Objective and Introduction:
Our objective was to design a system for fireplace heat recovery. In most wood-burning
fireplaces, much of the heat that is not directly blown into the room ends up being lost through
the chimney and to the outside. Because the heat convected from a fire is dependent only in
the direction it is felt, we felt that the most valuable way to recover heat was to place water
pipes around the back of the fireplace. The introduction of a new temperature sink has no
effect on the heat that convects into the interior of the home, so we found this concept to be a
minimalistic design change to the standard fireplace structure.
In our research, we have found that most wood-burning fireplaces can reach steady
temperatures of 1100o
F to 1500o
F. By running pipes through the system, we effectively create
a heat exchanger system that can take advantage of the large amounts of heat energy that is
normally lost. By utilizing thermally conductive pipes that can withstand such high
temperatures, we can heat the flowing water to nearly a boil, lightening the load on the
residential boiler.
Heat exchangers are systems that have two fluids flowing adjacent to each other at
different temperatures. Because of the Zeroth Law of Thermodynamics, the fluid of higher
temperature will convect its heat across the heat transfer surface area to the fluid of lower
temperature. This process will continuously occur until the system reaches a temperature
equilibrium for both fluids, but the flowing nature of the fluids allow the system to exchange
heat indefinitely.
Design Criteria and Assumptions:
Our assignment consisted of designing a heat recovery system for a fireplace. Due to
the excessive heat energy that is wasted during the process, we approached the task by
designing a heat exchanger that would attempt to recover the lost energy and use it to assist a
residence’s boiler system. By having a secondary water-heating system available, it is possible
to lighten the load on the boiler and save on energy costs.
In the proposal of our design, many assumptions had to be made in order to allow our
experience with thermodynamics and fluid dynamics to properly apply to the system. For
example, our water-flow input was assumed to be turbulent and fully developed right from the
start. For the Extended Bernoulli’s Equation to apply, we assumed our pipe system to be
perfectly sealed, allowing a steady, incompressible, flow of water to be analyzed with continuity
analyses.
Had we not made these assumptions, we would not have the tools necessary to perform
the accurate calculations on such a complex system.
3
Design Procedure:
We started the design by analyzing the two fluids of the heat exchanger: the fire-heated
air surrounding the pump-controlled water. In order to acquire an overall analysis of the
system, it was necessary to find the Overall Heat Transfer Coefficient.
(Eq. 1)
To find the convection coefficient of the water being heated, we utilize the velocity of
the water and its fluid properties to find the Reynolds Number. The temperature at which the
fluid properties are found is the Bulk Fluid Temperature (Table A-9E).
(Eq. 2 & 3)
With the dimensionless Reynolds Number, we can find the Nusselt Number.
(Eq. 4)
Because the Nusselt number is the ratio of conductive to convective heat transfer, we can
utilize it to calculate the Convective Heat Transfer Coefficient of the internal water flow.
(Eq. 5)
The process to find the convection coefficient of the heated air is actually different. This
is due to the fact that the air around the fire was assumed to be ambient, so we modeled that
fluid to be under free or natural convection. The major differences in analysis are the
utilization of the Film Temperature and the addition of the Coefficient of Volume Expansion.
(Eq. 6 & 7)
These new variables are used to find the Rayleigh Number, which is necessary to find the
Nusselt Number for natural convection systems.
( )
{
( ) ⁄
[ ( )
⁄
]
⁄
} (Eq. 8 & 9)
4
The equation to find the Free Convection Heat Transfer Coefficient is then the same as that for a
forced convection system.
(Eq. 10)
With these individual convection heat transfer coefficients, the Overall Heat Transfer
Coefficient of the entire system can then be represented.
(Eq. 11)
Using this coefficient, we can use the heat exchanger equations to fully analyze the system.
( )
(Eq. 12 & 13)
The pressure analysis of the system was performed using the Extended Bernoulli’s
Equation.
∑ (Eq. 14)
However, the two points of our analysis occurs before and after the pipes split and reattach, so
there is no need to include change in height. Also, because the diameter of pipe at both
analysis points are the same, there is no change in fluid velocity as well. This allows our
equation to be simplified to the following:
∑ (Eq. 15)
in this equation refers to the output pressure of the pump we have selected. The pressure
of a pump is determined using the horsepower and volume flow rate with the relations:
( )( )
(Eq. 16)
(Eq. 17)
The added terms shown on the Extended Bernoulli’s Equation refer to the frictional losses and
the minor losses, respectively. These terms contribute to pressure drop in the system caused
by fluid friction against the sides of the pipe and the dynamics of fluids flowing through joints
and manifolds.
5
Design Phase
Figure 1: Fireplace Heat Exchanger Piping system with Pump
After extensive research, the material chosen for the pipe was copper. In addition to its
low cost and high thermal conductivity, it was a standard component in many heating systems.
This was a safe material choice because wood fires burn at 1100o
F to 1500o
F [1]
, but the
melting point of copper is upwards of 1900o
F [2]
. Because our elbow joints and manifolds
would consist of welded connections, their ability to withstand temperature usage could last
indefinitely. However, during our calculations, we assumed that fouling would not occur.
Realistically, corrosion may become an issue in this system, as it does in all piping systems. We
chose a standard inner diameter pipe size of 2.465 inches [3]
, making it easily accessible if
components ever needed to be replaced.
The single pipe travels through a manifold that divides the flow of water into 7
individual pipes of equivalent area. This is done to decrease the speed of the flow and increase
surface area exposure to the fire, thus allowing more heat absorption as the water passes.
After passing along the walls of the fireplace, the pipes reemerge from the “heat exchanger”
and enter a second manifold that rejoins the flow of all 7 pipes. We decided this to be the best
course of action in order to simplify our fluid analysis as well as reduce the heat loss of the
water to the surroundings. As previously stated, the pipes are all welded to each other rather
6
than connected via gasket threaded to ensure temperature resistance and stave off water
leakages.
According to the New York City Plumbing Code, the maximum water pressure within a
building is 85 pounds per square inch. When exceeded, a water-pressure reducer must be
installed. Given this information, we found it acceptable to use a 2-horsepower pump that
would supply a pressure of 38.56 pounds per square inch.
Results & Discussion:
In order to perform a proper analysis on the system to calculate all the relevant
information, assumptions were made in regards to the simplicity of the system. It was
presumed that the water flow was fully developed and turbulent and moving through a
smooth, corrosion-free pipe. In order to use Bernoulli’s equation, it was required to accept that
the fluid flow was steady and incompressible as well.
The air outside of the pipes is assumed to be subject to no external forces, so the
buoyancy of hot air is assumed to be the only motion taking place. This allowed us to model
the “shell-side” fluid in this “heat exchanger” as a free or natural convection system.
The initial condition of the pipe fluid was assumed to be 60o
F water flowing at 0.6 ft/s.
In order for the water to leave the system at the desired 180o
F, heat energy from the cross-
flow air must transfer to the water. The ambient heated air adjacent to the pipes was assumed
to be 200o
F, and after calculations, the outlet temperature of the air was found to be 148o
F.
This was done by finding the convection heat transfer coefficients for both fluids (hH20 = 194.5
BTU/h·ft2
·R and hair = 0.99 BTU/h·ft2
·R) and determining the heat transfer surface area to be the
surface area of the exposed piping (AS = 4.1667 ft2
). The total heat transfer rate of the system
( ) was found to be 146.25 BTU/s.
With the system being powered by a 2-horsepower pump, it was determined that the
volume flow rate through the 0.205-inch diameter pipe was 88.9 gallons per minute; it followed
that the pressure offered by this pump was measured to be 38.56 pounds per square inch. The
utilization of the extended Bernoulli’s equation allowed us to calculate a total pressure drop
from the beginning to end of the heat exchanger was only 3.15 pounds per square inch.
7
Cost Analysis:
As with all upgrades and installations, it must be determined whether or not it is
financially feasible to make such renovations. Assuming that the fireplace infrastructure is
already in place, the additional costs involved consist of the piping system, the pump itself, and
labor.
Using Plumbing Supply as reference [5]
, the cost of Type “L” Rigid Copper Pipe with a
diameter of 2.5 inches is approximately $35.00 per linear foot. The pipe cost, excluding the
manifold, would amount to $2065.00 for 59 linear feet and $928.48 for 28x 90o
elbows.
According to Water Pumps Direct [6]
, a 2-horsepower pump rated for 89 gallons per minute
would cost $400.
Thus, the total cost of the pump and copper piping, excluding the custom manifolds and
the copper piping required to reconnect the system back to the main plumbing infrastructure,
would come out to $3400.00 before labor.
Conclusion & Recommendation:
Our design uses a heat exchanger to capture some of the lost heat given off by the fire.
The water in the pipes is heated with this lost energy, which can then be fed directly into the
boiler, essentially lessening the load on the water heating system. This can directly lead to
reduced energy costs and a more environmentally friendly system. Though we may not
recommend going out of your way to perform such an installation, if the renovation of a
fireplace was already intended, this could be a fiscally responsible move. If installed properly
this system should last at least 50 years under normal operating conditions [7]
.
8
Appendix
 Detailed derivations and calculations regarding the Shell Fluid (Heated Air)
 Detailed derivations and calculations regarding the Tube Fluid (Water)
 Detailed derivations and calculations regarding the Heat Exchanger as a whole
 Detailed derivations and calculations regarding the Fluid Pressure of the system
1. http://homeguides.sfgate.com/temperatures-woodburning-stove-48039.html
2. http://www.engineeringtoolbox.com/melting-temperature-metals-d_860.html
3. http://www.petersenproducts.com/Specifications/Pipe_Copper.aspx
4. http://www.nyc.gov/html/dob/downloads/pdf/plumbing_code.pdf
5. http://www.plumbingsupply.com/copperpipe.html
6. http://www.waterpumpsdirect.com/pumps/2-hp-sprinkler-pumps.html
7. http://colerepair.com/Copper%20Water%20Pipe.html
Fireplace Heat Exchanger Design
Fireplace Heat Exchanger Design
Fireplace Heat Exchanger Design
Fireplace Heat Exchanger Design

More Related Content

Similar to Fireplace Heat Exchanger Design

Numerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heatNumerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heatCarnegie Mellon University
 
Numerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFD
Numerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFDNumerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFD
Numerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFDCarnegie Mellon University
 
Heat exchanger parallel flow
Heat exchanger parallel flowHeat exchanger parallel flow
Heat exchanger parallel flowAree Salah
 
Analysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical FinsAnalysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical FinsIRJET Journal
 
Performance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural NetworksPerformance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural NetworksIJERD Editor
 
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...iosrjce
 
HMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdf
HMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdfHMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdf
HMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdfRaviShankar269655
 
countercurrent heat exchanger lab 2023.pdf
countercurrent  heat exchanger lab 2023.pdfcountercurrent  heat exchanger lab 2023.pdf
countercurrent heat exchanger lab 2023.pdfDimaJawhar
 
Numerical Simulation of Helically Coiled Closed Loop Pulsating Heat Pipe
Numerical Simulation of Helically Coiled Closed Loop Pulsating Heat PipeNumerical Simulation of Helically Coiled Closed Loop Pulsating Heat Pipe
Numerical Simulation of Helically Coiled Closed Loop Pulsating Heat PipeDr. Amarjeet Singh
 
Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...
Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...
Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...ijsrd.com
 
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...P singh
 

Similar to Fireplace Heat Exchanger Design (20)

C1303071722
C1303071722C1303071722
C1303071722
 
Sub1571
Sub1571Sub1571
Sub1571
 
Team_4_HEX Report.pdf
Team_4_HEX Report.pdfTeam_4_HEX Report.pdf
Team_4_HEX Report.pdf
 
J012256367
J012256367J012256367
J012256367
 
Numerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heatNumerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heat
 
Numerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFD
Numerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFDNumerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFD
Numerical Simulation of a Tube in Tube Helical Coiled Heat Exchanger using CFD
 
D013161520
D013161520D013161520
D013161520
 
Heat exchanger parallel flow
Heat exchanger parallel flowHeat exchanger parallel flow
Heat exchanger parallel flow
 
Analysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical FinsAnalysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical Fins
 
Performance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural NetworksPerformance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural Networks
 
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
 
K012627075
K012627075K012627075
K012627075
 
K012627075
K012627075K012627075
K012627075
 
Seminar Report on heat pipes
Seminar Report on heat pipesSeminar Report on heat pipes
Seminar Report on heat pipes
 
HMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdf
HMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdfHMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdf
HMT HEAT EXCHAnnnvnnbnnbnnvnvnvnvNGER 1.pdf
 
countercurrent heat exchanger lab 2023.pdf
countercurrent  heat exchanger lab 2023.pdfcountercurrent  heat exchanger lab 2023.pdf
countercurrent heat exchanger lab 2023.pdf
 
Numerical Simulation of Helically Coiled Closed Loop Pulsating Heat Pipe
Numerical Simulation of Helically Coiled Closed Loop Pulsating Heat PipeNumerical Simulation of Helically Coiled Closed Loop Pulsating Heat Pipe
Numerical Simulation of Helically Coiled Closed Loop Pulsating Heat Pipe
 
Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...
Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...
Analysis of Heat Transfer in Spiral Plate Heat Exchanger Using Experimental a...
 
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...
EXPERIMENTAL STUDY ON THE ANALYSIS OF HEAT ENHANCEMENT IN CORRUGATED TWISTED ...
 
D031201025031
D031201025031D031201025031
D031201025031
 

More from Christopher Cho

More from Christopher Cho (10)

Cosplay Commission (League, Rifle)
Cosplay Commission (League, Rifle)Cosplay Commission (League, Rifle)
Cosplay Commission (League, Rifle)
 
Magnetic Egg Carriage
Magnetic Egg CarriageMagnetic Egg Carriage
Magnetic Egg Carriage
 
Magnetic Knife Strip
Magnetic Knife StripMagnetic Knife Strip
Magnetic Knife Strip
 
Desk Design
Desk DesignDesk Design
Desk Design
 
Bed Frame Design
Bed Frame DesignBed Frame Design
Bed Frame Design
 
Senior Design Pre-Protoytpe
Senior Design Pre-ProtoytpeSenior Design Pre-Protoytpe
Senior Design Pre-Protoytpe
 
Raspberry Pi Enclosure
Raspberry Pi EnclosureRaspberry Pi Enclosure
Raspberry Pi Enclosure
 
MindSumo - Single Serve Dessert
MindSumo - Single Serve DessertMindSumo - Single Serve Dessert
MindSumo - Single Serve Dessert
 
Flood Wall Design Proposal
Flood Wall Design ProposalFlood Wall Design Proposal
Flood Wall Design Proposal
 
Stapler Chassis
Stapler ChassisStapler Chassis
Stapler Chassis
 

Fireplace Heat Exchanger Design

  • 1. Fireplace Heat Exchanger Project December 5, 2013 MEC 422 Group Brandon Ye 107716055 Cade Dong 107747116 Christopher Cho 107806330
  • 2. 1 Table of Contents Objective and Introduction ………………………………..... Page 2 Design Criteria and Assumptions ………………………………..... Page 2 Design Procedure ………………………………..... Page 3 Design Phase ………………………………..... Page 5 Results & Discussions ………………………………..... Page 6 Cost Analysis ………………………………..... Page 7 Conclusion & Recommendation ………………………………..... Page 8 Appendix ………………………………..... Page 9
  • 3. 2 Objective and Introduction: Our objective was to design a system for fireplace heat recovery. In most wood-burning fireplaces, much of the heat that is not directly blown into the room ends up being lost through the chimney and to the outside. Because the heat convected from a fire is dependent only in the direction it is felt, we felt that the most valuable way to recover heat was to place water pipes around the back of the fireplace. The introduction of a new temperature sink has no effect on the heat that convects into the interior of the home, so we found this concept to be a minimalistic design change to the standard fireplace structure. In our research, we have found that most wood-burning fireplaces can reach steady temperatures of 1100o F to 1500o F. By running pipes through the system, we effectively create a heat exchanger system that can take advantage of the large amounts of heat energy that is normally lost. By utilizing thermally conductive pipes that can withstand such high temperatures, we can heat the flowing water to nearly a boil, lightening the load on the residential boiler. Heat exchangers are systems that have two fluids flowing adjacent to each other at different temperatures. Because of the Zeroth Law of Thermodynamics, the fluid of higher temperature will convect its heat across the heat transfer surface area to the fluid of lower temperature. This process will continuously occur until the system reaches a temperature equilibrium for both fluids, but the flowing nature of the fluids allow the system to exchange heat indefinitely. Design Criteria and Assumptions: Our assignment consisted of designing a heat recovery system for a fireplace. Due to the excessive heat energy that is wasted during the process, we approached the task by designing a heat exchanger that would attempt to recover the lost energy and use it to assist a residence’s boiler system. By having a secondary water-heating system available, it is possible to lighten the load on the boiler and save on energy costs. In the proposal of our design, many assumptions had to be made in order to allow our experience with thermodynamics and fluid dynamics to properly apply to the system. For example, our water-flow input was assumed to be turbulent and fully developed right from the start. For the Extended Bernoulli’s Equation to apply, we assumed our pipe system to be perfectly sealed, allowing a steady, incompressible, flow of water to be analyzed with continuity analyses. Had we not made these assumptions, we would not have the tools necessary to perform the accurate calculations on such a complex system.
  • 4. 3 Design Procedure: We started the design by analyzing the two fluids of the heat exchanger: the fire-heated air surrounding the pump-controlled water. In order to acquire an overall analysis of the system, it was necessary to find the Overall Heat Transfer Coefficient. (Eq. 1) To find the convection coefficient of the water being heated, we utilize the velocity of the water and its fluid properties to find the Reynolds Number. The temperature at which the fluid properties are found is the Bulk Fluid Temperature (Table A-9E). (Eq. 2 & 3) With the dimensionless Reynolds Number, we can find the Nusselt Number. (Eq. 4) Because the Nusselt number is the ratio of conductive to convective heat transfer, we can utilize it to calculate the Convective Heat Transfer Coefficient of the internal water flow. (Eq. 5) The process to find the convection coefficient of the heated air is actually different. This is due to the fact that the air around the fire was assumed to be ambient, so we modeled that fluid to be under free or natural convection. The major differences in analysis are the utilization of the Film Temperature and the addition of the Coefficient of Volume Expansion. (Eq. 6 & 7) These new variables are used to find the Rayleigh Number, which is necessary to find the Nusselt Number for natural convection systems. ( ) { ( ) ⁄ [ ( ) ⁄ ] ⁄ } (Eq. 8 & 9)
  • 5. 4 The equation to find the Free Convection Heat Transfer Coefficient is then the same as that for a forced convection system. (Eq. 10) With these individual convection heat transfer coefficients, the Overall Heat Transfer Coefficient of the entire system can then be represented. (Eq. 11) Using this coefficient, we can use the heat exchanger equations to fully analyze the system. ( ) (Eq. 12 & 13) The pressure analysis of the system was performed using the Extended Bernoulli’s Equation. ∑ (Eq. 14) However, the two points of our analysis occurs before and after the pipes split and reattach, so there is no need to include change in height. Also, because the diameter of pipe at both analysis points are the same, there is no change in fluid velocity as well. This allows our equation to be simplified to the following: ∑ (Eq. 15) in this equation refers to the output pressure of the pump we have selected. The pressure of a pump is determined using the horsepower and volume flow rate with the relations: ( )( ) (Eq. 16) (Eq. 17) The added terms shown on the Extended Bernoulli’s Equation refer to the frictional losses and the minor losses, respectively. These terms contribute to pressure drop in the system caused by fluid friction against the sides of the pipe and the dynamics of fluids flowing through joints and manifolds.
  • 6. 5 Design Phase Figure 1: Fireplace Heat Exchanger Piping system with Pump After extensive research, the material chosen for the pipe was copper. In addition to its low cost and high thermal conductivity, it was a standard component in many heating systems. This was a safe material choice because wood fires burn at 1100o F to 1500o F [1] , but the melting point of copper is upwards of 1900o F [2] . Because our elbow joints and manifolds would consist of welded connections, their ability to withstand temperature usage could last indefinitely. However, during our calculations, we assumed that fouling would not occur. Realistically, corrosion may become an issue in this system, as it does in all piping systems. We chose a standard inner diameter pipe size of 2.465 inches [3] , making it easily accessible if components ever needed to be replaced. The single pipe travels through a manifold that divides the flow of water into 7 individual pipes of equivalent area. This is done to decrease the speed of the flow and increase surface area exposure to the fire, thus allowing more heat absorption as the water passes. After passing along the walls of the fireplace, the pipes reemerge from the “heat exchanger” and enter a second manifold that rejoins the flow of all 7 pipes. We decided this to be the best course of action in order to simplify our fluid analysis as well as reduce the heat loss of the water to the surroundings. As previously stated, the pipes are all welded to each other rather
  • 7. 6 than connected via gasket threaded to ensure temperature resistance and stave off water leakages. According to the New York City Plumbing Code, the maximum water pressure within a building is 85 pounds per square inch. When exceeded, a water-pressure reducer must be installed. Given this information, we found it acceptable to use a 2-horsepower pump that would supply a pressure of 38.56 pounds per square inch. Results & Discussion: In order to perform a proper analysis on the system to calculate all the relevant information, assumptions were made in regards to the simplicity of the system. It was presumed that the water flow was fully developed and turbulent and moving through a smooth, corrosion-free pipe. In order to use Bernoulli’s equation, it was required to accept that the fluid flow was steady and incompressible as well. The air outside of the pipes is assumed to be subject to no external forces, so the buoyancy of hot air is assumed to be the only motion taking place. This allowed us to model the “shell-side” fluid in this “heat exchanger” as a free or natural convection system. The initial condition of the pipe fluid was assumed to be 60o F water flowing at 0.6 ft/s. In order for the water to leave the system at the desired 180o F, heat energy from the cross- flow air must transfer to the water. The ambient heated air adjacent to the pipes was assumed to be 200o F, and after calculations, the outlet temperature of the air was found to be 148o F. This was done by finding the convection heat transfer coefficients for both fluids (hH20 = 194.5 BTU/h·ft2 ·R and hair = 0.99 BTU/h·ft2 ·R) and determining the heat transfer surface area to be the surface area of the exposed piping (AS = 4.1667 ft2 ). The total heat transfer rate of the system ( ) was found to be 146.25 BTU/s. With the system being powered by a 2-horsepower pump, it was determined that the volume flow rate through the 0.205-inch diameter pipe was 88.9 gallons per minute; it followed that the pressure offered by this pump was measured to be 38.56 pounds per square inch. The utilization of the extended Bernoulli’s equation allowed us to calculate a total pressure drop from the beginning to end of the heat exchanger was only 3.15 pounds per square inch.
  • 8. 7 Cost Analysis: As with all upgrades and installations, it must be determined whether or not it is financially feasible to make such renovations. Assuming that the fireplace infrastructure is already in place, the additional costs involved consist of the piping system, the pump itself, and labor. Using Plumbing Supply as reference [5] , the cost of Type “L” Rigid Copper Pipe with a diameter of 2.5 inches is approximately $35.00 per linear foot. The pipe cost, excluding the manifold, would amount to $2065.00 for 59 linear feet and $928.48 for 28x 90o elbows. According to Water Pumps Direct [6] , a 2-horsepower pump rated for 89 gallons per minute would cost $400. Thus, the total cost of the pump and copper piping, excluding the custom manifolds and the copper piping required to reconnect the system back to the main plumbing infrastructure, would come out to $3400.00 before labor. Conclusion & Recommendation: Our design uses a heat exchanger to capture some of the lost heat given off by the fire. The water in the pipes is heated with this lost energy, which can then be fed directly into the boiler, essentially lessening the load on the water heating system. This can directly lead to reduced energy costs and a more environmentally friendly system. Though we may not recommend going out of your way to perform such an installation, if the renovation of a fireplace was already intended, this could be a fiscally responsible move. If installed properly this system should last at least 50 years under normal operating conditions [7] .
  • 9. 8 Appendix  Detailed derivations and calculations regarding the Shell Fluid (Heated Air)  Detailed derivations and calculations regarding the Tube Fluid (Water)  Detailed derivations and calculations regarding the Heat Exchanger as a whole  Detailed derivations and calculations regarding the Fluid Pressure of the system 1. http://homeguides.sfgate.com/temperatures-woodburning-stove-48039.html 2. http://www.engineeringtoolbox.com/melting-temperature-metals-d_860.html 3. http://www.petersenproducts.com/Specifications/Pipe_Copper.aspx 4. http://www.nyc.gov/html/dob/downloads/pdf/plumbing_code.pdf 5. http://www.plumbingsupply.com/copperpipe.html 6. http://www.waterpumpsdirect.com/pumps/2-hp-sprinkler-pumps.html 7. http://colerepair.com/Copper%20Water%20Pipe.html