SlideShare a Scribd company logo
1 of 36
CONTROLING EARTH FAULT CURRENTS USING
RAPID EARTH FAULT CURRENT LIMITERS
Mark Mills
BLACK SATURDAY BUSHFIRES
Black Saturday bushfires were a series of bushfires on the 7th February 2009,
which are rated are among the worst ever seen in Australia.
 Melbourne broke temperature records by experiencing three
consecutive days above 43 °C, peaking over 45 °C
 400 individual fires.
 358 Fire Fighters deployed.
 3500 structures destroyed.
 11,800 head of livestock lost.
Ref: Wikipedia
VICTORIA BUSHFIRE ROYAL COMMISSION
Royal commission convened to investigate causes of fires and provide
recommendations.
 Arson, some fires were deliberately lit.
 Alleged, man operating a power tool, sparks caused ignition.
 An incorrectly-rigged SWER line was ripped down at Kilmore East.
Ref: Wikipedia
ELECTRCIAL CAUSE OF FIRE AT KILMORE EAST
 As wind speeds were reaching their peak, an incorrectly-rigged SWER line
was ripped down at Kilmore East.
 This sparked a bushfire that would become the deadliest and most intense
firestorm ever experienced in Australia's post-1788 history.
 It was estimated that the amount of energy released during the firestorm in
the Kinglake-Marysville area was equivalent to the amount of energy that
would be released by 1,500 Hiroshima-sized atomic bombs.
 The accepted recommendations require the implementation of a range of
initiatives over a ten year period that will reduce the risk of bushfire ignition by
distribution networks by ‘nearly two thirds’.
 The outworking of these recommendations is through the Victorian
Government’s Powerline Bushfire Safety Program (PBSP) taskforce.
 Installation of Rapid Earth Fault Limiters (REFCL) in 22 zone substations by
December 2022.
 New network bushfire design standards for specified line replacement works
within defined areas.
ROYAL COMMISSION RECOMENDATIONS
The installation of REFCLs must comply with the following, in the event of a phase-
to-ground fault:
 Reduce the voltage on the faulted conductor in relation to the station earth
when measured at the corresponding zone substation for high impedance faults
to 250 volts within 2 seconds.
 Reduce the voltage on the faulted conductor in relation to the station earth
when measured at the corresponding zone substation for low impedance faults:
 1,900 volts within 85 milliseconds.
 750 volts within 500 milliseconds.
 250 volts within 2 seconds.
 During diagnostic tests for high impedance faults, limit
 Fault current to 0.5 amps or less; and
 The thermal energy on the electric line to a maximum I2t value of 0.1 A2s
RAPID EARTH FAULT CURRENT LIMITERS
 A REFCL is a protection device that reduces the risk of fires caused by
powerlines and is installed on a zone substation transformer neutral connection
to earth.
 It does this by rapidly limiting the energy that is released in certain types of
powerline faults, known as earth faults. As such the REFCL device trialed
protects the 22kV network from phase to ground earth faults. Other voltages in
the future.
 There are various types of technology that fall under the REFCL umbrella.
 The Ground Fault Neutraliser (GFN).
 Arc Suppression Coil (ASC).
 Solid State Fault Current Limiters (SSFCL) coupled with faulted phase
earthing (FPE).
 Other combinations are available
WHAT ARE RAPID EARTH FAULT CURRENT LIMITERS
ARC SUPPRESSION COIL - GROUND FAULT NEUTRALISER - GFN
 An Arc Suppression Coil (ASC) is an inductor that connects the neutral of the
source substation transformer to earth. Ground Fault Neutraliser (GFN) is a
proprietary design.
 The inductance value is tuned to achieve near-resonance with the total network
capacitance to earth.
 In this state the connection between the neutral and earth has very high
impedance at 50Hz, so earth fault currents are greatly reduced – typically to less
than ten amps.
 Test system comprised a 505mH inductor (80 amps of inductive current) in
parallel with a variable capacitor which ranged from 0 to 20uF, network tuned.
 The test network tuned at a setting around ten amps, i.e. the parallel capacitor
provided about 70 amps of capacitive current at full neutral displacement,
which meant it had a value around 17.5 microfarads.
ARC SUPRESSION COIL - GROUND FAULT NEUTRALISER
GROUND FAULT NEUTRALISER - GFN
 High voltage transistor switch in the neutral to earth connection of the
substation.
 The SSFCL switch comprised a ladder of six insulated gate bipolar transistor
switches, with a series RC over-voltage damping circuit.
 Over voltage protection via 24 kilovolt metal-oxide varistor across the switch for
power frequency over-voltage protection.
 This switch could be set to open when neutral current exceeded a set threshold.
By opening this connection, the earth fault current path was interrupted and
the earth fault current was limited to the capacitive current of the network (test
case 200 amps).
 The SSFCL operated at solid state speeds, i.e. in microseconds.
 A current transformer provided an analogue current feedback.
SOLID STATE FAULT CURRENT LIMITERS
SOLID STATE FAULT CURRENT LIMITERS
GROUND SENSOR
6 STAGE BIPOLAR
TRANSISTOR
RC
NETWORK
VARISTOR
STANDARD POWERLINE INSTALLATION – TN-S SYSTEM
Ref: REFCL Information Forum- CitiPower/PowerCor
NER POWERLINE INSTALLATION
Ref: REFCL Information Forum- CitiPower/PowerCor
GFN POWERLINE INSTALLATION
Ref: REFCL Information Forum- CitiPower/PowerCor
GROUND FAULT VOLTAGES
REFCL OPERATIONS
Ref: REFCL Information Forum- CitiPower/PowerCor
TESTING
 Typical 3m wire contact length of downed conductor.
 Fires are unlikely to occur if lineal soil current intensity is less than
0.15A/m (amps per metre) of fallen conductor on the ground .
 Equivalent to about 0.5 amps fault current in a worst-case ‘wire down’
earth fault (3m contact length).
 Grass fires often took many tens of seconds to ignite.
POWERLINE WIRE DOWN FAULT
Ref: Marxsen Consulting, REFCL technologies final
report 151204
Arcing video: https://www.youtube.com/watch?v=Q1MNBV48x0Q
POWERLINE WIRE DOWN FAULT
Ref: Marxsen Consulting, REFCL technologies final report 151204
Rapid earth fault current limiters
LOW IMPEDANCE FAULT
 Within 85 milliseconds of fault occurrence the REFCL must limit the voltage
on the faulted conductor to less than 1,900 volts
 Within 500ms of fault occurrence the REFCL must further limit the voltage
on the faulted conductor to less than 750 volts.
 Within two seconds of fault occurrence the REFCL must further limit the
voltage on the faulted conductor to less than 250 volts except during
diagnostic tests.
Definition of a Low impedance fault: a resistance from any high voltage powerline
conductor to earth of value equal in ohms to the nominal phase-to-earth voltage in
volts divided by 31.75 (400 Ohms in a 22kV network).
REFCL PERFORMANCE STANDARD
From tests, it was concluded that to extinguish bounce arcs, the REFCL must reduce
the conductor voltage below 1,900 volts.
FALLEN POWERLINE BOUNCE ARCS
Ref: Marxsen Consulting, REFCL technologies final report 151204
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 2 4 6 8 10 12
VOLTAGE
TIME sec
REFCL VOLTAGE
LOW IMPEDANCE REFCL PERFORMANCE STANDARD
Time Voltage
0.085 1900
0.5 750
2 250
AS3007 Table F3
Time Voltage
10 50
5 80
1 120
0.5 150
0.4 180
0.1 300
0.05 420
0.03 550
REFCLTouch Voltage AS3007 V REFCL Operational Performance
HIGH IMPEDANCE FAULT
 The REFCL must detect the fault within 1.5 seconds of its occurrence.
 Within two seconds of fault occurrence, the REFCL must limit the voltage
on the faulted conductor to less than 250 volts except during diagnostic
tests.
 During diagnostic tests to confirm if the fault is sustained or not or to
identify which powerline it is on, the REFCL must:
 Limit the fault current to less than 0.5 amps.
 Limit the I2t to less than 0.1 A2s.
Definitions of high-impedance fault: 25,400 Ohms in a 22kV network
REFCL PERFORMANCE STANDARD
REFCL PERFORMANCE IGNITION ENERGY CURVE
0
0.5
1
1.5
2
2.5
3
3.5
0 0.5 1 1.5 2 2.5
Current
Time
IGNITION ENERGY
I^2t = 0.1A/sec
0.4sec
Curve Limit the I2t to less than 0.1 A2s
The Kilmore South GFN was tested at less than 0.5 amps fault current level and the
results are shown in the table
FAULT DETECTION TEST RESULTS 25kΩ FROM KILMORE SOUTH
Ref: Marxsen Consulting, REFCL technologies final report 151204
REFCL must detect the fault within 1.5 seconds of its occurrence 0.4sec
For Ignition energy curve
The Kilmore South GFN with 15,600 ohm fault
FAULT DETECTION TEST RESULTS 15kΩ FROM KILMORE SOUTH
Ref: Marxsen Consulting, REFCL technologies final report 151204
The Kilmore South Solid State FCL with 15,600 ohm fault
SOLID STATE FCL LINE DIAGRAM
Ground Fault
BLOCKED
Limited: 800mA in <5ms
BODY DAMAGE CURVES AS60479
GFN High Impedance
SSFCL – 5ms – NOT ON GRAPH
Figure 20 – Conventional time/current zones of effects of a.c. currents (15 Hz to
100 Hz) on persons for a current path corresponding to left hand to feet
REMINDER - REFCL PERFORMANCE STANDARD
0
0.5
1
1.5
2
2.5
3
3.5
0 0.5 1 1.5 2 2.5
Current
Time
IGNITION ENERGY
I^2t = 0.1A/sec
0.4sec
Standard Earth Leakage AS2081
500mA/500ms: Definite Time
Standard earth leakage settings DON’T
clear fast enough to match REFCL on Low
impedance Faults
HIGH VOLTAGE MINING INSTALLATION
22kV REFCL supply
CB through
feed and E/L
Outcome:
1. REFCL operates
2. NO E/L detection at site sub
3. You don’t even know about it, until 22kV supply trips
The insulation levels within the 22kV HV circuit breakers and transformers have to
be selected above the expected ground potential rise of 22kV with the REFCL
installed
ASSET EVALUATION - EQUIPMENT SELECTIONS
The insulation levels within Voltage Transformers have to be selected above the
expected phase to ground fault voltage of ~22kV.
EQUIPEMENT SELECTIONS
Additionally surge arrestor selection needs to be set to the higher value of 24kV
The insulation levels for
Cables have to be selected
above the expected phase to
ground voltage of ~22kV.
CABLE CATEGORY SELECTIONS AS1429.1
 The REFCL systems have rapid clearance times.
 Ignition energy/current density curve will generally be the driver for REFCL
operations.
 No guarantee site protection will detect and operate, has to be faster than
REFCL. Review protection schemes.
 Ground fault (summation of CT in circuit breaker or protection relay)
 Earth leakage (RCD type or CT on MEN link)
 Transfer voltages still need to be controlled under current protection schemes
(AS/NZS3007, AS/NZS2067 etc.).
 Equipment selections will be based on IT earth requirements.
 Isolation transformers – isolate supply authority from site network?
 When will REFCL legislation move into mining with our extensive networks?
WHAT DOES THIS MEAN FOR US?
End
Thanks for Listening
Contact Details
Mark Mills
MIEAust CPENG NER, RPEQ
Office: 02 49368700
Mobile: 0419 614 675
Email: mark.mills@mrm.net.au
Web: www.mrm.net.au
RAPID EARTH FAULT CURRENT LIMITERS

More Related Content

More from NSW Environment and Planning

Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)NSW Environment and Planning
 
Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)NSW Environment and Planning
 
Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)NSW Environment and Planning
 
Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...NSW Environment and Planning
 
Demolition of a former mine site - Luke Egan and David Wood
Demolition of a former mine site - Luke Egan and David WoodDemolition of a former mine site - Luke Egan and David Wood
Demolition of a former mine site - Luke Egan and David WoodNSW Environment and Planning
 
Application of high energy micro-mist technology - Jon Roberts
Application of high energy micro-mist technology - Jon RobertsApplication of high energy micro-mist technology - Jon Roberts
Application of high energy micro-mist technology - Jon RobertsNSW Environment and Planning
 
Equipment failure - a liability or an asset? - Roger Costanzi
Equipment failure - a liability or an asset? - Roger CostanziEquipment failure - a liability or an asset? - Roger Costanzi
Equipment failure - a liability or an asset? - Roger CostanziNSW Environment and Planning
 
Critical risk and control frameworks - James Ritchie
Critical risk and control frameworks - James RitchieCritical risk and control frameworks - James Ritchie
Critical risk and control frameworks - James RitchieNSW Environment and Planning
 
ACARP project to industrialise wall-flow DPF technology for diesel engines us...
ACARP project to industrialise wall-flow DPF technology for diesel engines us...ACARP project to industrialise wall-flow DPF technology for diesel engines us...
ACARP project to industrialise wall-flow DPF technology for diesel engines us...NSW Environment and Planning
 
Collision management risk evaluation for mobile equipment - Dr Chris Doran
Collision management risk evaluation for mobile equipment - Dr Chris Doran Collision management risk evaluation for mobile equipment - Dr Chris Doran
Collision management risk evaluation for mobile equipment - Dr Chris Doran NSW Environment and Planning
 

More from NSW Environment and Planning (20)

05 reviewing your SMS
05 reviewing your SMS05 reviewing your SMS
05 reviewing your SMS
 
04. slinging and lifting equipment
04. slinging and lifting equipment04. slinging and lifting equipment
04. slinging and lifting equipment
 
Control focused inspection tools (Mark Smith)
Control focused inspection tools (Mark Smith)Control focused inspection tools (Mark Smith)
Control focused inspection tools (Mark Smith)
 
Central assessment unit CAU(Steve Bentham)
Central assessment unit CAU(Steve Bentham)Central assessment unit CAU(Steve Bentham)
Central assessment unit CAU(Steve Bentham)
 
Autonomous mining equipment (Owen Barry)
Autonomous mining equipment (Owen Barry)Autonomous mining equipment (Owen Barry)
Autonomous mining equipment (Owen Barry)
 
Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)Fires on mobile plant refuelling (Ross Stutchbury)
Fires on mobile plant refuelling (Ross Stutchbury)
 
Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)Mobile plant rollovers and collisions (Bill McGlynn)
Mobile plant rollovers and collisions (Bill McGlynn)
 
Metropolitan colliery gas (Dave Gordon)
Metropolitan colliery gas (Dave Gordon)Metropolitan colliery gas (Dave Gordon)
Metropolitan colliery gas (Dave Gordon)
 
Airborne dust update (Mark Shepherd)
Airborne dust update (Mark Shepherd)Airborne dust update (Mark Shepherd)
Airborne dust update (Mark Shepherd)
 
Emergency planning (Matt U'Brien)
Emergency planning (Matt U'Brien)Emergency planning (Matt U'Brien)
Emergency planning (Matt U'Brien)
 
Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)Electrical performance presentation (Craig Harris)
Electrical performance presentation (Craig Harris)
 
Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...Where do I stand for fire protection on mobile and transportable equipment an...
Where do I stand for fire protection on mobile and transportable equipment an...
 
The culture of hydraulic safety - Kyle Probert
The culture of hydraulic safety - Kyle ProbertThe culture of hydraulic safety - Kyle Probert
The culture of hydraulic safety - Kyle Probert
 
Demolition of a former mine site - Luke Egan and David Wood
Demolition of a former mine site - Luke Egan and David WoodDemolition of a former mine site - Luke Egan and David Wood
Demolition of a former mine site - Luke Egan and David Wood
 
Application of high energy micro-mist technology - Jon Roberts
Application of high energy micro-mist technology - Jon RobertsApplication of high energy micro-mist technology - Jon Roberts
Application of high energy micro-mist technology - Jon Roberts
 
Equipment failure - a liability or an asset? - Roger Costanzi
Equipment failure - a liability or an asset? - Roger CostanziEquipment failure - a liability or an asset? - Roger Costanzi
Equipment failure - a liability or an asset? - Roger Costanzi
 
Critical risk and control frameworks - James Ritchie
Critical risk and control frameworks - James RitchieCritical risk and control frameworks - James Ritchie
Critical risk and control frameworks - James Ritchie
 
ACARP project to industrialise wall-flow DPF technology for diesel engines us...
ACARP project to industrialise wall-flow DPF technology for diesel engines us...ACARP project to industrialise wall-flow DPF technology for diesel engines us...
ACARP project to industrialise wall-flow DPF technology for diesel engines us...
 
Collision management risk evaluation for mobile equipment - Dr Chris Doran
Collision management risk evaluation for mobile equipment - Dr Chris Doran Collision management risk evaluation for mobile equipment - Dr Chris Doran
Collision management risk evaluation for mobile equipment - Dr Chris Doran
 
Learning from disasters - John Flint
Learning from disasters - John FlintLearning from disasters - John Flint
Learning from disasters - John Flint
 

Recently uploaded

2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis UsageNeil Kimberley
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...lizamodels9
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menzaictsugar
 
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCRashishs7044
 
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCRashishs7044
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Pereraictsugar
 
Future Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionFuture Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionMintel Group
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03DallasHaselhorst
 
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City GurgaonCall Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaoncallgirls2057
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyotictsugar
 
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadIslamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadAyesha Khan
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Kirill Klimov
 
Case study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detailCase study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detailAriel592675
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesKeppelCorporation
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckHajeJanKamps
 
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,noida100girls
 
International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...ssuserf63bd7
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCRashishs7044
 

Recently uploaded (20)

2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
 
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
8447779800, Low rate Call girls in Shivaji Enclave Delhi NCR
 
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
8447779800, Low rate Call girls in Kotla Mubarakpur Delhi NCR
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Perera
 
Future Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionFuture Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted Version
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03
 
Corporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information TechnologyCorporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information Technology
 
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City GurgaonCall Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
 
Investment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy CheruiyotInvestment in The Coconut Industry by Nancy Cheruiyot
Investment in The Coconut Industry by Nancy Cheruiyot
 
Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)
 
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadIslamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024
 
Case study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detailCase study on tata clothing brand zudio in detail
Case study on tata clothing brand zudio in detail
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation Slides
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
 
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
 
International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
 

Rapid earth fault current limiters

  • 1. CONTROLING EARTH FAULT CURRENTS USING RAPID EARTH FAULT CURRENT LIMITERS Mark Mills
  • 2. BLACK SATURDAY BUSHFIRES Black Saturday bushfires were a series of bushfires on the 7th February 2009, which are rated are among the worst ever seen in Australia.  Melbourne broke temperature records by experiencing three consecutive days above 43 °C, peaking over 45 °C  400 individual fires.  358 Fire Fighters deployed.  3500 structures destroyed.  11,800 head of livestock lost. Ref: Wikipedia
  • 3. VICTORIA BUSHFIRE ROYAL COMMISSION Royal commission convened to investigate causes of fires and provide recommendations.  Arson, some fires were deliberately lit.  Alleged, man operating a power tool, sparks caused ignition.  An incorrectly-rigged SWER line was ripped down at Kilmore East. Ref: Wikipedia
  • 4. ELECTRCIAL CAUSE OF FIRE AT KILMORE EAST  As wind speeds were reaching their peak, an incorrectly-rigged SWER line was ripped down at Kilmore East.  This sparked a bushfire that would become the deadliest and most intense firestorm ever experienced in Australia's post-1788 history.  It was estimated that the amount of energy released during the firestorm in the Kinglake-Marysville area was equivalent to the amount of energy that would be released by 1,500 Hiroshima-sized atomic bombs.
  • 5.  The accepted recommendations require the implementation of a range of initiatives over a ten year period that will reduce the risk of bushfire ignition by distribution networks by ‘nearly two thirds’.  The outworking of these recommendations is through the Victorian Government’s Powerline Bushfire Safety Program (PBSP) taskforce.  Installation of Rapid Earth Fault Limiters (REFCL) in 22 zone substations by December 2022.  New network bushfire design standards for specified line replacement works within defined areas. ROYAL COMMISSION RECOMENDATIONS
  • 6. The installation of REFCLs must comply with the following, in the event of a phase- to-ground fault:  Reduce the voltage on the faulted conductor in relation to the station earth when measured at the corresponding zone substation for high impedance faults to 250 volts within 2 seconds.  Reduce the voltage on the faulted conductor in relation to the station earth when measured at the corresponding zone substation for low impedance faults:  1,900 volts within 85 milliseconds.  750 volts within 500 milliseconds.  250 volts within 2 seconds.  During diagnostic tests for high impedance faults, limit  Fault current to 0.5 amps or less; and  The thermal energy on the electric line to a maximum I2t value of 0.1 A2s RAPID EARTH FAULT CURRENT LIMITERS
  • 7.  A REFCL is a protection device that reduces the risk of fires caused by powerlines and is installed on a zone substation transformer neutral connection to earth.  It does this by rapidly limiting the energy that is released in certain types of powerline faults, known as earth faults. As such the REFCL device trialed protects the 22kV network from phase to ground earth faults. Other voltages in the future.  There are various types of technology that fall under the REFCL umbrella.  The Ground Fault Neutraliser (GFN).  Arc Suppression Coil (ASC).  Solid State Fault Current Limiters (SSFCL) coupled with faulted phase earthing (FPE).  Other combinations are available WHAT ARE RAPID EARTH FAULT CURRENT LIMITERS
  • 8. ARC SUPPRESSION COIL - GROUND FAULT NEUTRALISER - GFN
  • 9.  An Arc Suppression Coil (ASC) is an inductor that connects the neutral of the source substation transformer to earth. Ground Fault Neutraliser (GFN) is a proprietary design.  The inductance value is tuned to achieve near-resonance with the total network capacitance to earth.  In this state the connection between the neutral and earth has very high impedance at 50Hz, so earth fault currents are greatly reduced – typically to less than ten amps.  Test system comprised a 505mH inductor (80 amps of inductive current) in parallel with a variable capacitor which ranged from 0 to 20uF, network tuned.  The test network tuned at a setting around ten amps, i.e. the parallel capacitor provided about 70 amps of capacitive current at full neutral displacement, which meant it had a value around 17.5 microfarads. ARC SUPRESSION COIL - GROUND FAULT NEUTRALISER
  • 11.  High voltage transistor switch in the neutral to earth connection of the substation.  The SSFCL switch comprised a ladder of six insulated gate bipolar transistor switches, with a series RC over-voltage damping circuit.  Over voltage protection via 24 kilovolt metal-oxide varistor across the switch for power frequency over-voltage protection.  This switch could be set to open when neutral current exceeded a set threshold. By opening this connection, the earth fault current path was interrupted and the earth fault current was limited to the capacitive current of the network (test case 200 amps).  The SSFCL operated at solid state speeds, i.e. in microseconds.  A current transformer provided an analogue current feedback. SOLID STATE FAULT CURRENT LIMITERS
  • 12. SOLID STATE FAULT CURRENT LIMITERS GROUND SENSOR 6 STAGE BIPOLAR TRANSISTOR RC NETWORK VARISTOR
  • 13. STANDARD POWERLINE INSTALLATION – TN-S SYSTEM Ref: REFCL Information Forum- CitiPower/PowerCor
  • 14. NER POWERLINE INSTALLATION Ref: REFCL Information Forum- CitiPower/PowerCor
  • 15. GFN POWERLINE INSTALLATION Ref: REFCL Information Forum- CitiPower/PowerCor
  • 17. REFCL OPERATIONS Ref: REFCL Information Forum- CitiPower/PowerCor
  • 18. TESTING  Typical 3m wire contact length of downed conductor.  Fires are unlikely to occur if lineal soil current intensity is less than 0.15A/m (amps per metre) of fallen conductor on the ground .  Equivalent to about 0.5 amps fault current in a worst-case ‘wire down’ earth fault (3m contact length).  Grass fires often took many tens of seconds to ignite. POWERLINE WIRE DOWN FAULT Ref: Marxsen Consulting, REFCL technologies final report 151204
  • 19. Arcing video: https://www.youtube.com/watch?v=Q1MNBV48x0Q POWERLINE WIRE DOWN FAULT Ref: Marxsen Consulting, REFCL technologies final report 151204
  • 21. LOW IMPEDANCE FAULT  Within 85 milliseconds of fault occurrence the REFCL must limit the voltage on the faulted conductor to less than 1,900 volts  Within 500ms of fault occurrence the REFCL must further limit the voltage on the faulted conductor to less than 750 volts.  Within two seconds of fault occurrence the REFCL must further limit the voltage on the faulted conductor to less than 250 volts except during diagnostic tests. Definition of a Low impedance fault: a resistance from any high voltage powerline conductor to earth of value equal in ohms to the nominal phase-to-earth voltage in volts divided by 31.75 (400 Ohms in a 22kV network). REFCL PERFORMANCE STANDARD
  • 22. From tests, it was concluded that to extinguish bounce arcs, the REFCL must reduce the conductor voltage below 1,900 volts. FALLEN POWERLINE BOUNCE ARCS Ref: Marxsen Consulting, REFCL technologies final report 151204
  • 23. 0 200 400 600 800 1000 1200 1400 1600 1800 2000 0 2 4 6 8 10 12 VOLTAGE TIME sec REFCL VOLTAGE LOW IMPEDANCE REFCL PERFORMANCE STANDARD Time Voltage 0.085 1900 0.5 750 2 250 AS3007 Table F3 Time Voltage 10 50 5 80 1 120 0.5 150 0.4 180 0.1 300 0.05 420 0.03 550 REFCLTouch Voltage AS3007 V REFCL Operational Performance
  • 24. HIGH IMPEDANCE FAULT  The REFCL must detect the fault within 1.5 seconds of its occurrence.  Within two seconds of fault occurrence, the REFCL must limit the voltage on the faulted conductor to less than 250 volts except during diagnostic tests.  During diagnostic tests to confirm if the fault is sustained or not or to identify which powerline it is on, the REFCL must:  Limit the fault current to less than 0.5 amps.  Limit the I2t to less than 0.1 A2s. Definitions of high-impedance fault: 25,400 Ohms in a 22kV network REFCL PERFORMANCE STANDARD
  • 25. REFCL PERFORMANCE IGNITION ENERGY CURVE 0 0.5 1 1.5 2 2.5 3 3.5 0 0.5 1 1.5 2 2.5 Current Time IGNITION ENERGY I^2t = 0.1A/sec 0.4sec Curve Limit the I2t to less than 0.1 A2s
  • 26. The Kilmore South GFN was tested at less than 0.5 amps fault current level and the results are shown in the table FAULT DETECTION TEST RESULTS 25kΩ FROM KILMORE SOUTH Ref: Marxsen Consulting, REFCL technologies final report 151204 REFCL must detect the fault within 1.5 seconds of its occurrence 0.4sec For Ignition energy curve
  • 27. The Kilmore South GFN with 15,600 ohm fault FAULT DETECTION TEST RESULTS 15kΩ FROM KILMORE SOUTH Ref: Marxsen Consulting, REFCL technologies final report 151204 The Kilmore South Solid State FCL with 15,600 ohm fault
  • 28. SOLID STATE FCL LINE DIAGRAM Ground Fault BLOCKED Limited: 800mA in <5ms
  • 29. BODY DAMAGE CURVES AS60479 GFN High Impedance SSFCL – 5ms – NOT ON GRAPH Figure 20 – Conventional time/current zones of effects of a.c. currents (15 Hz to 100 Hz) on persons for a current path corresponding to left hand to feet
  • 30. REMINDER - REFCL PERFORMANCE STANDARD 0 0.5 1 1.5 2 2.5 3 3.5 0 0.5 1 1.5 2 2.5 Current Time IGNITION ENERGY I^2t = 0.1A/sec 0.4sec Standard Earth Leakage AS2081 500mA/500ms: Definite Time Standard earth leakage settings DON’T clear fast enough to match REFCL on Low impedance Faults
  • 31. HIGH VOLTAGE MINING INSTALLATION 22kV REFCL supply CB through feed and E/L Outcome: 1. REFCL operates 2. NO E/L detection at site sub 3. You don’t even know about it, until 22kV supply trips
  • 32. The insulation levels within the 22kV HV circuit breakers and transformers have to be selected above the expected ground potential rise of 22kV with the REFCL installed ASSET EVALUATION - EQUIPMENT SELECTIONS
  • 33. The insulation levels within Voltage Transformers have to be selected above the expected phase to ground fault voltage of ~22kV. EQUIPEMENT SELECTIONS Additionally surge arrestor selection needs to be set to the higher value of 24kV
  • 34. The insulation levels for Cables have to be selected above the expected phase to ground voltage of ~22kV. CABLE CATEGORY SELECTIONS AS1429.1
  • 35.  The REFCL systems have rapid clearance times.  Ignition energy/current density curve will generally be the driver for REFCL operations.  No guarantee site protection will detect and operate, has to be faster than REFCL. Review protection schemes.  Ground fault (summation of CT in circuit breaker or protection relay)  Earth leakage (RCD type or CT on MEN link)  Transfer voltages still need to be controlled under current protection schemes (AS/NZS3007, AS/NZS2067 etc.).  Equipment selections will be based on IT earth requirements.  Isolation transformers – isolate supply authority from site network?  When will REFCL legislation move into mining with our extensive networks? WHAT DOES THIS MEAN FOR US?
  • 36. End Thanks for Listening Contact Details Mark Mills MIEAust CPENG NER, RPEQ Office: 02 49368700 Mobile: 0419 614 675 Email: mark.mills@mrm.net.au Web: www.mrm.net.au RAPID EARTH FAULT CURRENT LIMITERS