SlideShare a Scribd company logo
1 of 26
Download to read offline
Dr. Ahmad Al-Subhi
SWITCHGEAR AND PROTECTION
Lecture 22
GENERATOR PROTECTION
Prepared by: Dr. Ahmad Al-Subhi
- Generator is the most important and expensive equipment in
power system.
- Synchronous generators are utilized in a wide range of sizes,
and different winding configurations, neutral grounding
connections, mechanical and cooling configurations,
connections to loads, and interconnections to utility grids.
- Sizes under consideration can range from a few hundred kilo-
Volt-Ampere (kVA) for standby duties in industrial facilities to
over 1000 MVA in large hydro or nuclear-generating facilities.
Prepared by: Dr. Ahmad Al-Subhi
- As the generator is accompanied by prime mover, excitation
system, voltage regulator, cooling system, etc., its protection
becomes very complex and elaborate.
- There are many different types of faults that synchronous
generators may experience.
- Hence, diverse types and complexities of protection may be
required.
- Faults occur less frequently than on transmission lines.
- But the damage caused by generator faults takes much more
time and money for repairing.
Prepared by: Dr. Ahmad Al-Subhi
- Since there are several types of failures, corresponding types
of relays are used to detect and address each type of failure.
- With the utilization of multi-function computerized relays,
multiple types of failures can be addressed by one relay
assembly.
Prepared by: Dr. Ahmad Al-Subhi
- The protection of the generator presents a very challenging
problem because of its system connections on three different
sides:
- It can be seen that on the one side, it is connected to the prime
mover and on the other side, it has to run in synchronism with
the grid because of its connection to the power system.
- On the third side, it is connected to the source of DC
excitation.
Prepared by: Dr. Ahmad Al-Subhi
- Unlike other apparatus, opening a breaker to isolate the faulty
generator is not sufficient to prevent further damage.
- This is because the generator will continue to supply power to
the stator winding fault until its field excitation is suppressed.
- It is therefore necessary to stop the field supply, shut off the
steam, water or fuel supply to the prime mover, trip the boiler
and shut off all auxiliaries of the generator.
- So, it is characterized by several protective devices that can be
more than 20 devices according to generator size.
Prepared by: Dr. Ahmad Al-Subhi
- Protection schematic for generators up to 5 MVA:
Prepared by: Dr. Ahmad Al-Subhi
- Protection schematic for generators over 5 MVA:
Prepared by: Dr. Ahmad Al-Subhi
- What can go wrong with generator?
Prepared by: Dr. Ahmad Al-Subhi
- Stator and rotor faults:
Prepared by: Dr. Ahmad Al-Subhi
Stator Faults:
- These are the faults associated with the stator of the generator.
- The stator faults means faults associated with the three phase
armature windings of the generator.
- These faults are mainly due to the insulation failure of the
armature windings.
- The main types of stator faults are:
1. Phase to phase faults: not common.
2. Phase to ground faults: common.
3. Inter-turn faults: not common and difficult to detect.
Prepared by: Dr. Ahmad Al-Subhi
โ€ข Phase to Phase Faults:
- The phase to phase faults means short circuit between two
phase windings.
- Such faults are uncommon
because the insulation used
between the coils of different phases in a slot is large.
- Differential protection scheme discussed in transformer
protection is implemented to detect this type of faults.
- Most manufacturers recommend this type of protection for all
units larger than 1 MVA.
Prepared by: Dr. Ahmad Al-Subhi
Example 1: A generator stator winding protected by a percentage
differential relay is shown in the figure below. The relay has 15%
slope. The high resistance ground fault has occurred near the
grounded neutral end of the generator winding while the generator
is carrying load. The currents flowing at each end of the generator
winding are shown. Assuming CTs ratio are 500/5, will the relay
operate?
Prepared by: Dr. Ahmad Al-Subhi
Solution:
Prepared by: Dr. Ahmad Al-Subhi
- Id = 3.4 โ€“ 3 = 0.4 A.
- Ir = (3.4 + 3) / 2 = 3.2 A
- Point is (3.2, 0.4)
- Relay will not operate.
โ€ข Phase to Ground Faults:
- These faults mainly occur in the armature slots.
- The faults are dangerous and can cause severe damage to the
expensive machine.
- If the fault currents are high,
severe burning of stator core may occur.
- This may lead to the requirement of replacing the laminations
which is very costly and time consuming.
- The stator is protected from phase to earth faults using
differential and earth fault protection schemes discussed in
transformer protection.
Prepared by: Dr. Ahmad Al-Subhi
โ€ข Inter-turn Faults:
- Short circuits between the turns of one coil may occur if the
stator winding is made up of multiturn coils.
- This is common for hydro generators but not for large steam
turbine generators, which usually have only one turn windings.
- The inter-turn fault is a short circuit between the turns of the
same phase winding.
- Differential relaying, will not
respond to faults between turns
because there is no difference in the currents at the ends of a
winding with shorted turns.
Prepared by: Dr. Ahmad Al-Subhi
- Applicability of differential protection to stator faults:
Prepared by: Dr. Ahmad Al-Subhi
Differential protection
scheme provides very
fast protection to the
stator winding against
phase to phase faults
and phase to ground
faults only.
- A protection scheme called โ€œTransverse differential protectionโ€
is implemented to protect the stator from inter-turn faults.
- It can detect the unbalance between normally identical windings
caused by an inter-turn fault when the generator has two
windings per phase.
Prepared by: Dr. Ahmad Al-Subhi
Example 2: Application of transverse differential protection to
protect the stator from inter-turn faults:
Prepared by: Dr. Ahmad Al-Subhi
Rotor Faults:
- So the commonly occurring faults with respect to a rotor are:
1. Phase to ground faults.
2. Inter-turn faults.
- These faults are caused due to the severe mechanical and
thermal stresses, acting on the field winding insulation.
- Rotor earth fault protection and rotor temperature indicators are
essential and are provided to large rating generators.
Prepared by: Dr. Ahmad Al-Subhi
- The rotor is usually provided with the following protective
schemes:
1. Field ground fault protection.
2. Loss of excitation protection.
3. Protection against rotor overheating.
4. Rotor shorted turn protection.
Prepared by: Dr. Ahmad Al-Subhi
Abnormal conditions of generator:
- In practice, there are number of situations in which generator is
subjected to some abnormal running conditions.
- The protection must be provided against such conditions.
- These abnormal conditions include:
- Each of these conditions along with their protective schemes are
explained in details in various books.
Prepared by: Dr. Ahmad Al-Subhi
1. Overloading.
2. Over-speeding.
3. Unbalanced loading.
4. Over voltage.
5. Failure of prime mover.
6. Loss of excitation.
7. Overheating.
- Rotating machines are also complicated because of the fact
that important parts of the machine are in mechanical motion.
- This gives rise to problems related to vibration, bearing failure,
mechanical resonance, and other purely mechanical failure
modes that can cause the machine to be removed from service.
- Moreover, mechanical parts are subject to aging and wear that
require periodic monitoring in order to preserve the expected
life of the machine and maintain it in good working condition.
Prepared by: Dr. Ahmad Al-Subhi
- In general, following are some protective schemes applied to
generator protection:
Prepared by: Dr. Ahmad Al-Subhi
1. Differential protection.
2. Inter-turn fault protection.
3. Stator earth fault protection.
4. Rotor earth fault protection.
5. Vibration protection.
6. Field failure protection.
7. Overload protection.
8. Overvoltage protection.
9. Reverse power protection.
10. Pole slipping protection.
11. Back up impedance protection.
12. Under frequency protection.
13. Miscellaneous protection.
14. Negative phase sequence protection.
15. Bearing failure protection.
16. Coolant failure protection.
17. Fire protection.
18. Protection of power plant auxiliaries.
- This table gives data about the present practice of generator
protection:
Prepared by: Dr. Ahmad Al-Subhi
- For more detailed analysis and explanation about generator
protection, refer to the following books:
Prepared by: Dr. Ahmad Al-Subhi

More Related Content

Similar to Lecture_22_-_Generator_Protection by Dr. AHmad-al-Subhi

Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear johny renoald
ย 
Generator Protection
Generator ProtectionGenerator Protection
Generator ProtectionPriten Vasa
ย 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
ย 
induction motor protection system seminar report
induction motor protection system seminar reportinduction motor protection system seminar report
induction motor protection system seminar reportdipali karangale
ย 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Rahul Ruddra
ย 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarBhushan Kumbhalkar
ย 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of GeneratorRahuldey1991
ย 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.pptThien Phan Bแบฃn
ย 
IRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit InterupterIRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit InterupterIRJET Journal
ย 
Equipment protection
Equipment protectionEquipment protection
Equipment protectionSlides Hub
ย 
Generator protection
Generator protectionGenerator protection
Generator protectionSSVASAVA
ย 
Selecting Electric Motor Protection for Plant and Process Optimization
Selecting Electric Motor Protection for Plant and Process OptimizationSelecting Electric Motor Protection for Plant and Process Optimization
Selecting Electric Motor Protection for Plant and Process OptimizationIRJET Journal
ย 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.javid iqbal sodagar
ย 
GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)siddharth sharma
ย 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
ย 
Experiments manual
Experiments manual Experiments manual
Experiments manual Ramesh Meti
ย 
Understanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitUnderstanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitBassam Gomaa
ย 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word DocumentBarunava Sikdar
ย 
Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Living Online
ย 
Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Living Online
ย 

Similar to Lecture_22_-_Generator_Protection by Dr. AHmad-al-Subhi (20)

Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
ย 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
ย 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
ย 
induction motor protection system seminar report
induction motor protection system seminar reportinduction motor protection system seminar report
induction motor protection system seminar report
ย 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
ย 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
ย 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
ย 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
ย 
IRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit InterupterIRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit Interupter
ย 
Equipment protection
Equipment protectionEquipment protection
Equipment protection
ย 
Generator protection
Generator protectionGenerator protection
Generator protection
ย 
Selecting Electric Motor Protection for Plant and Process Optimization
Selecting Electric Motor Protection for Plant and Process OptimizationSelecting Electric Motor Protection for Plant and Process Optimization
Selecting Electric Motor Protection for Plant and Process Optimization
ย 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
ย 
GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)
ย 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
ย 
Experiments manual
Experiments manual Experiments manual
Experiments manual
ย 
Understanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitUnderstanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuit
ย 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
ย 
Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...
ย 
Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...
ย 

More from AniruddhaRay11

Lecture 6a - High Voltage Circuit Breakers Overview.pdf
Lecture 6a - High Voltage Circuit Breakers Overview.pdfLecture 6a - High Voltage Circuit Breakers Overview.pdf
Lecture 6a - High Voltage Circuit Breakers Overview.pdfAniruddhaRay11
ย 
Lecture 4 - Introduction to Circuit Breakers.pdf
Lecture 4 - Introduction to Circuit Breakers.pdfLecture 4 - Introduction to Circuit Breakers.pdf
Lecture 4 - Introduction to Circuit Breakers.pdfAniruddhaRay11
ย 
Lecture 3a - Introduction to Fuse.pdf
Lecture 3a - Introduction to Fuse.pdfLecture 3a - Introduction to Fuse.pdf
Lecture 3a - Introduction to Fuse.pdfAniruddhaRay11
ย 
Lecture 9c - Wave Trap.pptx
Lecture 9c - Wave Trap.pptxLecture 9c - Wave Trap.pptx
Lecture 9c - Wave Trap.pptxAniruddhaRay11
ย 
Lecture 3b - Fuses Coordination in Power System.pdf
Lecture 3b - Fuses Coordination in Power System.pdfLecture 3b - Fuses Coordination in Power System.pdf
Lecture 3b - Fuses Coordination in Power System.pdfAniruddhaRay11
ย 
Air Blast Circuit Breaker(ABCB)_Switchgear & protection.pptx
Air Blast Circuit Breaker(ABCB)_Switchgear & protection.pptxAir Blast Circuit Breaker(ABCB)_Switchgear & protection.pptx
Air Blast Circuit Breaker(ABCB)_Switchgear & protection.pptxAniruddhaRay11
ย 

More from AniruddhaRay11 (6)

Lecture 6a - High Voltage Circuit Breakers Overview.pdf
Lecture 6a - High Voltage Circuit Breakers Overview.pdfLecture 6a - High Voltage Circuit Breakers Overview.pdf
Lecture 6a - High Voltage Circuit Breakers Overview.pdf
ย 
Lecture 4 - Introduction to Circuit Breakers.pdf
Lecture 4 - Introduction to Circuit Breakers.pdfLecture 4 - Introduction to Circuit Breakers.pdf
Lecture 4 - Introduction to Circuit Breakers.pdf
ย 
Lecture 3a - Introduction to Fuse.pdf
Lecture 3a - Introduction to Fuse.pdfLecture 3a - Introduction to Fuse.pdf
Lecture 3a - Introduction to Fuse.pdf
ย 
Lecture 9c - Wave Trap.pptx
Lecture 9c - Wave Trap.pptxLecture 9c - Wave Trap.pptx
Lecture 9c - Wave Trap.pptx
ย 
Lecture 3b - Fuses Coordination in Power System.pdf
Lecture 3b - Fuses Coordination in Power System.pdfLecture 3b - Fuses Coordination in Power System.pdf
Lecture 3b - Fuses Coordination in Power System.pdf
ย 
Air Blast Circuit Breaker(ABCB)_Switchgear & protection.pptx
Air Blast Circuit Breaker(ABCB)_Switchgear & protection.pptxAir Blast Circuit Breaker(ABCB)_Switchgear & protection.pptx
Air Blast Circuit Breaker(ABCB)_Switchgear & protection.pptx
ย 

Recently uploaded

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
ย 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
ย 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
ย 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
ย 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
ย 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
ย 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
ย 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
ย 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
ย 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
ย 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
ย 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
ย 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
ย 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
ย 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
ย 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
ย 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
ย 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7Call Girls in Nagpur High Profile Call Girls
ย 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEslot gacor bisa pakai pulsa
ย 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
ย 

Recently uploaded (20)

The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
ย 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
ย 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
ย 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
ย 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
ย 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
ย 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
ย 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
ย 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
ย 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
ย 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
ย 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
ย 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
ย 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
ย 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
ย 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
ย 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
ย 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
ย 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
ย 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
ย 

Lecture_22_-_Generator_Protection by Dr. AHmad-al-Subhi

  • 1. Dr. Ahmad Al-Subhi SWITCHGEAR AND PROTECTION Lecture 22 GENERATOR PROTECTION Prepared by: Dr. Ahmad Al-Subhi
  • 2. - Generator is the most important and expensive equipment in power system. - Synchronous generators are utilized in a wide range of sizes, and different winding configurations, neutral grounding connections, mechanical and cooling configurations, connections to loads, and interconnections to utility grids. - Sizes under consideration can range from a few hundred kilo- Volt-Ampere (kVA) for standby duties in industrial facilities to over 1000 MVA in large hydro or nuclear-generating facilities. Prepared by: Dr. Ahmad Al-Subhi
  • 3. - As the generator is accompanied by prime mover, excitation system, voltage regulator, cooling system, etc., its protection becomes very complex and elaborate. - There are many different types of faults that synchronous generators may experience. - Hence, diverse types and complexities of protection may be required. - Faults occur less frequently than on transmission lines. - But the damage caused by generator faults takes much more time and money for repairing. Prepared by: Dr. Ahmad Al-Subhi
  • 4. - Since there are several types of failures, corresponding types of relays are used to detect and address each type of failure. - With the utilization of multi-function computerized relays, multiple types of failures can be addressed by one relay assembly. Prepared by: Dr. Ahmad Al-Subhi
  • 5. - The protection of the generator presents a very challenging problem because of its system connections on three different sides: - It can be seen that on the one side, it is connected to the prime mover and on the other side, it has to run in synchronism with the grid because of its connection to the power system. - On the third side, it is connected to the source of DC excitation. Prepared by: Dr. Ahmad Al-Subhi
  • 6. - Unlike other apparatus, opening a breaker to isolate the faulty generator is not sufficient to prevent further damage. - This is because the generator will continue to supply power to the stator winding fault until its field excitation is suppressed. - It is therefore necessary to stop the field supply, shut off the steam, water or fuel supply to the prime mover, trip the boiler and shut off all auxiliaries of the generator. - So, it is characterized by several protective devices that can be more than 20 devices according to generator size. Prepared by: Dr. Ahmad Al-Subhi
  • 7. - Protection schematic for generators up to 5 MVA: Prepared by: Dr. Ahmad Al-Subhi
  • 8. - Protection schematic for generators over 5 MVA: Prepared by: Dr. Ahmad Al-Subhi
  • 9. - What can go wrong with generator? Prepared by: Dr. Ahmad Al-Subhi
  • 10. - Stator and rotor faults: Prepared by: Dr. Ahmad Al-Subhi
  • 11. Stator Faults: - These are the faults associated with the stator of the generator. - The stator faults means faults associated with the three phase armature windings of the generator. - These faults are mainly due to the insulation failure of the armature windings. - The main types of stator faults are: 1. Phase to phase faults: not common. 2. Phase to ground faults: common. 3. Inter-turn faults: not common and difficult to detect. Prepared by: Dr. Ahmad Al-Subhi
  • 12. โ€ข Phase to Phase Faults: - The phase to phase faults means short circuit between two phase windings. - Such faults are uncommon because the insulation used between the coils of different phases in a slot is large. - Differential protection scheme discussed in transformer protection is implemented to detect this type of faults. - Most manufacturers recommend this type of protection for all units larger than 1 MVA. Prepared by: Dr. Ahmad Al-Subhi
  • 13. Example 1: A generator stator winding protected by a percentage differential relay is shown in the figure below. The relay has 15% slope. The high resistance ground fault has occurred near the grounded neutral end of the generator winding while the generator is carrying load. The currents flowing at each end of the generator winding are shown. Assuming CTs ratio are 500/5, will the relay operate? Prepared by: Dr. Ahmad Al-Subhi
  • 14. Solution: Prepared by: Dr. Ahmad Al-Subhi - Id = 3.4 โ€“ 3 = 0.4 A. - Ir = (3.4 + 3) / 2 = 3.2 A - Point is (3.2, 0.4) - Relay will not operate.
  • 15. โ€ข Phase to Ground Faults: - These faults mainly occur in the armature slots. - The faults are dangerous and can cause severe damage to the expensive machine. - If the fault currents are high, severe burning of stator core may occur. - This may lead to the requirement of replacing the laminations which is very costly and time consuming. - The stator is protected from phase to earth faults using differential and earth fault protection schemes discussed in transformer protection. Prepared by: Dr. Ahmad Al-Subhi
  • 16. โ€ข Inter-turn Faults: - Short circuits between the turns of one coil may occur if the stator winding is made up of multiturn coils. - This is common for hydro generators but not for large steam turbine generators, which usually have only one turn windings. - The inter-turn fault is a short circuit between the turns of the same phase winding. - Differential relaying, will not respond to faults between turns because there is no difference in the currents at the ends of a winding with shorted turns. Prepared by: Dr. Ahmad Al-Subhi
  • 17. - Applicability of differential protection to stator faults: Prepared by: Dr. Ahmad Al-Subhi Differential protection scheme provides very fast protection to the stator winding against phase to phase faults and phase to ground faults only.
  • 18. - A protection scheme called โ€œTransverse differential protectionโ€ is implemented to protect the stator from inter-turn faults. - It can detect the unbalance between normally identical windings caused by an inter-turn fault when the generator has two windings per phase. Prepared by: Dr. Ahmad Al-Subhi
  • 19. Example 2: Application of transverse differential protection to protect the stator from inter-turn faults: Prepared by: Dr. Ahmad Al-Subhi
  • 20. Rotor Faults: - So the commonly occurring faults with respect to a rotor are: 1. Phase to ground faults. 2. Inter-turn faults. - These faults are caused due to the severe mechanical and thermal stresses, acting on the field winding insulation. - Rotor earth fault protection and rotor temperature indicators are essential and are provided to large rating generators. Prepared by: Dr. Ahmad Al-Subhi
  • 21. - The rotor is usually provided with the following protective schemes: 1. Field ground fault protection. 2. Loss of excitation protection. 3. Protection against rotor overheating. 4. Rotor shorted turn protection. Prepared by: Dr. Ahmad Al-Subhi
  • 22. Abnormal conditions of generator: - In practice, there are number of situations in which generator is subjected to some abnormal running conditions. - The protection must be provided against such conditions. - These abnormal conditions include: - Each of these conditions along with their protective schemes are explained in details in various books. Prepared by: Dr. Ahmad Al-Subhi 1. Overloading. 2. Over-speeding. 3. Unbalanced loading. 4. Over voltage. 5. Failure of prime mover. 6. Loss of excitation. 7. Overheating.
  • 23. - Rotating machines are also complicated because of the fact that important parts of the machine are in mechanical motion. - This gives rise to problems related to vibration, bearing failure, mechanical resonance, and other purely mechanical failure modes that can cause the machine to be removed from service. - Moreover, mechanical parts are subject to aging and wear that require periodic monitoring in order to preserve the expected life of the machine and maintain it in good working condition. Prepared by: Dr. Ahmad Al-Subhi
  • 24. - In general, following are some protective schemes applied to generator protection: Prepared by: Dr. Ahmad Al-Subhi 1. Differential protection. 2. Inter-turn fault protection. 3. Stator earth fault protection. 4. Rotor earth fault protection. 5. Vibration protection. 6. Field failure protection. 7. Overload protection. 8. Overvoltage protection. 9. Reverse power protection. 10. Pole slipping protection. 11. Back up impedance protection. 12. Under frequency protection. 13. Miscellaneous protection. 14. Negative phase sequence protection. 15. Bearing failure protection. 16. Coolant failure protection. 17. Fire protection. 18. Protection of power plant auxiliaries.
  • 25. - This table gives data about the present practice of generator protection: Prepared by: Dr. Ahmad Al-Subhi
  • 26. - For more detailed analysis and explanation about generator protection, refer to the following books: Prepared by: Dr. Ahmad Al-Subhi