacer
Chamber connection kit2
Insulation kit for high humidity
Wiring adaptor for electrical appendices5
Installation box for adaptor PCB
High-efficiency filter
(including chamber)
Filter chamber
Replacement long-life filter
Ultra long-life filter
Replacement ultra long-life filter
(Colorimetric method 65%)
(Colorimetric method 90%)
Replacement
high-efficiency filter
(Colorimetric method 65%)
(Colorimetric method 90%)
Remote controller Wireless type Cooling only
Wired type3
Branch duct chamber
Remote sensor KRCS01-4B
CEILING MOUNTED CASSETTE TYPE
Kit name
KHFJ5F50
BRC1NU61
BRC7NU66
KAF501DA56
KHFJ5F60 KHFP5MA160
KAF501DA80 KAF501DA112 KAF501DA160
FHNQ21MV1 FHNQ26MV1 FHNQ30MV1 FHNQ36MV1 FHNQ42MV1 FHNQ48MV1
FHNQ13MV1 FHNQ18MV1
Name of option Remark
Replacement long-life filter
L-type piping kit (for upward direction)
Remote controller
Resin net
Wired type1
Wireless type
CEILING SUSPENDED TYPE
Note: 1
Wiring for wired remote controller to be procured locally.
Kit name
BRC1C61
BRC4C64
FDBNQ18MV1
FDBNQ09MV1 FDBNQ13MV1 FDBNQ21MV1 FDBNQ26MV1
Name of option Remark
Remote controller
Wired type1
Wireless type
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Note: 1
Wiring for wired remote controller to be procured locally.
Kit name
BRC1C61
BRC4C64
FDMNQ36MV1
FDMNQ26MV1 FDMNQ30MV1 FDMNQ42MV1 FDMNQ48MV1
Name of option Remark
Remote controller
Wired type1
Wireless type
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
BRC1E62
Navigation Remote Controller Wired type3
BRC1E62
Navigation Remote Controller Wired type1
BRC1E62
Navigation Remote Controller Wired type1
4
155
11
o
/ 45
40
90
5 80
14
55
195
30 or more 30 or more
4-M8~M10
Hanging bolt
(Service space)
(Service space)
1
B
127
8
10
17
18
(Hanging
position)
(Hanging position)
A
16
210
36
170
58
192
85
160
105
102
142
90
185
260
4
170
7
225
Drain pipe connection VP20
6
275
Brand name plate
The Front
(Note.2)
80
275
105
(For left piping)
300
3 2 5
80
6
(Required
space)
Obstacle
680
Floor side
5
155
55
(Required
space)
300
or
more
13
For
height
installation
From
the
floor
side
2500
or
more
105
15
(Required
space)
135
5
Position : Hole of wall for taking out in piping back
(View from the front)
65
50
135
145
9 60
65
12
40
60
60
115
Position slit hole for taking out in piping back
(View from the front)
DIMENSIONS (Unit: mm)
21 22
CEILING SUSPENDED TYPE
236
3×P.150=450
16
260
16
151 704
10
688
150
900
127
(All Around)
219
10
12-M4 Holes
52
674
5
7
4
6
664
170
110
684
260
(All Around)
1
228
3×P150=450
500
10-M4 Holes
164
2
29
50
134
107
10
or
more
300 or more
317
3
704
500
167
580
151
126
8
271
(Suspension bolt pinch)
3
55
(Suspension
bolt
pinch)
755
137
900
Service space
DUCT CONNECTION LOW STATIC PRESSURE TYPE
A B
[FHNQ13/18/21/26/30/36/42/48MV1]
[FDBNQ09/13/18MV1]
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Air discharge grille
Air suction grille
Air filter
Gas pipe connection
Liquid pipe connection
Drain pipe connection
Earth terminal (Inside the electric components box)
Suspension bracket
Backward pipe and wiring connection opening lid
Upward pipe and wiring connection opening lid
Right side pipe connection
Left back drain pipe connection
Left side drain pipe connection
Right side drain pipe connection
Hole of wall for taking out in pipe back
Upward drain pipe connection
Upward gas pipe connection
Upward liquid pipe connection
Notes:
1
Location of unit's Name plate : Bottom of fan housing inside the suction grille.
2
In case of using wireless remote controller, this position will be a signal receiver.
Refer to the drawing of wireless remote controller in detail.
3
The remote control code is the standard <about 3m outside the machine> attached.
(0.5mm2
x2 wicks O.D. 5.4)(It is not attached to VRV.)
Note: 1
Location of unit's Name Plate: Chamber cap
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
1
2
3
4
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
5
6
7
8
920 960
1120 1160
1120 1160
FHNQ13MV1
FHNQ18MV1
FHNQ21MV1
1360 1400
FHNQ26MV1
1360 1400
FHNQ30MV1
1550 1590
FHNQ36MV1
1550 1590
FHNQ42MV1
1550 1590
FHNQ48MV1
CEILING MOUNTED CASSETTE TYPE
Notes:
1
Sticking location for manufacture's label
manufacture's label for indoor unit:
Suction grille inner side's electric components box's lid surface
manufacture's label for decoration panel :
Decoration panel's corner decoration cover inner surface
2
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller
in detail.
3
When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit
continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
4
Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less
between the indoor unit and the ceiling opening so that
the panel overlap allowance can be ensured.
5
Please do not place the thing been damp and troubled under an indoor unit.
When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
[FCNQ13-48MV1] [FCNQ13-48MV1]
[FCNQ13-26MV1] [FCNQ13-26MV1]
[FCNQ13-26MV1]
[FCNQ13-26MV1] [FCNQ30-48MV1]
[FCNQ30-48MV1]
[FCNQ30-48MV1] [FCNQ30-48MV1]
7
6
950
8
950
Pipe Connection
Side
Drain Connection
Side
Note 2
A arrow view
9
C
B
420
710(Hanging bolt pitch)
420
860~910(Ceiling opening space) (Note 4)
860~910(Ceiling
opening
space)
(Note
4)
780(Hanging
bolt
pitch)
95
330
165
Connection position
of branch duct
160
20
16-M4 Prepared hole
50
350
124
80
175
125
2
(square-shaped type)
4 1
157
246
55
4-M8~M10
2x100=200 80
124
10
Hanging bolt
Connection position
of branch duct
C/L
110
(round shape type)
840
55
280
256
40
Adjustable(0~675)
340
850
Connection position
of branch duct
1500
or
more
Connection position
of branch duct
20-M4 Prepared hole
60
From
the
floor
side
2500
or
more
130
124
2x100=200
35 or less
(Note 4)
55
A
150
840
55
160
157
256
105
(square-shaped type)
For
height
installation
42
(required
space)
(Note 4)
95
3 85
124
35 or less
5
(round shape type)
64
350
81
110
50
124
81 2x100=200
350
Connection position
of branch duct
160
16-M4 Hole
B arrow view
(round shape type)
110
C/L
124
85
157
(square-shaped type)
95
Connection position
of branch duct
80
157
213
95
160
Connection position
of fresh air intake kit
(square-shaped type)
C arrow view
(knock
hole)
90
(round shape type)
124
183
109
25
C/L
124
80
2x100=200
(direct installation type)
ø100
20-M4
Prepared hole
Connection position
of branch duct
Connection position
of branch duct
90
350
157
93
2x100=200 85
67
Connection position
of branch duct
C/L
(round shape type)
160
Connection position
of branch duct
16-M4 Hole
167
(square-shaped type)
B arrow view
160
95
81
350
29
213
29
350
80
160
ø100
Connection position
of fresh air intake kit
C/L
157
90
(direct installation type)
67
(knock
hole)
Connection position
of branch duct
C arrow view
Connection position
of branch duct
2x100=200
(round shape type)
(square-shaped type)
196
93
90
80
25
95
160
20-M4
Prepared hole
167
280
50
288
80
167
95
157
340
840
165
10
4
Hanging bolt
1
175
55
4-M8~M10
Connection position
of branch duct
(round shape type)
Connection position
of branch duct
2
40
80
160
2x100=200
125
(square-shaped type)
C/L
298
20
350
850
Adjustable(0~675)
55
29
330
160
16-M4 Prepared hole
160
1500
or
more
81
93
157
130
Connection position
of branch duct
160
2x100=200
A
55
(square-shaped type)
From
the
floor
side
2500
or
more
(Note 4)
67
105
For
height
installation
85
150
(required
space)
350
42
29
64
(round shape type)
27-M4 Prepared hole
60
35 or less
(Note 4)
35 or less
3
Connection position
of branch duct
256
160 5
95
50
840
55
167
The necessary space is 500mm or more when the
air-outlet is blocked with the accessory.
Moreover when the corner areas are blocked
(both right and left of the blocked air outlet),
the necessary space is 200mm or more.
1500mm or more
200mm or more
1500mm or more
1500mm
or more
1500mm
or more
200mm
or more
Required space
300
or less
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power-source wiring and a unit
wiring connection
Connection wiring/remote control
wiring connection
Air-outlet
Suction grille
Corner decoration cover
Drain hose (accessory)
1
2
3
4
5
6
7
8
9
OUTDOOR UNIT // RNQ09/13MV1
23 24
DIMENSIONS (Unit: mm)
22
50
100
50
150
50
50
300
150
100
285 8
Handle
Wall height on air outlet side
=less than 1200
Minimum space for air passage
105.5
13
311
490
574
29.5
Drain outlet
(I.D. 15.9 hose for connection)
4-Hole for anchor bolts
(M8 or M10)
550
12 63
765
Brand name label
Manufacture’s
label
196
165
105
Wiring
inlet
Gas stop valve
( 15.9CuT for RNQ13)
( 9.5CuT for RNQ09)
Service
port
In case of removing
stop valve cover
Liquid stop valve
( 6.4CuT)
300 or more
1353
1337
151
74
16
263
7×P150=1050
1550
(All Around)
51
20-M4 Holes
8
10
16
305
150
280
1321
50
123
1314
175
305
18-M4 Holes
212
206
(All Around)
152
827
274
1334
7×P150=1050 2
1
29
7
6
5
4
1353
146
3
151
600
116
(Suspension
bolt
pinch)
381
3
1403
1550
(Suspension bolt pinch)
126
55
427
8
680
Service space
[FDMNQ30/36/42/48MV1]
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Note: 1
Location of unit's Name Plate: Chamber cap
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
1
2
3
4
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
5
6
7
8
300 or more
7×P150=1050
263
151
20-M4 Holes
51
1350
1137
16
1121
8
10
305
(All Around)
16
150
74
280
1153
7
5
6
4
1114
1134
1
29
50
123
18-M4 Holes
152
206
274
175
2
305
(All Around)
727
212
7×P150=1050
126
600
1350
8
116
1153
680
3
381
3
(Suspension bolt pinch)
146
1203
151
427
(Suspension
bolt
pinch)
55
Service space
Service space
300 or more
260
10
236
16
151
102
1300
219
1104
1074
1088
18-M4 Holes
16
(All Around)
52
10
150
6×P.150=900
700
50
16-M4 Holes 29
2
6×P150=900
164
134
1064
(All Around)
170
260
228
107
1084
1
110
5
6
4
7
10
or
more
271
317
500
167
580
137
(Suspension
bolt
pinch)
(Suspension bolt pinch)
3
1300
151
55
1155 126
8
3
1104
[FDBNQ21/26MV1]
[FDMNQ26MV1]
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Note: 1
Location of unit's Name Plate: Chamber cap
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
1
2
3
4
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
5
6
7
8
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Note: 1
Location of unit's Name Plate: Chamber cap
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
1
2
3
4
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
5
6
7
8
OUTDOOR UNIT // RNQ30MV1, RNQ30MY1
OUTDOOR UNIT // RNQ36MV1, RNQ36/42/48MY1
OUTDOOR UNIT // RNQ18/21MV1
OUTDOOR UNIT // RNQ26MV1, RNQ26MY1
25 26
30
620
91
160
30
30
Hole for anchor bolt 4-M12
55
(345∼355)
37
320
160
350
38
145
5
84
53
7
95
6
80
55
19
416
68
161
595
61
16
260
262
36
279
285
8 90
16
5
95
13
53
5
55
223
6
7
67
52
339
89
95
19
2
5
3
6
4
990
142
340
60
89
1
940
7
53
96
89
58
1
16
24
54
350
(345~355)
3
71
45
145
41
7
6
95
620
60
5
95
4
89
320
8
84
48
70
410
54
1345
30
80
30
102
140
55
19
900
5
5
376
435
19
140
6
61
117
142
2
191
7
30
16
Hole for anchor
bolt 4-M12
5
6
7
53
67
55
95
13
223
52
1
2
3
4
5
6
7
8
Gas pipe connection
Liquid pipe connection
Service port (in the unit)
Grounding terminal
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain pipe connection
DIMENSIONS (Unit: mm)
Gas pipe connection
Liquid pipe connection
Service port
Grounding terminal
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain pipe connection
1
2
3
4
5
6
7
8
50
50
300
300
50
300
150
50
100
20
845
573.5
20
131
7
342
300
78
326
300
Drain outlet
I.D. 18 hose for connection
4-Hole for anchor bolts
(M8 or M10)
595
Brand name label
Wiring inlet
Name plate
105
144
60
Earth terminal
in switch box
Gas stop valve
( 15.9CuT for RNQ21MV1)
( 12.7CuT for RNQ18MV1)
Liquid stop valve
( 6.4CuT)
Service port
Wall height on air outlet side
=less than 1000
Minimum space for air passage
325
36
350
78
580
330
825
25
10
300
2
124
Drain outlet
I.D. 15.9 hose for connection
4-Hole for anchor bolts
(M8 or M10)
735
Brand name label Wiring inlet
Name plate
30
18
64
155
160
89
Earth terminal
in switch box
Gas stop valve
( 15.9CuT)
Liquid stop valve
( 9.5CuT)
Service port
350
100
50
100
100
50
350
50
350
Wall height on air outlet side
=less than 1200
Minimum space for air passage
27 28
1000 or more
100 or
more 100 or
more
1000
or more
300
or more
L
H
L H
100 or
more 100 or
more
300 or more
1000 or more
200 or more
100 or
more 100 or
more
500 or less
1000 or more
1000
or
more
An obstruction
in the overhead space
100 or
more
100 or more
300 or more
1000 or more
200 or more
500 or less
1000
or
more
An obstruction
in the overhead
space
100 or
more
100 or more
When there is an obstruction on the inlet side
When there are obstructions
on the inlet side and
both sides
2. For multiple units installation
(more than two units)
When there are
obstructions on
both sides
1) When the overhead space is open
1. For single unit installation
When there is an
obstruction only
on the inlet side
2) When there is an obstruction
in the overhead space
1) When the overhead space is open
When there are obstructions
on both sides
2) When there is an obstruction
in the overhead space
When there is an
obstruction on the
inlet side
When there are obstructions
on the inlet side and
both sides
2. For multiple units installation (more than two units)
1. For single unit installation
1. For single unit installation
2. For multiple units installation
(more than two units)
1. For single unit installation
2. For multiple units installation
(more than two units)
1. For single unit installation
2. For multiple units installation
(more than two units)
Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.
1 When there is an obstruction on the outlet side
2
1) When the overhead space is open
(There is no limit to the height of the obstruction on the
outlet side.)
When there are obstructions on both
the inlet and outlet sides
(When the obstruction on the outlet side is higher than the
unit itself)
3
H
L
500
or more
100
or more
L H
100 or more
100 or more
100 or more
100 or more
500 or more
100 or more
500 or less
1000
or
more
An obstruction
in the overhead
space
500 or less
500 or more
1000
or
more
An obstruction
in the overhead space
150 or more
150 or more
150 or more
500 or less
1000
or
more
An obstruction
in the overhead
space
Installation service space for outdoor unit
For RNQ30-48MV1/Y1
REMOTE CONTROLLER
Wired type
Staple
17
17
0~5
117
17
(fl12~fl16)
A EXposed body, exposed cord C Exposed body, embedded code
( Distance between
remote controller
and control box )
B Exposed body, embedded cord
Conduit
CONTROL BOX
Through hole
Size
Specifications of cord
0.75~1.25 mm2
Total length 500 m
Type Vinyl cord with sheath or cable (Insulated thickness: 1 mm or more)
Note) 1. Remote controller cord and
staple are not attached.
they are field supplied
parts.
Note)
The dimension of hole.
* Countries requiring EMC: Shield wire (insulated thickness: 1 mm or more)
120
120
17 18
42
84
38
Cord
outlet
hole
28
23
46
Wireless type
BRC1C61
BRC1NU61
BRC7NU66
Transmitting part
157
62 17.5
Liquid crystal
remote controller
(Wireless)
Remote controller
holder
CEILING SUSPENDED TYPE
A
22
38
6
A
41
13
A
25
R2
7
B
44.5
10
20
B
A
25
25
17
41.5
7
A
B
111
119
24
6
Hole type
a
10
20
4
B
a (mm)
Receiver
The Front
Remote controller holder
installation procedure
<Installation to wall surface>
Remote controller holder
installation procedure
<Installation to wall surface>
Transmitting part
115.5
54 18.1
Remote controller
(Wireless)
Remote controller
holder
Receiver installation procedure
Service space for ceiling
installation
Receiver detail
Note :
More
than
90
(Srevice
space)
120
72
83.5
106
(Ceiling
opening)
70 18
0.5
35 49
(Ceiling opening)
2-5x9 Slot
Switch box
(field Supplied parts)
Do not install more than 3
receivers in the vicinity of one
another.
With 4 or more units, there is
always the possibility of
malfunction
Remote controller dimensions
Remote controller installation procedure
Receiver detail
Remote controller dimensions
BRC7F633F BRC4C64 CEILING MOUNTED CASSETTE TYPE <Round Flow>
• Receiver installation procedure • Receiver detail
Receiver
Drain piping
side
Refrigerant
piping side
Decoration panel
19
Upper case Lower case
40
23
46
28
48.5
42
84
5X7 oblong hole
Code outlet hole
5X15 oblong hole
Lower case portion
Lower case portion
Staple
19
A Exposed cord C Embedded cord
(use switch box)
B Embedded cord
84
46
Switch box for two switch
ex.) KJB211A
(optional accessory)
Condit
19
0~5
Switch box
[field supplied part]
(Between remote
controller and
control box)
48.5
19
Note)2
Through hole
40
( 8- 10)
84
28
Switch box for one switch
ex.) KJB111A
(optional accessory)
• Installation method
2.If the hole size is too large or the location
is not proper, the hole may come out from
the remote controller.
Note)
1. Remote controller cord and staple are not attached. They are field
supplied parts.
Size
Specifications of cord
0.75~1.25 mm2
Total length 500 m
Type Vinyl cord with sheath or cable (insulated thickness: 1mm or more)
BRC1E62
(Green)
120
120
   
Operation
lamp
Top left
outlet
Left outlet
Top center
outlet
DIMENSIONS (Unit: mm) (Unit: mm)
29 30
MEMO

More Related Content

What's hot

Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 CertifiedHazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 CertifiedThorne & Derrick International
 
Hazloc Explosion-proof Heaters AEU1 - Brochure
Hazloc Explosion-proof Heaters AEU1 - BrochureHazloc Explosion-proof Heaters AEU1 - Brochure
Hazloc Explosion-proof Heaters AEU1 - BrochureThorne & Derrick UK
 
Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Dr. Haider alsenisal
 
Rittal Pano Isıtıcıları
Rittal Pano IsıtıcılarıRittal Pano Isıtıcıları
Rittal Pano Isıtıcılarıerdinc klima
 
Dc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and TipsDc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and TipsSimon MECO FanCoil Unit
 
Burkert 6013 - 2/2 Solenoid Valve > นิวเมติก.com
Burkert 6013 - 2/2 Solenoid Valve > นิวเมติก.comBurkert 6013 - 2/2 Solenoid Valve > นิวเมติก.com
Burkert 6013 - 2/2 Solenoid Valve > นิวเมติก.comDNTMb Inc.
 
Pollution control solutions prowess-2k16-1-1
Pollution control solutions prowess-2k16-1-1Pollution control solutions prowess-2k16-1-1
Pollution control solutions prowess-2k16-1-1Atul Saxena
 
2 building enclosures #2 (2014)
2 building enclosures #2 (2014)2 building enclosures #2 (2014)
2 building enclosures #2 (2014)RCorduroy
 
Integrative high pressure solar water heater
Integrative high pressure solar water heater Integrative high pressure solar water heater
Integrative high pressure solar water heater Jussi Han
 
Industrial Steam Turbines Portfolio_EN
Industrial Steam Turbines Portfolio_ENIndustrial Steam Turbines Portfolio_EN
Industrial Steam Turbines Portfolio_ENFran Dubois
 
Wadbros Imports & Exports, Mumbai, Designer Exhaust Fan
Wadbros Imports & Exports, Mumbai, Designer Exhaust FanWadbros Imports & Exports, Mumbai, Designer Exhaust Fan
Wadbros Imports & Exports, Mumbai, Designer Exhaust FanIndiaMART InterMESH Limited
 

What's hot (18)

Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 CertifiedHazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
Hazloc AEU1 Air Heater - Hazardous Area Explosion Proof ATEX Zone 1 Certified
 
Inverter Ducted Brochure
Inverter Ducted BrochureInverter Ducted Brochure
Inverter Ducted Brochure
 
Hazloc Explosion-proof Heaters AEU1 - Brochure
Hazloc Explosion-proof Heaters AEU1 - BrochureHazloc Explosion-proof Heaters AEU1 - Brochure
Hazloc Explosion-proof Heaters AEU1 - Brochure
 
Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206Ap 23 7900 001 (package air conditioning units) 2011 1206
Ap 23 7900 001 (package air conditioning units) 2011 1206
 
Section Nine Rittal4racks 2012
Section Nine    Rittal4racks 2012Section Nine    Rittal4racks 2012
Section Nine Rittal4racks 2012
 
Rittal Pano Isıtıcıları
Rittal Pano IsıtıcılarıRittal Pano Isıtıcıları
Rittal Pano Isıtıcıları
 
Dc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and TipsDc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and Tips
 
Breezair tbs580
Breezair tbs580 Breezair tbs580
Breezair tbs580
 
Burkert 6013 - 2/2 Solenoid Valve > นิวเมติก.com
Burkert 6013 - 2/2 Solenoid Valve > นิวเมติก.comBurkert 6013 - 2/2 Solenoid Valve > นิวเมติก.com
Burkert 6013 - 2/2 Solenoid Valve > นิวเมติก.com
 
SHEL LAB Ovens Catalog
SHEL LAB Ovens CatalogSHEL LAB Ovens Catalog
SHEL LAB Ovens Catalog
 
Carrier Aspire Brochure
Carrier Aspire BrochureCarrier Aspire Brochure
Carrier Aspire Brochure
 
Pollution control solutions prowess-2k16-1-1
Pollution control solutions prowess-2k16-1-1Pollution control solutions prowess-2k16-1-1
Pollution control solutions prowess-2k16-1-1
 
2 building enclosures #2 (2014)
2 building enclosures #2 (2014)2 building enclosures #2 (2014)
2 building enclosures #2 (2014)
 
Vacuum Oven - Laboratory or Process Scale
Vacuum Oven - Laboratory or Process ScaleVacuum Oven - Laboratory or Process Scale
Vacuum Oven - Laboratory or Process Scale
 
Integrative high pressure solar water heater
Integrative high pressure solar water heater Integrative high pressure solar water heater
Integrative high pressure solar water heater
 
Siemens Steam Turbines 2MW-250MW
Siemens Steam Turbines 2MW-250MWSiemens Steam Turbines 2MW-250MW
Siemens Steam Turbines 2MW-250MW
 
Industrial Steam Turbines Portfolio_EN
Industrial Steam Turbines Portfolio_ENIndustrial Steam Turbines Portfolio_EN
Industrial Steam Turbines Portfolio_EN
 
Wadbros Imports & Exports, Mumbai, Designer Exhaust Fan
Wadbros Imports & Exports, Mumbai, Designer Exhaust FanWadbros Imports & Exports, Mumbai, Designer Exhaust Fan
Wadbros Imports & Exports, Mumbai, Designer Exhaust Fan
 

Similar to Điều Hòa Cassette Âm Trần 18000BTU Daikin 2HP FCNQ18MV1/RNQ18MV19

Điêu hòa âm trần 36000BTU 2 chiều
Điêu hòa âm trần 36000BTU 2 chiềuĐiêu hòa âm trần 36000BTU 2 chiều
Điêu hòa âm trần 36000BTU 2 chiềuMyravn1
 
VRV-A-DIDVA1808B.pdf
VRV-A-DIDVA1808B.pdfVRV-A-DIDVA1808B.pdf
VRV-A-DIDVA1808B.pdfRahmanOde
 
MULTI V 5 Catalogue_Small[20231107_182247769].pdf
MULTI V 5 Catalogue_Small[20231107_182247769].pdfMULTI V 5 Catalogue_Small[20231107_182247769].pdf
MULTI V 5 Catalogue_Small[20231107_182247769].pdfAnkitavaghela5
 
42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdfCarrier Singapore
 
Compressed Coalescing Filters for Industrial Use
Compressed Coalescing Filters for Industrial UseCompressed Coalescing Filters for Industrial Use
Compressed Coalescing Filters for Industrial UseClassic Controls, Inc.
 
ELGI Airmate Air Accessories Total Compressed Air Solutions
ELGI Airmate Air Accessories Total Compressed Air SolutionsELGI Airmate Air Accessories Total Compressed Air Solutions
ELGI Airmate Air Accessories Total Compressed Air SolutionsVijayEngineeringandM1
 
Rittal Fan Filtre Ürünleri
Rittal Fan Filtre ÜrünleriRittal Fan Filtre Ürünleri
Rittal Fan Filtre Ürünlerierdinc klima
 
Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...
Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...
Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...Kinetrol USA
 
Uscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATOUscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATOColinGroup Craiova
 
Air compressor in saudi arabia
Air compressor in saudi arabiaAir compressor in saudi arabia
Air compressor in saudi arabia3tsaudi
 
Manual 48GC-4-6-03SI.pdf
Manual 48GC-4-6-03SI.pdfManual 48GC-4-6-03SI.pdf
Manual 48GC-4-6-03SI.pdfDiego839645
 
Louisville july august
Louisville july augustLouisville july august
Louisville july augusttsksc186
 
Edus391004 n vrviii installation manual 2
Edus391004 n vrviii installation manual 2Edus391004 n vrviii installation manual 2
Edus391004 n vrviii installation manual 2Hangkheang Khy
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfSergioPereira229337
 
Mitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 seriesMitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 seriesDien Ha The
 
Mitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 seriesMitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 seriesDien Ha The
 

Similar to Điều Hòa Cassette Âm Trần 18000BTU Daikin 2HP FCNQ18MV1/RNQ18MV19 (20)

Điêu hòa âm trần 36000BTU 2 chiều
Điêu hòa âm trần 36000BTU 2 chiềuĐiêu hòa âm trần 36000BTU 2 chiều
Điêu hòa âm trần 36000BTU 2 chiều
 
Carrier Inverter Ducted_tcm175-49778 (1).pdf
Carrier Inverter Ducted_tcm175-49778 (1).pdfCarrier Inverter Ducted_tcm175-49778 (1).pdf
Carrier Inverter Ducted_tcm175-49778 (1).pdf
 
VRV-A-DIDVA1808B.pdf
VRV-A-DIDVA1808B.pdfVRV-A-DIDVA1808B.pdf
VRV-A-DIDVA1808B.pdf
 
MULTI V 5 Catalogue_Small[20231107_182247769].pdf
MULTI V 5 Catalogue_Small[20231107_182247769].pdfMULTI V 5 Catalogue_Small[20231107_182247769].pdf
MULTI V 5 Catalogue_Small[20231107_182247769].pdf
 
42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf42GWC Hydronic Cassette Fan Coil Units.pdf
42GWC Hydronic Cassette Fan Coil Units.pdf
 
Vrv x-didvx1808 b
Vrv x-didvx1808 bVrv x-didvx1808 b
Vrv x-didvx1808 b
 
Compressed Coalescing Filters for Industrial Use
Compressed Coalescing Filters for Industrial UseCompressed Coalescing Filters for Industrial Use
Compressed Coalescing Filters for Industrial Use
 
ELGI Airmate Air Accessories Total Compressed Air Solutions
ELGI Airmate Air Accessories Total Compressed Air SolutionsELGI Airmate Air Accessories Total Compressed Air Solutions
ELGI Airmate Air Accessories Total Compressed Air Solutions
 
Rittal Fan Filtre Ürünleri
Rittal Fan Filtre ÜrünleriRittal Fan Filtre Ürünleri
Rittal Fan Filtre Ürünleri
 
Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...
Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...
Installation, Operation & Maintenance Instructions for Kinetrol Rotary Actuat...
 
Uscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATOUscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATO
 
Air compressor in saudi arabia
Air compressor in saudi arabiaAir compressor in saudi arabia
Air compressor in saudi arabia
 
QX1402 VDL(H) spec.
QX1402 VDL(H) spec.QX1402 VDL(H) spec.
QX1402 VDL(H) spec.
 
Manual 48GC-4-6-03SI.pdf
Manual 48GC-4-6-03SI.pdfManual 48GC-4-6-03SI.pdf
Manual 48GC-4-6-03SI.pdf
 
Louisville july august
Louisville july augustLouisville july august
Louisville july august
 
Edus391004 n vrviii installation manual 2
Edus391004 n vrviii installation manual 2Edus391004 n vrviii installation manual 2
Edus391004 n vrviii installation manual 2
 
Three part specification
Three part specificationThree part specification
Three part specification
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdf
 
Mitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 seriesMitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 series
 
Mitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 seriesMitsubishi inverter freqrol-d700 series
Mitsubishi inverter freqrol-d700 series
 

Recently uploaded

FULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | DelhiFULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | DelhiMalviyaNagarCallGirl
 
Call Girl Service in Karachi +923081633338 Karachi Call Girls
Call Girl Service in Karachi +923081633338 Karachi Call GirlsCall Girl Service in Karachi +923081633338 Karachi Call Girls
Call Girl Service in Karachi +923081633338 Karachi Call GirlsAyesha Khan
 
Akola Call Girls #9907093804 Contact Number Escorts Service Akola
Akola Call Girls #9907093804 Contact Number Escorts Service AkolaAkola Call Girls #9907093804 Contact Number Escorts Service Akola
Akola Call Girls #9907093804 Contact Number Escorts Service Akolasrsj9000
 
FULL ENJOY - 9953040155 Call Girls in Paschim Vihar | Delhi
FULL ENJOY - 9953040155 Call Girls in Paschim Vihar | DelhiFULL ENJOY - 9953040155 Call Girls in Paschim Vihar | Delhi
FULL ENJOY - 9953040155 Call Girls in Paschim Vihar | DelhiMalviyaNagarCallGirl
 
Patrakarpuram ) Cheap Call Girls In Lucknow (Adult Only) 🧈 8923113531 𓀓 Esco...
Patrakarpuram ) Cheap Call Girls In Lucknow  (Adult Only) 🧈 8923113531 𓀓 Esco...Patrakarpuram ) Cheap Call Girls In Lucknow  (Adult Only) 🧈 8923113531 𓀓 Esco...
Patrakarpuram ) Cheap Call Girls In Lucknow (Adult Only) 🧈 8923113531 𓀓 Esco...akbard9823
 
9654467111 Call Girls In Noida Sector 62 Short 1500 Night 6000
9654467111 Call Girls In Noida Sector 62 Short 1500 Night 60009654467111 Call Girls In Noida Sector 62 Short 1500 Night 6000
9654467111 Call Girls In Noida Sector 62 Short 1500 Night 6000Sapana Sha
 
Islamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad Escorts
Islamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad EscortsIslamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad Escorts
Islamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad Escortswdefrd
 
Burari Call Girls : ☎ 8527673949, Low rate Call Girls
Burari Call Girls : ☎ 8527673949, Low rate Call GirlsBurari Call Girls : ☎ 8527673949, Low rate Call Girls
Burari Call Girls : ☎ 8527673949, Low rate Call Girlsashishs7044
 
Pragati Maidan Call Girls : ☎ 8527673949, Low rate Call Girls
Pragati Maidan Call Girls : ☎ 8527673949, Low rate Call GirlsPragati Maidan Call Girls : ☎ 8527673949, Low rate Call Girls
Pragati Maidan Call Girls : ☎ 8527673949, Low rate Call Girlsashishs7044
 
Delhi Room Call Girls : ☎ 8527673949, Low rate Call girl service
Delhi Room Call Girls : ☎ 8527673949, Low rate Call girl serviceDelhi Room Call Girls : ☎ 8527673949, Low rate Call girl service
Delhi Room Call Girls : ☎ 8527673949, Low rate Call girl serviceashishs7044
 
Roadrunner Lodge, Motel/Residence, Tucumcari NM
Roadrunner Lodge, Motel/Residence, Tucumcari NMRoadrunner Lodge, Motel/Residence, Tucumcari NM
Roadrunner Lodge, Motel/Residence, Tucumcari NMroute66connected
 
FULL ENJOY - 9953040155 Call Girls in Uttam Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Uttam Nagar | DelhiFULL ENJOY - 9953040155 Call Girls in Uttam Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Uttam Nagar | DelhiMalviyaNagarCallGirl
 
FULL ENJOY - 9953040155 Call Girls in Gtb Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Gtb Nagar | DelhiFULL ENJOY - 9953040155 Call Girls in Gtb Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Gtb Nagar | DelhiMalviyaNagarCallGirl
 
Bur Dubai Call Girls O58993O4O2 Call Girls in Bur Dubai
Bur Dubai Call Girls O58993O4O2 Call Girls in Bur DubaiBur Dubai Call Girls O58993O4O2 Call Girls in Bur Dubai
Bur Dubai Call Girls O58993O4O2 Call Girls in Bur Dubaidajasot375
 
Alex and Chloe by Daniel Johnson Storyboard
Alex and Chloe by Daniel Johnson StoryboardAlex and Chloe by Daniel Johnson Storyboard
Alex and Chloe by Daniel Johnson Storyboardthephillipta
 
SHIVNA SAHITYIKI APRIL JUNE 2024 Magazine
SHIVNA SAHITYIKI APRIL JUNE 2024 MagazineSHIVNA SAHITYIKI APRIL JUNE 2024 Magazine
SHIVNA SAHITYIKI APRIL JUNE 2024 MagazineShivna Prakashan
 
FULL ENJOY - 9953040155 Call Girls in Dwarka Mor | Delhi
FULL ENJOY - 9953040155 Call Girls in Dwarka Mor | DelhiFULL ENJOY - 9953040155 Call Girls in Dwarka Mor | Delhi
FULL ENJOY - 9953040155 Call Girls in Dwarka Mor | DelhiMalviyaNagarCallGirl
 
Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857
Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857
Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857delhimodel235
 
Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...
Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...
Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...dajasot375
 
Kishangarh Call Girls : ☎ 8527673949, Low rate Call Girls
Kishangarh Call Girls : ☎ 8527673949, Low rate Call GirlsKishangarh Call Girls : ☎ 8527673949, Low rate Call Girls
Kishangarh Call Girls : ☎ 8527673949, Low rate Call Girlsashishs7044
 

Recently uploaded (20)

FULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | DelhiFULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Laxmi Nagar | Delhi
 
Call Girl Service in Karachi +923081633338 Karachi Call Girls
Call Girl Service in Karachi +923081633338 Karachi Call GirlsCall Girl Service in Karachi +923081633338 Karachi Call Girls
Call Girl Service in Karachi +923081633338 Karachi Call Girls
 
Akola Call Girls #9907093804 Contact Number Escorts Service Akola
Akola Call Girls #9907093804 Contact Number Escorts Service AkolaAkola Call Girls #9907093804 Contact Number Escorts Service Akola
Akola Call Girls #9907093804 Contact Number Escorts Service Akola
 
FULL ENJOY - 9953040155 Call Girls in Paschim Vihar | Delhi
FULL ENJOY - 9953040155 Call Girls in Paschim Vihar | DelhiFULL ENJOY - 9953040155 Call Girls in Paschim Vihar | Delhi
FULL ENJOY - 9953040155 Call Girls in Paschim Vihar | Delhi
 
Patrakarpuram ) Cheap Call Girls In Lucknow (Adult Only) 🧈 8923113531 𓀓 Esco...
Patrakarpuram ) Cheap Call Girls In Lucknow  (Adult Only) 🧈 8923113531 𓀓 Esco...Patrakarpuram ) Cheap Call Girls In Lucknow  (Adult Only) 🧈 8923113531 𓀓 Esco...
Patrakarpuram ) Cheap Call Girls In Lucknow (Adult Only) 🧈 8923113531 𓀓 Esco...
 
9654467111 Call Girls In Noida Sector 62 Short 1500 Night 6000
9654467111 Call Girls In Noida Sector 62 Short 1500 Night 60009654467111 Call Girls In Noida Sector 62 Short 1500 Night 6000
9654467111 Call Girls In Noida Sector 62 Short 1500 Night 6000
 
Islamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad Escorts
Islamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad EscortsIslamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad Escorts
Islamabad Call Girls # 03091665556 # Call Girls in Islamabad | Islamabad Escorts
 
Burari Call Girls : ☎ 8527673949, Low rate Call Girls
Burari Call Girls : ☎ 8527673949, Low rate Call GirlsBurari Call Girls : ☎ 8527673949, Low rate Call Girls
Burari Call Girls : ☎ 8527673949, Low rate Call Girls
 
Pragati Maidan Call Girls : ☎ 8527673949, Low rate Call Girls
Pragati Maidan Call Girls : ☎ 8527673949, Low rate Call GirlsPragati Maidan Call Girls : ☎ 8527673949, Low rate Call Girls
Pragati Maidan Call Girls : ☎ 8527673949, Low rate Call Girls
 
Delhi Room Call Girls : ☎ 8527673949, Low rate Call girl service
Delhi Room Call Girls : ☎ 8527673949, Low rate Call girl serviceDelhi Room Call Girls : ☎ 8527673949, Low rate Call girl service
Delhi Room Call Girls : ☎ 8527673949, Low rate Call girl service
 
Roadrunner Lodge, Motel/Residence, Tucumcari NM
Roadrunner Lodge, Motel/Residence, Tucumcari NMRoadrunner Lodge, Motel/Residence, Tucumcari NM
Roadrunner Lodge, Motel/Residence, Tucumcari NM
 
FULL ENJOY - 9953040155 Call Girls in Uttam Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Uttam Nagar | DelhiFULL ENJOY - 9953040155 Call Girls in Uttam Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Uttam Nagar | Delhi
 
FULL ENJOY - 9953040155 Call Girls in Gtb Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Gtb Nagar | DelhiFULL ENJOY - 9953040155 Call Girls in Gtb Nagar | Delhi
FULL ENJOY - 9953040155 Call Girls in Gtb Nagar | Delhi
 
Bur Dubai Call Girls O58993O4O2 Call Girls in Bur Dubai
Bur Dubai Call Girls O58993O4O2 Call Girls in Bur DubaiBur Dubai Call Girls O58993O4O2 Call Girls in Bur Dubai
Bur Dubai Call Girls O58993O4O2 Call Girls in Bur Dubai
 
Alex and Chloe by Daniel Johnson Storyboard
Alex and Chloe by Daniel Johnson StoryboardAlex and Chloe by Daniel Johnson Storyboard
Alex and Chloe by Daniel Johnson Storyboard
 
SHIVNA SAHITYIKI APRIL JUNE 2024 Magazine
SHIVNA SAHITYIKI APRIL JUNE 2024 MagazineSHIVNA SAHITYIKI APRIL JUNE 2024 Magazine
SHIVNA SAHITYIKI APRIL JUNE 2024 Magazine
 
FULL ENJOY - 9953040155 Call Girls in Dwarka Mor | Delhi
FULL ENJOY - 9953040155 Call Girls in Dwarka Mor | DelhiFULL ENJOY - 9953040155 Call Girls in Dwarka Mor | Delhi
FULL ENJOY - 9953040155 Call Girls in Dwarka Mor | Delhi
 
Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857
Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857
Low Rate Call Girls in Laxmi Nagar Delhi Call 9990771857
 
Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...
Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...
Call Girl in Bur Dubai O5286O4116 Indian Call Girls in Bur Dubai By VIP Bur D...
 
Kishangarh Call Girls : ☎ 8527673949, Low rate Call Girls
Kishangarh Call Girls : ☎ 8527673949, Low rate Call GirlsKishangarh Call Girls : ☎ 8527673949, Low rate Call Girls
Kishangarh Call Girls : ☎ 8527673949, Low rate Call Girls
 

Điều Hòa Cassette Âm Trần 18000BTU Daikin 2HP FCNQ18MV1/RNQ18MV19

  • 1. PCSVN1420A All rights reserved 07/14 SS c 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. Cautions on product corrosion Warning Ask a quali ed installer or contractor to install this product. Do not try to install the product by yourself. Improper installation can result in water or refrigerant leakage, electrical shock re or explosion. Use only those parts and accessories supplied or speci ed by Daikin. Ask a quali ed installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical sho re or explosion. Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. notice. Đại lyù phaân phoái: Miễn phí cöôùc cuoäc goïi TRUNG TÂM DICH VU KHÁCH HÀNG
  • 2. RNQ26MV1 Outdoor unit Indoor unit FDMNQ26MV1 RNQ26MY1 RNQ30MV1 FDMNQ30MV1 RNQ30MY1 RNQ36MV1 FDMNQ36MV1 RNQ36MY1 RNQ42MY1 FDMNQ42MV1 RNQ48MY1 FDMNQ48MV1 RNQ21MV1 RNQ26MV1 RNQ18MV1 Outdoor unit Indoor unit DUCT CONNECTION LOW STATIC PRESSURE TYPE MIDDLE STATIC PRESSURE TYPE FDBNQ18MV1 FDBNQ21MV1 FDBNQ26MV1 RNQ26MY1 RNQ26MY1 RNQ21MV1 RNQ18MV1 Outdoor unit Indoor unit CEILING SUSPENDED TYPE FHNQ18MV1 FHNQ21MV1 FHNQ26MV1 FHNQ30MV1 FHNQ36MV1 FHNQ48MV1 FHNQ42MV1 1 2 26 21 RNQ21MV1 RNQ26MV1 18 RNQ18MV1 13 09 Outdoor unit Indoor unit CEILING MOUNTED CASSETTE TYPE Round Flow Series Pair FCNQ18MV1 RNQ13MV1 FCNQ13MV1 FCNQ21MV1 FCNQ26MV1 RNQ26MY1 30 RNQ30MV1 FCNQ30MV1 RNQ30MY1 36 RNQ36MV1 RNQ26MV1 RNQ30MV1 RNQ36MV1 FCNQ36MV1 RNQ36MY1 42 RNQ42MY1 FCNQ42MV1 48 26,000 21,000 18,000/17,700*1 13,000 9,200 Btu/h 30,000 36,000/35,000*2 42,600/42,000*2,3 48,000 7.6 6.2 5.3/5.2*1 3.8 2.7 kW 8.8 10.6/10.4*2 12.5/12.3*2,3 14.1 RNQ48MY1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1 FCNQ48MV1 Outdoor unit OUTDOOR UNIT P r o d u c t L i n e u p RNQ13MV1 FHNQ13MV1 RNQ13MV1 FDBNQ13MV1 RNQ09MV1 FDBNQ09MV1 New wide lineup of SkyAir series. Note : *1 Applicable to FDBNQ series. *2 Applicable to FHNQ series. *3 Applicable to FDMNQ series. RNQ09MV1 RNQ13MV1 RNQ18MV1 RNQ21MV1 RNQ26MV1 RNQ26MY1 RNQ30MV1 RNQ30MY1 RNQ36MV1 RNQ36MY1 RNQ42MY1 RNQ48MY1
  • 3. Airflow distribution Creates uniform comfort throughout the space Comfort enhanced by Round Flow! With uniform temperature distribution Enhanced Comfort Greater comfort Improved energy saving • Condition after exposure to the smoke of 600 cigarettes in 1 m3 enclosed space. Treated surface Untreated surface Grimy surface Resists soiling External panels are treated with a coating that repels dirt. Avoids uneven temperature and discomfort caused by drafts. To prevent dirt sticking to the external panels, they have been coated with a surface treatment. Because air flows out from corner outlets, comfort spreads more widely. 360° airflow Air movement is gentle with Round Flow Condensation does not easily form on and dirt does not cling to non-flocking flaps. It is easy to clean. Non-flocking flaps Prevents mould and microorganisms growing out of the dust and moisture that adheres to the filters. Filter has anti-mould and bactericidal treatment Grime prevention and bactericidal coating: Make cleaning easier. Adapts easily to the installation space. Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet. 3-way flow L-shaped 2-way flow Opposite 2-way flow (E.g., installed in a corner) (E.g., installed in a long room) (E.g., installed near a wall) (E.g., installed in middle of ceiling) 4-way flow also possible. All-round flow 360° airflow can maintain comfort even if air discharge speed is lower. Typical flow patterns There are a total of 23 flow patterns. If you raise the set temperature by 1 to 1.5°C,and velocity is decreased by 25%, you still obtain the same feeling temperature and comfort. Operation sound increases when using 2-way or 3-way flow. • • • • • *1 • *4 • • • • • • • • *6 Cleanliness Comfort Work & Servicing Control features Others Options Features Accessory required for indoor unit. Option *1 Applicable when wired remote controller is used *2 Applicable when BRC1E62 is used *3 Applicable when BRC1C61 is used *4 Applicable to RNQ30-48M outdoor units *5 Applicable to RNQ13-26M outdoor units *6 For the outdoor units CEILING MOUNTED CASSETTE TYPE FCNQ13/18/21/26/30/36/42/48MV1 Swing pattern selection Switchable fan speed (2 step) Auto swing Programme "Dry" High ceiling application Drain pump mechanism • Anti-bacterial air filter Pre charged for up to 15 m *5 Pre charged for up to 10 m Long-life filter Filter sign Ceiling soiling prevention Ultra long-life filter • High-efficiency filter Fresh air intake kit Control by 2 remote controllers Auto-restart Group control by 1 remote controller • External command control • Central remote control • Interlock control • DIII-NET communication standard Anti corrosion treated heat exchangers Two selectable temperature-sensors Round Flow BRC1E62 Navigation Remote Controller (Wired Remote Controller) BRC7F633F A signal receiver must be added to the indoor unit. Wireless remote controller and signal receiver unit are sold as a set. Wireless LCD remote controller Signal receiver unit (Installed type) Note: Remote controller cable not included. Cables must be procured locally. Note: Remote controller cable not included. Cables must be procured locally. Wired LCD remote controller BRC1C61 3 4 Remote controller *2 *2 *2 *2 *3 Setpoint range set Weekly schedule timer Setpoint auto reset Off timer (programmed) On/Off timer Cassette air conditioner with 360° uniform airflow sets the standard Cassette air conditioner with 360° uniform airflow sets the standard 43/32dB(A) FCNQ36M (220V) High Low Sound level
  • 4. Options required for specific operating environments High-efficiency filter Available in two types: 65% and 90% colorimetry. Using this kit, a duct can be fitted to increase the intake of outdoor air. *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally. **Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking. ***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and may also influence temperature sending. Fresh air intake kit Even in smoky environments where the air conditioning is on most of the time, the ultra long-life filter only has to be changed once a year. Ultra long-life filter Panel spacer Use when only minimal space is available between drop ceilings and ceiling slabs. Sealing material of air discharge outlet Sealing material block air discharge openings not used in 2-way or 3-way blow. Branch duct (direct-connection round duct) Outside Note: Use of options will increase operating sound. The units can be installed in the following different ways. Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing your unit. Direct installation type Flexible duct T-joint pipe Intake duct (procured locally) (duct length: 4 m max.) Intake duct (procured locally) (duct length: 4 m max.) Connection chamber Suction chamber Duct flange (with insulation material) Intake duct (procured locally) Chamber type (with T-joint pipe and without fan) Flexible duct (procured locally) T-joint pipe (procured locally) Chamber type (without T-joint pipe and fan) KDDP55X160 KDDP55B160K KDDP55B160 Easier to maintain With Ultra long-life filters (option), maintenance is not required in normal shops or offices for up to four years. The condition of the drain pan and drain water can be checked by removing the drain plug and intake grille. Drain plug Just open the intake grille! 40mm Panel spacer A round duct can be attached without the need for a chamber. A flanged port for direct connection of a round duct is provided. An existing branch duct chamber can also be fitted (square slit hole). Connection chamber Suction chamber Smoky atmosphere: annual filter change Ordinary store or office: filter change every 4 years *For dust concentration of 0.3 mg/m3 (Requires separately sold Air Cleaner.) 1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year *For dust concentration of 0.15 mg/m3 4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years Note: Quick and easy to install Just 256 mm high. Installable in tight ceiling spaces (13-26M) Fine square panels Compact body and quiet operation *Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor. Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. Note: Air direction is set to the standard position when the unit is shipped from the factory. The position can be changed from the remote controller. Panel size is same for all models, FCNQ13-48M. It is easy to maintain a neat appearance when multiple units are installed. Optimal comfort and convenience assured by 2 air discharge modes Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature must be set during commissioning by the technicians. Two selectable temperature-sensors Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level. Suitable for high ceilings Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses. On/Off timer Indoor unit High Low dB(A) 13/18M 31 28 21/26M 35 28 30/36M 43 32 42M 44 34 48M 44 36 Same for all models Air direction Auto air direction control Settable to 5 different levels between 15° and 60° Settable to 5 different levels between 25° and 60° Auto-swing between 15° and 60° Auto-swing between 25° and 60° Recommended for shops with light coloured ceilings that must be kept spotless. Standard position to prevent draft. Standard setting Setting to prevent soiling of ceiling* The air direction is set automatically to the memorised position of the previous air direction. Desired situation Auto-swing 5-levels air direction setting *Closing of the corner discharge outlets is recommended. Number of air discharge outlets used 4-way flow 3-way flow 2-way flow 4-way flow 3-way flow 2-way flow 3.1 m 3.4 m 4.0 m All round flow 2.7 m 3.0 m 3.5 m 3.0 m 3.3 m 3.5 m 3.5 m 3.8 m - 3.4 m 3.9 m 4.5 m All round flow 3.2 m 3.6 m 4.2 m 3.6 m 4.0 m 4.2 m 4.2 m 4.2 m - Standard Ceiling height High ceiling High ceiling Criteria for ceiling height and number of air discharge outlets 950 mm 950 m m Note: Factory settings are for standard ceiling height and all-round flow. High ceiling settings (1) and (2) are set with the remote controller by field setting. 256 mm *1 266 mm *2 *1 298 mm high with 30-48M *2 308 mm high with 30-48M All models can be installed without using lifter because of the light weight. Drain pump is equipped as standard accessory with 850 mm lift. Transparent drain socket Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height. Since the orientation of the intake grill can be adjusted after installing, the direction of the intake grill lines can be unified when multiple units are installed. Note: If the wireless remote control option is installed, a light receptor unit is housed in one of the adjuster pockets. Easy height adjustment Installable in any direction Because the drain socket is transparent, after the drain piping has been installed, it is easy to check if the drain come out through the socket. High setting provides maximum reach while low setting minimises drafts. Switchable fan speed: High/Low 175 mm 850 mm 30-48M 13-26M 5 6 CEILING MOUNTED CASSETTE TYPE Round Flow (Ceiling height is reference value) Connection to a centralised control system is available without option
  • 5. * For dust concentration of 0.15 mg/m 3 (mm) Uses quiet stream fan and other quiet technologies. Turbulent flow is reduced Straightening plate Quiet stream fan 50° 18/21M 44 40 26/30M 45 40 36/42M 48 42 48M 49 43 Indoor unit High Low 13M 43 39 195 960 1,160 680 Height Indoor unit Width Depth 13M 18/21M 1,400 1,590 26/30M 36/42/48M Quiet operation Easier to maintain Sound operation has been reduced on the exposed ceiling suspended type unit. Oil resistant grille Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments. Oil-resistant plastic is used for the air suction grille. This satisfies durability in restaurants and other similar environments. For all maintenance tasks, access is from bottom surface. Two time settings (2500 hrs and 1250 hrs) are available to match the installation environment. Maintenance time warning is displayed on the remote controller (filter sign). It is easy to wipe dirt off the flat side and lower surfaces of the unit. Easy-clean, flat surfaces Long-life filter lasts about 1 year* Diffuses comfortable air throughout the room Installation flexibility for freedom of design Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. Programme "Dry" Auto-swing (up&down) brings comfort to the room. Wide air discharge openings produce a spreading 100° airflow Air is blown up to 50° in the downward direction. Switchable fan speed: High/Low Installable on ceilings 3.5 m high 100° *Water used in the test-run can now be drained from the air discharge opening rather than from the side as was formerly the case. The unit fits more snugly into tight spaces. Flexible installation Uniform height and depth. Compact design for small-capacity models to meet tighter dimensional constraints. 30 mm or more 30 mm or more Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. (220V) dB(A) Pipes more easily rigged Plastic cover is used to conceal piping work holes. When piping work the cover is easily taken off, and after piping work easily attached again to conceal the holes. All wiring and internal servicing can be done from under the unit Non-flocking flap Condensation does not easily form on and dirt does not cling to non-flocking flap. It is easy to clean. Non-flocking flap CEILING SUSPENDED TYPE 7 8 Upgrade to a quiet and compact system. Upgrade to a quiet and compact system. Accessory required for indoor unit. Option Wired LCD remote controller Features *1 Installable on max. 3.5 m high ceiling *2Applicable to RNQ30-48M outdoor units *3Applicable to RNQ13-26M outdoor units *4 For the outdoor units • • • *1 • • *4 Cleanliness Comfort Work & Servicing Control features Others Switchable fan speed (2 step) Auto swing Programme "Dry" High ceiling application • Anti-bacterial air filter *3 Pre charged for up to 10 m *2 Pre charged for up to 15 m Long-life filter Auto-restart Anti corrosion treated heat exchangers Remote controller • On/Off timer FHNQ13/18/21/26/30/36/42/48MV1 44/40dB(A) FHNQ21M (220V) High Low Sound level BRC7NU66 A signal receiver must be added to the indoor unit. Note: Remote controller cable not included. Cables must be procured locally. Wireless remote controller and signal receiver unit are sold as a set. Wired LCD remote controller Wireless LCD remote controller BRC1NU61 Signal receiver unit (Installed type)
  • 6. Quiet operation Quiet operation 9 10 DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Freedom of layout BRC4C64 A signal receiver must be added to the indoor unit. Wireless remote controller and signal receiver unit are sold as a set. Wireless LCD remote controller Wired LCD remote controller BRC1C61 Accessory required for indoor unit Option Signal receiver unit (Separate type) Switchable fan speed: High/Low Drain pipe connection can be done inside the unit. Refrigerant and drain pipe outlets are at the same opening. The duct system allows the efficient location of discharge outlets in accordance with the room layout Duct connection is simpler with standard rear intake chambers BRC1E62 Navigation Remote Controller (Wired Remote Controller) Indoor unit High Low 21/26M 43 40 09/13/18M 41 38 (220V) dB(A) Indoor unit High Low 30M 44 36 26M 42 38 42/48M 46 37 36M 45 37 (220V) dB(A) BRC4C64 A signal receiver must be added to the indoor unit. Wireless remote controller and signal receiver unit are sold as a set. Wireless LCD remote controller Wired LCD remote controller BRC1C61 Accessory required for indoor unit Option Signal receiver unit (Separate type) BRC1E62 Navigation Remote Controller (Wired Remote Controller) FDBNQ09/13/18/21/26MV1 FDMNQ26/30/36/42/48MV1 DUCT CONNECTION LOW STATIC PRESSURE TYPE 45/37dB(A) FDMNQ36M (220V) High Low Sound level 43/40dB(A) FDBNQ26M (220V) High Low Sound level Ideal for quiet, beautiful living spaces Unit can be mounted in the ceiling and air can be delivered freely by duct. Suitable for condominiums and apartments, houses and hotels • • *1 • • • *4 Comfort Work & Servicing Control features Others Features *1 Applicable when wired remote controller is used *2 Applicable when BRC1E62 is used *3 Applicable when BRC1C61 is used *4 For the outdoor units Switchable fan speed (2 step) Programme "Dry" *4 Pre charged for up to 10 m Control by 2 remote controllers Auto-restart Group control by 1 remote controller Anti corrosion treated heat exchangers Two selectable temperature-sensors Remote controller *2 *2 *2 *2 *3 Setpoint range set Weekly schedule timer Setpoint auto reset Off timer (programmed) On/Off timer • • *1 • • • *6 Comfort Work & Servicing Control features Others Features *1 Applicable when wired remote controller is used *2 Applicable when BRC1E62 is used *3 Applicable when BRC1C61 is used *4 Applicable to RNQ30-48M outdoor units *5 Applicable to RNQ26M outdoor units *6 For the outdoor units Switchable fan speed (2 step) Programme "Dry" *4 Pre charged for up to 15 m *5 Pre charged for up to 10 m Control by 2 remote controllers Auto-restart Group control by 1 remote controller Anti corrosion treated heat exchangers Two selectable temperature-sensors Remote controller *2 *2 *2 *2 *3 Setpoint range set Weekly schedule timer Setpoint auto reset Off timer (programmed) On/Off timer Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening) Ventilation grille Door-installed ventilation grille Ventilation grille Wall-installed ventilation grille Under-door cutout Under-door cutout When air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms. Ventilates air through the partitioning wall. (See right) Partitioning wall Note: The under-door cutout method should be used only when there is a small volume of airflow. (This feature also applies to duct connection middle static pressure type.) Compact Small, lightweight, and easy-to-install indoor unit. Suction chamber Air filter (Note) [Duct connection] or more or more or more To prevent increased operation sound, avoid installing the air suction grille directly below the suction chamber. Note : 270 mm is the minimum size. Extra height is necessary for drain piping slope and insulation. Note : 325 mm is the minimum size. Extra height is necessary for drain piping slope and insulation. Air conditioner 305 mm Ordinary duct (procured locally) Air discharge Air intake (Note) or more or more or more 325 325 mm mm 325 mm Ordinary duct (procured locally)
  • 7. OUTDOOR UNIT Quiet Operation Fitted with Super Aero Grille To suppress turbulence and achieve quiet operation, the curved ribs of the grille are optimised to meet the outflow of air. Equipped with scroll compressor for quiet operation Smooth running, minimal vibration, low operating sound. Allowed refrigerant piping length and level difference Max. length Max. level difference Pre charged1 RNQ09/13M RNQ18/21M RNQ26M RNQ30-48M 10 m 30 m 10 m 15 m 20 m 30 m 30 m (Equivalent length 50m) 50 m (Equivalent length 70m) 15 m (Applies to RNQ30-48M) Installation and maintenance Pre charged for up to 15 metres If refrigerant piping length does not exceed 10m (RNQ09-26M), 15m (RNQ30-48M), there is no need for on-site gas charging. Durability As the bottom frame is subject to corrosion, corrosion-proof galvarium steel plate is adopted to enhance the durability. Heat exchange fins provided with anti-corrosion treatment 11 12 RNQ09MV1 RNQ13MV1 RNQ18MV1 RNQ21MV1 RNQ26MV1 RNQ26MY1 RNQ30MV1 RNQ30MY1 RNQ36MV1 RNQ36MY1 RNQ42MY1 RNQ48MY1 Operation sound dB(A) (Applies to RNQ42-48M) (Applies to RNQ30-48M) (Applies to RNQ09-26, 36-48M) 4-direction piping offers greater layout freedom The outer panel for the piping connection part of the front, right side and backside can be removed and is easier for post-installation piping work. (Applies to RNQ30-48M) Note: 1 Additional refrigerant charging is required if the refrigerant pipe is longer than the length. Outdoor unit Sound level RNQ09MV1 48 RNQ13MV1 49 RNQ18MV1 51 RNQ21MV1 52 RNQ26MV1/RNQ26MY1 54 RNQ30MV1/RNQ30MY1 55 RNQ36MV1/RNQ36MY1 54 RNQ42MY1 56 RNQ48MY1 58 Construction Non-treated fin Anti corrosion treated heat exchangers Aluminium Aluminium Corrosion resistant acrylic resin Hydrophilic film (In case of RNQ09-21M:220-240 V, RNQ26-36M:220 V/380 V, 240 V/415 V, RNQ42-48M:380 V, 415 V) Separation available Central remote controller Easily adaptable to large-scale, high-function, centralised remote control system. Centralised control, with setting as simple as it is with a standard remote controller, of up to 64 groups (1,024 indoor units) is possible. DCS302CA61 (Option) With its high functionality, the full colour “all-in-one” graphic controller facilitates management of SkyAir System in a variety of ways. DCS601C51 (Option) Unified on/off controller Centralised control of on/off by group or all at once for up to 256 indoor units. DCS301BA61 (Option) Schedule timer Unified control of weekly schedule for up to 1,024 indoor units. DST301BA61 (Option) Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time. Simple system provides a diverse assortment of control modes. Control by 1 remote controller Control pattern Applicable model FCNQ FDBNQ FDMNQ Wired remote controller Wireless remote controller Control by 2 remote controllers Group control Control by external command Centralised remote control Interlock control with Heat Reclaim Ventilator (Basic system) Control by 1 wireless remote controller and 1 wired remote controller (See note 2, 3) Signal receiver unit installed on indoor unit Signal receiver unit installed on indoor unit Can be operated simultaneously or independently by remote controller (set by ventilation mode) Heat Reclaim Ventilator Non-polar, double-core (max. wiring length 500 m) Connects 2 wired remote controllers (See note 1) Automatic address setting function Automatic address setting function Signal receiver unit installed on 1 indoor unit Optional wiring adaptor for electrical appendices is necessary Can be operated simultaneously by remote controller (set by ventilation mode) Heat Reclaim Ventilator For control from 2 locations such as in room and control room, exits, etc. For simultaneous control of up to 16 indoor units. Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room. Centralised control of up to 64 indoor groups from remote location up to 1 kilometer away. Link by remote controller group control. Zone link control by centralised control. Optional wiring adaptor for electrical appendices is necessary Note: 1 BRC1E62 can connect to BRC1E62 only. 2 It is not possible to use two wireless remote controllers. 3 BRC1E62 cannot connect to wireless remote controller. Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking Can also be operated independently by remote controller. Central remote controller (option) Heat Reclaim Ventilator Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking Central remote controller (option) Heat Reclaim Ventilator Central remote controller (option) Central remote controller (option) FCNQ only FCNQ series only To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, Anti corrosion treated heat exchangers (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.
  • 8. LCD REMOTE CONTROLLER Optional accessory Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.) Facilitates maintenance and repair All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be remotely set without having to use stepladder access for manual setting. Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically). Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction. Ceiling mounted cassette type shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning units, thus simplifying interlocking operations. Easily adaptable to large-scale, high-function, centralised remote control systems. Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy. LCD panel shows operating status in letters, numbers, and motion. Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle. Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool). Programming time display Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning. Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs. CEILING MOUNTED CASSETTE TYPE CEILING SUSPENDED TYPE DUCT CONNECTION LOW STATIC PRESSURE TYPE BRC7NU66 BRC7F633F BRC4C64 DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE BRC4C64 Wired remote controller has built-in temperature-sensor (Applies to wired remote controllers (BRC1C61/1E62)) (Applies to wired remote controller (BRC1E62)) 13 14 Clear Display Navigation Remote Controller (Wired Remote Controller BRC1E62) - 5 actions per day can be scheduled for each day of the week. - The holiday function will disable schedule timer for the days that have been set as holiday. - 3 independent schedules can be set. (e.g. summer, winter, mid-season) Display is available in 11 languages. Dot matrix display Backlight display Convenience Weekly schedule Multilingual display Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units. Remote controller options are shown on the page introducing each indoor unit model. NEW (English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish, and Polish). NEW A combination of fine dots enables various icons. Large text display is easy to see. This simple, modern designed remote controller with fresh white colour matches your interior design. Operation is much easier and smoother, just follow the indications on the navigation remote controller. Energy saving NEW - Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts. - Period can be preset from 30 to 180 minutes in10-minute increments. Off timer (programmed) Setpoint range set NEW Setpoint auto reset Restaurant sample Restaurant opened Temperature is set to 27ºC 27°C - Saves energy by limiting the min. and max. set temperature. - Avoids excessive heating or cooling. - This function is convenient when the remote controller is installed at a place where any number of people may operate it. - Even if the set temperature is changed, it returns to the preset temperature after apreset period of time. - Period selectable from 30min/60min/90min/120min. Full tables at lunchtime Then is lowered to 24ºC for crowded room 24°C After 30 minutes* Automatically returns to preset temperature (27ºC) *Setting possible for after 30, 60, 90, and 120 minutes. Returns to 27°C automatically Signal receiver unit (For ceiling mounted cassette type) Wireless remote controller for each indoor unit type LCD wireless remote controller Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the ceiling mounted cassette type. Wireless remote controller BRC7F633F The wireless remote controller is supplied in a set with a signal receiver. Signal receiver unit is contained inside decoration panel or indoor unit. Shape of signal receiver unit differs according to the indoor unit. The rubber switch and the oil-resistant plastic casing are adopted for durability. Only 17 mm thick. Can be installed either recessed or exposed. Easy to read because of large LCD screen. Wired LCD remote controller BRC1C61
  • 9. Note: Some features only available on selected models. See model pages for full list of features applicable to each unit. You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.) Group control by 1 remote controller Two types are available: 65% and 90% colorimetry. High-efficiency filter unit You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed. Fresh-air intake kit Work and Servicing Control features Options Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping. Maintenance is not required for one year. The filter is washable and can be reused. If refrigerant piping length does not exceed 15 m, there is no need for on-site gas charging. The filter sign warns you when it is time to clean the filter. *When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit. Drain pump mechanism Long-life filter Pre charged for up to 15 metres Filter sign Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required. Ceiling soiling prevention function If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored. Ultra long-life filter Auto-restart Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 kilometer away. Central remote control Enables interlocking control with external equipment such as Heat Reclaim Ventilator. Interlock control Standardly equipped interface enables connection to centralised control system without need of an adaptor. DIII-NET communication standard Using 2 remote controllers you can operate the equipment locally or from a remote location. Note: When a wireless remote controller is used, remote control by two remote controllers is not possible. Control by 2 remote controllers RNQ09-26M : 10 m *Applicable to RNQ30-48M. Requires no maintenance for about 4 years* (10,000h) in stores and offices. *For dust concentration of 0.15 mg/m3 *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally. **Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking. ***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending. Note: Others To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated Anti corrosion treated heat exchangers (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit. In high corrosive areas, regular maintenance needs to be carried out. Anti corrosion treated heat exchangers Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room. External command control *An option is required. 15 16 Abundance of functions that provide comfortable air-conditioning in stores and offices. Cleanliness The Air filter has a anti-bacterial treatment to help prevent the growth of bacteria and mould on it. Anti-bacterial air filter Note: Some features only available on selected models. See model pages for full list of features applicable to each unit. Note: Wireless remote controllers have no temperature-sensor. Use the temperature-sensor in the indoor unit when controlling air conditioning from another room. Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling of the room. Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner. High setting provides maximum reach while low setting minimises drafts. Auto-swing Programme "Dry" Switchable fan speed (1) Standard setting (2) Ceiling soiling prevention setting (standard, ceiling soiling prevention) Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply. You can freely set 2 air discharge setting by remote controller. Swing pattern selection Delivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings. High-ceiling application Two selectable temperature-sensors Comfort The air flow direction can be fixed at your desited angle by the remote controller. Temperature-sensors are included in the indoor unit and optional wired remote controller. Temperature sensing closer to target area is possible to further increase the comfort level. Remote Controller Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts. Off timer (programmed) Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses. On/Off timer Up to five operation ON/OFF settings can be programmed per day for each day of the week. Not only can the time be set for the operation ON setting, but also the temperature. Weekly schedule timer Even if the set temperature is changed, it returns to the preset temperature after a preset period of time. Saves energy by limiting the minimum and maximum set temperatures. Avoids excessive heating and cooling. Setpoint auto reset Setpoint range set
  • 10. CEILING MOUNTED CASSETTE TYPE CEILING SUSPENDED TYPE DUCT CONNECTION LOW STATIC PRESSURE TYPE DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE SPECIFICATIONS 43/39 24 White VP20 (I.Do / 20XO.Do / 26) 19.4 to 46 o / 6.4 49 36 40 49 --------- --------- --------- 1.2 (Charged for 10 m) 0.9 51 1.4 (Charged for 10 m) 1.4 52 1.5 (Charged for 10 m) 1.8 2.0 (Charged for 10 m) 2.2 1.9 (Charged for 15 m) 3.2 (Charged for 15 m) 2.7 2.7 (Charged for 15 m) 3.75 3.2 (Charged for 15 m) 4.5 Ivory white 30 10 15 Hermetically sealed rotary type o / 12.7 o / 15.9 o / 18.0 (Hole) °CWB °CDB Certified operation range Certified operation range Motor output Compressor Dimensions (HXWXD) Colour mm dB(A) kW Refrigerant charge (R-410A) kg dB(A) Sound level3 Dimensions (HXWXD) mm Machine weight kg kg V1 Y1 Piping connections mm Liquid (Flare) mm Gas (Flare) mm Drain Indoor unit Outdoor unit Machine weight kg Airflow rate (H/L) m3 /min 16/- 565/- Outdoor unit Colour mm Heat insulation Max. interunit piping length m m Max. installation level difference Type Sound level (H/L) (220 V)3 Indoor unit Both liquid and gas piping cfm 14 to 23 14 to 25 17 18 Note : 1 Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). 2 Capacities are net, including a deduction for cooling for indoor fan motor heat. 3 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. °CDB Certified Operation range Sound level3 °CWB Certified Operation range Motor output Compressor Dimensions (HXWXD) Colour mm mm dB(A) kW Refrigerant charge (R-410A) kg dB(A) Dimensions (HXWXD) mm Machine weight kg V1 Y1 Unit Piping connections mm Liquid (Flare) mm Gas (Flare) mm Drain Indoor unit Outdoor unit Decoration panel Unit Decoration panel Machine weight kg kg Unit Decoration panel Airflow rate (H/L) m3 /min cfm Outdoor unit Colour mm Heat insulation Max. interunit piping length m m Max. installation level difference Type Sound level (H/L)3 Indoor unit Hermetically sealed rotary type Hermetically sealed scroll type o / 6.4 o / 15.9 o / 12.7 50X950X950 5.5 ---------- 10 15 20 30 Ivory white Fresh white Both liquid and gas piping 30 30 (Equivalent length 50) 30 (Equivalent length 50) 50 (Equivalent length 70) o / 26.0 (Hole) o / 18.0 (Hole) VP25 (I.Do / 25XO.Do / 32) 19.4 to 46 o / 9.5 21 to 46 14 to 23 14 to 25 0.9 1.4 1.8 2.2 2.7 3.75 4.5 31/28 35/28 43/32 44/34 44/36 49 51 52 54 55 54 56 58 36 40 49 56 77 103 --------- --------- --------- --------- --------- 56 74 103 107 111 19.5 21 24 256X840X840 298X840X840 1.2 (Charged for 10 m) 1.4 (Charged for 10 m) 1.5 (Charged for 10 m) 2.0 (Charged for 10 m) 1.9 (Charged for 15 m) 3.2 (Charged for 15 m) 2.7 (Charged for 15 m) 3.2 (Charged for 15 m) 13/10 21/13.5 32/20 33/22.5 459/353 741/477 1,130/706 1,165/794 Cooling capacity1,2 kW Y1 V1 Y1 V1 kW Power consumption Model Name Indoor unit Power supply Cooling1 Btu/h W/W COP 13 FCNQ13MV1 RNQ13MV1 3.8 13,000 550X765X285 1.24 3.07 18 FCNQ18MV1 RNQ18MV1 5.3 18,000 595X845X300 1.89 2.80 2.80 21 FCNQ21MV1 RNQ21MV1 --------- --------- --------- 6.2 21,000 2.21 26 FCNQ26MV1 RNQ26MV1 7.6 26,000 735X825X300 735X825X300 2.53 3.00 30 FCNQ30MV1 RNQ30MV1 8.8 30,000 990X940X320 2.73 3.22 36 FCNQ36MV1 RNQ36MV1 RNQ26MY1 26 FHNQ26MV1 RNQ26MV1 RNQ26MY1 RNQ30MY1 RNQ36MY1 10.6 36,000 1,345X900X320 3.31 3.20 42 FCNQ42MV1 --------- 12.5 42,600 4.15 3.01 48 FCNQ48MV1 --------- RNQ42MY1 RNQ48MY1 14.1 48,000 5.04 2.80 1 Phase, 220–240 V, 50 Hz --------- --------- 3 Phase, 380–415 V, 50 Hz Hermetically sealed scroll type o / 9.5 o / 26.0 (Hole) 50 (Equivalent length 70) 30 21 to 46 45/40 48/42 49/43 55 54 54 56 58 77 56 103 --------- --------- 74 56 20 103 107 111 195X1,590X680 26-27/22-23 38-40/23-25 918-953/777-812 1,341-1,412/812-883 30 FHNQ30MV1 RNQ30MV1 8.8 30,000 990X940X320 3.07 2.87 7.6 26,000 2.65 36 FHNQ36MV1 RNQ36MV1 RNQ30MY1 RNQ36MY1 10.4 35,000 1,345X900X320 3.64 2.86 42 FHNQ42MV1 --------- 12.3 42,000 4.51 2.73 48 FHNQ48MV1 --------- RNQ42MY1 RNQ48MY1 14.1 48,000 5.51 2.56 42-44/24-26 1,483-1,553/847-918 --------- 3 Phase, 380–415 V, 50 Hz Outdoor unit Outdoor unit Cooling capacity1,2 kW Y1 V1 Y1 V1 kW Power consumption Model Name Indoor unit Power supply Cooling1 Btu/h W/W COP 13 FHNQ13MV1 RNQ13MV1 195X960X680 3.8 13,000 550X765X285 1.58 2.40 18 FHNQ18MV1 RNQ18MV1 195X1,160X680 195X1,400X680 26 32 35 44/40 777-812/671-706 22-23/19-20 5.3 18,000 595X845X300 2.04 2.60 2.60 21 FHNQ21MV1 RNQ21MV1 --------- --------- --------- 6.2 21,000 2.38 1 Phase, 220–240 V, 50 Hz --------- Outdoor unit Outdoor unit °CDB °CWB Certified Operation range Certified Operation range Motor output Compressor Indoor unit Dimensions (HXWXD) Colour mm dB(A) kW Refrigerant charge (R-410A) Sound level4 Sound level (H/L) (220 V)4 dB(A) Dimensions (HXWXD) mm Machine weight kg V1 Y1 Piping connections mm Liquid (Flare) mm Gas (Flare) mm Drain Indoor unit Machine weight kg kg Airflow rate (H/L)3 Fan Outdoor unit Colour Heat insulation Max. interunit piping length m m Max. installation level difference Type ---------- Both liquid and gas piping mm Outdoor unit Ivory white mmH2O cfm Rated external static pressure3 10 15 20 19.4 to 46 21 to 46 14 to 23 14 to 25 m3 /min 30 30 (Equivalent length 50 m) 3/4B (I.Do / 21.6XO.Do / 27.2) o / 6.4 o / 9.5 o / 12.7 o / 9.5 o / 15.9 o / 18.0 (Hole) 0.65 0.9 1.4 1.8 2.2 25 32 35 36 40 49 56 ---------- ---------- ---------- ---------- 56 Hermetically sealed rotary type 0.9 (Charged for 10 m) 1.2 (Charged for 10 m) 1.4 (Charged for 10 m) 1.5 (Charged for 10 m) 2.0 (Charged for 10 m) 459/388 13/11 635/530 18/15 41/38 43/40 48 49 51 52 54 2.0 Y1 V1 Y1 V1 Cooling capacity1,2 kW kW Power consumption Model Name Indoor unit Power supply Cooling1 Btu/h W/W COP 09 FDBNQ09MV1 RNQ09MV1 260X900X580 2.7 9,200 550X765X285 0.86 3.14 13 FDBNQ13MV1 RNQ13MV1 3.8 13,000 1.28 2.97 18 FDBNQ18MV1 RNQ18MV1 5.2 17,700 595X845X300 2.06 2.52 21 FDBNQ21MV1 RNQ21MV1 260X1,300X580 6.2 21,000 2.38 2.60 26 FDBNQ26MV1 RNQ26MV1 --------- --------- --------- --------- RNQ26MY1 7.6 26,000 735X825X300 2.62 2.90 1 Phase, 220–240 V, 50 Hz --------- 3 Phase, 380–415 V, 50 Hz Outdoor unit Outdoor unit Note : 1 Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). 2 Capacities are net, including a deduction for cooling for indoor fan motor heat. 3 Please see fan characteristic document in detail. 4 Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. °CDB °CWB Certified Operation range Certified Operation range Motor output Compressor Indoor unit Dimensions (HXWXD) Colour mm dB(A) kW Refrigerant charge (R-410A) Sound level4 Sound level (H/L) (220 V)4 dB(A) Dimensions (HXWXD) mm Machine weight kg V1 Y1 Piping connections mm Liquid (Flare) mm Gas (Flare) mm Drain Indoor unit Machine weight kg kg Airflow rate (H)3 Fan Outdoor unit Colour Heat insulation Max. interunit piping length m m Max. installation level difference Type ---------- Both liquid and gas piping mm Outdoor unit Ivory white mmH2O cfm Rated external static pressure3 20 30 21 to 46 14 to 25 m3 /min 30 (Equivalent length 50 m) 50 (Equivalent length 70 m) 3/4B (I.Do / 21.6XO.Do / 27.2) o / 9.5 o / 15.9 o / 26.0 (Hole) o / 18.0 (Hole) 2.2 2.7 3.75 4.5 43 52 56 77 103 ---------- ---------- 56 74 103 107 111 Hermetically sealed rotary type Hermetically sealed scroll type 2.0 (Charged for 10 m) 1.9 (Charged for 15 m) 3.2 (Charged for 15 m) 2.7 (Charged for 15 m) 3.2 (Charged for 15 m) 812 23 1,306 37 1,483 42 42/38 44/36 45/37 46/37 54 55 54 56 58 8.5 9.8 8.0 Y1 V1 Y1 V1 Cooling capacity1,2 kW kW Power consumption Model Name Indoor unit Power supply Cooling1 Btu/h W/W COP 26 FDMNQ26MV1 RNQ26MV1 305X1,350X680 7.6 26,000 735X825X300 2.62 2.90 2.90 30 FDMNQ30MV1 RNQ30MV1 305X1,550X680 8.8 30,000 990X940X320 3.03 36 FDMNQ36MV1 RNQ36MV1 10.6 36,000 3.53 3.00 1,345X900X320 42 FDMNQ42MV1 --------- 12.3 42,000 4.49 2.74 48 FDMNQ48MV1 --------- RNQ26MY1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1 14.1 48,000 5.56 2.54 1 Phase, 220–240 V, 50 Hz --------- 3 Phase, 380–415 V, 50 Hz Outdoor unit Outdoor unit
  • 11. For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option (shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect. A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation. Round flow type: List of optional parts required to achieve different flow patterns 1 In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable. 2 Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position. 3 It is not possible to use panel spacers in a 2-way flow installation. 4 It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed. Panel/grille related Independently installable optional parts Operation control related Auxillary function related Filter related Optional accessory parts Independently installable optional parts Optional accessory parts Independently installable optional parts Optional accessory parts Panel spacer1 Panel spacer1 o o o x o Wireless remote controller o o o o o Fresh air intake kit (direct mount) o o o o o x o o x x High-efficiency filter2 Filter related Ultra-long-life filter2 o o o x x Ultra-long-life filter2 o o o x x High-humidity operation kit Panel/grille related Operation control related Auxillary function related Panel spacer1 Wireless remote controller Fresh air intake kit (direct mount) High-humidity operation kit All round flow 4-way flow o3 o3 x x o3 o3 o x x x o o o3 o x x o o x o o x o3 o o x x 3-way flow 2-way flow 1-way branch / unit 3-way flow Branch duct1 (Chamber type) (Round duct type) o o o4 x x o 2-way branch / unit 2-way flow 1-way branch / unit 2-way flow x o o4 x x o x o o4 x x o Branch duct connection Wireless remote controller Fresh air intake kit (direct mount) High-efficiency filter2 High-humidity operation kit Ultra-long-life filter2 Panel spacer1 Wireless remote controller Fresh air intake kit (direct mount) High-efficiency filter2 High-humidity operation kit Ultra-long-life filter2 Panel spacer1 Wireless remote controller Fresh air intake kit (direct mount) Fresh air intake kit (Chamber type)1,2 o o o x o Fresh air intake kit (Chamber type)1,2 o3 o x x o o o x o o o3 o x x x o o o o Fresh air intake kit (Chamber type)1,2 Fresh air intake kit (Chamber type)1,2 Fresh air intake kit (Chamber type)1,2 High-efficiency filter2 High-humidity operation kit Ultra-long-life filter2 19 20 Indoor unit Indoor unit OPTIONS Outdoor unit Kit name RNQ18MV1 RNQ21MV1 RNQ09MV1 RNQ13MV1 RNQ26MV1 RNQ30MV1 RNQ36MV1 ------- ------- ------- ------- ------- ------- RNQ26MY1 RNQ30MY1 RNQ36MY1 RNQ42MY1 RNQ48MY1 Central drain plug Name of option KKPJ5F180 ------- ------- KKP014A4 Touch Controller4 DCS601C51 Note: 1 Refer to page 6 for the details. 2 Required for installing high-efficiency filter or ultra long-life filter. 3 Wiring for wired remote controller to be procured locally. 4 The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 5 Installation box for adaptor PCB (KRP1H98) is necessary. Note: 1 Wiring for wired remote controller to be procured locally. Kit name DCS302CA61 DCS301BA61 DST301BA61 KRP1C63 KDDFP55B160 KDBH55K160F KDBP55H160FA KKSJ55KA160 KDDP55B160 KDDP55B160K KDDP55X160 KRP4AA53 KAFP551K160 KAFP556B80 KAFP557B80 KAFP552B80 KDTP55K80 KDJP55B160 KDJP55B80 BRC7F633F BRC1C61 KAFP553B80 KDTP55K160 KAFP556B160 KAFP557B160 KAFP552B160 KAFP553B160 BYCP125K-W1 KRP1H98 KAFP55B160 KAFP55H160H FCNQ21MV1 FCNQ26MV1 FCNQ30MV1 FCNQ13MV1 FCNQ18MV1 FCNQ36MV1 FCNQ42MV1 FCNQ48MV1 Name of option Remark Chamber type Decoration panel Fresh air intake kit1 Central remote controller4 Unified ON/OFF controller4 Schedule timer4 Adaptor for wiring5 Without T-joint pipe and fan With T-joint pipe, without fan Direct installation type Sealing material of air discharge outlet Panel spacer Chamber connection kit2 Insulation kit for high humidity Wiring adaptor for electrical appendices5 Installation box for adaptor PCB High-efficiency filter (including chamber) Filter chamber Replacement long-life filter Ultra long-life filter Replacement ultra long-life filter (Colorimetric method 65%) (Colorimetric method 90%) Replacement high-efficiency filter (Colorimetric method 65%) (Colorimetric method 90%) Remote controller Wireless type Cooling only Wired type3 Branch duct chamber Remote sensor KRCS01-4B CEILING MOUNTED CASSETTE TYPE Kit name KHFJ5F50 BRC1NU61 BRC7NU66 KAF501DA56 KHFJ5F60 KHFP5MA160 KAF501DA80 KAF501DA112 KAF501DA160 FHNQ21MV1 FHNQ26MV1 FHNQ30MV1 FHNQ36MV1 FHNQ42MV1 FHNQ48MV1 FHNQ13MV1 FHNQ18MV1 Name of option Remark Replacement long-life filter L-type piping kit (for upward direction) Remote controller Resin net Wired type1 Wireless type CEILING SUSPENDED TYPE Note: 1 Wiring for wired remote controller to be procured locally. Kit name BRC1C61 BRC4C64 FDBNQ18MV1 FDBNQ09MV1 FDBNQ13MV1 FDBNQ21MV1 FDBNQ26MV1 Name of option Remark Remote controller Wired type1 Wireless type DUCT CONNECTION LOW STATIC PRESSURE TYPE Note: 1 Wiring for wired remote controller to be procured locally. Kit name BRC1C61 BRC4C64 FDMNQ36MV1 FDMNQ26MV1 FDMNQ30MV1 FDMNQ42MV1 FDMNQ48MV1 Name of option Remark Remote controller Wired type1 Wireless type DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE BRC1E62 Navigation Remote Controller Wired type3 BRC1E62 Navigation Remote Controller Wired type1 BRC1E62 Navigation Remote Controller Wired type1
  • 12. 4 155 11 o / 45 40 90 5 80 14 55 195 30 or more 30 or more 4-M8~M10 Hanging bolt (Service space) (Service space) 1 B 127 8 10 17 18 (Hanging position) (Hanging position) A 16 210 36 170 58 192 85 160 105 102 142 90 185 260 4 170 7 225 Drain pipe connection VP20 6 275 Brand name plate The Front (Note.2) 80 275 105 (For left piping) 300 3 2 5 80 6 (Required space) Obstacle 680 Floor side 5 155 55 (Required space) 300 or more 13 For height installation From the floor side 2500 or more 105 15 (Required space) 135 5 Position : Hole of wall for taking out in piping back (View from the front) 65 50 135 145 9 60 65 12 40 60 60 115 Position slit hole for taking out in piping back (View from the front) DIMENSIONS (Unit: mm) 21 22 CEILING SUSPENDED TYPE 236 3×P.150=450 16 260 16 151 704 10 688 150 900 127 (All Around) 219 10 12-M4 Holes 52 674 5 7 4 6 664 170 110 684 260 (All Around) 1 228 3×P150=450 500 10-M4 Holes 164 2 29 50 134 107 10 or more 300 or more 317 3 704 500 167 580 151 126 8 271 (Suspension bolt pinch) 3 55 (Suspension bolt pinch) 755 137 900 Service space DUCT CONNECTION LOW STATIC PRESSURE TYPE A B [FHNQ13/18/21/26/30/36/42/48MV1] [FDBNQ09/13/18MV1] 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Air discharge grille Air suction grille Air filter Gas pipe connection Liquid pipe connection Drain pipe connection Earth terminal (Inside the electric components box) Suspension bracket Backward pipe and wiring connection opening lid Upward pipe and wiring connection opening lid Right side pipe connection Left back drain pipe connection Left side drain pipe connection Right side drain pipe connection Hole of wall for taking out in pipe back Upward drain pipe connection Upward gas pipe connection Upward liquid pipe connection Notes: 1 Location of unit's Name plate : Bottom of fan housing inside the suction grille. 2 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail. 3 The remote control code is the standard <about 3m outside the machine> attached. (0.5mm2 x2 wicks O.D. 5.4)(It is not attached to VRV.) Note: 1 Location of unit's Name Plate: Chamber cap Liquid pipe connection Gas pipe connection Drain pipe connection Ground terminal 1 2 3 4 Switch box Control wiring intake (for remote controller) Control wiring intake (for outdoor unit) Suspension bracket 5 6 7 8 920 960 1120 1160 1120 1160 FHNQ13MV1 FHNQ18MV1 FHNQ21MV1 1360 1400 FHNQ26MV1 1360 1400 FHNQ30MV1 1550 1590 FHNQ36MV1 1550 1590 FHNQ42MV1 1550 1590 FHNQ48MV1 CEILING MOUNTED CASSETTE TYPE Notes: 1 Sticking location for manufacture's label manufacture's label for indoor unit: Suction grille inner side's electric components box's lid surface manufacture's label for decoration panel : Decoration panel's corner decoration cover inner surface 2 In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail. 3 When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required. 4 Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the indoor unit and the ceiling opening so that the panel overlap allowance can be ensured. 5 Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. [FCNQ13-48MV1] [FCNQ13-48MV1] [FCNQ13-26MV1] [FCNQ13-26MV1] [FCNQ13-26MV1] [FCNQ13-26MV1] [FCNQ30-48MV1] [FCNQ30-48MV1] [FCNQ30-48MV1] [FCNQ30-48MV1] 7 6 950 8 950 Pipe Connection Side Drain Connection Side Note 2 A arrow view 9 C B 420 710(Hanging bolt pitch) 420 860~910(Ceiling opening space) (Note 4) 860~910(Ceiling opening space) (Note 4) 780(Hanging bolt pitch) 95 330 165 Connection position of branch duct 160 20 16-M4 Prepared hole 50 350 124 80 175 125 2 (square-shaped type) 4 1 157 246 55 4-M8~M10 2x100=200 80 124 10 Hanging bolt Connection position of branch duct C/L 110 (round shape type) 840 55 280 256 40 Adjustable(0~675) 340 850 Connection position of branch duct 1500 or more Connection position of branch duct 20-M4 Prepared hole 60 From the floor side 2500 or more 130 124 2x100=200 35 or less (Note 4) 55 A 150 840 55 160 157 256 105 (square-shaped type) For height installation 42 (required space) (Note 4) 95 3 85 124 35 or less 5 (round shape type) 64 350 81 110 50 124 81 2x100=200 350 Connection position of branch duct 160 16-M4 Hole B arrow view (round shape type) 110 C/L 124 85 157 (square-shaped type) 95 Connection position of branch duct 80 157 213 95 160 Connection position of fresh air intake kit (square-shaped type) C arrow view (knock hole) 90 (round shape type) 124 183 109 25 C/L 124 80 2x100=200 (direct installation type) ø100 20-M4 Prepared hole Connection position of branch duct Connection position of branch duct 90 350 157 93 2x100=200 85 67 Connection position of branch duct C/L (round shape type) 160 Connection position of branch duct 16-M4 Hole 167 (square-shaped type) B arrow view 160 95 81 350 29 213 29 350 80 160 ø100 Connection position of fresh air intake kit C/L 157 90 (direct installation type) 67 (knock hole) Connection position of branch duct C arrow view Connection position of branch duct 2x100=200 (round shape type) (square-shaped type) 196 93 90 80 25 95 160 20-M4 Prepared hole 167 280 50 288 80 167 95 157 340 840 165 10 4 Hanging bolt 1 175 55 4-M8~M10 Connection position of branch duct (round shape type) Connection position of branch duct 2 40 80 160 2x100=200 125 (square-shaped type) C/L 298 20 350 850 Adjustable(0~675) 55 29 330 160 16-M4 Prepared hole 160 1500 or more 81 93 157 130 Connection position of branch duct 160 2x100=200 A 55 (square-shaped type) From the floor side 2500 or more (Note 4) 67 105 For height installation 85 150 (required space) 350 42 29 64 (round shape type) 27-M4 Prepared hole 60 35 or less (Note 4) 35 or less 3 Connection position of branch duct 256 160 5 95 50 840 55 167 The necessary space is 500mm or more when the air-outlet is blocked with the accessory. Moreover when the corner areas are blocked (both right and left of the blocked air outlet), the necessary space is 200mm or more. 1500mm or more 200mm or more 1500mm or more 1500mm or more 1500mm or more 200mm or more Required space 300 or less Liquid pipe connection Gas pipe connection Drain pipe connection Power-source wiring and a unit wiring connection Connection wiring/remote control wiring connection Air-outlet Suction grille Corner decoration cover Drain hose (accessory) 1 2 3 4 5 6 7 8 9
  • 13. OUTDOOR UNIT // RNQ09/13MV1 23 24 DIMENSIONS (Unit: mm) 22 50 100 50 150 50 50 300 150 100 285 8 Handle Wall height on air outlet side =less than 1200 Minimum space for air passage 105.5 13 311 490 574 29.5 Drain outlet (I.D. 15.9 hose for connection) 4-Hole for anchor bolts (M8 or M10) 550 12 63 765 Brand name label Manufacture’s label 196 165 105 Wiring inlet Gas stop valve ( 15.9CuT for RNQ13) ( 9.5CuT for RNQ09) Service port In case of removing stop valve cover Liquid stop valve ( 6.4CuT) 300 or more 1353 1337 151 74 16 263 7×P150=1050 1550 (All Around) 51 20-M4 Holes 8 10 16 305 150 280 1321 50 123 1314 175 305 18-M4 Holes 212 206 (All Around) 152 827 274 1334 7×P150=1050 2 1 29 7 6 5 4 1353 146 3 151 600 116 (Suspension bolt pinch) 381 3 1403 1550 (Suspension bolt pinch) 126 55 427 8 680 Service space [FDMNQ30/36/42/48MV1] DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Note: 1 Location of unit's Name Plate: Chamber cap Liquid pipe connection Gas pipe connection Drain pipe connection Ground terminal 1 2 3 4 Switch box Control wiring intake (for remote controller) Control wiring intake (for outdoor unit) Suspension bracket 5 6 7 8 300 or more 7×P150=1050 263 151 20-M4 Holes 51 1350 1137 16 1121 8 10 305 (All Around) 16 150 74 280 1153 7 5 6 4 1114 1134 1 29 50 123 18-M4 Holes 152 206 274 175 2 305 (All Around) 727 212 7×P150=1050 126 600 1350 8 116 1153 680 3 381 3 (Suspension bolt pinch) 146 1203 151 427 (Suspension bolt pinch) 55 Service space Service space 300 or more 260 10 236 16 151 102 1300 219 1104 1074 1088 18-M4 Holes 16 (All Around) 52 10 150 6×P.150=900 700 50 16-M4 Holes 29 2 6×P150=900 164 134 1064 (All Around) 170 260 228 107 1084 1 110 5 6 4 7 10 or more 271 317 500 167 580 137 (Suspension bolt pinch) (Suspension bolt pinch) 3 1300 151 55 1155 126 8 3 1104 [FDBNQ21/26MV1] [FDMNQ26MV1] DUCT CONNECTION LOW STATIC PRESSURE TYPE Note: 1 Location of unit's Name Plate: Chamber cap Liquid pipe connection Gas pipe connection Drain pipe connection Ground terminal 1 2 3 4 Switch box Control wiring intake (for remote controller) Control wiring intake (for outdoor unit) Suspension bracket 5 6 7 8 DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE Note: 1 Location of unit's Name Plate: Chamber cap Liquid pipe connection Gas pipe connection Drain pipe connection Ground terminal 1 2 3 4 Switch box Control wiring intake (for remote controller) Control wiring intake (for outdoor unit) Suspension bracket 5 6 7 8
  • 14. OUTDOOR UNIT // RNQ30MV1, RNQ30MY1 OUTDOOR UNIT // RNQ36MV1, RNQ36/42/48MY1 OUTDOOR UNIT // RNQ18/21MV1 OUTDOOR UNIT // RNQ26MV1, RNQ26MY1 25 26 30 620 91 160 30 30 Hole for anchor bolt 4-M12 55 (345∼355) 37 320 160 350 38 145 5 84 53 7 95 6 80 55 19 416 68 161 595 61 16 260 262 36 279 285 8 90 16 5 95 13 53 5 55 223 6 7 67 52 339 89 95 19 2 5 3 6 4 990 142 340 60 89 1 940 7 53 96 89 58 1 16 24 54 350 (345~355) 3 71 45 145 41 7 6 95 620 60 5 95 4 89 320 8 84 48 70 410 54 1345 30 80 30 102 140 55 19 900 5 5 376 435 19 140 6 61 117 142 2 191 7 30 16 Hole for anchor bolt 4-M12 5 6 7 53 67 55 95 13 223 52 1 2 3 4 5 6 7 8 Gas pipe connection Liquid pipe connection Service port (in the unit) Grounding terminal Refrigerant piping intake Power supply wiring intake Control wiring intake Drain pipe connection DIMENSIONS (Unit: mm) Gas pipe connection Liquid pipe connection Service port Grounding terminal Refrigerant piping intake Power supply wiring intake Control wiring intake Drain pipe connection 1 2 3 4 5 6 7 8 50 50 300 300 50 300 150 50 100 20 845 573.5 20 131 7 342 300 78 326 300 Drain outlet I.D. 18 hose for connection 4-Hole for anchor bolts (M8 or M10) 595 Brand name label Wiring inlet Name plate 105 144 60 Earth terminal in switch box Gas stop valve ( 15.9CuT for RNQ21MV1) ( 12.7CuT for RNQ18MV1) Liquid stop valve ( 6.4CuT) Service port Wall height on air outlet side =less than 1000 Minimum space for air passage 325 36 350 78 580 330 825 25 10 300 2 124 Drain outlet I.D. 15.9 hose for connection 4-Hole for anchor bolts (M8 or M10) 735 Brand name label Wiring inlet Name plate 30 18 64 155 160 89 Earth terminal in switch box Gas stop valve ( 15.9CuT) Liquid stop valve ( 9.5CuT) Service port 350 100 50 100 100 50 350 50 350 Wall height on air outlet side =less than 1200 Minimum space for air passage
  • 15. 27 28 1000 or more 100 or more 100 or more 1000 or more 300 or more L H L H 100 or more 100 or more 300 or more 1000 or more 200 or more 100 or more 100 or more 500 or less 1000 or more 1000 or more An obstruction in the overhead space 100 or more 100 or more 300 or more 1000 or more 200 or more 500 or less 1000 or more An obstruction in the overhead space 100 or more 100 or more When there is an obstruction on the inlet side When there are obstructions on the inlet side and both sides 2. For multiple units installation (more than two units) When there are obstructions on both sides 1) When the overhead space is open 1. For single unit installation When there is an obstruction only on the inlet side 2) When there is an obstruction in the overhead space 1) When the overhead space is open When there are obstructions on both sides 2) When there is an obstruction in the overhead space When there is an obstruction on the inlet side When there are obstructions on the inlet side and both sides 2. For multiple units installation (more than two units) 1. For single unit installation 1. For single unit installation 2. For multiple units installation (more than two units) 1. For single unit installation 2. For multiple units installation (more than two units) 1. For single unit installation 2. For multiple units installation (more than two units) Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book. 1 When there is an obstruction on the outlet side 2 1) When the overhead space is open (There is no limit to the height of the obstruction on the outlet side.) When there are obstructions on both the inlet and outlet sides (When the obstruction on the outlet side is higher than the unit itself) 3 H L 500 or more 100 or more L H 100 or more 100 or more 100 or more 100 or more 500 or more 100 or more 500 or less 1000 or more An obstruction in the overhead space 500 or less 500 or more 1000 or more An obstruction in the overhead space 150 or more 150 or more 150 or more 500 or less 1000 or more An obstruction in the overhead space Installation service space for outdoor unit For RNQ30-48MV1/Y1 REMOTE CONTROLLER Wired type Staple 17 17 0~5 117 17 (fl12~fl16) A EXposed body, exposed cord C Exposed body, embedded code ( Distance between remote controller and control box ) B Exposed body, embedded cord Conduit CONTROL BOX Through hole Size Specifications of cord 0.75~1.25 mm2 Total length 500 m Type Vinyl cord with sheath or cable (Insulated thickness: 1 mm or more) Note) 1. Remote controller cord and staple are not attached. they are field supplied parts. Note) The dimension of hole. * Countries requiring EMC: Shield wire (insulated thickness: 1 mm or more) 120 120 17 18 42 84 38 Cord outlet hole 28 23 46 Wireless type BRC1C61 BRC1NU61 BRC7NU66 Transmitting part 157 62 17.5 Liquid crystal remote controller (Wireless) Remote controller holder CEILING SUSPENDED TYPE A 22 38 6 A 41 13 A 25 R2 7 B 44.5 10 20 B A 25 25 17 41.5 7 A B 111 119 24 6 Hole type a 10 20 4 B a (mm) Receiver The Front Remote controller holder installation procedure <Installation to wall surface> Remote controller holder installation procedure <Installation to wall surface> Transmitting part 115.5 54 18.1 Remote controller (Wireless) Remote controller holder Receiver installation procedure Service space for ceiling installation Receiver detail Note : More than 90 (Srevice space) 120 72 83.5 106 (Ceiling opening) 70 18 0.5 35 49 (Ceiling opening) 2-5x9 Slot Switch box (field Supplied parts) Do not install more than 3 receivers in the vicinity of one another. With 4 or more units, there is always the possibility of malfunction Remote controller dimensions Remote controller installation procedure Receiver detail Remote controller dimensions BRC7F633F BRC4C64 CEILING MOUNTED CASSETTE TYPE <Round Flow> • Receiver installation procedure • Receiver detail Receiver Drain piping side Refrigerant piping side Decoration panel 19 Upper case Lower case 40 23 46 28 48.5 42 84 5X7 oblong hole Code outlet hole 5X15 oblong hole Lower case portion Lower case portion Staple 19 A Exposed cord C Embedded cord (use switch box) B Embedded cord 84 46 Switch box for two switch ex.) KJB211A (optional accessory) Condit 19 0~5 Switch box [field supplied part] (Between remote controller and control box) 48.5 19 Note)2 Through hole 40 ( 8- 10) 84 28 Switch box for one switch ex.) KJB111A (optional accessory) • Installation method 2.If the hole size is too large or the location is not proper, the hole may come out from the remote controller. Note) 1. Remote controller cord and staple are not attached. They are field supplied parts. Size Specifications of cord 0.75~1.25 mm2 Total length 500 m Type Vinyl cord with sheath or cable (insulated thickness: 1mm or more) BRC1E62 (Green) 120 120     Operation lamp Top left outlet Left outlet Top center outlet DIMENSIONS (Unit: mm) (Unit: mm)