Potential +/- Difference Inc .
             Bi-Toroid Transformer Tests




 Potential + / - Difference Inc.
 Bi-Toroid Transformer Tests
               For
     Magna International




Prepared for: Dave Pascoe – Magna International
        Prepared by: Thane Heins - PDI
              Date: July 15th, 2009




                                            July 18, 2009
Potential +/- Difference Inc .
                              Bi-Toroid Transformer Tests

    The Bi-Toroid Transformer is designed to convert Reactive Power to Real Power.
     This is accomplished by introducing an additional secondary coil and alternate
     flux path route – keeping the primary coil isolated from the secondary induced
                                 BEMF magnetic fluxes

The extra energy required to produce a transformer that operates at over 100% efficiency
 comes from the fact that the two secondary coils self regulate their own flux required to
maintain the voltage across the load and the primary coil is unaffected by secondary load.



Transformer    TEST # 1 TEST # 2 TEST #3        TEST #4 TEST #5 TEST #6
   Type        Efficiency Efficiency Efficiency Efficiency Efficiency Efficiency


Conventional        -            -            -          74%            -               -
  E I Type


 Bi-Toroid        191%         310%         989%           -         406%         304%


Table 1 Conventional Transformer vs Bi-Toroid Transformer Efficiency Comparison

The table above shows the efficiency variations for the Bi-Toroid Transformer during the
period of July 10th to July 18th, 2009.

TEST #1 employs a “split” primary core – where an “artificial” air gap is inserted to
increase core reluctance.

TEST #2 employs a solid core – where the core is just sitting on the secondary core – also
facilitating an air gap and higher reluctance between the primary core and secondary
core.

TEST #3 employs a solid core (slightly thicker than test #2) which is physically clamped
to the secondary core – thus removing as much air gap as possible. A new primary coil is
included in the test which has the same wire gauge and coil resistance as test #2.

TEST #4 is a Conventional Transformer.

TEST #5 employs a 10 ohm load in place of the 27 ohm load.

TEST #6 is includes additional windings on Secondary #1.




                                                                             July 18, 2009
Potential +/- Difference Inc .
                               Bi-Toroid Transformer Tests

TEST # 1 Split Primary Core




         Fig. 1 TEST # 1 New “Split” Primary and Secondary 1 & 2 - July 10th, 2009




Fig. 2 Primary Input Voltage                       Fig. 3 Primary Input Current &
                                                          Output Voltage
TEST DATA #1 July 10th, 2009

Primary Input Voltage = 57.7 volts
Primary Input Current = 0.026 amps
Power Factor = 83.3 degrees / 0.116
Primary Input Power = 174 mW

Secondary Output Voltage = 3.0 volts
Secondary Load = 27 ohms
Secondary Output Power = 333 mW

Efficiency = 191%


                                                                        July 18, 2009
Potential +/- Difference Inc .
                             Bi-Toroid Transformer Tests




Fig. 4 & 5   Voltage & Current Sine Waves – Power Factor = 0.116 / 83.3 degrees




                                                                        July 18, 2009
Potential +/- Difference Inc .
                           Bi-Toroid Transformer Tests

TEST # 2 Solid Primary Core




   Fig. 6 TEST # 2 New Primary “Solid” Core – JULY 11th, 2009




        Fig. 7 Primary Input Current & Output Voltage




                                                                July 18, 2009
Potential +/- Difference Inc .
                             Bi-Toroid Transformer Tests

TEST DATA # 2 July 11th, 2009

Primary Input Voltage = 58.8 volts
Primary Input Current = 0.017 amps
Power Factor = 83.3 degrees / 0.116
Primary Input Power = 115 mW

Secondary Output Voltage = 3.1 volts
Secondary Load = 27 ohms
Secondary Output Power = 356 mW

Efficiency = 310%




  Fig. 8   Voltage & Current Sine Waves Power Factor = 0.116 / 83.3 degrees




                                                                        July 18, 2009
Potential +/- Difference Inc .
                           Bi-Toroid Transformer Tests

TEST # 3 Hard Physical Primary Connection




  Fig. 9 TEST # 3 New Primary Core “Hard Physical Connection” – JULY 13th, 2009




               Fig. 10 Primary Input Current & Output Voltage




                                                                     July 18, 2009
Potential +/- Difference Inc .
                             Bi-Toroid Transformer Tests

TEST DATA # 3 July 13th, 2009

Primary Input Voltage = 104.7 volts
Primary Input Current = 0.001 amps
Power Factor = 70 degrees / 0.34
Primary Input Power = 36 mW

Secondary Output Voltage = 3.1 volts
Secondary Load = 27 ohms
Secondary Output Power = 356 mW

Efficiency = 989%




Fig. 11   Voltage & Current Sine Waves - Power Factor = 0.34 / 70 degrees




                                                                        July 18, 2009
Potential +/- Difference Inc .
                           Bi-Toroid Transformer Tests

TEST # 4 Conventional Transformer Efficiency




  Fig. 12 TEST # 4 Conventional Transformer Input Voltage – JULY 15th, 2009




              Fig. 13 Primary Input Current & Output Voltage




                                                                      July 18, 2009
Potential +/- Difference Inc .
                             Bi-Toroid Transformer Tests

TEST DATA # 4 July 15th, 2009

Primary Input Voltage = 2.71 volts
Primary Input Current = 0.200 amps
Power Factor = 18 degrees / 0.95
Primary Input Power = 516 mW

Secondary Output Voltage = 3.2 volts
Secondary Load = 27 ohms
Secondary Output Power = 379 mW

Efficiency = 73.5%




Fig. 14   Voltage & Current Sine Waves - Power Factor = 0.95 / 18 degrees




                                                                        July 18, 2009
Potential +/- Difference Inc .
                           Bi-Toroid Transformer Tests

TEST # 5 Ten Ohm Load Test




Fig. 15 TEST # 5 Bi-Toroid Transformer Input Voltage 10 Ohm Load – JULY 17th, 2009




       Fig. 16 Primary Input Current & Output Voltage


                                                                      July 18, 2009
Potential +/- Difference Inc .
                             Bi-Toroid Transformer Tests

TEST DATA # 5 July 16th, 2009

Primary Input Voltage = 120.9 volts
Primary Input Current = 0.005 amps
Power Factor = 84 degrees / 0.10
Primary Input Power = 63 mW

Secondary Output Voltage = 1.6 volts
Secondary Load = 10 ohms
Secondary Output Power = 256 mW

Efficiency = 406%




Fig. 17   Voltage & Current Sine Waves - Power Factor = 0.10 / 84 degrees




                                                                        July 18, 2009
Potential +/- Difference Inc .
                           Bi-Toroid Transformer Tests

TEST # 6 Ten Ohm Load Test NEW SECONDARY 1 WINDINGS




Fig. 18 TEST # 6 Bi-Toroid Transformer Input Voltage 10 Ohm Load – JULY 18th, 2009




              Fig. 19 Primary Input Current & Output Voltage




                                                                      July 18, 2009
Potential +/- Difference Inc .
                             Bi-Toroid Transformer Tests

TEST DATA # 6 July 18th, 2009

Primary Input Voltage = 119.9 volts
Primary Input Current = 0.006 amps
Power Factor = 80 degrees / 0.17
Primary Input Power = 125 mW

Secondary Output Voltage = 2.22 volts
Secondary Load = 10 ohms
Secondary Output Power = 493 mW

Efficiency = 394%




Fig. 20   Voltage & Current Sine Waves - Power Factor = 0.17 / 80 degrees




                                                                        July 18, 2009
Potential +/- Difference Inc .
                            Bi-Toroid Transformer Tests

TEST # 7 Test Equipment Accuracy Confirmations




Fig 21 Load Voltage across 27 Ohm Load




             Fig 22 Load Current through 27 Ohm Load

TEST DATA #7 July 16th, 2009

Load Voltage = 3 volts
Load Resistance = 27.5 ohms
Calculated Load Current = 0.109 amps

Metered Load Current = 0.111 amps
Meter Error = 1.8%



                                                          July 18, 2009
Potential +/- Difference Inc .
   Bi-Toroid Transformer Tests




                                 July 18, 2009
Potential +/- Difference Inc .
                            Bi-Toroid Transformer Tests




Fig. 23 Voltage & Current Sine Waves - Power Factor = 0.36 / 69 degrees




                                                                          July 18, 2009
Potential +/- Difference Inc .
                            Bi-Toroid Transformer Tests




Fig. 26 Voltage & Current Sine Waves - Power Factor = 0.05 / 87 degrees




                                                                          July 18, 2009

More Related Content

Viewers also liked

Open Letter to Dr. Marc Garneau, Liberal Party of Canada
Open Letter to Dr. Marc Garneau, Liberal Party of CanadaOpen Letter to Dr. Marc Garneau, Liberal Party of Canada
Open Letter to Dr. Marc Garneau, Liberal Party of CanadaThane Heins
 
Potential Difference Inc. MAGNA International ReGenX & BiTT Presentation
Potential Difference Inc. MAGNA International ReGenX & BiTT PresentationPotential Difference Inc. MAGNA International ReGenX & BiTT Presentation
Potential Difference Inc. MAGNA International ReGenX & BiTT PresentationThane Heins
 
Cross & Beyond Ministries March 2011
Cross & Beyond Ministries March 2011Cross & Beyond Ministries March 2011
Cross & Beyond Ministries March 2011gwoodward
 
Cross & Beyond March 2011
Cross & Beyond March 2011Cross & Beyond March 2011
Cross & Beyond March 2011gwoodward
 
Regenerative Acceleration Generator Technology Third Party Validation
Regenerative Acceleration Generator Technology Third Party ValidationRegenerative Acceleration Generator Technology Third Party Validation
Regenerative Acceleration Generator Technology Third Party ValidationThane Heins
 
A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...
A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...
A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...Thane Heins
 
P di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosureP di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosureThane Heins
 
KERS To KEGS Regenerative Acceleration Report
KERS To KEGS Regenerative Acceleration Report KERS To KEGS Regenerative Acceleration Report
KERS To KEGS Regenerative Acceleration Report Thane Heins
 
PDi ReGen-X Prospectus
PDi ReGen-X ProspectusPDi ReGen-X Prospectus
PDi ReGen-X ProspectusThane Heins
 
ReGen-X Introduction A New Quantum Leap Energy Innovation
ReGen-X Introduction A New Quantum Leap Energy InnovationReGen-X Introduction A New Quantum Leap Energy Innovation
ReGen-X Introduction A New Quantum Leap Energy InnovationThane Heins
 
Potential Difference MAGNA International ReGenX & BiTT Presentation
Potential Difference MAGNA International ReGenX & BiTT PresentationPotential Difference MAGNA International ReGenX & BiTT Presentation
Potential Difference MAGNA International ReGenX & BiTT PresentationThane Heins
 
Nouha belaid - La presse gratuite en Tunisie, exemple de Tendance Magazine
Nouha belaid - La presse gratuite en Tunisie, exemple de Tendance MagazineNouha belaid - La presse gratuite en Tunisie, exemple de Tendance Magazine
Nouha belaid - La presse gratuite en Tunisie, exemple de Tendance MagazineNouha Belaid
 

Viewers also liked (13)

Open Letter to Dr. Marc Garneau, Liberal Party of Canada
Open Letter to Dr. Marc Garneau, Liberal Party of CanadaOpen Letter to Dr. Marc Garneau, Liberal Party of Canada
Open Letter to Dr. Marc Garneau, Liberal Party of Canada
 
Potential Difference Inc. MAGNA International ReGenX & BiTT Presentation
Potential Difference Inc. MAGNA International ReGenX & BiTT PresentationPotential Difference Inc. MAGNA International ReGenX & BiTT Presentation
Potential Difference Inc. MAGNA International ReGenX & BiTT Presentation
 
Cross & Beyond Ministries March 2011
Cross & Beyond Ministries March 2011Cross & Beyond Ministries March 2011
Cross & Beyond Ministries March 2011
 
Cross & Beyond March 2011
Cross & Beyond March 2011Cross & Beyond March 2011
Cross & Beyond March 2011
 
Regenerative Acceleration Generator Technology Third Party Validation
Regenerative Acceleration Generator Technology Third Party ValidationRegenerative Acceleration Generator Technology Third Party Validation
Regenerative Acceleration Generator Technology Third Party Validation
 
A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...
A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...
A CONVENIENT TRUTH - Mother Earth Day 2013... global warming, the beginning o...
 
Secova pkg
Secova pkgSecova pkg
Secova pkg
 
P di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosureP di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosure
 
KERS To KEGS Regenerative Acceleration Report
KERS To KEGS Regenerative Acceleration Report KERS To KEGS Regenerative Acceleration Report
KERS To KEGS Regenerative Acceleration Report
 
PDi ReGen-X Prospectus
PDi ReGen-X ProspectusPDi ReGen-X Prospectus
PDi ReGen-X Prospectus
 
ReGen-X Introduction A New Quantum Leap Energy Innovation
ReGen-X Introduction A New Quantum Leap Energy InnovationReGen-X Introduction A New Quantum Leap Energy Innovation
ReGen-X Introduction A New Quantum Leap Energy Innovation
 
Potential Difference MAGNA International ReGenX & BiTT Presentation
Potential Difference MAGNA International ReGenX & BiTT PresentationPotential Difference MAGNA International ReGenX & BiTT Presentation
Potential Difference MAGNA International ReGenX & BiTT Presentation
 
Nouha belaid - La presse gratuite en Tunisie, exemple de Tendance Magazine
Nouha belaid - La presse gratuite en Tunisie, exemple de Tendance MagazineNouha belaid - La presse gratuite en Tunisie, exemple de Tendance Magazine
Nouha belaid - La presse gratuite en Tunisie, exemple de Tendance Magazine
 

Similar to Complete Magna Transformer Tests July 10th & 11th, 2009

PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...
PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...
PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...Thane Heins
 
Bi-Toroid Transformer Performance vs Conventional EI Transformer
Bi-Toroid Transformer Performance vs Conventional EI TransformerBi-Toroid Transformer Performance vs Conventional EI Transformer
Bi-Toroid Transformer Performance vs Conventional EI TransformerThane Heins
 
OP amp parameters
OP amp parametersOP amp parameters
OP amp parametersOmkar Rane
 
ET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdf
ET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdfET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdf
ET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdfgffddffv vfdfvfvf
 
Lica unit2 ppt converted
Lica unit2 ppt convertedLica unit2 ppt converted
Lica unit2 ppt convertedelakkia8
 
How to Make a Bi-Toroid Transformer and Exceed 100 % Efficiency
How to Make a Bi-Toroid Transformer and Exceed 100 % EfficiencyHow to Make a Bi-Toroid Transformer and Exceed 100 % Efficiency
How to Make a Bi-Toroid Transformer and Exceed 100 % EfficiencyThane Heins
 
Lab 4 Report Switching Voltage Regulators
Lab 4 Report Switching Voltage Regulators Lab 4 Report Switching Voltage Regulators
Lab 4 Report Switching Voltage Regulators Katrina Little
 
Unit-I Characteristics of opamp
Unit-I Characteristics of opampUnit-I Characteristics of opamp
Unit-I Characteristics of opampDr.Raja R
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
UPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection SolutionUPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection SolutioniTQAN Maju Resources
 
Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]Jitendra Jangid
 
Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]Jitendra Jangid
 
How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013
How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013
How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013Thane Heins
 
Electric power calculations
Electric power calculationsElectric power calculations
Electric power calculationsmichaeljmack
 
Unit-II Applications of Operational Amplifier
Unit-II Applications of Operational AmplifierUnit-II Applications of Operational Amplifier
Unit-II Applications of Operational AmplifierDr.Raja R
 
Mueller experiments kromrey_brandt_tesla_bedini
Mueller experiments kromrey_brandt_tesla_bediniMueller experiments kromrey_brandt_tesla_bedini
Mueller experiments kromrey_brandt_tesla_bediniPublicLeaker
 

Similar to Complete Magna Transformer Tests July 10th & 11th, 2009 (20)

PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...
PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...
PDi Multiple Bi-Toroid Transformer (Bi-TT) Testing for MAGNA International - ...
 
Bi-Toroid Transformer Performance vs Conventional EI Transformer
Bi-Toroid Transformer Performance vs Conventional EI TransformerBi-Toroid Transformer Performance vs Conventional EI Transformer
Bi-Toroid Transformer Performance vs Conventional EI Transformer
 
OP amp parameters
OP amp parametersOP amp parameters
OP amp parameters
 
ET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdf
ET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdfET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdf
ET191012(GENERAL VIVA presentatfvfvfvdfvfdvfio).pdf
 
Lica unit2 ppt converted
Lica unit2 ppt convertedLica unit2 ppt converted
Lica unit2 ppt converted
 
How to Make a Bi-Toroid Transformer and Exceed 100 % Efficiency
How to Make a Bi-Toroid Transformer and Exceed 100 % EfficiencyHow to Make a Bi-Toroid Transformer and Exceed 100 % Efficiency
How to Make a Bi-Toroid Transformer and Exceed 100 % Efficiency
 
Lab 4 Report Switching Voltage Regulators
Lab 4 Report Switching Voltage Regulators Lab 4 Report Switching Voltage Regulators
Lab 4 Report Switching Voltage Regulators
 
Unit-I Characteristics of opamp
Unit-I Characteristics of opampUnit-I Characteristics of opamp
Unit-I Characteristics of opamp
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
UPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection SolutionUPS (Uninterrupted Power Supply) - Power Protection Solution
UPS (Uninterrupted Power Supply) - Power Protection Solution
 
Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]
 
Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]Hardware Wrkshp C [Compatibility Mode]
Hardware Wrkshp C [Compatibility Mode]
 
INTRODUCTION to Potential Difference Inc. Bi-Toroid Transformer (BiTT)
INTRODUCTION to Potential Difference Inc. Bi-Toroid Transformer (BiTT)INTRODUCTION to Potential Difference Inc. Bi-Toroid Transformer (BiTT)
INTRODUCTION to Potential Difference Inc. Bi-Toroid Transformer (BiTT)
 
How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013
How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013
How to Make a Bi-Toroid Transformer and Exceed 100 Percent Efficiency in 2013
 
testing of dc machine
testing of dc machinetesting of dc machine
testing of dc machine
 
Electric power calculations
Electric power calculationsElectric power calculations
Electric power calculations
 
Unit-II Applications of Operational Amplifier
Unit-II Applications of Operational AmplifierUnit-II Applications of Operational Amplifier
Unit-II Applications of Operational Amplifier
 
Design 1st & Hillcrest Petroleum Advanced Energy - Generator Testing FTC Report
Design 1st & Hillcrest Petroleum Advanced Energy - Generator Testing FTC ReportDesign 1st & Hillcrest Petroleum Advanced Energy - Generator Testing FTC Report
Design 1st & Hillcrest Petroleum Advanced Energy - Generator Testing FTC Report
 
Complete Site Testing
Complete Site TestingComplete Site Testing
Complete Site Testing
 
Mueller experiments kromrey_brandt_tesla_bedini
Mueller experiments kromrey_brandt_tesla_bediniMueller experiments kromrey_brandt_tesla_bedini
Mueller experiments kromrey_brandt_tesla_bedini
 

More from Thane Heins

Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)
Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)
Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)Thane Heins
 
BiTT Test Dr. Fusina Defence Research and Development Canada Bi-Toroid Trans...
BiTT Test Dr. Fusina Defence Research and Development Canada  Bi-Toroid Trans...BiTT Test Dr. Fusina Defence Research and Development Canada  Bi-Toroid Trans...
BiTT Test Dr. Fusina Defence Research and Development Canada Bi-Toroid Trans...Thane Heins
 
Open letter to prime minister harper
Open letter to prime minister harperOpen letter to prime minister harper
Open letter to prime minister harperThane Heins
 
118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...
118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...
118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...Thane Heins
 
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent DisclosurePDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent DisclosureThane Heins
 
Potential Difference IP Licensing Model1
Potential Difference IP Licensing Model1Potential Difference IP Licensing Model1
Potential Difference IP Licensing Model1Thane Heins
 
A CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail Agenda
A CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail AgendaA CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail Agenda
A CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail AgendaThane Heins
 
An Alternative Solution to the Global ChemTrail Geo Engineering Agenda
An Alternative Solution to the Global ChemTrail Geo Engineering AgendaAn Alternative Solution to the Global ChemTrail Geo Engineering Agenda
An Alternative Solution to the Global ChemTrail Geo Engineering AgendaThane Heins
 
UN Ban on ChemTrail / Geo Engineering 2010
UN Ban on ChemTrail / Geo Engineering 2010UN Ban on ChemTrail / Geo Engineering 2010
UN Ban on ChemTrail / Geo Engineering 2010Thane Heins
 
Ottawa University / NRC ReGenX Test Set-up
Ottawa University / NRC ReGenX Test Set-upOttawa University / NRC ReGenX Test Set-up
Ottawa University / NRC ReGenX Test Set-upThane Heins
 
BiTT JLN Labs_Report Independent Third Party Test FRANCE
BiTT JLN Labs_Report Independent Third Party Test FRANCEBiTT JLN Labs_Report Independent Third Party Test FRANCE
BiTT JLN Labs_Report Independent Third Party Test FRANCEThane Heins
 
ReGenX JLN Labs Independent Report[1]
ReGenX JLN Labs Independent Report[1]ReGenX JLN Labs Independent Report[1]
ReGenX JLN Labs Independent Report[1]Thane Heins
 
Kinectrics Draft Report With Over 100 Errors k 01[1]
Kinectrics Draft Report With Over 100 Errors k 01[1]Kinectrics Draft Report With Over 100 Errors k 01[1]
Kinectrics Draft Report With Over 100 Errors k 01[1]Thane Heins
 
How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...
How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...
How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...Thane Heins
 
Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...
Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...
Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...Thane Heins
 
Draft India Water Security and Delivery Presentation[1]
Draft India Water Security and Delivery Presentation[1]Draft India Water Security and Delivery Presentation[1]
Draft India Water Security and Delivery Presentation[1]Thane Heins
 
How a Bi-Toroid Transformer Outperforms a Conventional Transformer
How a Bi-Toroid Transformer Outperforms a Conventional TransformerHow a Bi-Toroid Transformer Outperforms a Conventional Transformer
How a Bi-Toroid Transformer Outperforms a Conventional TransformerThane Heins
 
Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009
Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009
Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009Thane Heins
 

More from Thane Heins (18)

Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)
Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)
Hartwick National Research Council of Canada Dec. 2009 ReGen-X Generator Test(1)
 
BiTT Test Dr. Fusina Defence Research and Development Canada Bi-Toroid Trans...
BiTT Test Dr. Fusina Defence Research and Development Canada  Bi-Toroid Trans...BiTT Test Dr. Fusina Defence Research and Development Canada  Bi-Toroid Trans...
BiTT Test Dr. Fusina Defence Research and Development Canada Bi-Toroid Trans...
 
Open letter to prime minister harper
Open letter to prime minister harperOpen letter to prime minister harper
Open letter to prime minister harper
 
118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...
118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...
118 recorded chemtrails june 20 over ottawa, kanata, almonte, carleton place,...
 
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent DisclosurePDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
 
Potential Difference IP Licensing Model1
Potential Difference IP Licensing Model1Potential Difference IP Licensing Model1
Potential Difference IP Licensing Model1
 
A CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail Agenda
A CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail AgendaA CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail Agenda
A CONVENIENT TRUTH - An Alternative Solution to the Global ChemTrail Agenda
 
An Alternative Solution to the Global ChemTrail Geo Engineering Agenda
An Alternative Solution to the Global ChemTrail Geo Engineering AgendaAn Alternative Solution to the Global ChemTrail Geo Engineering Agenda
An Alternative Solution to the Global ChemTrail Geo Engineering Agenda
 
UN Ban on ChemTrail / Geo Engineering 2010
UN Ban on ChemTrail / Geo Engineering 2010UN Ban on ChemTrail / Geo Engineering 2010
UN Ban on ChemTrail / Geo Engineering 2010
 
Ottawa University / NRC ReGenX Test Set-up
Ottawa University / NRC ReGenX Test Set-upOttawa University / NRC ReGenX Test Set-up
Ottawa University / NRC ReGenX Test Set-up
 
BiTT JLN Labs_Report Independent Third Party Test FRANCE
BiTT JLN Labs_Report Independent Third Party Test FRANCEBiTT JLN Labs_Report Independent Third Party Test FRANCE
BiTT JLN Labs_Report Independent Third Party Test FRANCE
 
ReGenX JLN Labs Independent Report[1]
ReGenX JLN Labs Independent Report[1]ReGenX JLN Labs Independent Report[1]
ReGenX JLN Labs Independent Report[1]
 
Kinectrics Draft Report With Over 100 Errors k 01[1]
Kinectrics Draft Report With Over 100 Errors k 01[1]Kinectrics Draft Report With Over 100 Errors k 01[1]
Kinectrics Draft Report With Over 100 Errors k 01[1]
 
How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...
How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...
How to Eliminate Transformer Cooling Requirements Using Bi-Toroid Transformer...
 
Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...
Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...
Worldwide ReGenX and BiTT Commercialization and Integration Projects and Part...
 
Draft India Water Security and Delivery Presentation[1]
Draft India Water Security and Delivery Presentation[1]Draft India Water Security and Delivery Presentation[1]
Draft India Water Security and Delivery Presentation[1]
 
How a Bi-Toroid Transformer Outperforms a Conventional Transformer
How a Bi-Toroid Transformer Outperforms a Conventional TransformerHow a Bi-Toroid Transformer Outperforms a Conventional Transformer
How a Bi-Toroid Transformer Outperforms a Conventional Transformer
 
Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009
Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009
Complete MAGNA International Bi-Toroid Transformer Tests July 10th & 11th, 2009
 

Complete Magna Transformer Tests July 10th & 11th, 2009

  • 1. Potential +/- Difference Inc . Bi-Toroid Transformer Tests Potential + / - Difference Inc. Bi-Toroid Transformer Tests For Magna International Prepared for: Dave Pascoe – Magna International Prepared by: Thane Heins - PDI Date: July 15th, 2009 July 18, 2009
  • 2. Potential +/- Difference Inc . Bi-Toroid Transformer Tests The Bi-Toroid Transformer is designed to convert Reactive Power to Real Power. This is accomplished by introducing an additional secondary coil and alternate flux path route – keeping the primary coil isolated from the secondary induced BEMF magnetic fluxes The extra energy required to produce a transformer that operates at over 100% efficiency comes from the fact that the two secondary coils self regulate their own flux required to maintain the voltage across the load and the primary coil is unaffected by secondary load. Transformer TEST # 1 TEST # 2 TEST #3 TEST #4 TEST #5 TEST #6 Type Efficiency Efficiency Efficiency Efficiency Efficiency Efficiency Conventional - - - 74% - - E I Type Bi-Toroid 191% 310% 989% - 406% 304% Table 1 Conventional Transformer vs Bi-Toroid Transformer Efficiency Comparison The table above shows the efficiency variations for the Bi-Toroid Transformer during the period of July 10th to July 18th, 2009. TEST #1 employs a “split” primary core – where an “artificial” air gap is inserted to increase core reluctance. TEST #2 employs a solid core – where the core is just sitting on the secondary core – also facilitating an air gap and higher reluctance between the primary core and secondary core. TEST #3 employs a solid core (slightly thicker than test #2) which is physically clamped to the secondary core – thus removing as much air gap as possible. A new primary coil is included in the test which has the same wire gauge and coil resistance as test #2. TEST #4 is a Conventional Transformer. TEST #5 employs a 10 ohm load in place of the 27 ohm load. TEST #6 is includes additional windings on Secondary #1. July 18, 2009
  • 3. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST # 1 Split Primary Core Fig. 1 TEST # 1 New “Split” Primary and Secondary 1 & 2 - July 10th, 2009 Fig. 2 Primary Input Voltage Fig. 3 Primary Input Current & Output Voltage TEST DATA #1 July 10th, 2009 Primary Input Voltage = 57.7 volts Primary Input Current = 0.026 amps Power Factor = 83.3 degrees / 0.116 Primary Input Power = 174 mW Secondary Output Voltage = 3.0 volts Secondary Load = 27 ohms Secondary Output Power = 333 mW Efficiency = 191% July 18, 2009
  • 4. Potential +/- Difference Inc . Bi-Toroid Transformer Tests Fig. 4 & 5 Voltage & Current Sine Waves – Power Factor = 0.116 / 83.3 degrees July 18, 2009
  • 5. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST # 2 Solid Primary Core Fig. 6 TEST # 2 New Primary “Solid” Core – JULY 11th, 2009 Fig. 7 Primary Input Current & Output Voltage July 18, 2009
  • 6. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST DATA # 2 July 11th, 2009 Primary Input Voltage = 58.8 volts Primary Input Current = 0.017 amps Power Factor = 83.3 degrees / 0.116 Primary Input Power = 115 mW Secondary Output Voltage = 3.1 volts Secondary Load = 27 ohms Secondary Output Power = 356 mW Efficiency = 310% Fig. 8 Voltage & Current Sine Waves Power Factor = 0.116 / 83.3 degrees July 18, 2009
  • 7. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST # 3 Hard Physical Primary Connection Fig. 9 TEST # 3 New Primary Core “Hard Physical Connection” – JULY 13th, 2009 Fig. 10 Primary Input Current & Output Voltage July 18, 2009
  • 8. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST DATA # 3 July 13th, 2009 Primary Input Voltage = 104.7 volts Primary Input Current = 0.001 amps Power Factor = 70 degrees / 0.34 Primary Input Power = 36 mW Secondary Output Voltage = 3.1 volts Secondary Load = 27 ohms Secondary Output Power = 356 mW Efficiency = 989% Fig. 11 Voltage & Current Sine Waves - Power Factor = 0.34 / 70 degrees July 18, 2009
  • 9. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST # 4 Conventional Transformer Efficiency Fig. 12 TEST # 4 Conventional Transformer Input Voltage – JULY 15th, 2009 Fig. 13 Primary Input Current & Output Voltage July 18, 2009
  • 10. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST DATA # 4 July 15th, 2009 Primary Input Voltage = 2.71 volts Primary Input Current = 0.200 amps Power Factor = 18 degrees / 0.95 Primary Input Power = 516 mW Secondary Output Voltage = 3.2 volts Secondary Load = 27 ohms Secondary Output Power = 379 mW Efficiency = 73.5% Fig. 14 Voltage & Current Sine Waves - Power Factor = 0.95 / 18 degrees July 18, 2009
  • 11. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST # 5 Ten Ohm Load Test Fig. 15 TEST # 5 Bi-Toroid Transformer Input Voltage 10 Ohm Load – JULY 17th, 2009 Fig. 16 Primary Input Current & Output Voltage July 18, 2009
  • 12. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST DATA # 5 July 16th, 2009 Primary Input Voltage = 120.9 volts Primary Input Current = 0.005 amps Power Factor = 84 degrees / 0.10 Primary Input Power = 63 mW Secondary Output Voltage = 1.6 volts Secondary Load = 10 ohms Secondary Output Power = 256 mW Efficiency = 406% Fig. 17 Voltage & Current Sine Waves - Power Factor = 0.10 / 84 degrees July 18, 2009
  • 13. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST # 6 Ten Ohm Load Test NEW SECONDARY 1 WINDINGS Fig. 18 TEST # 6 Bi-Toroid Transformer Input Voltage 10 Ohm Load – JULY 18th, 2009 Fig. 19 Primary Input Current & Output Voltage July 18, 2009
  • 14. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST DATA # 6 July 18th, 2009 Primary Input Voltage = 119.9 volts Primary Input Current = 0.006 amps Power Factor = 80 degrees / 0.17 Primary Input Power = 125 mW Secondary Output Voltage = 2.22 volts Secondary Load = 10 ohms Secondary Output Power = 493 mW Efficiency = 394% Fig. 20 Voltage & Current Sine Waves - Power Factor = 0.17 / 80 degrees July 18, 2009
  • 15. Potential +/- Difference Inc . Bi-Toroid Transformer Tests TEST # 7 Test Equipment Accuracy Confirmations Fig 21 Load Voltage across 27 Ohm Load Fig 22 Load Current through 27 Ohm Load TEST DATA #7 July 16th, 2009 Load Voltage = 3 volts Load Resistance = 27.5 ohms Calculated Load Current = 0.109 amps Metered Load Current = 0.111 amps Meter Error = 1.8% July 18, 2009
  • 16. Potential +/- Difference Inc . Bi-Toroid Transformer Tests July 18, 2009
  • 17. Potential +/- Difference Inc . Bi-Toroid Transformer Tests Fig. 23 Voltage & Current Sine Waves - Power Factor = 0.36 / 69 degrees July 18, 2009
  • 18. Potential +/- Difference Inc . Bi-Toroid Transformer Tests Fig. 26 Voltage & Current Sine Waves - Power Factor = 0.05 / 87 degrees July 18, 2009