NO.
BY G.C.
ITEM DESCRIPTIONQTY SUPPLY INST.
MFR. & MODEL NUMBER PLUMB ELECT GAS REMARKS NO.NO.
BY G.C.
ITEM DESCRIPTIONQTY SUPPLY INST.
MFR. & MODEL NUMBER PLUMB ELECT GAS REMARKS NO.
EXTERIOR INTERIOR
GRADE
CEILING
TO UTILITY
COMPANY
M
ROOF
GRADE
E.C. TO COORDINATE WITH AMEREN
ELECTRIC FOR MAIN SERVICE ENTRANCE
INSTALLATION. VERIFY RESPONSIBILITIES
FOR INSTALLING CONDUIT AND WIRE.
E.C. TO PROVIDE NEW METER
FOR EXISTING METER BASE.
PROVIDE NEW BASE IF NONE
EXISTS.
E.C. TO PROVIDE NEW NEMA-3R,
400-AMP DISCONNECT SWITCH
WITH NEW 300-AMP FUSES.
TO UTILITY
COMPANY
NEW 4#500kcmil, 1#3G IN 3-1/2"C.
NEW
PANEL
LP
IN3-1/2"C
400A
NEW
PANEL
LP2
125A
IN1-1/4"C
NEW #1/0 C.U. GROUND TO
BUILDING STEEL, COPPER
PLUMBING AND 10'-0" DRIVEN ROD
Imo's Pizza - St. Charles, MO

Imo's Pizza - St. Charles, MO

  • 3.
    NO. BY G.C. ITEM DESCRIPTIONQTYSUPPLY INST. MFR. & MODEL NUMBER PLUMB ELECT GAS REMARKS NO.NO. BY G.C. ITEM DESCRIPTIONQTY SUPPLY INST. MFR. & MODEL NUMBER PLUMB ELECT GAS REMARKS NO.
  • 21.
    EXTERIOR INTERIOR GRADE CEILING TO UTILITY COMPANY M ROOF GRADE E.C.TO COORDINATE WITH AMEREN ELECTRIC FOR MAIN SERVICE ENTRANCE INSTALLATION. VERIFY RESPONSIBILITIES FOR INSTALLING CONDUIT AND WIRE. E.C. TO PROVIDE NEW METER FOR EXISTING METER BASE. PROVIDE NEW BASE IF NONE EXISTS. E.C. TO PROVIDE NEW NEMA-3R, 400-AMP DISCONNECT SWITCH WITH NEW 300-AMP FUSES. TO UTILITY COMPANY NEW 4#500kcmil, 1#3G IN 3-1/2"C. NEW PANEL LP IN3-1/2"C 400A NEW PANEL LP2 125A IN1-1/4"C NEW #1/0 C.U. GROUND TO BUILDING STEEL, COPPER PLUMBING AND 10'-0" DRIVEN ROD