ComEd Vernon Hills Meeting
1. Vernon Hills
Reliability Update
October 18, 2011
North Region Reliability Engineering 1
2. Engineering Reliability Reviews
North Region Reliability Engineering reviews data and information on
North Region Reliability Engineering reviews data and information on
approximately 1,800 circuits annually to address opportunities for improvements
approximately 1,800 circuits annually to address opportunities for improvements
and corrective actions for the entire circuit or for pocket areas.
and corrective actions for the entire circuit or for pocket areas.
• Two-pronged approach to driving reliability reviews and “leading”
engineers to problem areas
– Reliability reviews based on yearly performance
• Per ICC, ComEd develops and reports on circuit SAIFI (frequency of outages)
i.e. where are current unfavorable trends
• ComEd develops statistics around three year average SAIFI numbers to identify
chronic unfavorable trending on any circuits
– Reliability reviews based on “pocket area” information
• ComEd has statistics and information on outages that are not “wide-spread” but
impact “pockets” of customers
• It is not uncommon to have a circuit that performs very well as a whole but does
have pockets of customers that experience chronic outages
• In addition, ComEd utilizes feedback from village administration on “pocket
area” issues – we want to hear about these so we can address them
North Region Reliability Engineering 2
3. Engineering Reliability Reviews
Transmission Line/Substation
Substation circuit breaker
Main line of
circuit
Fuse
Transformer
X
Fuse
Fuse
“Pocket area”
Fuse
North Region Reliability Engineering 3
4. System Performance Improvements
Trip saver: Fuse that will auto reset for transient faults
i.e. branch bounces off wire, fuse resets itself
and avoids sustained outage
URD cable replacement: Cable that has shown unfavorable trends of
performance and will be replaced in the same route as the old cable
Targeted Tree Trimming:
• Standard trimming – 10 foot zone in all directions around primary
conductors for 12,000-volt and below circuits
• Targeted trimming – minimize over-hang, extend beyond standard
zone above primary conductors, elimination of dead branches and
“soft-wood” species
North Region Reliability Engineering 4
5. System Performance Improvements
Hendrix cable: A overhead
installation of covered,
bundled primary wire that can
withstand tree branches and
small tree contact
Standard construction with bare conductors
create a “canopy for tree branches
HENDRIX construction has covered conductors and
reduces the “surface” footprint such not to provide a
canopy for branches
North Region Reliability Engineering 5
6. Vernon Hills – A6618
Improvements include
•Installation of HENDRIX spacer cable A overhead installation of covered, bundled
primary wire that can withstand tree branches and small tree contact. Proven to
reduce outages by 75-85%.
Enhanced tree
trimming will
be performed
in this area
3500’ feet
North Region Reliability Engineering 6
7. Vernon Hills – A6618
Improvements include
Install 140A or 200A
fuses with bypass
disconnects to isolate
all customers from
tree outages down-
stream
Additional fuse
Enhanced tree
trimming will Additional fuse
be performed
in this area
North Region Reliability Engineering 7
8. Vernon Hills – Feeder A6618
Improvements include
• Installation of an automatic recloser to reduce outage exposure to customers due to
tree related issues
Automatic
reclosing
device
North Region Reliability Engineering 8
9. Vernon Hills – A6616
Improvements include
• Replace URD cable
150’ feet
400’ feet
North Region Reliability Engineering 9
10. Vernon Hills – A6616
Improvements include
• Enhanced tree trimming on main line
Enhanced tree
trimming will
be performed
in this area
North Region Reliability Engineering 10
11. Vernon Hills – A6610
Improvements include
• Replace underground cable in Hawthorne Center
400’ feet
North Region Reliability Engineering 11
12. Vernon Hills – A666Y
Improvements include
• Infrared inspect cable joints (splices) located in existing manholes to identify
anomalies and make associated replacements as required
location of manholes
location of manholes
North Region Reliability Engineering 12
13. Vernon Hills – A668
Improvements completed in 2010
• Replace underground cable and install new switchgear to provide switching flexibility
to the mall
V
V
V
V
S
New switching cubicle
North Region Reliability Engineering 13
14. Vernon Hills – A668
Improvements completed in 2010
• Replace underground cable (mainline)
S
S
S S
North Region Reliability Engineering 14
15. Vernon Hills – A6628
Improvements completed and in-progress
• Replace underground cable
replaced
North Region Reliability Engineering 15
16. Vernon Hills – A6628
Improvements completed and in-progress
• Replace underground cable
replaced
in-progress
North Region Reliability Engineering 16
17. Vernon Hills – A6628
Improvements completed and in-progress
• Replace underground cable
replaced
in-progress
North Region Reliability Engineering 17
18. Vernon Hills – Distribution Automation
• Distribution Automation will serve approximately 4700
Vernon Hills customers (43% of the Village)
• One full-loop scheme is in service on feeders A6611/
C0923
• A second full-loop scheme will be livened by December
2011 on feeders A668/ A664
• A full loop scheme (in the engineering stage) on
feeders A666Y/ A122, will be built in 2012
Full-loop, bi-directional automation scheme
Substation Automated Automated Automated Substation
Circuit switch #1 switch #2 switch #3 Circuit
breaker (normally closed) (normally open) (normally closed) breaker
Circuit #1 Circuit #2
North Region Reliability Engineering 18
19. Smart Grid – Future Model
Delivery Automation,
Transmission Sensors
Sensors and Controls
and Automation
• Real-time reporting of
• Power factor monitoring
Home area network status and outages
•Optimized switching of
• Real-time usage and • Automated controls of
capacitor banks
pricing statistics relays and reclosers
• Usage – aware • Field force management
appliances PowerCo
PowerCo
1234
Smart Meter Distributed Generation Data collection, processing
• Report usage by time • Micro-generation and back office
• Report outages in • Solar • Automated billing
real-time • Wind • Disconnection of unoccupied /
• Remote disconnect • Net metering unpaid
• HAN gateway • Daily usage stats
• Time of Use pricing
Smart Grid will deliver enhanced reliability and create new
opportunity for customer control of energy usage and spend
North Region Reliability Engineering 19